D-PCA Wall-Tilt Up (Slender) Wall by ACI 14.8 2006-06 PDF

This document provides design calculations for a slender concrete wall with steel reinforcement. The wall is 16 feet tall and restrained at the top. Loads include a roof dead load of 60 psf, live load of 30 psf, and wind load of 20 psf. Reinforcement and concrete material properties are specified. Calculations are shown to check the axial stress and moment capacity of the wall section under factored load combinations. The results indicate the wall section is adequate and reinforcement criteria are satisfied.

Uploaded by

Divy Jain
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
158 views4 pages

D-PCA Wall-Tilt Up (Slender) Wall by ACI 14.8 2006-06 PDF

This document provides design calculations for a slender concrete wall with steel reinforcement. The wall is 16 feet tall and restrained at the top. Loads include a roof dead load of 60 psf, live load of 30 psf, and wind load of 20 psf. Reinforcement and concrete material properties are specified. Calculations are shown to check the axial stress and moment capacity of the wall section under factored load combinations. The results indicate the wall section is adequate and reinforcement criteria are satisfied.

Uploaded by

Divy Jain
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

www.pcaStructurePoint.

com
[email protected]
847.966.4357 (HELP) phone
847.581.0644 fax

Slender Wall Design


Alternative Design Method (ACI 318-05, 14.8)
Design of the wall shown is required. The wall is restrained at the top edge, and the roof
load is supported through 4 in. tee stems spaced at 4 ft on center.

Design Data
Loads:

Roof dead load q D := 60psf

Roof live load q L := 30psf

Wind q W := 20psf

Steel
fy := 60ksi Es := 29000ksi

ρ minh := 0.0020 ρ minv := 0.0012

Concrete
lbf
f'c := 4ksi wc := 150 φ := 0.9
3
ft
1 1
Ec := 57000 ⋅ f'c⋅ ⋅ psi Ec = 3605 ksi fr := 7.5⋅ f'c⋅ ⋅ psi fr = 474.341 psi
psi psi
⎡ ⎡
β 1 := if ⎢ f'c ≤ 4000psi , 0.85 , max⎢ 0.65 , 0.85 − 0.05⋅
(f'c − 4000psi) ⎥⎤ ⎥⎤ β 1 = 0.85
⎣ ⎣ 1000psi ⎦⎦
Geometry
Wall height l c := 16ft Stem width w := 4in

Parapet length l p := 2ft Tee beam spacing s := 4ft

Roof load eccentiricity e := 6.75in


Roof span l r := 40ft

Effective length factor k := 1.0

Wall thickness h := 6.50in


k ⋅ lc
Slenderness = 98.462
0.3⋅ h
Reinforcement location
d := 0.5⋅ h d = 3.25 in

Slender Wall by Chapter 14.8.mcd 2-1 6/1/2006


www.pcaStructurePoint.com
[email protected]
847.966.4357 (HELP) phone
847.581.0644 fax

Calculations
1. Trial wall section
2
in
Asminv := ρ minv⋅ h Asminv = 0.094
Minimum reinforcement area ft
2
in
Trial area of vertical reinforcement As := 0.175
ft
2. Effective wall length for roof reaction
l eff := min( w + 4 ⋅ h , s)
l eff = 2.5 ft

3. Roof loading per foot width of wall b := 1ft


s lr
Roof dead load PD1 := q D ⋅ PD1 = 1920 plf
l eff 2
⎛ lc ⎞
Wall dead load at midheight PD2 := h ⋅ ⎜ l p + ⋅ wc PD2 = 812.5 plf
⎝ 2 ⎠
s lr
Roof live load PL := q L ⋅ PL = 960 plf
l eff 2

4. Factored load combinations


(1.2D + 0.5Lr + 1.6W)
⎣ ( )
Pu := b ⋅ ⎡1.2⋅ PD1 + PD2 + 0.5⋅ PL⎤ Pu = 3.759 kips

Factored axial load at mid-height ⎛⎜ q W⋅ l c ⎞
2
e e
M ua := b ⋅ ⎜ 1.2⋅ PD1⋅ + 0.5⋅ PL⋅ + 1.6⋅
Moment (not-magnified) at ⎝ 2 2 8 ⎠
mid-height
M ua = 21.684 in⋅ kips

2
Ag := b ⋅ h Ag = 78 in
5. Check axial stress at mid-height

Gross area of concrete 0.06f'c = 240 psi

Allowable axial stress


Pu
= 48.192 psi
Ag
Axial stress check ⎛ Pu ⎞
if ⎜ ≤ 0.06⋅ f'c , "OK" , "NG" = "OK"
⎝ Ag ⎠

