Buton, Joshua C.-Part3-Computation

The document discusses the design requirements for indoor type substations for 4 industrial plants. It calculates the distribution transformer rating, motor and lighting loads, demand factors, diversity factor and average power factor to determine the required KVA rating. It also calculates the size of the secondary feeder and recommends the minimum copper conductor size to safely carry the required load in each case.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
100 views

Buton, Joshua C.-Part3-Computation

The document discusses the design requirements for indoor type substations for 4 industrial plants. It calculates the distribution transformer rating, motor and lighting loads, demand factors, diversity factor and average power factor to determine the required KVA rating. It also calculates the size of the secondary feeder and recommends the minimum copper conductor size to safely carry the required load in each case.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 49

INDUSTRIAL CUSTOMER NO.

1-5
INDOOR TYPE SUBSTATIONS
DESIGN OF INDUSTRIAL CUSTOMER REQUIRING INDOOR TYPE SUBSTATION

PLANT NO. 1

Lighting Load- 50 KW, 3-Ø, 230 volts

Demand Factor- 70%

Motor Load- 209 KW, 3-Ø,230 volts

Demand Factor- 80%

Average Power Factor- 88%

Diversity Factor- 102%

I. DISTRIBUTION TRANSFORMER RATING


SINCE,

Maximum Demand
Demand Factor =
Connected Load

Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL

Thus,
MDLL= (Lighing Load)(Demand Factor) = 50KW(.7) = 35KW
MDML= (Motor Load)(Demand Factor) = 209KW(.8) = 167.2 KW

Therefore,

∑ MD ' s= 35KW + 167.2 KW= 202.2KW


Hence,
∑ MD ' s 202.2 KW
SIMD= = = 198. 235 KW
Diversity Factor 102 %

Thus,

SIMD 198.235 KW
KVAT= = = 225.267KVA
Ave . Power Factor .88
KVAREF= 1.25(KVAT)= 1.25(225.267KVA) = 281.584KVA

Using 3 1- Ø Units:

281.584 KVA
KVAREF= = 93.861 KVA
3

Therefore use 3 pcs. O 100 KVA 1- Ø D.T.

Using of a single 3- Ø Unit:

KVAREF= 281.584KVA

Therefore use 1 pc. Of a 300 KVA 3- Ø D.T.

II. Size of Secondary Feeder


21.4 I d '
Circular Mill=
Safe DCVD

Where: d’= 540 ft.

I= KVAT/ √3 Vs = 225.267*103/√3 (230) = 565.469 A

Since,

3% .03
Safe DCVD= (Vs) = (230V) = 4.6V
150 % 1.5

Thus,

21.4 I d ' 21.4(565.469)(540)


Circular Mill= = = 1,420,556.47 Cir-Mil
Safe DCVD 4.6
Therefore:

Minimum Recommended Rating:

Use 3 pcs of 1,500,000 Circular Mills Copper Conductor

Use 1 pc of 750,000 Circular Mills Copper Conductor for neutral wire.

21.4 I d ' 21.4(565.469)(540)


Actual ACVD= = = 4.356V
ACTUAL CIR−MIL 1500000

Actual ACVD= 150% of Actual ACVD

= 1.5(4.356)

=6.534V

Thus,

ACTUAL ACVD
%VD= x 100
Vs

6.534
%VD= x 100=2.84%
230

Since, 2.84%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
DESIGN OF INDUSTRIAL CUSTOMER REQUIRING INDOOR TYPE SUBSTATION

PLANT NO. 2

Lighting Load- 80 KW, 3-Ø, 230 volts

Demand Factor- 84%

Motor Load- 269 KW, 3-Ø,230 volts

Demand Factor- 84%

Average Power Factor- 83%

Diversity Factor- 110%

I. DISTRIBUTION TRANSFORMER RATING


SINCE,
Maximum Demand
Demand Factor =
Connected Load

Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL

Thus,
MDLL= (Lighting Load)(Demand Factor) =80 KW(.84) = 67.2KW
MDML= (Motor Load)(Demand Factor) = 268KW(.84) = 225.96 KW
Therefore,

∑ MD ' s=67.2 KW +225.96 KW= 293.16 KW

Hence,

∑ MD ' s 293.16 KW
SIMD= = = 266.509 KW
Diversity Factor 110%

Thus,

SIMD 266.509 KW
KVAT= = = 321.095 KVA
Ave . Power Factor .83
KVAREF= 1.25(KVAT)= 1.25(321.095 KVA) = 401.368 KW

401.368 KVA
KVAREF= = 133.789 KVA
3
USE 3-PCS 167.5 KVA, 1-Ø, DISTRIBUTION TRANSFORMER.

Using of a single 3- Ø Unit:

KVAREF= 401.369 KVA


Therefore use 1 pc. Of a 500 KVA 3- Ø D.T.

II. Size of Secondary Feeder


21.4 I d '
Circular Mill=
Safe DCVD

Where: d’= 540 ft.

