Socomec Diris AP - Modbus / RS485 Manual
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
147 views

Rs485 - Jbus/Modbus: Diris Ap

Socomec Diris AP - Modbus / RS485 Manual
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

DIRIS Ap

®
RS485 – JBUS/MODBUS

GB
1
ON

C OM I

NL

Systèmes de Coupure et de Protection


Industrial Switching and Protection Systems
PRELIMINARY OPERATIONS
NB: Check the following points as soon • the package contains the product
For personnel and product safety as you receive the Diris Ap package: fitted with a pull-out terminal block,
please read the contents of these • the packing is in good condition, • operating instructions.
operating instructions carefully before • the product has not been damaged
connecting. during transit,
• the product reference number con-
forms to your order,

GENERAL INFORMATION
FUNCTIONS

The optional Communication module


provides an RS485 serial link (2 or 3
wires) with JBUS/MODBUS® protocol
for the use of Diris Ap from a PC or
PLC.

GENERAL POINTS

Recommendations: For standard configurations, an


You should use a shielded twisted pair RS 485 link is used to connect up to
(LIYCY type). In a disturbed environ- 31 Diris Ap with a PC or a PLC over
ment or large network (in terms of a distance of 1500 metres, using
length) we recommend the use of 2 JBUS/MODBUS© protocol.
shielded pairs (type LIYCY-CY). In this
case, one pair is used for the + and
the –, and another pair, where the 2
wires are short-circuited, for the 0 V.
1500 M
A repeater (1 channel) or an arrestor
(4 channels) should be used if you
intend to exceed the distance (1500
m) and/or maximum number (31) of
R = 120 Ω
Diris. Please contact us for more N° 1 N° 2 N° n
R = 120 Ω
information.
Programmable
controllers

DIRIS 109 B
NB :
Other systems
A 120 ohm resistance (found on the
additional module) must be fixed at
both ends of the link.

Other solutions are available (modem,


optical fibre, etc.). Please contact us 1500 M 1500 M

0+- -+0
R = 120 Ω N° 1 repetor N° n
RS485 R = 120 Ω
Programmable
controllers
DIRIS 110 B

Other systems

30 SOCOMEC - Ref. : 875 516 C


INSTALLATION
The module is fitted onto the back of
the DIRIS Ap in one of the 4 positions
provided.

CONNECTION

The DIRIS Ap must be switched off

ENGLISH
DIRIS 342 A

2 Fix the module in one of the four positions.


DIRIS 343 A

-+
0V
1


0
R= N
12
O

1
ON
DIRIS 347 A

Follow indications when connecting the terminal.


4 Switch on voltage supply.
SOCOMEC - Ref. : 875 516 C 31
PROGRAMMING
Programming starts after the reset to zero menu (rSET) or No. 2 pulse output duration (Out 2 DUR).

1 PROGRAMMING THE COMMUNICATION ADDRESS (COM ADR)


NB: The address default setting is 5 (ADR 5). If you want this value, press ▼. You will pass to communication speed
programming (COM BDS) If not, proceed as follows:
KEYS INSTRUCTION DISPLAY COMMENT

to display flashing the 1st digit (press


twice and three times for the 2nd and
Press once
3rd digit) or press to return to the
left.

Press ▼ to decrement or ▲ to increment the selected digit value


Press once to confirm
Press ▼ once to pass to speed programming (COM BDS)

NB: the address can vary between 1 to 255.

2 PROGRAMMING COMMUNICATION SPEED (COM BDS)


NB: The speed default setting is 9600 BDS (BDS 9600). If you want this value, press ▼. You will pass to communi-
cation parity programming (COM PAR). If not, proceed as follows:
KEYS INSTRUCTION DISPLAY COMMENT

Press once to display flashing 9600 bauds

Press again for:


Press once
38400, 2400, 4800 and 9600 bauds

Press again for:


Press once
2400, 38400, 19200 and 9600 bauds

Confirm speed.
Press once Press on ▼ to pass to parity
programming (PAR).

32 SOCOMEC - Ref. : 875 516 C


3 PROGRAMMING COMMUNICATION PARITY (COM PAR)
NB: As a default setting, the communication is without parity (PAR NO). If you want this setting, press ▼. You will pass
to communication stop bit programming (COM STOP). If not, proceed as follows:
KEYS INSTRUCTION DISPLAY COMMENT

Press once No parity

ou

ENGLISH
Press again for:
Press once EVEN (even parity) and NO (without
parity)

Press again for:


Press once ODD (odd parity) and NO (without
parity)

Confirm parity.
Press once Press on ▼ to pass to stop bit
programming (STOP)

4 PROGRAMMING COMMUNICATION STOP BIT (COM STOP)


NB: You will pass to No. 1 analog output programming (OUt 1 20 MA) if the analog output module is connected or
you will return to network type programming (nET)
KEYS INSTRUCTION DISPLAY COMMENT

Press once to display flashing stop bit value

or Press once 1 for 1 bit and 2 for 2 bits

Confirm stop bit.


Press once Press on ▼ to return to network type
programming.

SOCOMEC - Ref. : 875 516 C 33


COMMUNICATION
The JBUS/MODBUS® used by the The mode of communication is the
Diris Ap involves a dialogue using a RTU (Remote Terminal Unit) using
master-slave hierarchical structure. hexadecimal characters of at least 8
There are two possible dialogues: bits.
• the master communicates with a
slave (Diris Ap) and waits for its
reply
• the master communicates with all
the slaves (Diris Ap) without waiting
for their reply.

