Ordering Data

DATA SHEET

DC523
Digital Input/Output Module

1 Ordering Data
Part No. Description Product Life Cycle Phase *)
1SAP 240 500 R0001 DC523, digital input/output Active
module, 24 DC, 24 V DC / 0.5
A, 1-wire
1SAP 440 500 R0001 DC523-XC, digital input/output Active
module, 24 DC, 24 V DC / 0.5
A, 1-wire, XC Version

*) For planning and commissioning of new installations use modules in Active status
only.

2017-12-12 3ADR10043, 1, en_US 1


Technical Data

2 Dimensions

The dimensions are in mm and in brackets in inch.

3 Technical Data
The System Data of AC500 and S500 Ä Chapter 4 “System Data AC500” on page 6 are valid for
standard version.
The System Data of AC500-XC Ä Chapter 5 “System Data AC500-XC” on page 10 are valid for the
XC version.
Only additional details are therefore documented below.

Parameter Value
Process supply voltage UP
Connections Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP) as
well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP)
Rated value 24 V DC
Max. ripple 5%
Protection against reversed voltage Yes
Rated protection fuse on UP 10 A fast
Galvanic isolation Yes, per module
Input data length 3 bytes

2 3ADR10043, 1, en_US 2017-12-12


Technical Data of the Configurable Digital Inputs/Outputs

Parameter Value
Output data length 3 bytes
Current consumption
From 24 V DC power supply at the termi- Ca. 2 mA
nals UP/L+ and ZP/M of the CPU/Bus
Module
From UP at normal operation / with out- 0.1 A + max. 0.5 A per output
puts
Inrush current from UP (at power up) 0.008 A²s
Max. power dissipation within the module 6 W (outputs unloaded)
Sensor power supply
Connections Terminals 1.0...1.3 = +24 V, 1.4...1.7 = 0 V
Voltage 24 V DC with short-circuit and overload protection
Loadability Terminals 1.0...1.3, in total max. 0.5 A
Weight (without Terminal Unit) Ca. 125 g
Mounting position Horizontal
Or vertical with derating (output load reduced to
50 % at 40°C per group)
Cooling The natural convection cooling must not be hin-
dered by cable ducts or other parts in the switch-
gear cabinet.

NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity, reverse
supply, short circuit and continuous overvoltage up to 30 V DC.

Effects of mul- No effect, as every channel is protected individually by an internal smart high-side switch.
tiple overloads
on isolated
multi-channel
modules
3.1 Technical Data of the Configurable Digital Inputs/Outputs
Each of the configurable I/O channels is defined as input or output by the user program. This is done
by interrogating or allocating the corresponding channel.

Parameter Value
Number of channels per module 24 inputs/outputs (with transistors)
Distribution of the channels into groups 1 group of 24 channels
If the channels are used as inputs
Channels C0...C7 Terminals 2.0...2.7
Channels C8...C15 Terminals 3.0...3.7
Channels C16...C23 Terminals 4.0...4.7
If the channels are used as outputs
Channels C0...C7 Terminals 2.0...2.7

2017-12-12 3ADR10043, 1, en_US 3


Technical Data of the Configurable Digital Inputs/Outputs > Technical data of the digital inputs/outputs if used as outputs

Parameter Value
Channels C8 C15 Terminals 3.0...3.7
Channels C16...C23 Terminals 4.0...4.7
Indication of the input/output signals 1 yellow LED per channel, the LED is ON when the
input/output signal is high (signal 1)
Galvanic isolation From the rest of the module

3.1.1 Technical data of the digital inputs/outputs if used as inputs


Parameter Value
Number of channels per module Max. 24 digital inputs
Reference potential for all inputs Terminals 1.9, 2.9, 3.9 and 4.9 (minus pole of the
process supply voltage, signal name ZP)
Galvanic isolation From the rest of the module
Indication of the input signals 1 yellow LED per channel, the LED is ON when
the input signal is high (signal 1)
Input type acc. to EN 61131-2 Type 1
Input delay (0->1 or 1->0) Typ. 8 ms, configurable from 0.1 to 32 ms
Input signal voltage 24 V DC
Signal 0 -3 V...+5 V *
Undefined signal > +5 V...< +15 V
Signal 1 +15 V...+30 V
Ripple with signal 0 Within -3 V...+5 V *
Ripple with signal 1 Within +15 V...+30 V
Input current per channel
Input voltage +24 V Typ. 5 mA
Input voltage +5 V > 1 mA
Input voltage +15 V > 5 mA
Input voltage +30 V < 8 mA
Max. cable length
Shielded 1000 m
Unshielded 600 m

