Buton, Joshua C.-Part3-Computation
Buton, Joshua C.-Part3-Computation
1-5
INDOOR TYPE SUBSTATIONS
DESIGN OF INDUSTRIAL CUSTOMER REQUIRING INDOOR TYPE SUBSTATION
PLANT NO. 1
Maximum Demand
Demand Factor =
Connected Load
Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL
Thus,
MDLL= (Lighing Load)(Demand Factor) = 50KW(.7) = 35KW
MDML= (Motor Load)(Demand Factor) = 209KW(.8) = 167.2 KW
Therefore,
Thus,
SIMD 198.235 KW
KVAT= = = 225.267KVA
Ave . Power Factor .88
KVAREF= 1.25(KVAT)= 1.25(225.267KVA) = 281.584KVA
Using 3 1- Ø Units:
281.584 KVA
KVAREF= = 93.861 KVA
3
KVAREF= 281.584KVA
Since,
3% .03
Safe DCVD= (Vs) = (230V) = 4.6V
150 % 1.5
Thus,
= 1.5(4.356)
=6.534V
Thus,
ACTUAL ACVD
%VD= x 100
Vs
6.534
%VD= x 100=2.84%
230
Since, 2.84%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
DESIGN OF INDUSTRIAL CUSTOMER REQUIRING INDOOR TYPE SUBSTATION
PLANT NO. 2
Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL
Thus,
MDLL= (Lighting Load)(Demand Factor) =80 KW(.84) = 67.2KW
MDML= (Motor Load)(Demand Factor) = 268KW(.84) = 225.96 KW
Therefore,
Hence,
∑ MD ' s 293.16 KW
SIMD= = = 266.509 KW
Diversity Factor 110%
Thus,
SIMD 266.509 KW
KVAT= = = 321.095 KVA
Ave . Power Factor .83
KVAREF= 1.25(KVAT)= 1.25(321.095 KVA) = 401.368 KW
401.368 KVA
KVAREF= = 133.789 KVA
3
USE 3-PCS 167.5 KVA, 1-Ø, DISTRIBUTION TRANSFORMER.
Since,
3% .03
Safe DCVD= (Vs) = (230V) = 4.6V
150 % 1.5
Thus,
21.4 I d ' 21.4(806.019)(540)
Circular Mill= = = 2,024,859.905 Cir-Mil
Safe DCVD 4.6
Therefore:
= 1.5(4.1397)
=6.2096V
Thus,
ACTUAL ACVD
%VD= x 100
Vs
6.2096
%VD= x 100=2.70%
230
Since, 2.70%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
DESIGN OF INDUSTRIAL CUSTOMER REQUIRING INDOOR TYPE SUBSTATION
PLANT NO. 3
Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL
Thus,
MDLL= (Lighing Load)(Demand Factor) = 90KW(.82) = 73.8KW
MDML= (Motor Load)(Demand Factor) = 169KW(.84) = 141.96 KW
Therefore,
∑ MD ' s 215.76 KW
SIMD= = = 179.8 KW
Diversity Factor 120 %
Thus,
SIMD 179.8 KW
KVAT= = = 214.048 KVA
Ave . Power Factor .84
214.048 KVA
KVAREF= = 267.56 KVA
3
KVAREF= 214.048 KW
Therefore use 1 pc. Of a 300 KVA 3- Ø D.T.