The standard communications frame


consists of:

Slave address Function code Address Data CRC 16

NB: According to the JBUS/MODBUS® pro- To correctly use information, the


When selecting slave address 0, a tocol, transmission time must be less following functions are important:
message is sent to all the instruments than 3 silences, i.e. the emission time of 3 : to read n words (maximum 128).
present on the network (only for func- 3 characters so that the message is 6 : to write one word.
tions 6 and 16). processed by the Diris. 8 : to diagnose exchanges between
the master and the slave via
meters 1, 3, 4, 5 and 6.
Comment: 16 : to write n words (maximum 128).
The maximum reply time is 250ms
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)

Table of values with allocated current and voltage winf-ding ratios on 2 words
Decimal Hexa. Number Text Unit
address address of words
768 300 2 phase 1 current mA
770 302 2 phase 2 current mA
772 304 2 phase 3 current mA
774 306 2 Neutral current mA
776 308 2 phase to phase voltage U12 V/100
778 30A 2 phase to phase voltage U23 V/100
780 30C 2 phase to phase voltage U31 V/100
782 30E 2 phase to neutral voltage phase 1 V/100
784 310 2 phase to neutral voltage phase 2 V/100
786 312 2 phase to neutral voltage phase 3 V/100
788 314 2 Frequency Hz/100
790 316 2 Σ Active power +/- kW/100
792 318 2 Σ Reactive power +/- kvar/100
794 31A 2 Σ Apparent power +/- kVA/100
796 31C 2 Σ Power factor
0,001
-: capacitive et +: inductive
798 31E 2 Active power phase 1 +/- kW/100
800 320 2 Active power phase 2 +/- kW/100
802 322 2 Active power phase 3 +/- kW/100
804 324 2 Reactive power phase 1 +/- kvar/100
806 326 2 Reactive power phase 2 +/- kvar/100
808 328 2 Reactive power phase 3 +/- kvar/100
810 32A 2 Apparent power phase 1 kVA/100
812 32C 2 Apparent power phase 2 kVA/100
814 32E 2 Apparent power phase 3 kVA/100
816 330 2 Power factor phase 1
0,001
-: capacitive et +: inductive
818 332 2 Power factor phase 2
0,001
-: capacitive et +: inductive
820 334 2 Power factor phase 3
0.001
-: capacitive et +: inductive
822 336 2 Average value I1 mA

34 SOCOMEC - Ref. : 875 516 C


Decimal Hexa. Number Text Unit
address address of words
824 338 2 Average value I2 mA
826 33A 2 Average value I3 mA
828 33C 2 Average value Σ Active power + kW/100
830 33E 2 Average value Σ Active power - kW/100
832 340 2 Average value Σ Reactive power + kvar/100
834 342 2 Average value Σ Reactive power - kvar/100
836 344 2 Average value Σ Apparent power kVA/100
838 346 2 Maximum value I1 mA
840 348 2 Maximum value I2 mA
842 34A 2 Maximum value I3 mA
844 34C 2 Maximum value Σ Active power + kW/100
846 34E 2 Maximum value Σ Active power - kW/100
Maximum value Σ Reactive power +

ENGLISH
848 350 2 kvar/100
850 352 2 Maximum value Reactive power - kvar/100
852 354 2 Maximum value Σ Apparent power kVA/100
854 356 2 Hour meter 1/100 h
856 358 2 Active energy + kWh
858 35A 2 Reactive energy + kWh
860 35C 2 Apparent energy kVAr
862 35E 2 Active energy - kWh
864 360 2 Reactive energy - kvarh

Address available with the Monitoring or Control/Command option


Decimal Hexa. Number Text Unit
address address of words
866 362 2 input pulse meter 1 -
868 364 2 input pulse meter 2 -
870 366 2 Number of impulse meters -
872 368 2 current alarm: -
0 : no alarm
1 : I1
2 : I2
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : +∑P
9 : +∑Q
10 : ∑S
11 : F
12 : LPF
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : -∑P
30 : -∑Q
31 : -∑PFC
874 36A 2 current overrun: –
0 : no alarm
1 : I1
2 : I2
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : +∑P
9 : +∑Q

SOCOMEC - Ref. : 875 516 C 35


Decimal Hexa. Number Text Unit
address address of words
10 : ∑S
11 : F
12 : LPF
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : -∑P
30 : -∑Q
31 : -∑PFC
876 36C 2 Number of inputs-outputs –
High-order : No of inputs
High-order : No of outputs
878 36F 2 Status of inputs-outputs –
bit 0 : status input 1 (0 = open, 1 = closed)
bit 1 : status input 2 (0 = open, 1 = closed)
bit 2 : status input 3 (0 = open, 1 = closed)
bit 3 : status input 4 (0 = open, 1 = closed)
bit 4 : status input 5 (0 = open, 1 = closed)
bit 5 : status input 6 (0 = open, 1 = closed)
bit 15 : status output 1 (0 = open, 1 = closed)
bit 16 : status output 2 (0 = open, 1 = closed)
bit 17 : status output 3 (0 = open, 1 = closed)
bit 18 : status output 4 (0 = open, 1 = closed)
bit 19 : status output 5 (0 = open, 1 = closed)
bit 20 : status output 6 (0 = open, 1 = closed)
Instant value display
880 370 2 average value of currents mA
882 372 2 average value of phase to phase voltages V/100
884 374 2 average value of phase to neutral voltages V/100
886 376 2 minimum current on the 3 phases mA
888 378 2 minimum current on the neutral mA
890 37A 2 minimum phase to phase voltage
on the 3 phases V/100
882 37C 2 minimum frequency Hz/100
894 37F 2 maximum current on the 3 phases mA
896 380 2 maximum current on the neutral mA
898 382 2 maximum phase to phase voltage
on the 3 phases V/100
900 384 2 maximum frequency Hz/100
902 386 2 minimum power factor 0,001
904 388 2 minimum active power +/- kW/100
906 38A 2 minimum reactive power +/- kvar/100
908 38C 2 maximum power factor 0,001
910 38F 2 maximum active power +/- kW/100
912 390 2 maximum reactive power +/- kvar/100
Zone size: 146 words (decimal) or 92 (hexadecimal).