I= KVAT/ √3 Vs = 321.095*103/√3 (230) = 806.019 A

Since,

3% .03
Safe DCVD= (Vs) = (230V) = 4.6V
150 % 1.5

Thus,
21.4 I d ' 21.4(806.019)(540)
Circular Mill= = = 2,024,859.905 Cir-Mil
Safe DCVD 4.6

Therefore:

Minimum Recommended Rating:

Use 3 pcs of 2,125,000 Circular Mills Copper Conductor

Use 1 pc of 1,125,000 Circular Mills Copper Conductor for neutral wire.

21.4 I d ' 21.4(806.019)(540)


Actual ACVD= = = 4.1397V
ACTUAL CIR−MIL 2250000

Actual ACVD= 150% of Actual ACVD

= 1.5(4.1397)

=6.2096V

Thus,

ACTUAL ACVD
%VD= x 100
Vs

6.2096
%VD= x 100=2.70%
230

Since, 2.70%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
DESIGN OF INDUSTRIAL CUSTOMER REQUIRING INDOOR TYPE SUBSTATION

PLANT NO. 3

Lighting Load- 90 KW, 3-Ø, 230 volts

Demand Factor- 82%

Motor Load- 169 KW, 3-Ø,230 volts

Demand Factor- 84%

Average Power Factor- 84%

Diversity Factor- 120%

I. DISTRIBUTION TRANSFORMER RATING


SINCE,
Maximum Demand
Demand Factor =
Connected Load

Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL

Thus,
MDLL= (Lighing Load)(Demand Factor) = 90KW(.82) = 73.8KW
MDML= (Motor Load)(Demand Factor) = 169KW(.84) = 141.96 KW

Therefore,

∑ MD ' s= 73.8KW + 141.96 KW= 215.76 KW


Hence,

∑ MD ' s 215.76 KW
SIMD= = = 179.8 KW
Diversity Factor 120 %

Thus,

SIMD 179.8 KW
KVAT= = = 214.048 KVA
Ave . Power Factor .84

KVAREF= 1.25(KVAT)= 1.25(214.048 KVA) = 214.048 KW


Using 3 1- Ø Units:

214.048 KVA
KVAREF= = 267.56 KVA
3

Therefore use 3 pcs. O 100 KVA 1- Ø D.T.

Using of a single 3- Ø Unit:

KVAREF= 214.048 KW
Therefore use 1 pc. Of a 300 KVA 3- Ø D.T.

II. Size of Secondary Feeder


21.4 I d '
Circular Mill=
Safe DCVD

Where: d’= 540 ft.

I= KVAT/ √3 Vs = 214.048*103/√3 (230) = 537.037 A


Since,

3% .03
Safe DCVD= (Vs) = (230V) = 4.6V
150 % 1.5

Thus,

21.4 I d ' 21.4(537.037)(540)


Circular Mill= = = 1,349,808.629 Cir-Mil
Safe DCVD 4.6

Therefore:

Minimum Recommended Rating:

Use 3 pcs of 1,500,000 Circular Mills Copper Conductor

Use 1 pc of 750,000 Circular Mills Copper Conductor for neutral wire.

21.4 I d ' 21.4(537.307)(540)


Actual ACVD= = = 4.139V
ACTUAL CIR−MIL 1500000

Actual ACVD= 150% of Actual ACVD

= 1.5(4.139)

=6.209V

Thus,

ACTUAL ACVD
%VD= x 100
Vs

6.209
%VD= x 100=2.70%
230

Since, 2.70%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
DESIGN OF INDUSTRIAL CUSTOMER REQUIRING INDOOR TYPE SUBSTATION

PLANT NO. 4

Lighting Load- 59 KW, 3-Ø, 230 volts

Demand Factor- 82%

Motor Load-159 KW, 3-Ø,230 volts

Demand Factor- 83%

Average Power Factor- 28%

Diversity Factor- 101%

I. DISTRIBUTION TRANSFORMER RATING


SINCE,
Maximum Demand
Demand Factor =
Connected Load
Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL

Thus,
MDLL= (Lighing Load)(Demand Factor) = 90KW(.82) = 73.8KW
MDML= (Motor Load)(Demand Factor) = 159KW(.83) = 131.97 KW

Therefore,

∑ MD ' s= 73.8KW + 131.97 KW= 205.77 KW

Hence,

∑ MD ' s 205.77 KW
SIMD= = = 203.733 KW
Diversity Factor 101 %

Thus,

SIMD 203.733 KW
KVAT= = = 248.455 KVA
Ave . Power Factor .82
KVAREF= 1.25(KVAT)= 1.25(248.455 KVA) = 310.569 KVA
Using 3 1- Ø Units:

310.569 KVA
KVAREF= = 103.522 KVA
3

USE 3-PCS 125 KVA, 1-Ø, DISTRIBUTION TRANSFORMER..

Using of a single 3- Ø Unit:

KVAREF= 310.569 KVA


II. USE 1-PC OF 500 KVA, 3-Ø, DISTRIBUTION TRANSFORMER
III. Size of Secondary Feeder
21.4 I d '
Circular Mill=
Safe DCVD

Where: d’= 540 ft.