3% .03
Safe DCVD= (Vs) = (230V) = 4.6V
150 % 1.5
Thus,
Therefore:
= 1.5(4.139)
=6.209V
Thus,
ACTUAL ACVD
%VD= x 100
Vs
6.209
%VD= x 100=2.70%
230
Since, 2.70%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
DESIGN OF INDUSTRIAL CUSTOMER REQUIRING INDOOR TYPE SUBSTATION
PLANT NO. 4
Thus,
MDLL= (Lighing Load)(Demand Factor) = 90KW(.82) = 73.8KW
MDML= (Motor Load)(Demand Factor) = 159KW(.83) = 131.97 KW
Therefore,
Hence,
∑ MD ' s 205.77 KW
SIMD= = = 203.733 KW
Diversity Factor 101 %
Thus,
SIMD 203.733 KW
KVAT= = = 248.455 KVA
Ave . Power Factor .82
KVAREF= 1.25(KVAT)= 1.25(248.455 KVA) = 310.569 KVA
Using 3 1- Ø Units:
310.569 KVA
KVAREF= = 103.522 KVA
3
Since,
3% .03
Safe DCVD= (Vs) = (230V) = 4.6V
150 % 1.5
Thus,
Therefore:
= 1.5(4.118)
=6.177 V
Thus,
ACTUAL ACVD
%VD= x 100
Vs
6.177
%VD= x 100=2.69%
230
Since, 2.69%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
PLANT NO. 5
Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL
Thus,
MDLL= (Lighing Load)(Demand Factor) = 90KW(.82) = 73.8KW
MDML= (Motor Load)(Demand Factor) = 149KW(.83) = 123.67 KW
Therefore,
∑ MD ' s 197.47 KW
SIMD= = = 181.165 KW
Diversity Factor 109 %
Thus,
SIMD 181.165 KW
KVAT= = = 210.657 KVA
Ave . Power Factor .86
KVAREF= 1.25(KVAT)= 1.25(210.657 KVA) = 263.321 KVA
Using 3 1- Ø Units:
263.321 KVA
KVAREF= = 87.774 KVA
3
Since,
3% .03
Safe DCVD= (Vs) = (230V) = 4.6V
150 % 1.5
Thus,
Therefore:
= 1.5(4.074)
=6.111V
Thus,
ACTUAL ACVD
%VD= x 100
Vs
6.111
%VD= x 100= 2.66%
230
Since, 2.66%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
Where,
Also,
5% .05
Safe DCVD= (VP) = (7620V) = 254 V
150 % 1.5
Thus,
21.4(128.887)(700)
Circular Mill= =7,601.288 cir-mil
254
Therefore,
Using Method 2:
Actual ACVD=
√3 I d ' [Ra cos θ +Xt sin θ]
5280
Where,
cos θ = cos(32.346)=0.844
sin θ = sin (32.346)=0.536
From wire table
Ra= 3.79 Ω/mi
Xa=.665 Ω/mi
Xd= 0.187-((0.187-0.185)*(56-55.437)/(56-55))
Xd = 0.186Ω/mi
XT= Xa+Xd= 0.665+0.186 = 0.851 Ω/mi
Thus,
Actual ACVD=
√ 3 (128.887)( 700) [(3.79) (0.844) + (0.851)(0.536)]
5280
ACTUAL ACVD= 108.171 V
Therefore,
%VD = (108.171 Volts / 7620 Volts)*100 = 1.42%
1.42 % is less than the Allowable Voltage Drop of 5.00%. Therefore,
load is SAFE!
Using Method 3:
I. BUSBAR RATINGS
The busbar rating is a copper alloy UNSC1100 using the electrical busbar
ampacity of 100-149A at 30 o C rise 60 Hz. The dimension of the busbar is
1 3
x inches.
16 4
II. OPEN FUSED CUT-OUT RATINGS
For plant 1,3 and 5
KVA 300 x 103
I= = = 22.730 A
√ 3 Vp √ 3 (7620)
Therefore,
Use 3 pcs of 100-200 A, A type R and type T fuse link.
For plant 2 and 4
KVA 500 x 10 3
I= = = 37.884 A
√ 3 Vp √ 3 (7620)
Therefore,
Use 3 pcs of 100A, Standard Fuse Link(k Type) and Polymer
concrete Cut-outs.