Example:
To display all the values for Diris num-
ber 5 in one inquiry, the following
frame should be sent:

High-order Low-order High-order Low-order


Slave Function CRC 16
address address word n° word n°
05 03 03 00 00 92 C5A7

36 SOCOMEC - Ref. : 875 516 C


Table of values without allocated current and voltage winding ratios on 1
word
NB: Decimal Hexa. N° of Text Unit
Values should be multiplied by the fol- address address words
lowing coefficient: 1792 700 1 current phase 1 mA
1793 701 1 current phase 2 mA
CT = 100 = 20 VT = 20000 = 200 1794 702 1 current phase 3 mA
5 100 1795 703 1 Neutral current mA
CT x VT = 20 x 200 1796 704 1 phase to phase voltage U12 V/100
= 4000 1797 705 1 phase to phase voltage U23 V/100
1798 706 1 phase to phase voltage U31 V/100
Powers will be multiplied by 4000 (if 1799 707 1 phase to neutral phase 1 V/100
there is no VT, then VT = 1), currents 1800 708 1 phase to neutral phase 2 V/100
by 20 and voltages by 200. 1801 709 1 phase to neutral phase 3 V/100

ENGLISH
1802 70A 1 Frequency Hz/100
1803 70B 1 Σ Active power +/- kW/100
NB: 1804 70C 1 Σ Reactive power +/- kvar/100
For powers, when the highest order 1805 70D 1 Σ Apparent power +/- kVA/100
bit is at 1, the value is negative 1806 70E 1 Σ Power factor L/C
-: capacitive and +: inductive 0,001
1807 70F 1 Active power phase 1 +/- kW/100
1808 710 1 Active power phase 2 +/- kW/100
1809 711 1 Active power phase 3 +/- kW/100
1810 712 1 Reactive power phase 1 +/- kvar/100
1811 713 1 Reactive power phase 2 +/- kvar/100
1812 714 1 Reactive power phase 3 +/- kvar/100
1813 715 1 Apparent power phase 1 kVA/100
1814 716 1 Apparent power phase 2 kVA/100
1815 717 1 Apparent power phase 3 kVA/100
1816 718 1 Power factor phase 1
-: capacitive and +: inductive 0,001
1817 719 1 Power factor phase 2
-: capacitive and +: inductive 0,001
1818 71A 1 Power factor phase 3
-: capacitive and +: inductive 0,001
1819 71B 1 Average values I1 mA
1820 71C 1 Average values I2 mA
1821 71D 1 Average values I3 mA
1822 71E 1 Average value Σ Active power + kW/100
1823 71F 1 Average value Σ Active power - kW/100
1824 720 1 Average value Σ Reactive power + kvar/100
1825 721 1 Average value Σ Reactive power - kvar/100
1826 722 1 Average value Σ Apparent power KVA/100
1827 723 1 Maximum value I1 mA
1828 724 1 Maximum value I2 mA
1829 725 1 Maximum value I3 mA
1830 726 1 Maximum value Σ Active power + kW/100
1831 727 1 Maximum value Σ Active power - kW/100
1832 728 1 Maximum value Σ Reactive power + kvar/100
1833 729 1 Maximum value Σ Reactive power - kvar/100
1834 72A 1 Maximum value Σ Apparent power kVA/100

Allocated values of current and voltage winding ratios


1835 72C 1 Active energy + < 10000 kWh
1836 72D 1 Active energy + > 10000 kWh
1837 72D 1 Reactive energy + < 10000 kvarh
1838 72E 1 Reactive energy + > 10000 kvarh
1839 72F 1 Apparent energy < 10000 kVAh
1840 730 1 Apparent energy > 10000 kVAh
1841 731 1 Active energy - < 10000 kWh
1842 732 1 Active energy - > 10000 kWh
1843 733 1 Reactive energy - < 10000 kvarh
1844 734 1 Reactive energy - > 10000 kvarh

SOCOMEC - Ref. : 875 516 C 37


Address available with the Monitoring or Control/Command option
Decimal Hexa. N° of Text Unit
address address words
1845 735 1 impulse meter inputs 1 < 10000 -
1846 736 1 impulse meter inputs 1 > 10000 -
1847 737 1 impulse meter inputs 2 < 10000 -
1848 738 1 impulse meter inputs 2 > 10000 -
1849 739 1 impulse meter inputs 3 < 10000 -
1850 73A 1 impulse meter inputs 3 > 10000 -
1851 73B 1 impulse meter inputs 4 < 10000 -
1852 73C 1 impulse meter inputs 4 > 10000 -
1853 73D 1 impulse meter inputs 5 < 10000 -
1854 73E 1 impulse meter inputs 5 > 10000 -
1855 73F 1 impulse meter inputs 6 < 10000 -
1856 740 1 impulse meter inputs 6 > 10000 -