* Due to the direct connection to the output, the demagnetizing varistor is also effective at the input
(see figure) above. This is why the difference between UPx and the input signal must not exceed the
clamp voltage of the varistor. The varistor limits the clamp voltage to approx. 36 V. Consequently, the
input voltage must range from - 12 V to + 30 V when UPx = 24 V and from - 6 V to + 30 V when UPx
= 30 V.

3.1.2 Technical data of the digital inputs/outputs if used as outputs


Parameter Value
Number of channels per module Max. 24 transistor outputs
Reference potential for all outputs Terminals 1.9, 2.9, 3.9 and 4.9 (negative pole of
the process supply voltage, signal name ZP)

4 3ADR10043, 1, en_US 2017-12-12


Technical Data of the Configurable Digital Inputs/Outputs > Technical data of the digital inputs/outputs if used as outputs

Parameter Value
Common power supply voltage For all outputs: terminals 1.8, 2.8, 3.8 and 4.8
(positive pole of the process supply voltage, signal
name UP)
Output voltage for signal 1 UP (-0.8 V)
Output delay (0->1 or 1->0) On request
Output current
Rated value, per channel 500 mA at UP = 24 V
Maximum value (all channels together) 8A
Leakage current with signal 0 < 0.5 mA
Rated protection fuse on UP 10 A fast
Demagnetization when inductive loads are With varistors integrated in the module (see figure
switched off below)
Switching frequency
With resistive load On request
With inductive loads Max. 0.5 Hz
With lamp loads Max. 11 Hz with max. 5 W
Short-circuit proof / overload proof Yes
Overload message (I > 0.7 A) Yes, after ca. 100 ms
Output current limitation Yes, automatic reactivation after short-circuit/over-
load
Resistance to feedback against 24V signals Yes
Max. cable length
Shielded 1000 m
Unshielded 600 m

The following drawing shows the circuitry of a digital input/output with the varistors for demagnetiza-
tion when inductive loads are switched off.

UPx (+24 V)

Digital input/output

ZPx (0 V)

for demagnitization when inductive


loads are switched off

Fig. 1: Digital input/output (circuit diagram)

2017-12-12 3ADR10043, 1, en_US 5


System Data AC500
Environmental Conditions

3.2 Technical Data of the Fast Counter

The fast counter of the module does not work if the module is connected to a
– FBP interface module
– CS31 bus module
– CANopen bus module

Parameter Value
Used inputs C16 / C17
Used outputs C18
Counting frequency Max. 50 kHz
Input data length 13 bytes
Output data length 21 bytes
Detailed description See Fast Counter
Operating modes See Operating modes

4 System Data AC500


4.1 Environmental Conditions
Table 1: Process and supply voltages
Parameter Value
24 V DC
Voltage 24 V (-15 %, +20 %)
Protection against reverse polarity Yes
120 V AC
Voltage 120 V (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
230 V AC
Voltage 230 V AC (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
120...240 V AC wide range supply
Voltage 120...240 V (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
Allowed interruptions of power supply, according to EN 61131-2
DC supply Interruption < 10 ms, time between 2 interrup-
tions > 1 s, PS2
AC supply Interruption < 0.5 periods, time between 2 inter-
ruptions > 1 s

NOTICE!
Exceeding the maximum power supply voltage for process or supply voltages could
lead to unrecoverable damage of the system. The system could be destroyed.

6 3ADR10043, 1, en_US 2017-12-12


Insulation Test Voltages, Routine Test

NOTICE!
Improper voltage level or frequency range which cause damage of AC inputs:
– AC voltage above 264 V
– Frenquency below 47 Hz or above 62.4 Hz

NOTICE!
Improper connection leads cause overtemperature on terminals.
PLC modules may be destroyed by using wrong cable type, wire size and cable tem-
perature classification.