III. INSTRUMENT TRANSFORMER AND ACCESSORIES
A. Current Transformer Ratings
For Plant 1,3 and 5
KVA 300 x 103
I= = = 22.730 A
√ 3 Vp √ 3 (7620)
For plant 2 and 4
KVA 500 x 10 3
I= = = 37.884 A
√ 3 Vp √ 3 (7620)
Therefore, Use an indoor type current transformer bushing with primary voltage of 7.72
KV to 40.5 KV, primary current of 500 A to 5000 A, A secondary current of 1A to 5A,
frequency of 50Hz-60Hz.
7620
KVref= = 4.399 KV
√3
Therefore,
Use 3 pcs of Series 1 Polymer Housed, Zinc-Oxide Lightning Arrester
without cap, 6.3 KV to 36 KV, All ratings are available from 5to 10 MVA.
V. TRANSFORMER RATINGS
For Plant 1,3 and 5, use 1 unit of 300 KVA, 3-Ø Distribution Transformer.
VI. SHUNT CAPACITOR RATINGS
Capacitor bank 3-35 KV high voltage passive collective compensation
used in the system up to 35 KV to enhance power factor.
VII. TRANSDUCER RATINGS
Use 5-010 A current transducer, VT-120 A voltage
transducer and PC-010 A power transducer.
VIII. RECLOSER RATING
Use type 6H, 3- Ø, 100 A recloser
IX. CIRCUIT BREAKER RATINGS
7620
KVAref= = 4.399KV
√3
Iref= 250%(22.730)=56.825 A
Iref= 250%()=56.825 A
Therefore,
1120 FT
500 FT
PLANT NO. 6
Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL
Thus,
MDLL= (Lighing Load)(Demand Factor) = 305 KW(.86) = 262.3 KW
MDML= (Motor Load)(Demand Factor) = 302 KW(.84) = 253.6 KW
Therefore,
∑ MD ' s 515.98 KW
SIMD= = = 469.73 KW
Diversity Factor 110 %
Thus,
SIMD 469.73 KW
KVAT= = = 545.434 KVA
Ave . Power Factor .86
KVAREF= 1.25(KVAT)= 1.25(545.434 KVA) = 681.793 KVA
Using 3 1- Ø Units:
681.793 KVA
KVAREF= = 227.264 KVA
3
Since,
3% .03
Safe DCVD= (Vs) = (220V) = 4.4V
150 % 1.5
Thus,
Therefore:
= 1.5(4.376)
=6.564 V
Thus,
ACTUAL ACVD
%VD= x 100
Vs
6.564
%VD= x 100=2.98%
220
Since, 2.98%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
Thus,
Since,
21.4 Id '
Cir-Mil=
SAFE DCVD
KVAt
I=
√ 3 Vp
750 X 10 3
I= = 56.826A
√3 (7620)
Also,
5%
Safe DCVD= (7620)
150 %
= 254V
Thus,
21.4(58.826)(1260)
Cir-Mil= = 6244.820 Cir-Mil
254 V
THEREFORE,
METHOD 2:
ACTUAL ACVD = ( Id’√3/5280)* [Ra cos θ +Xt sin θ]
Xd= 0.187-((0.187-0.185)*(56-55.437)/(56-55))
Xd = 0.186Ω/mi
Therefore,
XT= 0.665+0.186=0.851 Ω/mi
Thus,
Actual ACVD= ( (58.826)(1260)√3/5280)* [(3.79)(0.86) +(0.851)(0.51)])
Actual ACVD= 89.804 V
Therefore,
ACTUAL ACVD
%VD= x 100%
Vp
89.804
%VD= x 100% = 1.17 %
7620
Since,
1.17%< 5%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
DESIGN OF INDUSTRIAL CUSTOMER REQUIRING OUTDOOR TYPE SUBSTATION
PLANT NO. 7
Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL
Thus,
MDLL= (Lighing Load)(Demand Factor) = 305 KW(.84) = 256.2 KW
MDML= (Motor Load)(Demand Factor) = 325 KW(.86) = 279.5 KW
Therefore,
∑ MD ' s 535.7 KW
SIMD= = =510.190 KW
Diversity Factor 105 %
Thus,
SIMD 510.190 KW
KVAT= = = 600.224 KVA
Ave . Power Factor .85
KVAREF= 1.25(KVAT)= 1.25(600.224KVA) = 750.28 KVA
Using 3 1- Ø Units:
750.28 KVA
KVAREF= = 250.093 KVA
3
Since,
3% .03
Safe DCVD= (Vs) = (220V) = 4.4V
150 % 1.5
Thus,
Therefore:
= 1.5(4.214)
=6.321 V
Thus,
ACTUAL ACVD
%VD= x 100
Vs
6.321
%VD= x 100= 2.87%
220
Since, 2.87%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
Thus,
KVAT= 1000< 31.788o KVA
Since,
21.4 Id '
Cir-Mil=
SAFE DCVD
KVAt
I=
√ 3 Vp
1000 X 103
I= = 75.768 A
√3 (7620)
Also,
5%
Safe DCVD= (7620)
150 %
= 254V
Thus,
21.4(75.768)(1120)
Cir-Mil= = 7,149.636 Cir-Mil
254 V
THEREFORE,
METHOD 2:
ACTUAL ACVD = ( Id’√3/5280)* [Ra cos θ +Xt sin θ]
Where, cos θ= .85
sin θ= .53
Xd= 0.187-((0.187-0.185)*(56-55.437)/(56-55))
Xd = 0.186Ω/mi
Therefore,
XT= 0.665+0.186= 0.851 Ω/mi
Thus,
Actual ACVD= ((75.768)(1120)√3/5280)* [(3.79)(0.85) +(0.851)(0.53)])
Actual ACVD=102.234 V
Therefore,
ACTUAL ACVD
%VD= x 100%
Vp
102.234
%VD= x 100% = 1.34%
7620
Since,
1.34%<5%,THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
DESIGN OF INDUSTRIAL CUSTOMER REQUIRING OUTDOOR TYPE SUBSTATION
PLANT NO. 8
Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL
Thus,
MDLL= (Lighing Load)(Demand Factor) = 98KW(.85) = 83.3 KW
MDML= (Motor Load)(Demand Factor) = 159KW(.85) = 135.15 KW
Therefore,
∑ MD ' s 218.45 KW
SIMD= = = 200.413 KW
Diversity Factor 109 %
Thus,
SIMD 200.413 KW
KVAT= = = 233.038 KVA
Ave . Power Factor .85
KVAREF= 1.25(KVAT)= 1.25(233.038 KVA) = 291.298 KVA
Using 3 1- Ø Units:
291.298 KVA
KVAREF= = 97.079 KVA
3
Since,
3% .03
Safe DCVD= (Vs) = (220V) = 4.4V
150 % 1.5
Thus,
Therefore:
= 1.5(4.363)
=6.545 V
Thus,
ACTUAL ACVD
%VD= x 100
Vs
6.545
%VD= x 100=2.98 %
220
Since, 2.98%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
Thus,
Since,
21.4 Id '
Cir-Mil=
SAFE DCVD
KVAt
I=
√ 3 Vp
300 X 10 3
I= = 22.730 A
√3 (7620)
Also,
5%
Safe DCVD= (7620)
150 %
= 254 V
Thus,
21.4(22.73)(1680)
Cir-Mil= = 3217.279 Cir- Mil
254 V
Therefore,
METHOD 2:
ACTUAL ACVD = ( Id’√3/5280)* [Ra cos θ +Xt sin θ]
Where, cos θ= .86
sin θ= .51
Xd= 0.187-((0.187-0.185)*(56-55.437)/(56-55))
Xd = 0.186Ω/mi
Therefore,
XT= 0.665+0.186=0.851 Ω/mi
Thus,
Actual ACVD= ((22.73)(1680)√3/5280)* [(3.79)(0.86)+(0.851)(0.51)])
Actual ACVD= 46.266 V
Therefore,
ACTUAL ACVD
%VD= x 100%
Vp
46.266
%VD= x 100%=0.607%
