DATA SHEET
DC523
Digital Input/Output Module
1 Ordering Data
Part No. Description Product Life Cycle Phase *)
1SAP 240 500 R0001 DC523, digital input/output Active
module, 24 DC, 24 V DC / 0.5
A, 1-wire
1SAP 440 500 R0001 DC523-XC, digital input/output Active
module, 24 DC, 24 V DC / 0.5
A, 1-wire, XC Version
*) For planning and commissioning of new installations use modules in Active status
only.
2 Dimensions
3 Technical Data
The System Data of AC500 and S500 Ä Chapter 4 “System Data AC500” on page 6 are valid for
standard version.
The System Data of AC500-XC Ä Chapter 5 “System Data AC500-XC” on page 10 are valid for the
XC version.
Only additional details are therefore documented below.
Parameter Value
Process supply voltage UP
Connections Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP) as
well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP)
Rated value 24 V DC
Max. ripple 5%
Protection against reversed voltage Yes
Rated protection fuse on UP 10 A fast
Galvanic isolation Yes, per module
Input data length 3 bytes
Parameter Value
Output data length 3 bytes
Current consumption
From 24 V DC power supply at the termi- Ca. 2 mA
nals UP/L+ and ZP/M of the CPU/Bus
Module
From UP at normal operation / with out- 0.1 A + max. 0.5 A per output
puts
Inrush current from UP (at power up) 0.008 A²s
Max. power dissipation within the module 6 W (outputs unloaded)
Sensor power supply
Connections Terminals 1.0...1.3 = +24 V, 1.4...1.7 = 0 V
Voltage 24 V DC with short-circuit and overload protection
Loadability Terminals 1.0...1.3, in total max. 0.5 A
Weight (without Terminal Unit) Ca. 125 g
Mounting position Horizontal
Or vertical with derating (output load reduced to
50 % at 40°C per group)
Cooling The natural convection cooling must not be hin-
dered by cable ducts or other parts in the switch-
gear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity, reverse
supply, short circuit and continuous overvoltage up to 30 V DC.
Effects of mul- No effect, as every channel is protected individually by an internal smart high-side switch.
tiple overloads
on isolated
multi-channel
modules
3.1 Technical Data of the Configurable Digital Inputs/Outputs
Each of the configurable I/O channels is defined as input or output by the user program. This is done
by interrogating or allocating the corresponding channel.
Parameter Value
Number of channels per module 24 inputs/outputs (with transistors)
Distribution of the channels into groups 1 group of 24 channels
If the channels are used as inputs
Channels C0...C7 Terminals 2.0...2.7
Channels C8...C15 Terminals 3.0...3.7
Channels C16...C23 Terminals 4.0...4.7
If the channels are used as outputs
Channels C0...C7 Terminals 2.0...2.7
Parameter Value
Channels C8 C15 Terminals 3.0...3.7
Channels C16...C23 Terminals 4.0...4.7
Indication of the input/output signals 1 yellow LED per channel, the LED is ON when the
input/output signal is high (signal 1)
Galvanic isolation From the rest of the module
* Due to the direct connection to the output, the demagnetizing varistor is also effective at the input
(see figure) above. This is why the difference between UPx and the input signal must not exceed the
clamp voltage of the varistor. The varistor limits the clamp voltage to approx. 36 V. Consequently, the
input voltage must range from - 12 V to + 30 V when UPx = 24 V and from - 6 V to + 30 V when UPx
= 30 V.
Parameter Value
Common power supply voltage For all outputs: terminals 1.8, 2.8, 3.8 and 4.8
(positive pole of the process supply voltage, signal
name UP)
Output voltage for signal 1 UP (-0.8 V)
Output delay (0->1 or 1->0) On request
Output current
Rated value, per channel 500 mA at UP = 24 V
Maximum value (all channels together) 8A
Leakage current with signal 0 < 0.5 mA
Rated protection fuse on UP 10 A fast
Demagnetization when inductive loads are With varistors integrated in the module (see figure
switched off below)
Switching frequency
With resistive load On request
With inductive loads Max. 0.5 Hz
With lamp loads Max. 11 Hz with max. 5 W
Short-circuit proof / overload proof Yes
Overload message (I > 0.7 A) Yes, after ca. 100 ms
Output current limitation Yes, automatic reactivation after short-circuit/over-
load
Resistance to feedback against 24V signals Yes
Max. cable length
Shielded 1000 m
Unshielded 600 m
The following drawing shows the circuitry of a digital input/output with the varistors for demagnetiza-
tion when inductive loads are switched off.
UPx (+24 V)
Digital input/output
ZPx (0 V)
The fast counter of the module does not work if the module is connected to a
– FBP interface module
– CS31 bus module
– CANopen bus module
Parameter Value
Used inputs C16 / C17
Used outputs C18
Counting frequency Max. 50 kHz
Input data length 13 bytes
Output data length 21 bytes
Detailed description See Fast Counter
Operating modes See Operating modes
NOTICE!
Exceeding the maximum power supply voltage for process or supply voltages could
lead to unrecoverable damage of the system. The system could be destroyed.
NOTICE!
Improper voltage level or frequency range which cause damage of AC inputs:
– AC voltage above 264 V
– Frenquency below 47 Hz or above 62.4 Hz
NOTICE!
Improper connection leads cause overtemperature on terminals.
