0% found this document useful (0 votes)
264 views

CO2 Suppression System

This document provides an offer for a CO2 fire suppression system for an emergency generator. It includes pricing and specifications for the following items: 1. A dual area conventional suppression control panel from Simplex, USA. 2. Two heat detectors and one electronic horn/strobe unit from Simplex, USA. 3. Additional strobes, an abort switch, supervision modules, and a maintenance switch from Simplex, USA. 4. Four CO2 cylinders with valves, handles and hoses from SRI, Malaysia. The total cost offered is $776,487.

Uploaded by

daniyalahmad119
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
264 views

CO2 Suppression System

This document provides an offer for a CO2 fire suppression system for an emergency generator. It includes pricing and specifications for the following items: 1. A dual area conventional suppression control panel from Simplex, USA. 2. Two heat detectors and one electronic horn/strobe unit from Simplex, USA. 3. Additional strobes, an abort switch, supervision modules, and a maintenance switch from Simplex, USA. 4. Four CO2 cylinders with valves, handles and hoses from SRI, Malaysia. The total cost offered is $776,487.

Uploaded by

daniyalahmad119
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

FOR: MAAM ASSOCIATES DATE: SEPTEMBER 14, 2018

ATTENTION: MR. DANIYAL FROM: BAQAR JAFRI


EMAIL. 65C, STREET 7, MAIN KHAYABAN-E-JAMI, DEFENCE HOUSING
YOUR REF: DRAWINGS AUTHORITY PHASE VII , KARACHI
PAGES SIXTEEN TEL: 111 723 389, FAX NO: +92 21 35806240
OUR REF: HHTPL/HO/E/WK/115629 E-MAIL: [email protected]

SUBJECT: SUPPLY, INSTALLATION & COMMISSIONING OF CO2 FIRE SUPPRESSION SYSTEM

Dear Mr. Daniyal,


With reference to subject requirement for supply, installation & commissioning of CO2 Fire Suppression System,
we are pleased to share our offer for world best system from Simplex, USA and SRI, Malaysia as under.

EMERGENCY GENERATOR
S.NO CAT. NO. DESCRIPTION QTY. Unit Price TOTAL
4004R
Dual Area Conventional Suppression / Deluge Release
Panel
Control Panel has
 Two Independent Programmable Releasing
Appliance Circuits (RACs)
 Four initiating device circuits (IDCs)
 Two notification appliance circuits (NACs)
 Short circuit Release Appliance Circuit Supervision
 Two Special Purpose Monitor Inputs (SPMs) that
accept manual release request and manual abort
request for Agent Release systems, and supervisory
for Pre-action or Deluge systems
1. 4004-9302  Three auxiliary relays with Fire, Fault, Remote 01-Nos. 109,832.00 109,832.00
selectable functions
 3 A power supply with battery charger
 Housing:
NEMA 1/IP30 rated cabinet and door
 Includes: Mounting Hardware, IOM Manual, EOL
Resistor kit
 Dry Rechargeable Gel Type 12Volt-7Ah Backup
Batteries
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA

1
T4E90X T54B Point Type heat detector
FEATURES
 Sealed Stainless Steel Construction
 Suitable for use in hazardous areas
 IP 67 RATED
 Vibration Resistant
 Hermetically sealed
 Impervious to most contaminants Shock
TECHNICAL SPECIFICATION
2. 516.033.012 Operating voltage @ 0.5A: 240Va.c. to 24Vdc 02-Nos. 55,000.00 110,000.00
Switching Current: 5 to 500mA
Contact Resistance: <1 ohm
Actuating Temp: 90°C
Fixed Temp. only: Type E Accuracy: + or - 5%
Operating Temp.: -40 to +270°C
Relative Humidity: 100% RH
Protection Category: IP67
Thread Size: M20 x 1.5mm
Complete With Housing
Zettler, Tyco Fire Protection Products, UK
Conventional Electronic Horn
True Alert Hooter cum Multi-Candela strobe Unit
 Operating Temperature: 32° to 122° F (0° to 50° C)
 Sound Output Characteristics 2400 to 3700 Hz
sweep, modulated at 120 Hz rate
 Sound Output Ratings @ 10 ft (3 m),
3. 4901-9820 Coded/Steady/Controllable from 82 dB to 96.5 dB 01-Nos. 4,950.00 4,950.00
 Self-Diagnostic and Test Feature
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
Conventional Horn
WHEELLOCK EXCEEDER STROBE 24V DC,
COLOR RED STROBE CANDELA SELECTABLE
4. HNW-NR COMPLETE WITH UNIVERSAL BASE 01-Nos. 2,000.00 2,000.00
Approvals:
UL, ULC, CSFM Listed; FM Approved
Cooper, Canada
Conventional Strobe
WHEELLOCK EXCEEDER STROBE 24V DC ,
COLOR WHITE STROBE CANDELA SELECTABLE
5. STW-NR 01-Nos. 2,000.00 2,000.00
COMPLETE WITH UNIVERSAL BASE
Approvals: UL, ULC, CSFM Listed; FM Approved
COOPER, CANADA
ABORT SWITCH
Supervisory Manual Fire Suppression System Release
Abort Station
 Push button momentary switch - mounted on a
stainless steel single-gang plate with a protruding
collar to protect the switch from accidental contact
6. 2080-9057  Temperature Range 32° F to 120° F (0° C to 49° C) 01-Nos. 25,000.00 25,000.00
 Humidity Range Up to 93% at 90°F (32° C)
Approvals:
UL, ULC, CSFM Listed;
FM Approved& MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA

2
Abort Supervision Module
 encapsulated 560Ω, 1/2 W resistor
 Provides feedback signal to Control Panel as long as
abort mode is under operation
7. 2081-9048 Approvals: 01-Nos. 3,000.00 3,000.00
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
2 Amp Coil Supervisory Module
Supervises and provides feedback signal to control panel
about Solenoid Status
Approvals:
8. 2081-9046 01-Nos. 5,270.00 5,270.00
UL, ULC, CSFM Listed; FM Approved;
MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
MAINTENANCE SWITCH WITH LAMP INDICATOR
Provides a secure and visible disconnect means for
servicing Fire Suppression System Releasing Appliance
Circuits (RACs)
 Maintained position key switch is mounted on a
stainless steel double-gang plate
 Key is removable only in the normal position
 Disabled position opens connection to output circuit
and places a 16.2 k. ohm resistor across the input
circuit to initiate a supervisory condition at the host
9. 2080-9060 01-Nos. 42,075.00 42,075.00
panel
 Disconnect indicator lamp is a bright incandescent
bulb with red lens, powered from separate 24 VDC
 Temperature Range 32° F to 120° F (0° C to 49° C)
 Humidity Range Up to 93% at 90°F (32° C)
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
MANUAL DUAL ACTION PULL STATIONS FOR RELEASING
APPLICATIONS
 Double action push and pull operation with a
normally open (N.O.) contact
 with 2975-9178 BACK BOX
2099-9152
 Temperature Range 32° to 140° F (0° to 60° C)
10. 2975-9178 01-Nos. 10,510.00 10,510.00
 Humidity Range Up to 90% RH at 90° F (38° F)
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
CO2001-CS- CO2 CYL. 68L, K. VLV & GAS 45KG WITH - 4 1-Set
11.
450-KV complete with:- c/W
CO2022-MS- CO2 HANDLE OR MANUAL LEVER 5MM – MS
12. 04-Nos
005-ZP SRI, MALAYSIA
CO2005-RB- DISCHARGE HOSE C/W CHK VLV 1/2"X18"
13. 04-Nos 340,000.00 340,000.00
015-BK SRI, MALAYSIA
CO2058-RB- FLEXIBLE HOSE1/4"x300mm MxM
14. 04-Nos
300-BK SRI, MALAYSIA
CDX226-PS- STICKER - SRI CO2 45KG K VALVE
15. 04-Nos
045-XX SRI, MALAYSIA
CO2054-CS- CO2 PILOT CYL 2.0KG c/w SOLE VLV&P.GAUGE
16. 01-Set 60,000.00 60,000.00
020-SP complete with:-

3
CO2058-RB- Flexible Hose 1/4"x457m
17.
457-BK SRI, MALAYSIA
CO2022-MS- CO2 HANDLE OR MANUAL LEVER 5MM – MS
18.
005-ZP SRI, MALAYSIA
Nozzle CO2 Discharge Brass 25mm RH
19. - 02-Nos 4,000.00 8,000.00
SRI Malaysia
Installation Material Including
 SEAMLESS SCHEDULE 80 STEEL PIPE (CARBON STEEL A53/A106-
GRADE B)
 WITH FORGED STEEL TEES/ELBOWS AND FISCHER/SIKLA PIPE
20. CLAMPS/ANCHORS AND SUPPORTS 01.Set L.SUM 200,000.00
 PIPE LABELS, RAL 3000 PAINT
 1.5 sq. mm 2 X CORE FIRE RESISTANCE CABLE
 PVC CONDUIT
 FITTINGS, GLANDS, JUNCTION BOXES, MOUNTING ACCESSORIES
NET TOTAL 922,637.00
GST@17% 156,848.29
Total- A1 1,079,485.29

