Water Piping Must Be Sized To Limit The Friction Head Losses in The
Water Piping Must Be Sized To Limit The Friction Head Losses in The
The water distribution system must always be designed on the basis of the minimum
pressure.
Generally, the minimum pressure to be provided at most fixtures is 8 psi and from 15 to 25 psi
for water closets.
Remember that these pressures are flow pressures and not statistic pressures.
1. Friction Head loss. Water piping must be sized to limit the friction head losses in the
piping system so that the highest and most remote water outlet will have the required
minimum pressure for adequate flow during periods of peak demand. Remember that
friction head loss is directly proportional to the length of run.
2. The equivalent length of piping – is its developed lengths plus the equivalent lengths of
pipe corresponding to friction head losses for fittings, valves, strainers, etc. When the
system is sized, the sizes of fittings and valves are not known and the added friction head
losses imposed must be approximated. A general rule of thumb that has proven to be
surprisingly accurate is to add 50% of the developed lengths to allow for all fittings and
valves.
Having established the uniform loss all that is needed now is to employ hydraulic Tables to
obtain the corresponding rates flow that will produce that loss for various sizes of pipes of
various materials.
For your example refer to this Table for 6”ф pipes and tubes. Similar Table for ½” diameter
other sizing tables maybe found in
q = 60.8 d 2½ ( )½
Where:
q = quantity of flow, g pm
Note: That the maximum velocity for our design purpose is 8 ft/sec in piping (10ft/sec. becomes
noisy & approaching & problem)
For Friction Head loss Tables, these are based upon the Hazen and Williams Formula
100 q1.85
f = .2083 ( )1.85×( )
C d 4.8655
Where:
q = flow, gpm
Investigate a 16 storey building where a street water pressure reported as 45 psi. The
highest fixture out let is 180 ft. above the levels of the pump, and the pumps are at the same level
as the street main. The building has flush valves water closets and the pressure required at the
highest fixture is 20 psi. The total combined cold and hot water fixture counts for the building is
4840 FU. The length of run from the pumps to the farthest and highest fixture is 350 ft. material
for the water service into the building will be Type K Copper tubing, and the water distribution
within the building will be Type L Copper tubing fixture unit load will be found as tabulated.
TABLE OF LOADS
COLD WATER TABULATION
4840 FU
1. q = rwc Δt – Formula 1
Tu – tc, °F (°K)
Therefore:
Δt
gal 1 BTU 8.33 lbs
q= Hr
([ )(
1b
°F
gal )
]
m3 4.19 kgJ 999.6 kg
= Hr
([ )(
kg
k
m3 Δt ) ]
Ex. Calculate the heat output rate required to heat 600 gph from 50 °F to 140 °F from Eq.1
BTU
=449,820
hr
ET = ( q−B
q )
x 100, B = internal heat loss of water heater
1 kilowatt of electric water heater power will raise 410 gal of water 1 °F.
These can be express in a series of formulas:
410 gal
Formula 2: =gal. of water kilowatt Δt
Δt
gph × Δt
Formula 3: =kw required
410 gal
Where :
Example: An electric water heater must be sized based on the following information.
40 gph hot water at a temperature of 140 °F.
The incoming water supply (normal in the Philippines) is 60 °F.
Using formula # 3
1. = 7.797 kw required 2.
= 799.4/ kw
HOT WATER CALCULATION
= 1,365,000 BTU / hr
= 400 kw
Where:
.5 = usage factor
A. The objective of the design of hot water circulation system is to have hot water of
required temperature readily available at any fixture as needed.
HEAT LOSS OF
INSULATED
COPPER TUBES
COMPUTATION ON
RECIRCULATING
COPPER TUBING
2 ½ “ Φ – 12 X 90 = 1080
2” Φ – 16 X 90 = 1440
1 ½” Φ – 13 X 45 = 585
1 ¼” Φ – 13 X 45 = 585
Assume:
1 “Φ - 200 x 10 = 2000
¾ - 200 x 10 = 2000
½ - 2000 x 8 = 1600
9290 BTU / hr
10 % Add 929
Head=120psi