Parameter Value
Temperature
Operating 0 °C ... +60 °C: Horizontal mounting of modules.
0 °C ... +40 °C: Vertical mounting of modules.
Output load reduced to 50 % per group.
Storage -40 °C ... +70 °C
Transport -40 °C ... +70 °C
Humidity Max. 95 %, without condensation
Air pressure
Operating > 800 hPa / < 2000 m
Storage > 660 hPa / < 3500 m
Ingress protection IP20

4.2 Creepage Distances and Clearances


The creepage distances and clearances meet the requirements of the overvoltage category II, pollu-
tion degree 2.

4.3 Insulation Test Voltages, Routine Test


Insulation Test 230 V circuits against other cir- 2500 V 1.2/50 µs
Voltages, Rou- cuitry
tine Test,
According to EN 120 V circuits against other cir- 1500 V 1.2/50 µs
61131-2 cuitry
120 V to 240 V circuits against 2500 V 1.2/50 µs
other circuitry

24 V circuits (supply, 24 V 500 V 1.2/50 µs


inputs/outputs, analogue inputs/
outputs), if they are electrically
isolated against other circuitry
COM interfaces, electrically iso- 500 V 1.2/50 µs
lated

2017-12-12 3ADR10043, 1, en_US 7


Electromagnetic Compatibility

COM interfaces, electrically not Not applicable Not applicable


isolated
FBP interface 500 V 1.2/50 µs
Ethernet 500 V 1.2/50 µs
ARCNET 500 V 1.2/50 µs

230 V circuits against other cir- 1350 V AC 2 s


cuitry
120 V circuits against other cir- 820 V AC 2 s
cuitry
120 V to 240 V circuits against 1350 V AC 2 s
other circuitry

24 V circuits (supply, 24 V 350 V AC 2 s


inputs/outputs, analogue inputs/
outputs), if they are electrically
isolated against other circuitry
COM interfaces, electrically iso- 350 V AC 2 s
lated
COM interfaces, electrically not Not applicable Not applicable
isolated
FBP interface 350 V AC 2 s
Ethernet 350 V AC 2 s
ARCNET 350 V AC 2 s

4.4 Power Supply Units


For the supply of the modules, power supply units according to PELV specifications must be used.

4.5 Electromagnetic Compatibility


Immunity
Immunity against electrostatic discharge (ESD): According to EN 61000-4-2, zone B, cri-
terion B
Electrostatic voltage in case of air discharge 8 kV
Electrostatic voltage in case of contact discharge 4 kV, in a closed switch-gear cabinet 6 kV
1)

ESD with communication connectors In order to prevent operating malfunc-


tions, it is recommended, that the oper-
ating personnel discharge themselves
prior to touching communication connec-
tors or perform other suitable measures
to reduce effects of electrostatic dis-
charges.
ESD with connectors of Terminal Bases The connectors between the Terminal
Bases and Processor Modules or Com-
munication Modules must not be touched
during operation. The same is valid for
the I/O-Bus with all modules involved.

8 3ADR10043, 1, en_US 2017-12-12


Mechanical Data

Immunity
Immunity against the influence of radiated (CW radi- According to EN 61000-4-3, zone B, cri-
ated): terion A
Test field strength 10 V/m
Immunity against transient interference voltages According to EN 61000-4-4, zone B, cri-
(burst): terion B
Supply voltage units (AC, DC) 4 kV
Digital inputs/outputs (24 V DC) 2 kV
Digital inputs/outputs (120/230 V AC) 2 kV
Analog inputs/outputs 1 kV
CS31 system bus 2 kV
Serial RS-485 interfaces (COM) 2 kV
Serial RS-232 interfaces (COM, not for PM55x 1 kV
and PM56x)
ARCNET 1 kV
FBP 1 kV
Ethernet 1 kV
I/O supply, DC-out 1 kV
Immunity against the influence of line-conducted According to EN 61000-4-6, zone B, cri-
interferences (CW conducted): terion A
Test voltage 3V zone B, 10 V is also met.
High energy surges According to EN 61000-4-5, zone B, cri-
terion B
Power supply DC 1 kV CM / 0.5 kV DM ²)
DC I/O supply 0.5 kV CM / 0.5 kV DM ²)
Communication Lines, shielded 1 kV CM ²)
AC-I/O unshielded 2 kV CM / 1 kV DM ²)
I/O analog, I/O DC unshielded 1 kV CM / 0.5 kV DM ²)
Radiation (radio disturbance) According to EN 55011, group 1, class A
1) High requirement for shipping classes are achieved with additional specific measures (see specific

documentation).
²) CM = Common Mode, DM = Differential Mode

4.6 Mechanical Data


Wiring method / terminals
Mounting Horizontal
Degree of protection IP 20
Housing According to UL 94
Vibration resistance acc. to EN 61131-2 all three axes
2 Hz...15 Hz, continuous 3.5 mm
15 Hz...150 Hz, continuous 1 g (higher values on
request)