I= KVAT/ √3 Vs = 248.455*103/√3 (230) = 623.676 A

Since,

3% .03
Safe DCVD= (Vs) = (230V) = 4.6V
150 % 1.5

Thus,

21.4 I d ' 21.4(623.676)(540)


Circular Mill= = = 1,566,782.577 Cir-Mil
Safe DCVD 4.6

Therefore:

Minimum Recommended Rating:

Use 3 pcs of 1,750,000 Circular Mills Copper Conductor

Use 1 pc of 875,000 Circular Mills Copper Conductor for neutral wire.

21.4 I d ' 21.4(623.676)(540)


Actual ACVD= = = 4.118 V
ACTUAL CIR−MIL 1750000

Actual ACVD= 150% of Actual ACVD

= 1.5(4.118)

=6.177 V

Thus,
ACTUAL ACVD
%VD= x 100
Vs

6.177
%VD= x 100=2.69%
230

Since, 2.69%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.

DESIGN OF INDUSTRIAL CUSTOMER REQUIRING INDOOR TYPE SUBSTATION

PLANT NO. 5

Lighting Load- 90 KW, 3-Ø, 230 volts

Demand Factor- 82%

Motor Load- 149 KW, 3-Ø,230 volts

Demand Factor- 83%

Average Power Factor- 86%

Diversity Factor- 109%

I. DISTRIBUTION TRANSFORMER RATING


SINCE,
Maximum Demand
Demand Factor =
Connected Load

Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL

Thus,
MDLL= (Lighing Load)(Demand Factor) = 90KW(.82) = 73.8KW
MDML= (Motor Load)(Demand Factor) = 149KW(.83) = 123.67 KW

Therefore,

∑ MD ' s= 73.8 KW + 123.67 KW= 197.47 KW


Hence,

∑ MD ' s 197.47 KW
SIMD= = = 181.165 KW
Diversity Factor 109 %

Thus,

SIMD 181.165 KW
KVAT= = = 210.657 KVA
Ave . Power Factor .86
KVAREF= 1.25(KVAT)= 1.25(210.657 KVA) = 263.321 KVA

Using 3 1- Ø Units:

263.321 KVA
KVAREF= = 87.774 KVA
3

Therefore use 3 pcs. O 100 KVA 1- Ø D.T.

Using of a single 3- Ø Unit:


KVAREF= 263.321 KVA

Therefore use 1 pc. Of a 300 KVA 3- Ø D.T.

II. Size of Secondary Feeder


21.4 I d '
Circular Mill=
Safe DCVD

Where: d’= 540 ft.

I= KVAT/ √3 Vs = 210.657*103/√3 (230) = 528.795 A

Since,

3% .03
Safe DCVD= (Vs) = (230V) = 4.6V
150 % 1.5

Thus,

21.4 I d ' 21.4(528.795)(540)


Circular Mill= = = 1,328,425.004 Cir-Mil
Safe DCVD 4.6

Therefore:

Minimum Recommended Rating:

Use 3 pcs of 1,500,000 Circular Mills Copper Conductor

Use 1 pc of 750,000 Circular Mills Copper Conductor for neutral wire.

21.4 I d ' 21.4(528.795)(540)


Actual ACVD= = = 4.074V
ACTUAL CIR−MIL 1500000

Actual ACVD= 150% of Actual ACVD

= 1.5(4.074)

=6.111V
Thus,

ACTUAL ACVD
%VD= x 100
Vs

6.111
%VD= x 100= 2.66%
230

Since, 2.66%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.

SIZE OF PRIMARY FEEDER FOR PLANT 1 TO 5


ANGLE OF PLANT 1= cos-1 0.88 = 28.358o
ANGLE OF PLANT 2= cos-1 0.83 = 33.901o
ANGLE OF PLANT 3= cos-1 0.84 = 32.860o
ANGLE OF PLANT 4= cos-1 0.82 = 34.915o
ANGLE OF PLANT 5= cos-1 0.86 = 30.683o
Thus,
KVAT= KVA1+ KVA2 +KVA3+ KVA4+ KVA5
=3(100)<28.358o+3(167.5)<33.901o+3(75)<32.860o
+3(125)<34.915o+3(100)<30.683o
KVAT= 1701.079<32.443 KVA
Since,
21.4 I d '
Circular Mill=
Safe DCVD

Where,

d’= 5(140)= 700 ft

I= KVAT/ √3 Vp = 1701.079*103/√3 (7620)= 128.887 A

Also,

5% .05
Safe DCVD= (VP) = (7620V) = 254 V
150 % 1.5

Thus,

21.4(128.887)(700)
Circular Mill= =7,601.288 cir-mil
254

Therefore,

Use 3 pcs of 16,510 CM(AWG NO.8) of copper conductor

Using Method 2:

Actual ACVD=
√3 I d ' [Ra cos θ +Xt sin θ]
5280
Where,

cos θ = cos(32.346)=0.844
sin θ = sin (32.346)=0.536
From wire table
Ra= 3.79 Ω/mi
Xa=.665 Ω/mi

GMD = √3 (44)(44 )(88) = 55.437


55 .185
55.437 xd
56 .187

Xd= 0.187-((0.187-0.185)*(56-55.437)/(56-55))
Xd = 0.186Ω/mi
XT= Xa+Xd= 0.665+0.186 = 0.851 Ω/mi

Thus,

Actual ACVD=
√ 3 (128.887)( 700) [(3.79) (0.844) + (0.851)(0.536)]
5280
ACTUAL ACVD= 108.171 V
Therefore,
%VD = (108.171 Volts / 7620 Volts)*100 = 1.42%
1.42 % is less than the Allowable Voltage Drop of 5.00%. Therefore,
load is SAFE!