PLC modules may be destroyed by using wrong cable type, wire size and cable tem-
perature classification.
Parameter Value
Temperature
Operating 0 °C ... +60 °C: Horizontal mounting of modules.
0 °C ... +40 °C: Vertical mounting of modules.
Output load reduced to 50 % per group.
Storage -40 °C ... +70 °C
Transport -40 °C ... +70 °C
Humidity Max. 95 %, without condensation
Air pressure
Operating > 800 hPa / < 2000 m
Storage > 660 hPa / < 3500 m
Ingress protection IP20
Immunity
Immunity against the influence of radiated (CW radi- According to EN 61000-4-3, zone B, cri-
ated): terion A
Test field strength 10 V/m
Immunity against transient interference voltages According to EN 61000-4-4, zone B, cri-
(burst): terion B
Supply voltage units (AC, DC) 4 kV
Digital inputs/outputs (24 V DC) 2 kV
Digital inputs/outputs (120/230 V AC) 2 kV
Analog inputs/outputs 1 kV
CS31 system bus 2 kV
Serial RS-485 interfaces (COM) 2 kV
Serial RS-232 interfaces (COM, not for PM55x 1 kV
and PM56x)
ARCNET 1 kV
FBP 1 kV
Ethernet 1 kV
I/O supply, DC-out 1 kV
Immunity against the influence of line-conducted According to EN 61000-4-6, zone B, cri-
interferences (CW conducted): terion A
Test voltage 3V zone B, 10 V is also met.
High energy surges According to EN 61000-4-5, zone B, cri-
terion B
Power supply DC 1 kV CM / 0.5 kV DM ²)
DC I/O supply 0.5 kV CM / 0.5 kV DM ²)
Communication Lines, shielded 1 kV CM ²)
AC-I/O unshielded 2 kV CM / 1 kV DM ²)
I/O analog, I/O DC unshielded 1 kV CM / 0.5 kV DM ²)
Radiation (radio disturbance) According to EN 55011, group 1, class A
1) High requirement for shipping classes are achieved with additional specific measures (see specific
documentation).
²) CM = Common Mode, DM = Differential Mode
NOTICE!
Exceeding the maximum process or supply voltage (< -35 V DC and > + 35 V DC)
could lead to unrecoverable damage of the system.
NOTICE!
For the supply of the modules, power supply units according to PELV or SELV specifi-
cations must be used.
The creepage distances and clearances meet the requirements of the overvoltage
category II, pollution degree 2.
Parameter Value
Temperature
Operating -40 °C ... +70 °C
-40 °C ... -30 °C: Proper start-up of system; tech-
nical data not guaranteed
-40 °C ... 0 °C: Due to the LCD technology, the
display might respond very slowly.
-40 °C...+40 °C: Vertical mounting of modules
possible, output load limited to 50 % per group
+60 °C ...+70 °C with the following deratings:
● System is limited to max. 2 Communication
Modules per Terminal Base
● Applications certified for cULus up to 60 °C
● Digital inputs: maximum number of simultane-
ously switched on input channels limited to
75 % per group (e.g. 8 channels => 6 chan-
nels)
● Digital outputs: output current maximum
value (all channels together) limited to 75 %
per group (e.g. 8 A => 6 A)
● Analog outputs only if configured as voltage
output: maximum total output current per
group is limited to 75 % (e.g. 40 mA => 30
mA)
● Analog outputs only if configured as current
output: maximum number of simultaneously
used output channels limited to 75 % per
group (e.g. 4 channels => 3 channels)
Storage / Transport -40 °C ... +85 °C
Humidity Operating / Storage: 100 % r. H. with condensa-
tion
Air pressure Operating:
-1000 m .... 4000 m (1080 hPa ... 620 hPa)
>2000 m (<795 hPa):
● max. operating temperature must be reduced
by 10 K (e.g. 70 °C to 60°C)
● I/O module relay contacts must be operated
with 24V nominal only
Immunity to corrosive gases Operating: Yes, according to:
ISA S71.04.1985 Harsh group A, G3/GX
IEC 60721-3-3 3C2 / 3C3
Immunity to salt mist Operating: Yes, horizontal mounting only,
according to IEC 60068-2-52 severity level: 1
NOTICE!
Risk of corrosion!
Unused connectors and slots may corrode if XC devices are used in salt-mist environ-
ments.
Protect unused connectors and slots with TA535 protective caps for XC devices
TA535.
NOTICE!
Risk of malfunctions!
Unused slots for communication modules are not protected against accidental phys-
ical contact.
– Unused slots for communication modules must be covered with dummy communi-
cation modules (TA524 to achieve IP20 rating.
– I/O bus connectors must not be touched during operation.
Parameter Value
High energy transient interference Supply voltage units (DC): 1 kV CM* / 0.5 kV DM*
voltages (surge)
Digital inputs/outputs (24 V DC): 1 kV CM* / 0.5 kV DM*
Analog inputs/outputs: 1 kV CM* / 0.5 kV DM*
Communication lines shielded: 1 kV CM*
I/O supply (DC-out): 0,5 kV CM* / 0.5 kV DM*
* CM = Common Mode, * DM = Differential Mode
Influence of radiated disturbances Test field strength: 10 V/m
Influence of line-conducted interfer- Test voltage: 10 V
ences
Power frequency magnetic fields 30 A/m 50 Hz
30 A/m 60 Hz
— —