Lecture 2a: Conductor Ampacity - Terminations and Derating Factors
Lecture 2a: Conductor Ampacity - Terminations and Derating Factors
Lecture 2a
Conductor Ampacity – Terminations
and Derating Factors
Revised by: Justine Joshua Ramos Adapted from: Allan C. Nerves, Ph.D., P.E.E.
Last Revision: August 2020 Electrical & Electronics Engineering Institute
University of the Philippines Diliman
Terminations and Derating Factors
This material illustrates the factors that can affect the decision:
a. Termination Ratings
b. Ambient Temperature
c. Conduit Fill
Conductor temperature
limitations can be compared
to the strength of a chain. A
chain is only as strong as its
weakest link. For example, a
90°C conductor has a
60°C termination on one
end and a 75°C termination
on the other. The weakest
link in this example is the
60°C termination (Figure3).
www.charlesrmiller.com
Conductor Termination: 100A or less
www.charlesrmiller.com
Example:
For example, a THHN conductor will have 75°C termination on one end and a
60/75 0C termination on the other. A temperature rating of 60/75 0C means the
equipment has been listed for both 60°C and 75°C conductors; therefore, it is
permissible to use the 75°C rating if the installed conductor is rated at least
75°C. Because all of the connection points in this example have at least a 75°C
rating, the conductor’s ampacity can be based on the 75°C column.
Example
Conductor Termination: over 100A
www.charlesrmiller.com
Example
Conductor Termination
www.charlesrmiller.com
Conductor Termination
www.charlesrmiller.com
Example
Schneider Electric
Derating Factors for Conductors
So, we need to or
Example:
Given three 30 mm2 RHW copper conductors in conduit,
at an ambient temperature of 47oC caused by heat
required in a chemical plant process., find the allowable
ampacity of the three conductors.
Solution:
Ampacity of 30 mm2 RHW copper wires at 30oC = 110 A
Correction factor at 47oC for RHW = 0.75
Allowable ampacity: 0.75 110 = 82.50 A
Derating Factors for Conductors
3 – 3.5 mm2 THHN
Derating Factors for Conductors
Derating Factors for Conductors
With termination consideration
Derating Factors for Conductors
Derating Factors for
Conductors
Specific case
Use of Nonmetallic-sheathed cable
Example
There are eight 50 mm2 THWN copper conductors in a given raceway.
Three of the wires carry a three-phase delta feed, four of the wires carry
a three-phase, four-wire system feed, motor load only; and one of the
wires is a grounding conductor. What is the allowable ampacity?
Solution:
One grounding wire – not counted
Three wires of 3-phase delta feed – all 3 are counted
Three wires of 3-phase, 4-wire system – all 3 are counted
Total wires counted: 6
From Table, use 80% factor for 6 wires
145 A is the allowable current for 50 mm2 THWN conductors
Therefore, allowable current for the eight wires is (0.8)(145) = 116 A.
Derating Factors for Conductors
Example:
A cable that contains five 1-phase control circuits of two 2.0 mm2 THHN
wires each is to extend from oa point in a boiler room that at times
reaches a temperature of 49 C. What is the allowable ampacity?
Solution:
Allowable ampacity for up to 3 – 2.0 mm2 THHN in conduit at 30oC is 25
A.
Correction factor for a temperature of 49oC is 0.82
All conductors are active and counted, no neutral or grounding
conductors present
Total number of conductors counted is 10 for which the reduction factor
is 50%
New allowable ampacity for each 2.0 mm2 THHN is (25A)(0.82)(0.50)
= 10.25 A
Derating Factors for Conductors
3. Circular Raceways Exposed to Sunlight on Rooftops
where conductors or cables are installed in circular raceways
exposed to direct sunlight on or above rooftops, the
adjustments shown in Table below shall be added to the
outdoor temperature to determine the applicable ambient
temperature for application of the correction factors in Tables
3.10.1.16 and 3.10.1.18.
Ambient Temperature Adjustment for Conduits Exposed to
Sunlight On or Above Rooftops: NEC Table 310.15(B)(2)(c)
Distance Above Roof to Bottom Temperature Temperature
of Conduit Added (oC) Added (oF)
0 to 13 mm (1/2 in.) 33 60
Above 13 mm to 90 mm (3.5 in.) 22 40
Above 90 mm to 300 mm (12 in.) 17 30
Above 300 mm to 900 mm (36 in.) 14 25
Derating Factors for Conductors
310.16
(2)(c)]=
Continuous Load
www.charlesrmiller.com
Continuous Load
www.charlesrmiller.com
Continuous Load
www.charlesrmiller.com
Continuous Load