PRICED BILL OF SERVICES

S.No. DESCRIPTION QTY UNIT PRICE AMOUNT


Construction Supervision with ENGINEERING SERVICES FOR
1. 01-JOB L. SUM 50,000.00
INSTALLATION AND COMMISSIONING
PROGRAMMING, TESTING & COMMISSIONING OF COMPLETE SYSTEM
2. 01-JOB L. SUM 15,000.00
AND PIPING NETWORK LEAKAGE TEST
SHOP DRAWING, P&IDS, LAYOUT DRAWING(S), ISOMETRIC DRAWING,
3. 01-JOB L. SUM 10,000.00
AS-BUILT DRAWING
NET TOTAL 75,000.00
SST @ 13% 9,750.00
TOTAL-A2 84,750.00

4
TRANSFORMER
S.NO CAT. NO. DESCRIPTION QTY. Unit Price TOTAL
4004R
Dual Area Conventional Suppression / Deluge Release
Panel
Control Panel has
 Two Independent Programmable Releasing
Appliance Circuits (RACs)
 Four initiating device circuits (IDCs)
 Two notification appliance circuits (NACs)
 Short circuit Release Appliance Circuit Supervision
 Two Special Purpose Monitor Inputs (SPMs) that
accept manual release request and manual abort
request for Agent Release systems, and supervisory
for Pre-action or Deluge systems
21. 4004-9302  Three auxiliary relays with Fire, Fault, Remote 01-Nos. 109,832.00 109,832.00
selectable functions
 3 A power supply with battery charger
 Housing:
NEMA 1/IP30 rated cabinet and door
 Includes: Mounting Hardware, IOM Manual, EOL
Resistor kit
 Dry Rechargeable Gel Type 12Volt-7Ah Backup
Batteries
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
T4E90X T54B Point Type heat detector
FEATURES
 Sealed Stainless Steel Construction
 Suitable for use in hazardous areas
 IP 67 RATED
 Vibration Resistant
 Hermetically sealed
 Impervious to most contaminants Shock
TECHNICAL SPECIFICATION
22. 516.033.012 Operating voltage @ 0.5A: 240Va.c. to 24Vdc 02-Nos. 55,000.00 110,000.00
Switching Current: 5 to 500mA
Contact Resistance: <1 ohm
Actuating Temp: 90°C
Fixed Temp. only: Type E Accuracy: + or - 5%
Operating Temp.: -40 to +270°C
Relative Humidity: 100% RH
Protection Category: IP67
Thread Size: M20 x 1.5mm
Complete With Housing
Zettler, Tyco Fire Protection Products, UK

5
Conventional Electronic Horn
True Alert Hooter cum Multi-Candela strobe Unit
 Operating Temperature: 32° to 122° F (0° to 50° C)
 Sound Output Characteristics 2400 to 3700 Hz
sweep, modulated at 120 Hz rate
 Sound Output Ratings @ 10 ft (3 m),
23. 4901-9820 Coded/Steady/Controllable from 82 dB to 96.5 dB 01-Nos. 4,950.00 4,950.00
 Self-Diagnostic and Test Feature
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
Conventional Horn
WHEELLOCK EXCEEDER STROBE 24V DC,
COLOR RED STROBE CANDELA SELECTABLE
24. HNW-NR COMPLETE WITH UNIVERSAL BASE 01-Nos. 2,000.00 2,000.00
Approvals:
UL, ULC, CSFM Listed; FM Approved
Cooper, Canada
Conventional Strobe
WHEELLOCK EXCEEDER STROBE 24V DC ,
COLOR WHITE STROBE CANDELA SELECTABLE
25. STW-NR 01-Nos. 2,000.00 2,000.00
COMPLETE WITH UNIVERSAL BASE
Approvals: UL, ULC, CSFM Listed; FM Approved
COOPER, CANADA
ABORT SWITCH
Supervisory Manual Fire Suppression System Release
Abort Station
 Push button momentary switch - mounted on a
stainless steel single-gang plate with a protruding
collar to protect the switch from accidental contact
26. 2080-9057  Temperature Range 32° F to 120° F (0° C to 49° C) 01-Nos. 25,000.00 25,000.00
 Humidity Range Up to 93% at 90°F (32° C)
Approvals:
UL, ULC, CSFM Listed;
FM Approved& MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
Abort Supervision Module
 encapsulated 560Ω, 1/2 W resistor
 Provides feedback signal to Control Panel as long as
abort mode is under operation
27. 2081-9048 Approvals: 01-Nos. 3,000.00 3,000.00
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
2 Amp Coil Supervisory Module
Supervises and provides feedback signal to control panel
about Solenoid Status
Approvals:
28. 2081-9046 01-Nos. 5,270.00 5,270.00
UL, ULC, CSFM Listed; FM Approved;
MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA

6
MAINTENANCE SWITCH WITH LAMP INDICATOR
Provides a secure and visible disconnect means for
servicing Fire Suppression System Releasing Appliance
Circuits (RACs)
 Maintained position key switch is mounted on a
stainless steel double-gang plate
 Key is removable only in the normal position
 Disabled position opens connection to output circuit
and places a 16.2 k. ohm resistor across the input
circuit to initiate a supervisory condition at the host
29. 2080-9060 01-Nos. 42,075.00 42,075.00
panel
 Disconnect indicator lamp is a bright incandescent
bulb with red lens, powered from separate 24 VDC
 Temperature Range 32° F to 120° F (0° C to 49° C)
 Humidity Range Up to 93% at 90°F (32° C)
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
MANUAL DUAL ACTION PULL STATIONS FOR RELEASING
APPLICATIONS
 Double action push and pull operation with a
normally open (N.O.) contact
 with 2975-9178 BACK BOX
2099-9152
 Temperature Range 32° to 140° F (0° to 60° C)
30. 2975-9178 01-Nos. 10,510.00 10,510.00
 Humidity Range Up to 90% RH at 90° F (38° F)
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
CO2001-CS- CO2 CYL. 68L, K. VLV & GAS 45KG WITH - 4 1-Set
31.
450-KV complete with:- c/W
CO2022-MS- CO2 HANDLE OR MANUAL LEVER 5MM – MS
32. 04-Nos
005-ZP SRI, MALAYSIA
CO2005-RB- DISCHARGE HOSE C/W CHK VLV 1/2"X18"
33. 04-Nos 340,000.00 340,000.00
015-BK SRI, MALAYSIA
CO2058-RB- FLEXIBLE HOSE1/4"x300mm MxM
34. 04-Nos
300-BK SRI, MALAYSIA
CDX226-PS- STICKER - SRI CO2 45KG K VALVE
35. 04-Nos
045-XX SRI, MALAYSIA
CO2054-CS- CO2 PILOT CYL 2.0KG c/w SOLE VLV&P.GAUGE
36.
020-SP complete with:-
CO2058-RB- Flexible Hose 1/4"x457m
37. 01-Set 60,000.00 60,000.00
457-BK SRI, MALAYSIA
CO2022-MS- CO2 HANDLE OR MANUAL LEVER 5MM – MS
38.
005-ZP SRI, MALAYSIA
Nozzle CO2 Discharge Brass 25mm RH
39. - 02-Nos 4,000.00 8,000.00
SRI Malaysia
Installation Material Including
 SEAMLESS SCHEDULE 80 STEEL PIPE (CARBON STEEL A53/A106
GRADE B)
 WITH FORGED STEEL TEES/ELBOWS AND FISCHER/SIKLA PIPE
40. CLAMPS/ANCHORS AND SUPPORTS 01.Set L.SUM 200,000.00
 PIPE LABELS, RAL 3000 PAINT
 1.5 sq. mm 2 X CORE FIRE RESISTANCE CABLE
 PVC CONDUIT
 FITTINGS, GLANDS, JUNCTION BOXES, MOUNTING ACCESSORIES
NET TOTAL 922,637.00
GST@17% 156,848.29

7
Total- B1 1,079,485.29

PRICED BILL OF SERVICES

S.No. DESCRIPTION QTY UNIT PRICE AMOUNT


Construction Supervision with ENGINEERING SERVICES FOR
4. 01-JOB L. SUM 50,000.00
INSTALLATION AND COMMISSIONING
PROGRAMMING, TESTING & COMMISSIONING OF COMPLETE SYSTEM
5. 01-JOB L. SUM 10,000.00
AND PIPING NETWORK LEAKAGE TEST
SHOP DRAWING, P&IDS, LAYOUT DRAWING(S), ISOMETRIC DRAWING,
6. 01-JOB L. SUM 10,000.00
AS-BUILT DRAWING
NET TOTAL 75,000.00
SST @ 13% 9,750.00
TOTAL-B2 84,750.00