Slender Wall by Chapter 14.8.mcd 2-2 6/1/2006


www.pcaStructurePoint.com
[email protected]
847.966.4357 (HELP) phone
847.581.0644 fax

6. Panel properties

Gross moment of inertia 3


b⋅ h 4
Ig := Ig = 274.625 in
12
Pu
Depth of equivalent concrete stress + As⋅ b ⋅ fy
block φ
a := a = 0.36 in
0.85⋅ f'c⋅ b
a
Neutral axis depth c := c = 0.423 in
β1

0.003
Net tensile steel strain ε t := ⋅ ( d − c) ε t = 0.02
(Check if section is c
tension-controlled)
(
if ε t > 0.005 , "OK" , "NG" = "OK" )
b ⋅ ( c)
3 Es ⎛ Pu ⎞ 2
Cracked moment of inertia Icr := + ⋅ ⎜ As⋅ b + ⋅ ( d − c)
3 Ec
⎝ fy

Icr 4
= 0.057 Icr = 15.58 in
Ig
fr⋅ Ig
M cr := M cr = 40.082 in⋅ kips
Cracking moment h
2
⎛ ⎞⎛
Pu
⋅⎜d − ⎞
a
M n := fy ⋅ ⎜ As⋅ b +
Moment capacity φ⋅ fy ⎝ 2⎠
⎝ ⎠
M n = 45.059 in⋅ kips φ⋅ M n = 40.553 in⋅ kips

7. Check design strength vs. required


(
if φ⋅ M n ≥ M cr , "OK" , "NG" = "OK" )
strength
M ua
M u := M u = 32.988 in⋅ kips
Magnified moment 2
5Pu ⋅ l c
1−
0.75⋅ 48⋅ Ec⋅ Icr

Mu ⎛ Mu ⎞
= 0.813 if ⎜ ≤ 1 , "OK" , "NG" = "OK"
φ⋅ M n φ⋅ M n
⎝ ⎠
Ultimate load deflections 2
5M u ⋅ l c
∆ u := ∆ u = 3.007 in
0.75⋅ 48⋅ Ec⋅ Icr
Double-check magnified moments
(Should be equal to M ui)
M ua + Pu ⋅ ∆ u = 32.988 in⋅ kips

Slender Wall by Chapter 14.8.mcd 2-3 6/1/2006


www.pcaStructurePoint.com
[email protected]
847.966.4357 (HELP) phone
847.581.0644 fax

8. Check service load deflections


(1.0*D + 1.0*Lr + 1.0W)
(For seismic devide by 1.4 to reduce
to service level)
⎛⎜ q W⋅ l c ⎞
2
e e
Service load (not magnified) moment M sa := b ⋅ ⎜ 1.0⋅ PD1⋅ + 1.0⋅ PL⋅ + 1.0⋅
⎝ 2 2 8 ⎠

M sa = 17.4 in⋅ kips


Service load axial load

⎣ ( )
Ps := b ⋅ ⎡1.0⋅ PD1 + PD2 + 1.0⋅ PL⎤
⎦ Ps = 3.693 kips

Allowable service load displacement lc


∆ s.allowable := ∆ s.allowable = 1.28 in
150
Find magnified moment and effective
moment of inertia δ := 1 η := 1

Let the service magnified moment Given


Ms = δ Msa
δ = max⎡⎢ 1 , ⎤
1
where
2 ⎥
⎢ 5 ⋅ Ps⋅ l c ⎥
⎢ 1 − 48E ⋅ η ⋅ I ⎥
Let the effective moment of inertia ⎣ c ( g) ⎦
I e = η Ig
where ⎡ ⎛ M ⎞3 ⎡ 3⎤ ⎤
⎢ cr ⎢ ⎛ Mcr ⎞ ⎥ Icr ⎥
η = min 1 , ⎜ +
⎢ δ⋅ M ⎢1 − ⎜ ⋅
⎥ I ⎥
⎣ ⎝ sa ⎠ ⎣ ⎝ δ ⋅ Msa ⎠ ⎦ g⎦

⎛δ⎞
⎜ := Find( δ , η )
Solve for δ and η ⎝η ⎠

δ = 1.015 η = 1.000

Magnified service moment M s := δ ⋅ M sa M s = 17.653 in⋅ kips

4
Effective moment of inertia Ie := η ⋅ Ig Ie = 274.625 in

2
Service load displacement 5M s⋅ l c
∆ s := ∆ s = 0.068 in
48⋅ Ec⋅ Ie
Sevice load displacement check ∆s
= 0.053
∆ s.allowable

(
if ∆ s ≤ ∆ s.allowable , "OK" , "NG" = "OK" )
Slender Wall by Chapter 14.8.mcd 2-4 6/1/2006