Using Method 3:

Using IEEE Exact Voltage Drop Formula

VD= V + I R cos θ + I X sin θ - √(V2 -(I X cos θ - I R sin θ)2))


Since, Rt=3.79(700)/5280= 0.502 Ω
Xt= 0.851(700)/5280= .113 Ω
Thus,
VD= 7.62*10^3+(128.887*0.502*0.844)+(128.887*0.113*0.536)-
√7.62*10^3-(128.887*0.113*0.844)-(128.887 *0.502*0.536) 2
VD= 62.472 Volts
Actual ACVD = 62.472 * √3 = 108.205 Volts
%VD = 108.205 / 7.62*10^3 = 1.42 %
1.42 % < 5.00%. Therefore, THE WIRE CAN SAFELY CARRY THE
REQUIRED LOAD.

Sizes and Ratings of Different Equipment For Plant 1,2,3,4 and 5.

I. BUSBAR RATINGS
The busbar rating is a copper alloy UNSC1100 using the electrical busbar
ampacity of 100-149A at 30 o C rise 60 Hz. The dimension of the busbar is

1 3
x inches.
16 4
II. OPEN FUSED CUT-OUT RATINGS
For plant 1,3 and 5
KVA 300 x 103
I= = = 22.730 A
√ 3 Vp √ 3 (7620)
Therefore,
Use 3 pcs of 100-200 A, A type R and type T fuse link.
For plant 2 and 4
KVA 500 x 10 3
I= = = 37.884 A
√ 3 Vp √ 3 (7620)
Therefore,
Use 3 pcs of 100A, Standard Fuse Link(k Type) and Polymer
concrete Cut-outs.
III. INSTRUMENT TRANSFORMER AND ACCESSORIES
A. Current Transformer Ratings
For Plant 1,3 and 5
KVA 300 x 103
I= = = 22.730 A
√ 3 Vp √ 3 (7620)
For plant 2 and 4
KVA 500 x 10 3
I= = = 37.884 A
√ 3 Vp √ 3 (7620)

Therefore, Use an indoor type current transformer bushing with primary voltage of 7.72
KV to 40.5 KV, primary current of 500 A to 5000 A, A secondary current of 1A to 5A,
frequency of 50Hz-60Hz.

B. Potential Transformer Rating


Use an indoor type of potential transformer with primary voltage of
1KV to 35 KV, secondary voltage of 0.1 to 0.12 KV and frequency of
50-60Hz.
C. Accessories
 Maximum Demand Meter
Bi-Metallic maximum demand meter
 Power factor meter
A digital PQQWE factor meter input voltage, 3- Ø wire system
110+10% or 45+ 10%, 3- Ø 50 Hz.
 AC Kilowatt-Hour meter
220 “H”-series DIN panel nominal voltages 63.5
V,110V,120V,220V,240V,400V,415V,440V, and 480 V AC.
 AC Voltmeter
VMD 1-2 Voltmeter for AC and DC from 0-600 V.
 AC Ammeter
AMT- 01-AC, Amperes with scales from 15A-999A.
 Frequency Meter
FRZ-DIG Frequency meter from 40-80 Hz.
 Switchboard Style

LV Switchboard(Modular Steel Sheet Construction).

IV. LIGHTNING ARRESTER

7620
KVref= = 4.399 KV
√3

Therefore,
Use 3 pcs of Series 1 Polymer Housed, Zinc-Oxide Lightning Arrester
without cap, 6.3 KV to 36 KV, All ratings are available from 5to 10 MVA.

V. TRANSFORMER RATINGS
For Plant 1,3 and 5, use 1 unit of 300 KVA, 3-Ø Distribution Transformer.
VI. SHUNT CAPACITOR RATINGS
Capacitor bank 3-35 KV high voltage passive collective compensation
used in the system up to 35 KV to enhance power factor.
VII. TRANSDUCER RATINGS
Use 5-010 A current transducer, VT-120 A voltage
transducer and PC-010 A power transducer.
VIII. RECLOSER RATING
Use type 6H, 3- Ø, 100 A recloser
IX. CIRCUIT BREAKER RATINGS
7620
KVAref= = 4.399KV
√3

For Plant 1,3,and 5

Iref= 250%(22.730)=56.825 A

For plant 2 and 4

Iref= 250%()=56.825 A

Therefore,

Use 4.76 KV, 1200A continuous current rating circuit breaker.

