Hasil Pengujian Differential Relay Transformer F87T: Transformator Bay Test Report

The document summarizes the results of testing a differential relay on a transformer bay. Key findings include: 1. The minimum operating current test found the relay operated as expected down to 1.15A on both the high voltage and low voltage sides. 2. Harmonic blocking was tested at the second and fifth harmonics, and the relay correctly blocked both as expected. 3. Slope testing found the relay operated as programmed at 30% for slope 1 and 80% for slope 2.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views

Hasil Pengujian Differential Relay Transformer F87T: Transformator Bay Test Report

The document summarizes the results of testing a differential relay on a transformer bay. Key findings include: 1. The minimum operating current test found the relay operated as expected down to 1.15A on both the high voltage and low voltage sides. 2. Harmonic blocking was tested at the second and fifth harmonics, and the relay correctly blocked both as expected. 3. Slope testing found the relay operated as programmed at 30% for slope 1 and 80% for slope 2.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 9

PT.

PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

HASIL PENGUJIAN DIFFERENTIAL RELAY TRANSFORMER F87T


Lokasi : GI Tangerang Lama Ratio CT sisi Primer : 300 / 5A
Bay : Trafo-05 Ratio CT sisi Sekunder : 2000 / 5A
Ratio sisi Terseier : -
Project :
Merk / Type : Schneider P642 No. Seri : 39672180/09/18 Rating In : 5A

No.
1 Pengujian arus kerja minimum
Setting I op : 0.3 pu Hasil Uji IR : HV side 1.15 A & LV side 1.5 A
IS : HV side 1.15 A & LV side 1.5 A
IT : HV side 1.15 A & LV side 1.5 A

2 Pengujian Harmonic Blocking


Setting 2nd harmonic blockir : 15% Hasil Uji 2nd harmonic : Block
5th harmonic blockir : 30% 5th harmonic : Block

3 Pengujian slope differential


Setting Slope 1 : 30% Hasil Uji Slope 1 : 0.3012
Slope 2 : 80% Slope 2 : 0.8

Fasa Pengukuran Stn


I1 HV A 1.892
I2 LV A 1
Idiff Pu
Ibias Pu

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujian : 23 November 2018


METER REFERENCE : CT Ratio 300 / 5 A
VT Ratio 150000 / 100 V
MEASURE AT : METER CONTROL PANEL SISI HV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(MVar) (MVar)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=270ᵒ

0% MVAR (NEG) 0 0 0 OK
25% -19.485 -19.4 -0.44 OK
50% -38.97 -38.84 -0.33 OK
75% -58.455 -58.28 -0.30 OK
100% -77.94 -77.69 -0.32 OK

MEASURE AT : METER CONTROL PANEL SISI HV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(MW) (MW)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=180ᵒ

0% MW (NEG) 0 0 0 OK
25% -19.485 -19.4 -0.44 OK
50% -38.97 -38.82 -0.38 OK
75% -58.455 -58.25 -0.35 OK
100% -77.94 -77.64 -0.38 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujain : 23 November 2018


METER REFERENCE : CT Ratio 300 / 5 A
VT Ratio 150000 / 100 V
MEASURE AT : METER CONTROL PANEL SISI HV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(MVar) (MVar)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=90ᵒ

0% MVAR (POS) 0 0 0 OK
25% 19.485 19.41 -0.38 OK
50% 38.97 38.85 -0.31 OK
75% 58.455 58.3 -0.27 OK
100% 77.94 77.71 -0.30 OK

MEASURE AT : METER CONTROL PANEL SISI HV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(MW) (MW)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=0ᵒ

0% MW (POS) 0 0 0 OK
25% 19.485 19.43 -0.28 OK
50% 38.97 38.89 -0.21 OK
75% 58.455 58.35 -0.18 OK
100% 77.94 77.78 -0.21 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujian : 22 November 2018


METER REFERENCE : CT Ratio 2000 / 5 A
VT Ratio 20000 / 100 V
MEASURE AT : METER CONTROL PANEL SISI LV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(MVar) (MVar)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=270ᵒ

