0% found this document useful (0 votes)
121 views

Interconnection Earthing System

The document discusses interconnecting earthing systems according to BSEN 62305 and NFPA780 standards. It states that interconnecting earthing systems is recommended to reduce resistance and provide an equi-potentially bonded system. Both BSEN 62305 and NFPA780 support interconnecting lightning protection, electric service, communications, and underground piping grounds.

Uploaded by

Talha Altaf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
121 views

Interconnection Earthing System

The document discusses interconnecting earthing systems according to BSEN 62305 and NFPA780 standards. It states that interconnecting earthing systems is recommended to reduce resistance and provide an equi-potentially bonded system. Both BSEN 62305 and NFPA780 support interconnecting lightning protection, electric service, communications, and underground piping grounds.

Uploaded by

Talha Altaf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Project : AMAAD BUSINESS PARK HOTEL

Contractor : Sinohydro Corporation Limited.

Date : 02/09/2020.

Subject : Interconnection of Earthing System as per BSEN 62305 and NFPA780.

Dear Sir,

With reference to your query regarding interconnection of Earthing systems as per the subject
standards, please note that referring to below clauses from IEC/ BS EN and NFPA , it is evident that
interconnection of earthing systems is a preferred and recommended practice which helps in overall
reduction of resistance of earthing network and providing an equi-potentially bonded earthing system.

As per Part 3 of the BS EN 62305, section 5.4.1 [Earth-termination system] General:

"From the viewpoint of lightning protection, a single integrated structure earth-termination system is
preferable and is suitable for all purposes (i.e. lightning protection, power systems and
telecommunication systems)."
However approval and agreement of local authority or the owner of the system should be obtained.

American NFPA 780 standard which states in clauses 4.14.1 and 4.14.1.1:

4.14.1 - All grounding media and buried metallic conductors that can assist in providing a path for
lightning currents in or on a structure shall be interconnected to provide a common ground potential.
4.14.1.1 This interconnection shall include lightning protection, electric service, communications, and
antenna system grounds as well as underground metallic piping systems.

For any further clarification, please feel free to contact us.

Yours faithfully,

ABB Electrical Industries Ltd.

Rizgar Ali Shyam Rajendran

Senior Sales Specialist Technical Support Engineer - Furse