INDUSTRIAL CUSTOMER NO. 6 AND 7


OUTDOOR TYPE SUBSTATIONS
1260 FT

1120 FT

INDUSTRIAL CUSTOMER NO. 8 AND 9


OUTDOOR TYPE SUBSTATIONS
1680 FT

500 FT

DESIGN OF INDUSTRIAL CUSTOMER REQUIRING OUTDOOR TYPE SUBSTATION

PLANT NO. 6

Lighting Load- 305 KW, 3-Ø, 220 volts

Demand Factor- 86%


Motor Load- 302 KW, 3-Ø,220 volts

Demand Factor- 84%

Average Power Factor- 86%

Diversity Factor- 110%

I. DISTRIBUTION TRANSFORMER RATING


SINCE,
Maximum Demand
Demand Factor =
Connected Load

Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL

Thus,
MDLL= (Lighing Load)(Demand Factor) = 305 KW(.86) = 262.3 KW
MDML= (Motor Load)(Demand Factor) = 302 KW(.84) = 253.6 KW

Therefore,

∑ MD ' s= 262.3 KW + 253.6 KW= 515.98 KW


Hence,

∑ MD ' s 515.98 KW
SIMD= = = 469.73 KW
Diversity Factor 110 %

Thus,

SIMD 469.73 KW
KVAT= = = 545.434 KVA
Ave . Power Factor .86
KVAREF= 1.25(KVAT)= 1.25(545.434 KVA) = 681.793 KVA
Using 3 1- Ø Units:

681.793 KVA
KVAREF= = 227.264 KVA
3

Therefore use 3 pcs. of 250 KVA 1- Ø D.T.

Using of a single 3- Ø Unit:

KVAREF= 681.793 KVA

Therefore use 1 pc. Of a 750 KVA 3- Ø D.T.

II. Size of Secondary Feeder


21.4 I d '
Circular Mill=
Safe DCVD

Where: d’= 500 ft.

I= KVAT/ √3 Vs = 545.434*103/√3 (220) = 1431.393 A

Since,

3% .03
Safe DCVD= (Vs) = (220V) = 4.4V
150 % 1.5

Thus,

21.4 I d ' 21.4(1431.393)(500)


Circular Mill= = = 3,262,023.886 Cir-Mil
Safe DCVD 4.4

Therefore:

Minimum Recommended Rating:

Use 3 pcs of 3,500,000 Circular Mills Copper Conductor

Use 1 pc of 1,750,000 Circular Mills Copper Conductor for neutral wire.


21.4 I d ' 21.4(1431.393)(500)
Actual ACVD= = =4.376V
ACTUAL CIR−MIL 3500000

Actual ACVD= 150% of Actual ACVD

= 1.5(4.376)

=6.564 V

Thus,

ACTUAL ACVD
%VD= x 100
Vs

6.564
%VD= x 100=2.98%
220

Since, 2.98%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.

Size of Primary Feeder

Angle of Plant no. 6 = cos-1(.86)= 30.863o

Thus,

KVAT= 750<(30.863)= 750< 30.863o KVA

Since,

21.4 Id '
Cir-Mil=
SAFE DCVD

Where, d’= 9(140)= 1260 ft

KVAt
I=
√ 3 Vp
750 X 10 3
I= = 56.826A
√3 (7620)
Also,

5%
Safe DCVD= (7620)
150 %

= 254V

Thus,

21.4(58.826)(1260)
Cir-Mil= = 6244.820 Cir-Mil
254 V

THEREFORE,

USE 3 pcs OF 16,510 CM (AWG NO. 8) OF COPPER CONDUCTOR USING

METHOD 2:
ACTUAL ACVD = ( Id’√3/5280)* [Ra cos θ +Xt sin θ]

Where, cos θ= .86o


sin θ= .51o
From wire table
Ra=3.79 Ω
Xa= 0.665 Ω
GMD= √3 (44)(44 )(88)= 55.437
55 .185
55.437 xd
56 .187

Xd= 0.187-((0.187-0.185)*(56-55.437)/(56-55))
Xd = 0.186Ω/mi
Therefore,
XT= 0.665+0.186=0.851 Ω/mi
Thus,
Actual ACVD= ( (58.826)(1260)√3/5280)* [(3.79)(0.86) +(0.851)(0.51)])
Actual ACVD= 89.804 V

Therefore,
ACTUAL ACVD
%VD= x 100%
Vp

89.804
%VD= x 100% = 1.17 %
7620

Since,

1.17%< 5%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
DESIGN OF INDUSTRIAL CUSTOMER REQUIRING OUTDOOR TYPE SUBSTATION

PLANT NO. 7

Lighting Load- 305 KW, 3-Ø, 220 volts

Demand Factor- 84%

Motor Load- 325 KW, 3-Ø,220 volts

Demand Factor- 86%

Average Power Factor- 85%

Diversity Factor- 105%

I. DISTRIBUTION TRANSFORMER RATING


SINCE,
Maximum Demand
Demand Factor =
Connected Load

Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL

Thus,
MDLL= (Lighing Load)(Demand Factor) = 305 KW(.84) = 256.2 KW
MDML= (Motor Load)(Demand Factor) = 325 KW(.86) = 279.5 KW

Therefore,

∑ MD ' s= 262.3 KW + 253.68 KW= 535.7 KW


Hence,

∑ MD ' s 535.7 KW
SIMD= = =510.190 KW
Diversity Factor 105 %

Thus,

SIMD 510.190 KW
KVAT= = = 600.224 KVA
Ave . Power Factor .85
KVAREF= 1.25(KVAT)= 1.25(600.224KVA) = 750.28 KVA

Using 3 1- Ø Units:

750.28 KVA
KVAREF= = 250.093 KVA
3

Therefore use 3 pcs. O 333 KVA 1- Ø D.T.

