4.plinth & Roof Details (With Diensions)
4.plinth & Roof Details (With Diensions)
NOTES :
X 1. THE DIMENSIONS ARE NOT TO BE SCALED.
PB1 B1 2. ALL DIMENSIONS ARE TO BE VERIFIED PROPERLY AT SITE.
5"
7"
4 4 S1 S4 S3 S2 3. ALL DRAWINGS ARE TO BE READ IN CONJUNCTION WITH ALL
8 @ 5" c/c +13'-9"(LVL)
4'-512" 4'-10" S2 (TOP & BOTTOM)
OTHER RELEVANT DRAWINGS.
4. - DIA OF TOR STEEL
PB5
5" THK B1 B2 B6 B3 B6 B2 B5 B1 5. CLEAR COVER TO MAIN REINFORCEMENT (MILD EXPOSURE)
10'-0"
a) FOR BEAMS = 25 mm
8 @ 5" c/c B5
10'-9"
10'-2"
10'-0"
b) FOR SLABS = 20 mm
11'-8"
RCC
15'-712"
15'-712"
10'-9"
PB5 8 @ 5" c/c 6. LAPPING:
PB4
3
PB2
PB2
COLUMN
B2
B2
a) LAP LENGTH SHALL BE = 50 x DIA OF BAR.
B4
b) DEVELOPMENT LENGTH SHALL BE = 50 x DIA OF BAR.
+13'-9" LVL LIVING @ +3' LVL BEDROOM-2 TOILET @
S1
9'-3"
9'-3"
+2'-10" LVL 7. PROVIDE CHAIR RODS WHEREVER NECESSARY
+13'-9" LVL
+3'-0"(LVL) PORTICO @ +1'-6" LVL
5" THK S3 8. PROVIDE SPACER RODS OF 25mm Ø (min) AT 1000mm C/C
+1'-6"(LVL) 9. GRADE OF CONCRETE IS M20
+0'-0"(R.L) 10.GRADE OF REINFORCING STEEL IS Fe 500
16'-9"
PB3
PB3 S4
B3
B3
* NOTE : ALL LEVELS MENTIONED ARE WITH RESPECT TO +0'0" - ROAD LEVEL
1'-6"
1'-6"
8 @ 6" c/c 3 # 12 CTLD ( ) S3 5" + 13'-4" LVL TWO WAY
IMPORTANT NOTES:-
7'-712"
7'-712"
S3 3 # 12 ST 3 # 12 ST
S4 7" + 13'-2" LVL TWO WAY * ONLY APPROVED DRAWINGS ( i.e., SEALED AND DULY SIGNED AS
FLOATING COLUMN 9" 9"
14'-112"
14'-112"
PB2
B2
B2
PB5 B5 S1 ROOF BEAM REINFORCEMENT DETAILS
PB1
B4
NOTICE OF STRUCTURAL ENGINEER.
LEAVE DOWELS (PB1* REINFORCEMENT FOLLOW END SECTION OF PB1) BEAM ID END SUPORT MID SPAN
LEAVE DOWELS * ANY MODIFICATION IN THE DESIGNER'S STRUCTURAL SYSTEM BEFORE/AFTER
STAIRCASE FOR STAIRCASE COMPLETION OF WORK SHALL BE IMMEDIATELY INTIMATED TO THE CONSULTANT
FOR STAIRCASE
+0'-0"(R.L) +0'-0"(R.L)
9" 9" * CLIENT / BUILDER ENSURES THAT STRICT ADHERENCE TO THE GOOD
VOID
3 # 12 ST CONSTRUCTION PRACTICE IS FOLLOWED AT SITE AS PER THE RELEVANT B.I.S. CODES.
3 # 12 ST 2 # 20 ST 2 # 20 ST
1 1
2
2 # 20 CTLD ( ) 8 @ 8" c/c * STRUCTURAL ENGINEER'S RESPONSIBILTY IS LIMITED TO DESIGNING & ISSUAL OF
1'-3"
1'-6"
8 @ 8" c/c
1'-6"
1'-6"
PB1 PB1* B1 8 @ 8" c/c B1 STRUCTURAL DRAWINGS ONLY
X 8 @ 6" c/c 2 # 20 CTLD ( )
3 # 12 ST
21'-6" 21'-6" 3 # 12 ST 2 # 20 ST 2 # 20 ST
9" 9"
A B A B PB2 PB3 +12'-3"
1'-3"
1'-3"
1'-3"
8 @ 8" c/c
1'-0"
8 @ 8" c/c 8 @ 6" c/c 2 # 12 CTLD ( )
18" 18" 18" 18" STRUCTURAL ENGINEER
3 # 12 ST 3 # 12 ST 2 # 16 ST 2 # 16 ST
9" 9" * ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS OTHERWISE SPECIFIED.
PB4 PB5 +12'-6"
* THE COPYRIGHT OF THIS DRAWING AND OF ALL ENCLOSURES ENTRUSTED TO
4 # 16 THE RECIPIENT PERSONALLY REMAINS THE EXCLUSIVE PROPERTY OF THE FIRM,
4 # 16 9" 9"
(To Shape) (To Shape) WITH OUT OUR WRITTEN CONSENT THEY SHOULD NOT BE COPIED OR REPRODUCED
+0'-0"(R.L) 2 # 16 ST 2 # 16 ST OR DELIVERED OR MADE KNOWN TO THIRD PARTY.
60°
2 # 12 CTLD ( ) 8 @ 8" c/c
1'-6"
1'-6"
3 # 12 ST 3 # 12 ST B3
Main Beam Secondary Beam Main Beam Secondary Beam
3 # 12 CTLD ( ) 8 @ 8" c/c
8 @ 6" c/c 2 # 12 CTLD ( ) PROPOSED RESIDENTIAL BUILDING FOR
2 # 16 ST 2 # 16 ST
2'-0"
2'-0"
TYPICAL BEAM TO BEAM JUNCTION DETAIL TYPICAL BEAM TO BEAM JUNCTION DETAIL 8 @ 6" c/c 3 # 12 CTLD ( )
Mr.BALA KRISHNAN
(where the depth of secondary beam is less than main beam) (where the depth of secondary beam is equal to main beam) 3 # 12 ST 3 # 12 ST
+12'-3"
CLIENT:-
AT COIMBATORE
9" 9"
0.25L 0.3L 0.3L END MID 9" 9" REFERENCE:
2 # 20 ST 2 # 20 ST W
NW
(50xDIA.)
SW
1'-3"
1'-3"
B4 8 @ 6" c/c N
STIRRUPS @ END STIRRUPS @ MID STIRRUPS @ END STIRRUPS @ END 2 # 20 CTLD ( )
N
SE
N
2 # 20 ST 2 # 20 ST
E
E
1
(1 TIES) 3 # 12 ST
3 # 12 ST
TYPICAL LONGITUDINAL SECTION OF BEAM 8 @ 8" c/c
1'-0"
1'-0"
B5 8 @ 6" c/c
3 # 12 ST
2 # 12 CTLD ( ) DETAIL : PLINTH BEAM & GF ROOF BEAM LAYOUT & DETAILS
3 # 12 ST
SCALE : 1"=9'-0" JOB NO : AG-01 REV DESIGN BY: BARATH
Distributor Main Reinforcement +12'-9"
@ Bottom 0.3L 0.3L 0.3L @ Top
DATE : 14-08-2020 DRG NO : AG-01-RF-01 R0
9" 9"
SHEET NO: 01
Slab tk
2'-0"
8 @ 5" c/c STRUCTURALS ARCHITECTS BUILDERS
A B C D