Display of non-allocated instant values of current and voltage winding ratios


Decimal Hexa. N° of Text Unit
address address words
1857 741 1 average value of currents mA
1858 742 1 average value of phase to phase voltages V/100
1859 743 1 average value of phase to neutral voltages V/100
1860 744 1 minimum current on the 3 phases mA
1861 745 1 minimum current on the neutral MA
1862 746 1 minimum phase to phase voltage on the 3 phases V/100
1863 748 1 minimum frequency Hz/100
1864 749 1 maximum current on the 3 phases MA
1865 74A 1 maximum current on the neutral MA
1866 74B 1 maximum phase to phase voltage on the 3 phases V/100
1867 74C 1 maximum frequency Hz/100
1868 74D 1 minimum power factor 0,001
1869 74E 1 minimum active power +/- kW/100
1870 74F 1 minimum reactive power +/- kvar/100
1871 750 1 maximum power factor 0,001
1872 751 1 maximum active power +/- kW/100
1873 752 1 maximum reactive power +/- kvar/100
1874 753 1 thd I1 0,1%
1875 754 1 thd I2 0,1%
1876 755 1 thd I3 0,1%
1877 756 1 thd In 0,1%
1878 757 1 thd U12 0,1%
1879 758 1 thd U23 0,1%
1880 759 1 thd U31 0,1%
1881 760 1 thd V1 0,1%
1882 761 1 thd V2 0,1%
1883 762 1 thd V3 0,1%
1884 763 1 minimum thd I 0,1%
1885 764 1 minimum thd In 0,1%
1886 765 1 minimum thd U 0,1%
1887 766 1 maximum thd I 0,1%
1888 768 1 maximum thd In 0,1%
1889 769 1 maximum thd U 0,1%
Size of this zone : 98 words (decimal) or 62 (hexadecimal)

38 SOCOMEC - Ref. : 875 516 C


Example :
To read 177 645 kWh, the following
message should be sent :

High-order Low-order High-order Low-order


Slave Function CRC 16
address address word n° word n°
05 03 07 2B 00 02 B4F3

Diris Ap reply:

Number Value Value


Slave Function CRC 16
of bytes high-order low-order

ENGLISH
05 03 04 285 B1 6FD6
645 177
Example:
To display all the values for Diris num-
ber 5 in one inquiry, the following
frame should be sent:

High-order Low-order High-order Low-order


Slave Function CRC 16
address address word n° word n°
05 03 07 00 00 62 C4D3

Alarm event log


Decimal Hexa. N° of Text Unit
address address words
1280 500 1 current alarm OUT 1 lower threshold –
0 : no alarm
1: I1
2 : I2
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : +ΣP
9 : +ΣQ
10 : ΣS
11 : F
12 : ΣFP
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : - ΣP
30 : -ΣQ
31 : CPF
1281 501 2 current alarm OUT 1 lower
threshold value –
1283 503 1 current alarm OUT 1 upper threshold –
0 : no alarm
1: I1
2 : I2

SOCOMEC - Ref. : 875 516 C 39


Decimal Hexa. N° of Text Unit
address address words
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : +ΣP
9 : +ΣQ
10 : ΣS
11 : F
12 : LPF
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : - ΣP
30 : -ΣQ
31 : CPF
1084 504 2 current alarm OUT 1 upper threshold value –
1086 506 1 duration sec
1087 507 1 alarm 1 OUT 1 lower threshold –
0 : no alarm
1: I1
2 : I2
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : +ΣP
9 : +ΣQ
10 : ΣS
11 : F
12 : LPF
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : -ΣP
30 : -ΣQ
31 : CPF
1288 508 2 alarm 1 OUT 1 lower threshold value –
1290 50A 1 alarm 1 OUT 1 upper threshold –
0 : no alarm
1: I1
2 : I2
3 : I3
4 : In
5 : U12
40 SOCOMEC - Ref. : 875 516 C
Decimal Hexa. N° of Text Unit
address address words
6 : U23
7 : U31
8 : +ΣP
9 : +ΣQ
10 : ΣS
11 : F
12 : LPF
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23

ENGLISH
20 : thd U31
21 : time
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : -ΣP
30 : -ΣQ
31 : CPF
1291 50B 2 alarm 1 OUT 1 upper threshold value –
1293 50D 1 duration sec
1294 50E 1 alarm 2 OUT 1 lower threshold –
0 : no alarm
1: I1
2 : I2
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : +ΣP
9 : +ΣQ
10 : ΣS
11 : F
12 : LPF
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : -ΣP
30 : -ΣQ
31 : CPF
1295 50F 2 alarm 2 OUT 1 lower threshold value –
1297 511 1 alarm 2 OUT 1 upper threshold –
0 : no alarm
1: I1
2 : I2
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : +ΣP
SOCOMEC - Ref. : 875 516 C 41
Decimal Hexa. N° of Text Unit
address address words
9 : +ΣQ
10 : ΣS
11 : F
12 : LPF
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time –
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : -ΣP
30 : -ΣQ
31 : CPF
1298 512 2 alarm 2 OUT 1 upper threshold value –
1300 514 1 duration sec
1301 515 1 alarm 3 OUT 1 lower threshold
0 : no alarm
1: I1
2 : I2
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : ΣP +
9 : ΣQ +
10 : ΣS
11 : F
12 : LPF
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time –
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : -ΣP
30 : -ΣQ
31 : CPF
1302 516 2 alarm 3 OUT 1 lower threshold value –
1304 518 1 alarm 3 OUT 1 upper threshold –
0 : no alarm
1: I1
2 : I2
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : ΣP +
9 : ΣQ +
10 : ΣS
11 : F
12 : LPF
15 : thd I1
16 : thd I2
42 SOCOMEC - Ref. : 875 516 C
Decimal Hexa. N° of Text Unit
address address words
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : -ΣP