2017-12-12 3ADR10043, 1, en_US 9


System Data AC500-XC
Environmental Conditions

Vibration resistance with SD Memory Card 15 Hz...150 Hz, continuous 1 g


inserted
Shock test All three axes
15 g, 11 ms, half-sinusoidal
Mounting of the modules
DIN rail according to DIN EN 50022 35 mm, depth 7.5 mm or 15 mm
Mounting with screws Screws with a diameter of 4 mm
Fastening torque 1.2 Nm

4.7 Approvals and certifications


Information on approvals and certificates can be found in the corresponding chapter of the
Main catalog, PLC Automation.

5 System Data AC500-XC


Assembly, construction and connection of devices of the variant AC500-XC is iden-
tical to AC500 (standard). The following description provides information on general
technical data of AC500-XC system.

5.1 Environmental Conditions


Table 2: Process and supply voltages
Parameter Value
24 V DC
Voltage 24 V (-15 %, +20 %)
Protection against reverse polarity Yes
120...240 V AC wide range supply
Voltage 120...240 V (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
Allowed interruptions of power supply
DC supply Interruption < 10 ms, time between 2 interruptions >
1 s, PS2

NOTICE!
Exceeding the maximum process or supply voltage (< -35 V DC and > + 35 V DC)
could lead to unrecoverable damage of the system.

NOTICE!
For the supply of the modules, power supply units according to PELV or SELV specifi-
cations must be used.

10 3ADR10043, 1, en_US 2017-12-12


Environmental Conditions

The creepage distances and clearances meet the requirements of the overvoltage
category II, pollution degree 2.

Parameter Value
Temperature
Operating -40 °C ... +70 °C
-40 °C ... -30 °C: Proper start-up of system; tech-
nical data not guaranteed
-40 °C ... 0 °C: Due to the LCD technology, the
display might respond very slowly.
-40 °C...+40 °C: Vertical mounting of modules
possible, output load limited to 50 % per group
+60 °C ...+70 °C with the following deratings:
● System is limited to max. 2 Communication
Modules per Terminal Base
● Applications certified for cULus up to 60 °C
● Digital inputs: maximum number of simultane-
ously switched on input channels limited to
75 % per group (e.g. 8 channels => 6 chan-
nels)
● Digital outputs: output current maximum
value (all channels together) limited to 75 %
per group (e.g. 8 A => 6 A)
● Analog outputs only if configured as voltage
output: maximum total output current per
group is limited to 75 % (e.g. 40 mA => 30
mA)
● Analog outputs only if configured as current
output: maximum number of simultaneously
used output channels limited to 75 % per
group (e.g. 4 channels => 3 channels)
Storage / Transport -40 °C ... +85 °C
Humidity Operating / Storage: 100 % r. H. with condensa-
tion
Air pressure Operating:
-1000 m .... 4000 m (1080 hPa ... 620 hPa)
>2000 m (<795 hPa):
● max. operating temperature must be reduced
by 10 K (e.g. 70 °C to 60°C)
● I/O module relay contacts must be operated
with 24V nominal only
Immunity to corrosive gases Operating: Yes, according to:
ISA S71.04.1985 Harsh group A, G3/GX
IEC 60721-3-3 3C2 / 3C3
Immunity to salt mist Operating: Yes, horizontal mounting only,
according to IEC 60068-2-52 severity level: 1

2017-12-12 3ADR10043, 1, en_US 11


Environmental Conditions

NOTICE!
Risk of corrosion!
Unused connectors and slots may corrode if XC devices are used in salt-mist environ-
ments.
Protect unused connectors and slots with TA535 protective caps for XC devices
TA535.