7620
Since,
0.607%<5%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
DESIGN OF INDUSTRIAL CUSTOMER REQUIRING OUTDOOR TYPE SUBSTATION
PLANT NO. 9
Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL
Thus,
MDLL= (Lighting Load)(Demand Factor) = 93 KW(.83) =77.19 KW
MDML= (Motor Load)(Demand Factor) = 149KW(.82) = 122.18 KW
Therefore,
∑ MD ' s 199.37 KW
SIMD= = = 182.908 KW
Diversity Factor 109 %
Thus,
SIMD 182.908 KW
KVAT= = = 220.371 KVA
Ave . Power Factor .83
KVAREF= 1.25(KVAT)= 1.25(220.371 KVA) = 275.464 KVA
Using 3 1- Ø Units:
275.464 KVA
KVAREF= = 91.821 KVA
3
Since,
3% .03
Safe DCVD= (Vs) = (220V) = 4.4 V
150 % 1.5
Thus,
Therefore:
= 1.5(3.868)
=5.802 V
Thus,
ACTUAL ACVD
%VD= x 100
Vs
5.802
%VD= x 100=2.64%
220
Since,
2.64%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
Thus,
Since,
21.4 Id '
Cir-Mil=
SAFE DCVD
KVAt
I=
√ 3 Vp
300 X 10 3
I= = 22.730 A
√3 (7620)
Also,
5%
Safe DCVD= (7620)
150 %
= 254V
Thus,
21.4(22.730)(700)
Cir-Mil= = 1,340.533 Cir-Mil
254 V
Therefore,
Use 3 pcs. of 16,510 (AWG NO.8) of Copper Conductor
METHOD 2:
ACTUAL ACVD = ( Id’√3/5280)* [Ra cos θ +Xt sin θ]
Where, cos θ= .83
sin θ= .56
From wire table
Ra= 3.79 Ω
Xa= 0.665 Ω
GMD= √3 (44)(44 )(88)=55.437
55 .185
55.437 xd
56 .187
Xd= 0.187-((0.187-0.185)*(56-55.437)/(56-55))
Xd = 0.186Ω/mi
Therefore,
XT= 0.665+.186=0.851 Ω/mi
Thus,
Actual ACVD= ((22.730)(700)√3/5280)* [(3.79)(0.83)+(0.851(0.56)]
Actual ACVD= 18.906 V
Therefore,
ACTUAL ACVD
%VD= x 100%
Vp
18.906
%VD= x 100%=0.248%
7620
Since,
X. BUSBAR RATINGS
The busbar rating is a copper alloy UNSC1100 using the electrical busbar
ampacity of 100-149A at 30 o C rise 60 Hz. The dimension of the busbar is
1 3
x inches.
16 4
XI. OPEN FUSED CUT-OUT RATINGS
For plant 6
KVA 750 x 10 3
I= = = 56.826 A
√ 3 Vp √ 3 (7620)
Therefore,
Use 3 pcs of type R and type T fuse link.
For plant 7
KVA 1000 x 103
I= = = 75.768 A
√ 3 Vp √ 3(7620)
Therefore,
Use 3 pcs of type R and type T fuse link.
For plant 8 & 9
KVA 300 x 103
I= = = 22.730 A
√ 3 Vp √ 3 (7620)
Therefore,
Use 3 pcs of type R and type T fuse link
XII. INSTRUMENT TRANSFORMER AND ACCESSORIES
D. Current Transformer Ratings
For Plant 6
I= 56.826 A
For plant 7
I=75.768 A
For plant 8 & 9
I= 22.730 A
Therefore, Use an indoor type current transformer bushing with primary voltage
of 7.72 KV to 40.5 KV, primary current of 500 A to 5000 A, A secondary current of
1A to 5A, frequency of 50Hz-60Hz.
Frequency Meter
FRZ-DIG Frequency meter from 40-80 Hz.
Switchboard Style
7620
KVAref= = 4.399 KV
√3
Therefore,