ENGLISH
30 : -ΣQ
31 : CPF
1305 519 2 alarm 3 OUT 1 upper threshold value –
1307 51B 1 duration s.
1308 51C 1 current alarm OUT 2 lower threshold –
0 : no alarm
1: I1
2 : I2
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : +ΣP
9 : +ΣQ
10 : ΣS
11 : F
12 : ΣFP
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : -ΣP
30 : -ΣQ
31 : CPF
1309 51D 2 current alarm OUT 2 lower threshold value –
1311 51F 1 current alarm OUT 2 upper threshold –
0 : no alarm
1: I1
2 : I2
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : +ΣP
9 : +ΣQ
10 : ΣS
11 : F
12 : ΣFP
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time –
22 : V1
SOCOMEC - Ref. : 875 516 C 43
Decimal Hexa. N° of Text Unit
address address words
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : -ΣP
30 : -ΣQ
31 : CPF
1312 520 2 current alarm OUT 2 upper threshold value –
1314 522 1 duration sec
1315 523 1 alarm 1 OUT 2 lower threshold –
0 : no alarm
1 : I1
2 : I2
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : +ΣP
9 : +ΣQ
10 : ΣS
11 : F
12 : LPF
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time –
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : -ΣP
30 : -ΣQ
31 : CPF
1316 524 2 alarm 1 OUT 2 lower threshold value –
1318 526 1 alarm 1 OUT 2 upper threshold –
0 : no alarm
1 : I1
2 : I2
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : +ΣP
9 : +ΣQ
10 : ΣS
11 : F
12 : LPF
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time –
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
44 SOCOMEC - Ref. : 875 516 C
Decimal Hexa. N° of Text Unit
address address words
29 : -ΣP
30 : -ΣQ
31 : CPF
1319 527 2 alarm 1 OUT 2 upper threshold value –
1321 529 1 duration s.
1322 52A 1 alarm 2 OUT 2 lower threshold –
0 : no alarm
1: I1
2 : I2
3 : I3
4 : In
5 : U12

ENGLISH
6 : U23
7 : U31
8 : +ΣP
9 : +ΣQ
10 : ΣS
11 : F
12 : LPF
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : -ΣP
30 : -ΣQ
31 : CPF
1323 52B 2 alarm 2 OUT 2 lower threshold value –
1325 52D 1 alarm 2 OUT 2 upper threshold –
0 : no alarm
1: I1
2 : I2
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : +ΣP
9 : +ΣQ
10 : ΣS
11 : F
12 : LPF
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : -ΣP
30 : -ΣQ
31 : CPF
1326 52E 2 alarm 2 OUT 2 upper threshold value –
1328 530 1 duration s
SOCOMEC - Ref. : 875 516 C 45
Decimal Hexa. N° of Text Unit
address address words
1329 531 1 alarm 3 OUT 2 lower threshold –
0 : no alarm
1: I1
2 : I2
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : +ΣP
9 : +ΣQ
10 : ΣS
11 : F
12 : LPF
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : -ΣP
30 : -ΣQ
31 : CPF
1330 532 2 alarm 3 OUT 2 lower threshold value –
1332 534 1 alarm 3 OUT 2 upper threshold –
0 : no alarm
1: I1
2 : I2
3 : I3
4 : In
5 : U12
6 : U23
7 : U31
8 : +ΣP
9 : +ΣQ
10 : ΣS
11 : F
12 : LPF
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : time –
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : -ΣP
30 : -ΣQ
31 : CPF
1333 535 2 alarm 3 OUT 2 upper threshold value –
1335 537 1 duration sec
1336 538 1 status inputs 1 and 2 –
Size of this zone : 56 words (decimal) or 38 (hexadecimal)

46 SOCOMEC - Ref. : 875 516 C


Table of current and voltage harmonics
Decimal Hexa. N° of Text Unit
address address words
2304 900 1 thd I1 0.1 %
2305 901 1 thd I2 0.1 %
2306 902 1 thd I3 0.1 %
2307 903 1 thd In 0.1 %
2308 904 1 thd U12 0.1 %
2309 905 1 thd U23 0.1 %
2310 906 1 thd U31 0.1 %
2311 907 1 thd V1 0.1 %
2312 908 1 thd V2 0.1 %
2313 909 1 thd V3 0.1 %