Using of a single 3- Ø Unit:

KVAREF= 750.28 KVA

Therefore use 1 pc. Of a 1000 KVA 3- Ø D.T.

II. Size of Secondary Feeder


21.4 I d '
Circular Mill=
Safe DCVD

Where: d’= 500 ft.

I= KVAT/ √3 Vs = 600.224*103/√3 (220) = 1575.180 A

Since,

3% .03
Safe DCVD= (Vs) = (220V) = 4.4V
150 % 1.5
Thus,

21.4 I d ' 21.4(1575.180)(500)


Circular Mill= = = 3,830,551.364 Cir-Mil
Safe DCVD 4.4

Therefore:

Minimum Recommended Rating:

Use 3 pcs of 4,000,000 Circular Mills Copper Conductor

Use 1 pc of 2,000,000 Circular Mills Copper Conductor for neutral wire.

21.4 I d ' 21.4(1575.180)(500)


Actual ACVD= = = 4.214 V
ACTUAL CIR−MIL 4000000

Actual ACVD= 150% of Actual ACVD

= 1.5(4.214)

=6.321 V

Thus,

ACTUAL ACVD
%VD= x 100
Vs

6.321
%VD= x 100= 2.87%
220

Since, 2.87%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.

Size of Primary Feeder

Angle of Plant no. 6 = cos-1(.85)= 31.788o

Thus,
KVAT= 1000< 31.788o KVA

Since,

21.4 Id '
Cir-Mil=
SAFE DCVD

Where, d’= 8(140)= 1120 ft

KVAt
I=
√ 3 Vp
1000 X 103
I= = 75.768 A
√3 (7620)
Also,

5%
Safe DCVD= (7620)
150 %

= 254V

Thus,

21.4(75.768)(1120)
Cir-Mil= = 7,149.636 Cir-Mil
254 V

THEREFORE,

USE 3 pcs OF 16,510 CM (AWG NO. 8) OF COPPER CONDUCTOR USING

METHOD 2:
ACTUAL ACVD = ( Id’√3/5280)* [Ra cos θ +Xt sin θ]
Where, cos θ= .85
sin θ= .53

From wire table


Ra=3.79 Ω
Xa= 0.665 Ω
GMD= √3 (44)(44 )(88)=55.437
55 .185
55.437 xd
56 .187

Xd= 0.187-((0.187-0.185)*(56-55.437)/(56-55))
Xd = 0.186Ω/mi
Therefore,
XT= 0.665+0.186= 0.851 Ω/mi

Thus,
Actual ACVD= ((75.768)(1120)√3/5280)* [(3.79)(0.85) +(0.851)(0.53)])
Actual ACVD=102.234 V
Therefore,
ACTUAL ACVD
%VD= x 100%
Vp

102.234
%VD= x 100% = 1.34%
7620

Since,
1.34%<5%,THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
DESIGN OF INDUSTRIAL CUSTOMER REQUIRING OUTDOOR TYPE SUBSTATION

PLANT NO. 8

Lighting Load- 98 KW, 3-Ø, 220 volts

Demand Factor- 85%

Motor Load- 159 KW, 3-Ø,220 volts

Demand Factor- 85%

Average Power Factor- 86%

Diversity Factor- 109%

I. DISTRIBUTION TRANSFORMER RATING


SINCE,
Maximum Demand
Demand Factor =
Con nected Load

Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL

Thus,
MDLL= (Lighing Load)(Demand Factor) = 98KW(.85) = 83.3 KW
MDML= (Motor Load)(Demand Factor) = 159KW(.85) = 135.15 KW

Therefore,

∑ MD ' s= 83.3 KW + 135.15KW= 218.45 KW


Hence,

∑ MD ' s 218.45 KW
SIMD= = = 200.413 KW
Diversity Factor 109 %

Thus,

SIMD 200.413 KW
KVAT= = = 233.038 KVA
Ave . Power Factor .85
KVAREF= 1.25(KVAT)= 1.25(233.038 KVA) = 291.298 KVA

Using 3 1- Ø Units:

291.298 KVA
KVAREF= = 97.079 KVA
3

Therefore use 3 pcs. O 100 KVA 1- Ø D.T.

Using of a single 3- Ø Unit:

KVAREF= 291.298 KVA

Therefore use 1 pc. Of a 300 KVA 3- Ø D.T.

II. Size of Secondary Feeder


21.4 I d '
Circular Mill=
Safe DCVD

Where: d’= 500 ft.