Table 3: Electromagnectic Compatibility


Parameter Value
Radiated emission (radio disturbances) Yes, according to:
CISPR 16-2-3
Conducted emission (radio disturbances) Yes, according to:
CISPR 16-2-1, CISPR 16-1-2
Electrostatic discharge (ESD) Yes, according to:
IEC 61000-4-2, zone B, criterion B
Fast transient interference voltages (burst) Yes, according to:
IEC 61000-4-4, zone B, criterion B
High energy transient interference voltages Yes, according to:
(surge)
IEC 61000-4-5, zone B, criterion B
Influence of radiated disturbances Yes, according to:
IEC 61000-4-3, zone B, criterion A
Influence of line-conducted interferences Yes, according to:
IEC 61000-4-6, zone B, criterion A
Influence of power frequency magnetic fields Yes, according to:
IEC 61000-4-8, zone B, criterion A

In order to prevent malfunctions, it is recommended, that the operating personnel dis-


charge themselves prior to touching communication connectors or perform other suit-
able measures to reduce effects of electrostatic discharges.

NOTICE!
Risk of malfunctions!
Unused slots for communication modules are not protected against accidental phys-
ical contact.
– Unused slots for communication modules must be covered with dummy communi-
cation modules (TA524 to achieve IP20 rating.
– I/O bus connectors must not be touched during operation.

12 3ADR10043, 1, en_US 2017-12-12


Environmental Tests

5.2 Mechanical Data


Wiring method Spring terminals
Degree of protection IP 20
Vibration resistance Yes, according to:
IEC 61131-2
IEC 60068-2-6
IEC 60068-2-64
Shock resistance Yes, according to:
IEC 60068-2-27
Assembly position Horizontal
Vertical (no application in salt mist environment)
Assembly on DIN rail
DIN rail type According to IEC 60715
35 mm, depth 7.5 mm or 15 mm
Assembly with screws
Screw diameter 4 mm
Fastening torque 1.2 Nm

5.3 Environmental Tests


Parameter Value
Storage IEC 60068-2-1 Test Ab: cold withstand test -40 °C / 16 h
IEC 60068-2-2 Test Bb: dry heat withstand test +85 °C / 16 h
Humidity IEC 60068-2-30 Test Db: Cyclic (12 h / 12 h) Damp-Heat Test
55 °C, 93 % r. H. / 25 °C, 95 % r. H., 6 cycles
IEC 60068-2-78, Stationary Humidity Test: 40 °C, 93 % r. H., 240 h
Insulation Test IEC 61131-2
Vibration resistance IEC 61131-2 / IEC 60068-26: 5 Hz ... 500 Hz, 2 g (with SD Memory
Card inserted)
IEC 60068-2-64: 5 Hz ... 500 Hz, 4 g rms
Shock resistance IEC 60068-2-27: all 3 axes 15 g, 11 ms, half-sinusoidal

Table 4: EMC Immunity


Parameter Value
Electrostatic discharge (ESD) Electrostatic voltage in case of air discharge: 8 kV
Electrostatic voltage in case of contact discharge: 6 kV
Fast transient interference voltages Supply voltage units (DC): 4 kV
(burst)
Digital inputs/outputs (24 V DC): 2 kV
Analog inputs/outputs: 2 kV
Communication lines shielded: 2 kV
I/O supply (DC-out): 2 kV

2017-12-12 3ADR10043, 1, en_US 13


Environmental Tests

Parameter Value
High energy transient interference Supply voltage units (DC): 1 kV CM* / 0.5 kV DM*
voltages (surge)
Digital inputs/outputs (24 V DC): 1 kV CM* / 0.5 kV DM*
Analog inputs/outputs: 1 kV CM* / 0.5 kV DM*
Communication lines shielded: 1 kV CM*
I/O supply (DC-out): 0,5 kV CM* / 0.5 kV DM*
* CM = Common Mode, * DM = Differential Mode
Influence of radiated disturbances Test field strength: 10 V/m
Influence of line-conducted interfer- Test voltage: 10 V
ences
Power frequency magnetic fields 30 A/m 50 Hz
30 A/m 60 Hz

— —
ABB Automation Products GmbH © Copyright 2017 ABB.
Eppelheimer Str. 82 All rights reserved. Subject to alterations.
69123 Heidelberg, Germany
Telephone: +49 (0)6221 701 1444
Fax: +49 (0)6221 701 1382
E-mail: [email protected]
abb.com/plc

14 3ADR10043, 1, en_US 2017-12-12