ENGLISH
2314 90A 1 harmonic I1 row 3 0.1 %
2315 90B 1 harmonic I2 row 3 0.1 %
2316 90C 1 harmonic I3 row 3 0.1 %
2317 90D 1 harmonic IN row 3 0.1 %
2318 90E 1 harmonic I1 row 5 0.1 %
2319 90F 1 harmonic I2 row 5 0.1 %
2320 910 1 harmonic I3 row 5 0.1 %
2321 911 1 harmonic IN row 5 0.1 %
2322 912 1 harmonic I1 row 7 0.1 %
2323 913 1 harmonic I2 row 7 0.1 %
2324 914 1 harmonic I3 row 7 0.1 %
2325 915 1 harmonic IN row 7 0.1 %
2326 916 1 harmonic I1 row 9 0.1 %
2327 917 1 harmonic I2 row 9 0.1 %
2328 918 1 harmonic I3 row 9 0.1 %
2329 919 1 harmonic IN row 9 0.1 %
2330 91A 1 harmonic I1 row 11 0.1 %
2331 91B 1 harmonic I2 row 11 0.1 %
2332 91C 1 harmonic I3 row 11 0.1 %
2333 91D 1 harmonic IN row 11 0.1 %
2334 91E 1 harmonic I1 row 13 0.1 %
2335 91F 1 harmonic I2 row 13 0.1 %
2336 920 1 harmonic I3 row 13 0.1 %
2337 921 1 harmonic IN row 13 0.1 %
2338 922 1 harmonic I1 row 15 0.1 %
2339 923 1 harmonic I2 row 15 0.1 %
2340 924 1 harmonic I3 row 15 0.1 %
2341 925 1 harmonic IN row 15 0.1 %
2342 926 1 harmonic U12 row 3 0.1 %
2343 927 1 harmonic U23 row 3 0.1 %
2344 928 1 harmonic U31 row 3 0.1 %
2345 929 1 harmonic U12 row 5 0.1 %
2346 92A 1 harmonic U23 row 5 0.1 %
2347 92B 1 harmonic U31 row 5 0.1 %
2348 92C 1 harmonic U12 row 7 0.1 %
2349 92D 1 harmonic U23 row 7 0.1 %
2350 92E 1 harmonic U31 row 7 0.1 %
2351 92F 1 harmonic U12 row 9 0.1 %
2352 930 1 harmonic U23 row 9 0.1 %
2353 931 1 harmonic U31 row 9 0.1 %
2354 932 1 harmonic U12 row 11 0.1 %
2355 933 1 harmonic U23 row 11 0.1 %
2356 934 1 harmonic U31 row 11 0.1 %
2357 935 1 harmonic U12 row 13 0.1 %
2358 936 1 harmonic U23 row 13 0.1 %
2359 937 1 harmonic U31 row 13 0.1 %
2360 938 1 harmonic U12 row 15 0.1 %
2361 939 1 harmonic U23 row 15 0.1 %
2362 93A 1 harmonic U31 row 15 0.1 %
2363 93B 1 harmonic V1 row 3 0.1 %
2364 93C 1 harmonic V2 row 3 0.1 %
SOCOMEC - Ref. : 875 516 C 47
Decimal Hexa. N° of Text Unit
address address words
2365 93D 1 harmonic V3 row 3 0.1 %
2366 93E 1 harmonic V1 row 5 0.1 %
2367 93F 1 harmonic V2 row 5 0.1 %
2368 940 1 harmonic V3 row 5 0.1 %
2369 941 1 harmonic V1 row 7 0.1 %
2370 942 1 harmonic V2 row 7 0.1 %
2371 943 1 harmonic V3 row 7 0.1 %
2372 944 1 harmonic V1 row 9 0.1 %
2373 945 1 harmonic V2 row 9 0.1 %
2374 946 1 harmonic V3 row 9 0.1 %
2375 947 1 harmonic V1 row 11 0.1 %
2376 948 1 harmonic V2 row 11 0.1 %
2377 949 1 harmonic V3 row 11 0.1 %
2378 94A 1 harmonic V1 row 13 0.1 %
2379 94B 1 harmonic V2 row 13 0.1 %
2380 94C 1 harmonic V3 row 13 0.1 %
2381 94D 1 harmonic V1 row 15 0.1 %
2382 94E 1 harmonic V2 row 15 0.1 %
2383 95F 1 harmonic V3 row 15 0.1 %
2384 95F 1 minimum thd I 0,1%
2385 951 1 minimum thd In 0,1%
2385 952 1 minimum thd U 0,1%
2386 953 1 maximum thd I 0,1%
2387 954 1 maximum thd In 0,1%
2388 955 1 maximum thd U 0,1%
Size of this zone : 80 words (decimal) or 50 (hexadecimal)

NB: if several options are used, the Option recognition table


number corresponding to the option Decimal Hexa. N° of Text Unit
must be added. address address words
26 100 1 0 : no option –
1 : metering option
2 : communication option
4 : metering and harmonics option
8 : unused
10 : inputs 1/outputs option
20 : analog outputs 1 option
40 : unused
80 : analog outputs 2 option
100 : inputs 2/outputs option
200 : inputs 3/outputs option
400 : CT option on the neutral
27 101 1 Identification Slot 1 option –
0xFF: no option
0x0: communication option
0x1: metering option
0x20: inputs/outputs option
0x30: analog outputs option
0x40: metering and harmonics option
0x50: Profibus option
28 102 1 Identification Slot 2 option –
29 103 1 Identification Slot 3 option –
30 104 1 Identification Slot 4 option –
Size of this zone : 5 words (decimal) or 5 (hexadecimal)

48 SOCOMEC - Ref. : 875 516 C


LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16)
Decimal Hexa. N° of Text Unit
address address words
512 200 1 Network type: –
0 : 1BL
1 : 2BL
2 : 3BL
3 : 3NBL
4 : 4BL
5 : 4NBL
513 201 1 CT secondary: A
1: 1 A
5: 5 A