I= KVAT/ √3 Vs = 233.038*103/√3 (220) = 611.566 A

Since,
3% .03
Safe DCVD= (Vs) = (220V) = 4.4V
150 % 1.5

Thus,

21.4 I d ' 21.4(611.566 )(500)


Circular Mill= = = 1,487,217.318 Cir-Mil
Safe DCVD 4.4

Therefore:

Minimum Recommended Rating:

Use 3 pcs of 1,500,000 Circular Mills Copper Conductor

Use 1 pc of 750,000 Circular Mills Copper Conductor for neutral wire.

21.4 I d ' 21.4(611.566 )(500)


Actual ACVD= = = 4.363 V
ACTUAL CIR−MIL 1500000

Actual ACVD= 150% of Actual ACVD

= 1.5(4.363)

=6.545 V

Thus,

ACTUAL ACVD
%VD= x 100
Vs

6.545
%VD= x 100=2.98 %
220

Since, 2.98%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.

Size of Primary Feeder


Angle of Plant no. 8 = cos-1(.86)= 30.863o

Thus,

KVAT= 300<(30.863)= 750< 30.863o KVA

Since,

21.4 Id '
Cir-Mil=
SAFE DCVD

Where, d’= 12(140)= 1680 ft

KVAt
I=
√ 3 Vp
300 X 10 3
I= = 22.730 A
√3 (7620)
Also,

5%
Safe DCVD= (7620)
150 %

= 254 V

Thus,

21.4(22.73)(1680)
Cir-Mil= = 3217.279 Cir- Mil
254 V

Therefore,

Use 3 pcs. of 16,510 (AWG NO.8) of Copper Conductor

METHOD 2:
ACTUAL ACVD = ( Id’√3/5280)* [Ra cos θ +Xt sin θ]
Where, cos θ= .86
sin θ= .51

From wire table


Ra= 3.79 Ω
Xa= 0.665 Ω
GMD= √3 (44)(44 )(88)=55.437
55 .185
55.437 xd
56 .187

Xd= 0.187-((0.187-0.185)*(56-55.437)/(56-55))
Xd = 0.186Ω/mi
Therefore,
XT= 0.665+0.186=0.851 Ω/mi

Thus,
Actual ACVD= ((22.73)(1680)√3/5280)* [(3.79)(0.86)+(0.851)(0.51)])
Actual ACVD= 46.266 V

Therefore,
ACTUAL ACVD
%VD= x 100%
Vp

46.266
%VD= x 100%=0.607%
7620

Since,
0.607%<5%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.
DESIGN OF INDUSTRIAL CUSTOMER REQUIRING OUTDOOR TYPE SUBSTATION

PLANT NO. 9

Lighting Load- 93 KW, 3-Ø, 220 volts

Demand Factor- 83%

Motor Load- 149 KW, 3-Ø,220 volts

Demand Factor- 82%

Average Power Factor- 83%

Diversity Factor- 109%

I. DISTRIBUTION TRANSFORMER RATING


SINCE,
Maximum Demand
Demand Factor =
Connected Load

Diversity Factor=
∑ MD ' s
SIMD
Where:
∑ MD ' s= MD + MDML
LL

Thus,
MDLL= (Lighting Load)(Demand Factor) = 93 KW(.83) =77.19 KW
MDML= (Motor Load)(Demand Factor) = 149KW(.82) = 122.18 KW

Therefore,

∑ MD ' s= 77.19 KW + 122.18 KW= 199.37 KW


Hence,

∑ MD ' s 199.37 KW
SIMD= = = 182.908 KW
Diversity Factor 109 %

Thus,

SIMD 182.908 KW
KVAT= = = 220.371 KVA
Ave . Power Factor .83
KVAREF= 1.25(KVAT)= 1.25(220.371 KVA) = 275.464 KVA

Using 3 1- Ø Units:

275.464 KVA
KVAREF= = 91.821 KVA
3

Therefore use 3 pcs. O 100 KVA 1- Ø D.T.

Using of a single 3- Ø Unit:

KVAREF= 275.464 KVA

Therefore use 1 pc. Of a 300 KVA 3- Ø D.T.

II. Size of Secondary Feeder


21.4 I d '
Circular Mill=
Safe DCVD
Where: d’= 500 ft.

I= KVAT/ √3 Vs = 275.464 *103/√3 (220) = 722.906 A

Since,

3% .03
Safe DCVD= (Vs) = (220V) = 4.4 V
150 % 1.5

Thus,

21.4 I d ' 21.4(722.906)(500)


Circular Mill= = = 1,757,975.955 Cir-Mil
Safe DCVD 4.4

Therefore:

Minimum Recommended Rating:

Use 3 pcs of 2,000,000 Circular Mills Copper Conductor

Use 1 pc of 1,000,000 Circular Mills Copper Conductor for neutral wire.

21.4 I d ' 21.4(722.906)(500)


Actual ACVD= = = 3.868 V
ACTUAL CIR−MIL 2000000

Actual ACVD= 150% of Actual ACVD

= 1.5(3.868)

=5.802 V

Thus,

ACTUAL ACVD
%VD= x 100
Vs

5.802
%VD= x 100=2.64%
220

Since,
2.64%< 3%, THE WIRE CAN SAFELY CARRY THE REQUIRED LOAD.