8
HT. TROLLY
S.NO CAT. NO. DESCRIPTION QTY. Unit Price TOTAL
4004R
Dual Area Conventional Suppression / Deluge Release
Panel
Control Panel has
 Two Independent Programmable Releasing
Appliance Circuits (RACs)
 Four initiating device circuits (IDCs)
 Two notification appliance circuits (NACs)
 Short circuit Release Appliance Circuit Supervision
 Two Special Purpose Monitor Inputs (SPMs) that
accept manual release request and manual abort
request for Agent Release systems, and supervisory
for Pre-action or Deluge systems
41. 4004-9302  Three auxiliary relays with Fire, Fault, Remote 01-Nos. 109,832.00 109,832.00
selectable functions
 3 A power supply with battery charger
 Housing:
NEMA 1/IP30 rated cabinet and door
 Includes: Mounting Hardware, IOM Manual, EOL
Resistor kit
 Dry Rechargeable Gel Type 12Volt-7Ah Backup
Batteries
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
T4E90X T54B Point Type heat detector
FEATURES
 Sealed Stainless Steel Construction
 Suitable for use in hazardous areas
 IP 67 RATED
 Vibration Resistant
 Hermetically sealed
 Impervious to most contaminants Shock
TECHNICAL SPECIFICATION
42. 516.033.012 Operating voltage @ 0.5A: 240Va.c. to 24Vdc 02-Nos. 55,000.00 110,000.00
Switching Current: 5 to 500mA
Contact Resistance: <1 ohm
Actuating Temp: 90°C
Fixed Temp. only: Type E Accuracy: + or - 5%
Operating Temp.: -40 to +270°C
Relative Humidity: 100% RH
Protection Category: IP67
Thread Size: M20 x 1.5mm
Complete With Housing
Zettler, Tyco Fire Protection Products, UK

9
Conventional Electronic Horn
True Alert Hooter cum Multi-Candela strobe Unit
 Operating Temperature: 32° to 122° F (0° to 50° C)
 Sound Output Characteristics 2400 to 3700 Hz
sweep, modulated at 120 Hz rate
 Sound Output Ratings @ 10 ft (3 m),
43. 4901-9820 Coded/Steady/Controllable from 82 dB to 96.5 dB 01-Nos. 4,950.00 4,950.00
 Self-Diagnostic and Test Feature
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
Conventional Horn
WHEELLOCK EXCEEDER STROBE 24V DC,
COLOR RED STROBE CANDELA SELECTABLE
44. HNW-NR COMPLETE WITH UNIVERSAL BASE 01-Nos. 2,000.00 2,000.00
Approvals:
UL, ULC, CSFM Listed; FM Approved
Cooper, Canada
Conventional Strobe
WHEELLOCK EXCEEDER STROBE 24V DC ,
COLOR WHITE STROBE CANDELA SELECTABLE
45. STW-NR 01-Nos. 2,000.00 2,000.00
COMPLETE WITH UNIVERSAL BASE
Approvals: UL, ULC, CSFM Listed; FM Approved
COOPER, CANADA
ABORT SWITCH
Supervisory Manual Fire Suppression System Release
Abort Station
 Push button momentary switch - mounted on a
stainless steel single-gang plate with a protruding
collar to protect the switch from accidental contact
46. 2080-9057  Temperature Range 32° F to 120° F (0° C to 49° C) 01-Nos. 25,000.00 25,000.00
 Humidity Range Up to 93% at 90°F (32° C)
Approvals:
UL, ULC, CSFM Listed;
FM Approved& MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
Abort Supervision Module
 encapsulated 560Ω, 1/2 W resistor
 Provides feedback signal to Control Panel as long as
abort mode is under operation
47. 2081-9048 Approvals: 01-Nos. 3,000.00 3,000.00
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
2 Amp Coil Supervisory Module
Supervises and provides feedback signal to control panel
about Solenoid Status
Approvals:
48. 2081-9046 01-Nos. 5,270.00 5,270.00
UL, ULC, CSFM Listed; FM Approved;
MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA

10
MAINTENANCE SWITCH WITH LAMP INDICATOR
Provides a secure and visible disconnect means for
servicing Fire Suppression System Releasing Appliance
Circuits (RACs)
 Maintained position key switch is mounted on a
stainless steel double-gang plate
 Key is removable only in the normal position
 Disabled position opens connection to output circuit
and places a 16.2 k. ohm resistor across the input
circuit to initiate a supervisory condition at the host
49. 2080-9060 01-Nos. 42,075.00 42,075.00
panel
 Disconnect indicator lamp is a bright incandescent
bulb with red lens, powered from separate 24 VDC
 Temperature Range 32° F to 120° F (0° C to 49° C)
 Humidity Range Up to 93% at 90°F (32° C)
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
MANUAL DUAL ACTION PULL STATIONS FOR RELEASING
APPLICATIONS
 Double action push and pull operation with a
normally open (N.O.) contact
 with 2975-9178 BACK BOX
2099-9152
 Temperature Range 32° to 140° F (0° to 60° C)
50. 2975-9178 01-Nos. 10,510.00 10,510.00
 Humidity Range Up to 90% RH at 90° F (38° F)
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
CO2001-CS- CO2 CYL. 68L, K. VLV & GAS 45KG WITH - 4 1-Set
51.
450-KV complete with:- c/W
CO2022-MS- CO2 HANDLE OR MANUAL LEVER 5MM – MS
52. 04-Nos
005-ZP SRI, MALAYSIA
CO2005-RB- DISCHARGE HOSE C/W CHK VLV 1/2"X18"
53. 04-Nos 340,000.00 340,000.00
015-BK SRI, MALAYSIA
CO2058-RB- FLEXIBLE HOSE1/4"x300mm MxM
54. 04-Nos
300-BK SRI, MALAYSIA
CDX226-PS- STICKER - SRI CO2 45KG K VALVE
55. 04-Nos
045-XX SRI, MALAYSIA
CO2054-CS- CO2 PILOT CYL 2.0KG c/w SOLE VLV&P.GAUGE
56.
020-SP complete with:-
CO2058-RB- Flexible Hose 1/4"x457m
57. 01-Set 60,000.00 60,000.00
457-BK SRI, MALAYSIA
CO2022-MS- CO2 HANDLE OR MANUAL LEVER 5MM – MS
58.
005-ZP SRI, MALAYSIA
Nozzle CO2 Discharge Brass 25mm RH
59. - 02-Nos 4,000.00 8,000.00
SRI Malaysia
Installation Material Including
 SEAMLESS SCHEDULE 80 STEEL PIPE (CARBON STEEL A53/A106-
GRADE B)
 WITH FORGED STEEL TEES/ELBOWS AND FISCHER/SIKLA PIPE
60. CLAMPS/ANCHORS AND SUPPORTS 01.Set L.SUM 200,000.00
 PIPE LABELS, RAL 3000 PAINT
 1.5 sq. mm 2 X CORE FIRE RESISTANCE CABLE
 PVC CONDUIT
 FITTINGS, GLANDS, JUNCTION BOXES, MOUNTING ACCESSORIES
NET TOTAL 922,637.00
GST@17% 156,848.29

11
Total- C1 1,079,485.29

PRICED BILL OF SERVICES

S.No. DESCRIPTION QTY UNIT PRICE AMOUNT


Construction Supervision with ENGINEERING SERVICES FOR
7. 01-JOB L. SUM 50,000.00
INSTALLATION AND COMMISSIONING
PROGRAMMING, TESTING & COMMISSIONING OF COMPLETE SYSTEM
8. 01-JOB L. SUM 10,000.00
AND PIPING NETWORK LEAKAGE TEST
SHOP DRAWING, P&IDS, LAYOUT DRAWING(S), ISOMETRIC DRAWING,
9. 01-JOB L. SUM 10,000.00
AS-BUILT DRAWING
NET TOTAL 75,000.00
SST @ 13% 9,750.00
TOTAL-C2 84,750.00

12
ELECTRICAL PLANT ROOM GENERATORS & DISTRIBUTION
S.NO CAT. NO. DESCRIPTION QTY. Unit Price TOTAL
4004R
Dual Area Conventional Suppression / Deluge Release
Panel
Control Panel has
 Two Independent Programmable Releasing
Appliance Circuits (RACs)
 Four initiating device circuits (IDCs)
 Two notification appliance circuits (NACs)
 Short circuit Release Appliance Circuit Supervision
 Two Special Purpose Monitor Inputs (SPMs) that
accept manual release request and manual abort
request for Agent Release systems, and supervisory
for Pre-action or Deluge systems
61. 4004-9302  Three auxiliary relays with Fire, Fault, Remote 01-Nos. 109,832.00 109,832.00
selectable functions
 3 A power supply with battery charger
 Housing:
NEMA 1/IP30 rated cabinet and door
 Includes: Mounting Hardware, IOM Manual, EOL
Resistor kit
 Dry Rechargeable Gel Type 12Volt-7Ah Backup
Batteries
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
T4E90X T54B Point Type heat detector
FEATURES
 Sealed Stainless Steel Construction
 Suitable for use in hazardous areas
 IP 67 RATED
 Vibration Resistant
 Hermetically sealed
 Impervious to most contaminants Shock
TECHNICAL SPECIFICATION
62. 516.033.012 Operating voltage @ 0.5A: 240Va.c. to 24Vdc 04-Nos. 55,000.00 220,000.00
Switching Current: 5 to 500mA
Contact Resistance: <1 ohm
Actuating Temp: 90°C
Fixed Temp. only: Type E Accuracy: + or - 5%
Operating Temp.: -40 to +270°C
Relative Humidity: 100% RH
Protection Category: IP67
Thread Size: M20 x 1.5mm
Complete With Housing
Zettler, Tyco Fire Protection Products, UK