0% MVAR (NEG) 0 0 0 OK
25% -17.32 -17.29 -0.17 OK
50% -34.64 -34.53 -0.32 OK
75% -51.96 -51.81 -0.29 OK
100% -69.28 -69.08 -0.29 OK

MEASURE AT : METER CONTROL PANEL SISI LV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(MW) (MW)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=180ᵒ

0% MW (NEG) 0 0 0 OK
25% -17.32 -17.24 -0.46 OK
50% -34.64 -34.5 -0.40 OK
75% -51.96 -51.96 0.00 OK
100% -69.28 -69.28 0.00 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujian : 22 November 2018


METER REFERENCE : CT Ratio 2000 / 5 A
VT Ratio 20000 / 100 V
MEASURE AT : METER CONTROL PANEL SISI LV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(MVar) (MVar)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=90ᵒ

0% MVAR (POS) 0 0 0 OK
25% 17.32 17.26 -0.35 OK
50% 34.64 34.55 -0.26 OK
75% 51.96 51.84 -0.23 OK
100% 69.28 69.13 -0.22 OK

MEASURE AT : METER CONTROL PANEL SISI LV

VALUE RESULT
INJECTION MEASUREMENT
CALCULATE DISPLAY
ERROR (%) OK/NOK
(W) (W)

I = 0 - 5 A Ø=0ᵒ
V = 57.74 V Ø=0ᵒ

0% MW (POS) 0 0 0 OK
25% 17.32 17.29 -0.17 OK
50% 34.64 34.59 -0.14 OK
75% 51.96 51.9 -0.12 OK
100% 69.28 69.2 -0.12 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujian : 21 November 2018


METER REFERENCE : VT Ratio 20000 / 100 V
MEASURE AT : VOLT METER CONTROL PANEL

VALUE RESULT
INJECTION PHASE
CALCULATE DISPLAY
ERROR (%) OK/NOK
(kV) (kV)
I = 0 - 57.74 V
0% 0 0 0 0 OK
25% 14,43 V 2.75 2.89 5.09 OK
V R-N
50% 28,87 V 5.5 5.78 5.09 OK
75% 43,31 V 8.25 8.64 4.73 OK
100% 57,74 V 11 11.52 4.73 OK
I = 0 - 57.74 V
0% 0 0 0 0 OK
25% 14,43 V 2.75 2.88 4.73 OK
V S-N
50% 28,87 V 5.5 5.76 4.73 OK
75% 43,31 V 8.25 8.63 4.61 OK
100% 57,74 V 11 11.52 4.73 OK
I = 0 - 57.74 V
0% 0 0 0 0 OK
25% 14,43 V 2.75 2.89 5.09 OK
V T-N
50% 28,87 V 5.5 5.78 5.09 OK
75% 43,31 V 8.25 8.65 4.85 OK
100% 57,74 V 11 11.53 4.82 OK
I = 0 - 100 V
0% 0 0 0 0 OK
25% 25 V 5 5 0.00 OK
V R-S
50% 50 V 10 9.99 -0.10 OK
75% 75 V 15 14.99 -0.07 OK
100% 100 V 20 20 0.00 OK
I = 0 - 100 V
0% 0 0 0 0 OK
25% 25 V 5 5.02 0.40 OK
V R-T
50% 50 V 10 10.01 0.10 OK
75% 75 V 15 14.94 -0.40 OK
100% 100 V 20 19.9 -0.50 OK
I = 0 - 100 V
0% 0 0 0 0 OK
25% 25 V 5 5.2 4.00 OK
V S-T
50% 50 V 10 9.93 -0.70 OK
75% 75 V 15 14.97 -0.20 OK
100% 100 V 20 20 0.00 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujian : 21 November 2018