ENGLISH
514 202 1 CT primary A
515 203 1 Voltage input on PT: –
0 : No
1 : Yes
516 204 2 PT primary V
518 206 1 PT secondary: V
60 : 60 V
100 : 100 V
110 : 110 V
115: 115 V
120: 120 V
173 : 173 V
190 : 190 V
519 207 1 synchronisation of I AVG/MAX: –
5 : 5 minutes
8 : 8 minutes
10 : 10 minutes
15 : 15 minutes
20 : 20 minutes
30 : 30 minutes
60 : 60 minutes
520 208 1 synchronisation of P/Q/S AVG/MAX: –
5 : 5 minutes
8 : 8 minutes
10 : 10 minutes
15 : 15 minutes
20 : 20 minutes
30 : 30 minutes
60 : 60 minutes
521 209 1 OUT 1 allocation –
0 : kWh +
1 : kvarh +
2 : kVAh
3 : kWh –
4 : kvarh -
522 20A 1 OUT 1 impulse value: –
0 : 0.1 kWh/kvarh/kVAh
1 : 1 kWh/kvarh/kVAh
2 : 10 kWh/kvarh/kVAh
3 : 100 kWh/kvarh/kVAh
4 : 1000 kWh/kvarh/kVAh
5 : 10000 kWh/kvarh/kVAh
523 20B 1 OUT 1 impulse duration: –
1 : 100 ms
2 : 200 ms
3 : 300 ms
4 : 400 ms
5 : 500 ms
6 : 600 ms
7 : 700 ms
8 : 800 ms
9 : 900 ms
524 20C 1 OUT 2 allocation: –
0 : kWh +
1 : kvarh +

SOCOMEC - Ref. : 875 516 C 49


Decimal Hexa. N° of Text Unit
address address words
2 : kVAh
3 : kWh –
4 : kvarh -
525 20D 1 OUT 2 impulse value: –
0 : 0.1 kWh/kvarh/kVAh
1 : 1 kWh/kvarh/kVAh
2 : 10 kWh/kvarh/kVAh
3 : 100 kWh/kvarh/kVAh
4 : 1000 kWh/kvarh/kVAh
5 : 10000 kWh/kvarh/kVAh
526 20E 1 OUT 2 impulse duration: –
1 : 100 ms
2 : 200 ms
3 : 300 ms
4 : 400 ms
5 : 500 ms
6 : 600 ms
7 : 700 ms
8 : 800 ms
9 : 900 ms
527 20F 1 Analog output type OUT 1 –
0 : 0/20 mA
1 : 4/20 mA
2: 30 V
528 210 1 Output allocation
analog OUT 1 –
0 : I1
1 : I2
2 : I3
3 : In
4 : U12
5 : U23
6 : U31
7 : ΣP
8 : ΣQ
9 : ΣS
10 : ΣPF
11 : V1
12 : V2
13 : V3
14 : F
529 211 1 value at 0 or 4 mA from output
analog OUT 1 –
530 212 1 unit at 0 or 4 mA from output
analog OUT 1 –
0: /
1:k
2: M
531 213 1 value at 20 mA from output
analog OUT 1 –
532 214 1 unit at 20 mA from output
analogique OUT 1 –
0: /
1:k
2: M
533 215 1 analog output type OUT 2 –
0 : 0/20 mA
1 : 4/20 mA
534 216 1 allocation of analog output OUT 2 –
0 : I1
1 : I2
2 : I3
3 : In
4 : U12
5 : U23
6 : U31

50 SOCOMEC - Ref. : 875 516 C


Decimal Hexa. N° of Text Unit
address address words
7 : ΣP
8 : ΣQ
9 : ΣS
10 : ΣPF
11 : V1
12 : V2
13 : V3
14 : F
535 217 1 value at 0 or 4 mA from output
analog output OUT 2 –
536 218 1 unit at 0 or 4 mA from
analog output OUT 2 –

ENGLISH
0: /
1:k
2: M
537 219 1 value at 20 mA from
analog output OUT –
538 21A 1 unit at 20 mA from output
analog OUT 2 –
0: /
1:k
2: M
539 21B 1 type of analog output OUT 3 –
0 : 0/20 mA
1 : 4/20 mA
2: 30 V
540 21C 1 output allocation
analog OUT 3 –
0 : I1
1 : I2
2 : I3
3 : In
4 : U12
5 : U23
6 : U31
7 : ΣP
8 : ΣQ
9 : ΣS
10 : ΣPF
11 : V1
12 : V2
13 : V3
14 : F
541 21D 1 value at 0 or 4 mA from
analog output OUT 3 –
542 21E 1 unit at 0 or 4 mA from output
analog output OUT 3 –
0: /
1:k
2: M
543 21F 1 value at 20 mA from output
analog OUT 3 –
544 220 1 unit at 20 mA from output
analog OUT 3 –
0: /
1:k
2: M
545 221 1 type of analog output OUT 4 –
0 : 0/20 mA
1 : 4/20 mA
2: 30 V
546 222 1 output allocation
analog OUT 4 –
0 :I1
1 : I2
2 : I3
3 : In

SOCOMEC - Ref. : 875 516 C 51


Decimal Hexa. N° of Text Unit
address address words
4 : U12
5 : U23
6 : U31
7 : ΣP
8 : ΣQ
9 : ΣS
10 : ΣPF
11 : V1
12 : V2
13 : V3
14 : F
547 223 1 value at 0 or 4 mA from output
analog OUT 4 –
548 224 1 unit at 0 or 4 mA from output
analog OUT 4 –
0: /
1:k
2: M
549 225 1 value at 20 mA from output
analog OUT 4 –
550 226 1 unit at 20 mA from output
analog OUT 4 –
0: /
1:k
2: M
551 227 1 allocation OUT 1 –
0 : command
1: I
2: U
3 : ΣP
4 : ΣQ
5 : ΣS
6: F
7 : ΣFP
8 : thd 3I
9 : thd 3U
10 : IN
11 : time
12 : V
13 : thd In
14 : thd 3V
15 : -ΣP
16: -ΣQ
17: CFP
552 228 1 lower threshold OUT 1 –
553 229 1 lower threshold unit OUT 1 –
0: /
1:k
2: M
554 22A 1 upper threshold OUT 1 –
555 22B 1 upper threshold unit OUT 1 –
0: /
1:k
2: M
556 22C 1 hysteresis 0 to 99 OUT 1 %
557 22D 1 specified time OUT 1 sec
558 22E 1 relay status OUT 1 –
0 : Open
1 : Closed
559 22F 1 allocation OUT 2 –
0 : Command
1: I
2: U
3 : +ΣP
4 : +ΣQ
5 : ΣS
6: F