Size of Primary Feeder

Angle of Plant no. 9 = cos-1(.83)= 33.901o

Thus,

KVAT= 300<(33.901)= 300< 33.901o KVA

Since,

21.4 Id '
Cir-Mil=
SAFE DCVD

Where, d’= 5(140)= 700 ft

KVAt
I=
√ 3 Vp
300 X 10 3
I= = 22.730 A
√3 (7620)
Also,

5%
Safe DCVD= (7620)
150 %

= 254V

Thus,

21.4(22.730)(700)
Cir-Mil= = 1,340.533 Cir-Mil
254 V

Therefore,
Use 3 pcs. of 16,510 (AWG NO.8) of Copper Conductor

METHOD 2:
ACTUAL ACVD = ( Id’√3/5280)* [Ra cos θ +Xt sin θ]
Where, cos θ= .83
sin θ= .56
From wire table
Ra= 3.79 Ω
Xa= 0.665 Ω
GMD= √3 (44)(44 )(88)=55.437
55 .185
55.437 xd
56 .187

Xd= 0.187-((0.187-0.185)*(56-55.437)/(56-55))
Xd = 0.186Ω/mi
Therefore,
XT= 0.665+.186=0.851 Ω/mi

Thus,
Actual ACVD= ((22.730)(700)√3/5280)* [(3.79)(0.83)+(0.851(0.56)]
Actual ACVD= 18.906 V

Therefore,
ACTUAL ACVD
%VD= x 100%
Vp

18.906
%VD= x 100%=0.248%
7620

Since,

0.248%<5%, THE WIRE CAN SAFELY CARRY THE REQUIERED LOAD.


SIZES AND RATINGS OF DIFFERENT EQUIPMENT FOR PLANT 6,7,8, AND 9.

X. BUSBAR RATINGS
The busbar rating is a copper alloy UNSC1100 using the electrical busbar
ampacity of 100-149A at 30 o C rise 60 Hz. The dimension of the busbar is

1 3
x inches.
16 4
XI. OPEN FUSED CUT-OUT RATINGS
For plant 6
KVA 750 x 10 3
I= = = 56.826 A
√ 3 Vp √ 3 (7620)
Therefore,
Use 3 pcs of type R and type T fuse link.
For plant 7
KVA 1000 x 103
I= = = 75.768 A
√ 3 Vp √ 3(7620)
Therefore,
Use 3 pcs of type R and type T fuse link.
For plant 8 & 9
KVA 300 x 103
I= = = 22.730 A
√ 3 Vp √ 3 (7620)
Therefore,
Use 3 pcs of type R and type T fuse link
XII. INSTRUMENT TRANSFORMER AND ACCESSORIES
D. Current Transformer Ratings
For Plant 6
I= 56.826 A
For plant 7
I=75.768 A
For plant 8 & 9
I= 22.730 A

Therefore, Use an indoor type current transformer bushing with primary voltage
of 7.72 KV to 40.5 KV, primary current of 500 A to 5000 A, A secondary current of
1A to 5A, frequency of 50Hz-60Hz.

E. Potential Transformer Rating


Use an indoor type of potential transformer with primary voltage of
1KV to 35 KV, secondary voltage of 0.1 to 0.12 KV and frequency of
50-60Hz.
F. Accessories
 Maximum Demand Meter
Bi-Metallic maximum demand meter
 Power factor meter
A digital PQQWE factor meter input voltage, 3- Ø wire system
110+10% or 45+ 10%, 3- Ø 50 Hz.
 AC Kilowatt-Hour meter
220 “H”-series DIN panel nominal voltages 63.5
V,110V,120V,220V,240V,400V,415V,440V, and 480 V AC.
 AC Voltmeter
VMD 1-2 Voltmeter for AC and DC from 0-600 V.
 AC Ammeter
AMT- 01-AC, Amperes with scales from 15A-999A.

 Frequency Meter
FRZ-DIG Frequency meter from 40-80 Hz.
 Switchboard Style

LV Switchboard(Modular Steel Sheet Construction).

XIII. LIGHTNING ARRESTER

7620
KVAref= = 4.399 KV
√3

Therefore,

Use 3 pcs of Series 1 Polymer Housed, Zinc-Oxide Lightning Arrester


without cap, 6.3 KV to 36 KV, All ratings are available from 5to 10 MVA.

XIV. TRANSFORMER RATINGS


For Plant 6 use 1 unit of 750 KVA, 3-Ø Distribution Transformer.
For Plant 7 use 1 unit of 1000 KVA, 3-Ø Distribution Transformer.
For Plant 8&9 use 1 unit of 300 KVA, 3-Ø Distribution Transformer.
XV. SHUNT CAPACITOR RATINGS
Capacitor bank 3-35 KV high voltage passive collective compensation
used in the system up to 35 KV to enhance power factor.
XVI. TRANSDUCER RATINGS
Use 5-010 A current transducer, VT-120 A voltage transducer and PC-010
A power transducer.
XVII. RECLOSER RATING
Use type 6H, 3- Ø, 100 A recloser