METER REFERENCE : VT Ration 150000 / 100 V
MEASURE AT : VOLT METER CONTROL PANEL

VALUE RESULT
INJECTION PHASE
CALCULATE DISPLAY
ERROR (%) OK/NOK
(kV) (kV)
I = 0 - 57.74 V
0% 0 0 0 0 OK
25% 14,43 V 21.67 21.63 -0.18 OK
V R-N
50% 28,87 V 43.35 43.3 -0.12 OK
75% 43,31 V 65.03 64.93 -0.15 OK
100% 57,74 V 86.7 86.47 -0.27 OK
I = 0 - 57.74 V
0% 0 0 0 0 OK
25% 14,43 V 21.67 21.671 0.00 OK
V S-N
50% 28,87 V 43.35 43.351 0.00 OK
75% 43,31 V 65.03 64.93 -0.15 OK
100% 57,74 V 86.7 86.478 -0.26 OK
I = 0 - 57.74 V
0% 0 0 0 0 OK
25% 14,43 V 21.67 132.1 0.01 OK
V T-N
50% 28,87 V 43.35 264.1 0 OK
75% 43,31 V 65.03 400 0.1 OK
100% 57,74 V 86.7 480.2 -0.05 OK
I = 0 - 100 V
0% 0 0 0 0 OK
25% 25 V 37.5 37.471 -0.08 OK
V R-S
50% 50 V 75 75.012 0.02 OK
75% 75 V 112.5 112.48 -0.02 OK
100% 100 V 150 150 0.00 OK
I = 0 - 100 V
0% 0 0 0 0 OK
25% 25 V 37.5 37.51 0.03 OK
V R-T
50% 50 V 75 74.944 -0.07 OK
75% 75 V 112.5 112.512 0.01 OK
100% 100 V 150 150.1 0.07 OK
I = 0 - 100 V
0% 0 0 0 0 OK
25% 25 V 37.5 37.511 0.03 OK
V S-T
50% 50 V 75 75.058 0.08 OK
75% 75 V 112.5 112.519 0.02 OK
100% 100 V 150 150 0.00 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujian : 19 November 2018


METER REFERENCE : CT Ratio 300 / 5A
MEASURE AT : AMPERE METER CONTROL PANEL

VALUE RESULT
INJECTION PHASE
CALCULATE DISPLAY
ERROR (%) OK/NOK
(A) (A)
I = 0 - 1.2 A
0% 0 0 0 0 OK
25% 0.33 19.8 19.78 -0.10 OK
I-R
50% 0.66 39.6 39.59 -0.03 OK
75% 1 60 59.99 -0.02 OK
100% 1.2 72 72.08 0.11 OK
I = 0 - 1.2 A
0% 0 0 0 0 OK
25% 0.33 19.8 131.6 -0.0505051 OK
I-S
50% 0.66 39.6 264.1 -0.05 OK
75% 1 60 400.1 0.08 OK
100% 1.2 72 480.4 -0.08 OK
I = 0 - 1.2 A
0% 0 0 0 0 OK
25% 0.33 19.8 132.1 -0.05 OK
I-T
50% 0.66 39.6 264.1 -0.03 OK
75% 1 60 400 0.05 OK
100% 1.2 72 480.2 0 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :
PT. PLN (Persero)
TRANSFORMATOR BAY TEST REPORT UPT DURIKOSAMBI

SUBSTATION NAME : GI TANGERANG LAMA Tanggal Pengujian : 19 November 2018


METER REFERENCE : CT Ratio 2000 / 5A
MEASURE AT : AMPERE METER CONTROL PANEL

VALUE RESULT
INJECTION PHASE
CALCULATE DISPLAY
ERROR (%) OK/NOK
(A) (A)
I = 0 - 1.2 A
0% 0 0 0 0 OK
25% 0.33 132 131.7 -0.23 OK
I-R
50% 0.66 264 264.2 0.08 OK
75% 1 400 400.6 0.15 OK
100% 1.2 480 480.1 0.02 OK
I = 0 - 1.2 A
0% 0 0 0 0 OK
25% 0.33 132 131.6 -0.30 OK
I-S
50% 0.66 264 264.1 0.04 OK
75% 1 400 400.1 0.03 OK
100% 1.2 480 480.4 0.08 OK
I = 0 - 1.2 A
0% 0 0 0 0 OK
25% 0.33 132 132.1 0.08 OK
I-T
50% 0.66 264 264.1 0.04 OK
75% 1 400 400 0.00 OK
100% 1.2 480 480.2 0.04 OK

Diuji oleh : Disupervisi oleh : Dievaluasi oleh :

PT. GLOBAL TWIN STAR PT. PLN (Persero) SPV GI Tangerang Lama PUSERTIF
Nama : Alfiyansyah Nama : Nama :