52 SOCOMEC - Ref. : 875 516 C


Decimal Hexa. N° of Text Unit
address address words
7 : LPF
8 : thd 3I
9 : thd 3U
10 : IN
11 : time
12 : V
13 : thd In
14 : thd 3V
15 : -ΣP
16: -ΣQ
17: CFP
560 230 1 lower threshold OUT 2 –

ENGLISH
561 231 1 lower threshold unit OUT 2 –
0: /
1:k
2: M
562 232 1 upper threshold OUT 2 –
563 233 1 upper threshold unit OUT 2 –
0: /
1:k
2: M
564 234 1 hysteresis 0 to 99 OUT 2 %
565 235 1 time delay OUT 2 sec
566 236 1 relay status OUT 2 –
0 : Open
1 : Closed
567 237 1 relay status 3 :
0 : Open
1 : Closed –
568 238 1 relay status 4 :
0 : Open
1 : Closed –
569 239 1 relay status 5 :
0 : Open
1 : Closed –
570 23A 1 relay status 6 :
0 : Open
1 : Closed –
571 23B 1 Secondary of neutral CT :
1:1A
5:5A A
572 23C 1 Primary of neutral CT A
Size of this zone: 61 words or 3D hexadecimals

Example:
Configuration of a 4-wired unbalanced
network (4 LNB) for Diris number 5.

High-order Low-order High-order Low-order


Slave Function CRC 16
address address word N° word N°
05 06 02 00 00 05 49F5

Diris Ap reply: Identical to message


sent

SOCOMEC - Ref. : 875 516 C 53


RESET TO ZERO: ENERGY METERS AND MAX. VALUES (FUNCTION 6)

NB: Decimal Hexad. N° of Text Unit


To reset several parameters to zero, address address words Hex
add the corresponding figure indicat- 1024 400 1 Reset to zero for: /
ed in the “text” column.
Max3I: 1
Example: reset Max P+ and kvarh + to
zero: 2 + 100 = 102 (Hex) MaxP+: 2
MaxP-: 4
MaxQ+: 8
MaxQ-: 10
MaxS: 20
Hour meter: 40
kWh+: 80
kvarh+: 100
kVA: 200
kWh-: 400
kvarh-: 800
all parameters: 1000
1025 401 1 R.A.Z. de : /
E1 : 0x1
E2 : 0x2
E3 : 0x4
E4 : 0x8
E5 : 0x10
E6 : 0x20
Min/Max I : 0x40
Min/Max In : 0x80
Min/Max U : 0x100
Min/Max F : 0x200
Min/Max PF : 0x400
Min/Max P : 0x800
Min/Max Q : 0x1000
Min/Max thd I : 0x2000
Min/Max thd In : 0x4000
Min/Max thd U : 0x8000
Zone size: 2 words or 2 hexadecimals

Example:
To reset all values for DIRIS number 5
to zero, the following frame should be
sent:

High-order Low-order High-order Low-order


Slave Function CRC 16
address address word N° word N°
05 06 04 00 10 00 84BE

Diris Ap reply: identical to the mes-


sage sent.

54 SOCOMEC - Ref. : 875 516 C


SAVED COMMAND (RESET)

The following command should be


done to save programming parame-
ters changes for DIRIS number 5.

NB: High-order Low-order


Diris Ap will not Slave Function Values CRC 16
address address
reply to this com-
mand. 05 06 06 00 0000 88C6

ENGLISH
TECHNICAL CARACTERITICS
COMMUNICATION

RS485 2 or 3 wires half duplex


Protocol JBUS/MODBUS® protocol / RTU mode
Speed 2400 to 38400 Bauds
Galvanic insulation 2.5 kV

SOCOMEC - Ref. : 875 516 C 55


Réf. : 875 516 C - 06/02

SIEGE SOCIAL DIRECTION COMMERCIALE


HEAD OFFICE SALES MANAGEMENT DIVISION Systèmes de Coupure et de Protection
Industrial Switching and Protection Systems
GROUPE SOCOMEC
Interrupteurs industriels et Onduleurs
SOCOMEC S.A.
au capital de 11 407 400 €
Ce document n’est pas contractuel. La société SOCOMEC
R.C. Strasbourg 5484500 149 B SOCOMEC se réserve le droit de modifier sans préavis les caractéris-
BP 10 - Rue de Westhouse 95, rue Pierre Grange tiques dans un souci permanent d’amélioration.
This document is not contractual. SOCOMEC reserves the
F-67235 Benfeld cedex F-94132 Fontenay-sous-Bois Cedex right to modify features without prior notice in view of
Tél. (33) 3 88 57 41 41 - Fax (33) 3 88 57 42 60 Tél. (33) 1 45 14 63 40 - Fax (33) 1 48 77 31 12 continued improvements.