13
Conventional Electronic Horn
True Alert Hooter cum Multi-Candela strobe Unit
 Operating Temperature: 32° to 122° F (0° to 50° C)
 Sound Output Characteristics 2400 to 3700 Hz
sweep, modulated at 120 Hz rate
 Sound Output Ratings @ 10 ft (3 m),
63. 4901-9820 Coded/Steady/Controllable from 82 dB to 96.5 dB 01-Nos. 4,950.00 4,950.00
 Self-Diagnostic and Test Feature
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
Conventional Horn
WHEELLOCK EXCEEDER STROBE 24V DC,
COLOR RED STROBE CANDELA SELECTABLE
64. HNW-NR COMPLETE WITH UNIVERSAL BASE 01-Nos. 2,000.00 2,000.00
Approvals:
UL, ULC, CSFM Listed; FM Approved
Cooper, Canada
Conventional Strobe
WHEELLOCK EXCEEDER STROBE 24V DC ,
COLOR WHITE STROBE CANDELA SELECTABLE
65. STW-NR 01-Nos. 2,000.00 2,000.00
COMPLETE WITH UNIVERSAL BASE
Approvals: UL, ULC, CSFM Listed; FM Approved
COOPER, CANADA
ABORT SWITCH
Supervisory Manual Fire Suppression System Release
Abort Station
 Push button momentary switch - mounted on a
stainless steel single-gang plate with a protruding
collar to protect the switch from accidental contact
66. 2080-9057  Temperature Range 32° F to 120° F (0° C to 49° C) 01-Nos. 25,000.00 25,000.00
 Humidity Range Up to 93% at 90°F (32° C)
Approvals:
UL, ULC, CSFM Listed;
FM Approved& MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
Abort Supervision Module
 encapsulated 560Ω, 1/2 W resistor
 Provides feedback signal to Control Panel as long as
abort mode is under operation
67. 2081-9048 Approvals: 01-Nos. 3,000.00 3,000.00
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
2 Amp Coil Supervisory Module
Supervises and provides feedback signal to control panel
about Solenoid Status
Approvals:
68. 2081-9046 01-Nos. 5,270.00 5,270.00
UL, ULC, CSFM Listed; FM Approved;
MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA

14
MAINTENANCE SWITCH WITH LAMP INDICATOR
Provides a secure and visible disconnect means for
servicing Fire Suppression System Releasing Appliance
Circuits (RACs)
 Maintained position key switch is mounted on a
stainless steel double-gang plate
 Key is removable only in the normal position
 Disabled position opens connection to output circuit
and places a 16.2 k. ohm resistor across the input
circuit to initiate a supervisory condition at the host
69. 2080-9060 01-Nos. 42,075.00 42,075.00
panel
 Disconnect indicator lamp is a bright incandescent
bulb with red lens, powered from separate 24 VDC
 Temperature Range 32° F to 120° F (0° C to 49° C)
 Humidity Range Up to 93% at 90°F (32° C)
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
MANUAL DUAL ACTION PULL STATIONS FOR RELEASING
APPLICATIONS
 Double action push and pull operation with a
normally open (N.O.) contact
 with 2975-9178 BACK BOX
2099-9152
 Temperature Range 32° to 140° F (0° to 60° C)
70. 2975-9178 01-Nos. 10,510.00 10,510.00
 Humidity Range Up to 90% RH at 90° F (38° F)
Approvals:
UL, ULC, CSFM Listed;
FM Approved & MEA (NYC)
Simplex-Tyco Fire Protection Products, Johnson
Controls, USA
CO2001-CS- CO2 CYL. 68L, K. VLV & GAS 45KG WITH - 4 1-Set
71.
450-KV complete with:- c/W
CO2022-MS- CO2 HANDLE OR MANUAL LEVER 5MM – MS
72. 20-Nos
005-ZP SRI, MALAYSIA
CO2005-RB- DISCHARGE HOSE C/W CHK VLV 1/2"X18"
73. 20-Nos 1,700,000.00 1,700,000.00
015-BK SRI, MALAYSIA
CO2058-RB- FLEXIBLE HOSE1/4"x300mm MxM
74. 20-Nos
300-BK SRI, MALAYSIA
CDX226-PS- STICKER - SRI CO2 45KG K VALVE
75. 20-Nos
045-XX SRI, MALAYSIA
CO2054-CS- CO2 PILOT CYL 2.0KG c/w SOLE VLV&P.GAUGE
76.
020-SP complete with:-
CO2058-RB- Flexible Hose 1/4"x457m
77. 01-Set 60,000.00 60,000.00
457-BK SRI, MALAYSIA
CO2022-MS- CO2 HANDLE OR MANUAL LEVER 5MM – MS
78.
005-ZP SRI, MALAYSIA
Nozzle CO2 Discharge Brass 25mm RH
79. - 04-Nos 4,000.00 16,000.00
SRI Malaysia
Installation Material Including
 SEAMLESS SCHEDULE 80 STEEL PIPE (CARBON STEEL A53/A106-
GRADE B)
 WITH FORGED STEEL TEES/ELBOWS AND FISCHER/SIKLA PIPE
80. CLAMPS/ANCHORS AND SUPPORTS 01.Set L.SUM 350,000.00
 PIPE LABELS, RAL 3000 PAINT
 1.5 sq. mm 2 X CORE FIRE RESISTANCE CABLE
 PVC CONDUIT
 FITTINGS, GLANDS, JUNCTION BOXES, MOUNTING ACCESSORIES
NET TOTAL 2,550,637.00
GST@17% 433,608.29

15
Total- D1 2,984,245.29

PRICED BILL OF SERVICES

S.No. DESCRIPTION QTY UNIT PRICE AMOUNT


Construction Supervision with ENGINEERING SERVICES FOR
10. 01-JOB L. SUM 80,000.00
INSTALLATION AND COMMISSIONING
PROGRAMMING, TESTING & COMMISSIONING OF COMPLETE SYSTEM
11. 01-JOB L. SUM 20,000.00
AND PIPING NETWORK LEAKAGE TEST
SHOP DRAWING, P&IDS, LAYOUT DRAWING(S), ISOMETRIC DRAWING,
12. 01-JOB L. SUM 10,000.00
AS-BUILT DRAWING
NET TOTAL 110,000.00
SST @ 13% 14,300.00
TOTAL-D2 124,300.00

TERMS & CONDITIONS:

 ABOVE PRICE IS SUBJECTED TO EXCHANGE RATE RS.157/DOLLAR. IN CASE OF DEVALUATION, THE PRICE WILL
BE CHANGED ACCORDINGLY. THIS CLAUSE WILL REMAIN INTACT IN THE PO.”
 ABOVE JOB IS QUOTED FOR OVER GROUND AND NON-CONCEALED WIRING ONLY. ALL CIVIL WORK,
DIGGING, ROAD CUTTING AND ANY OTHER TYPE OF INFRASTRUCTURAL CHANGE FOR THE INSTALLATION OF
ABOVE MATERIAL IS NOT QUOTED AND SHALL BE QUOTED SEPARATELY ON CLIENT’S REQUEST.

PRICE : FREE DELIVERY TO YOUR SITE


DELIVERY : 12-14 WEEKS
COMPLETION OF WORK : 4-5 WEEKS
PAYMENT : SUPPLY: 50% ADVANCE BALANCE AGAINST DELIVERY
SERVICES: 50% ADVANCE WITH DELIVERY OF EQUIPMENT, BALANCE
UPON WORK COMPLETION
OFFER VALIDITY : UPTO 15 DAYS- SUBJECT TO NO DEVALUATION
WARRANTY : ONE YEAR

1. WE RESERVE THE RIGHT TO CORRECT PRICES IN CASE OF ANY TYPOGRAPHIC/ARITHMETIC ERRORS.


2. WE RESERVE THE RIGHT TO AMEND THE PRICE IF ANY SUDDEN GLOBAL PRICE INCREASES.
3. ANY CHANGES OF THE BOQ- SPECIFICATION FOR ANY REASON WILL BE CONSIDERED AS EXTRA CHARGES.

WITH BEST REGARDS,

FOR:

_______________
Baqar Jafri
Manager Application and Services

16