Micom: Pics and Mics
Micom: Pics and Mics
P44x/EN PM/A11
Note: The technical manual for this device gives instructions for its installation, commissioning, and operation.
However, the manual cannot cover all conceivable circumstances or include detailed information on all
topics. In the event of questions or specific problems, do not take any action without proper authorization.
Contact the appropriate AREVA technical sales office and request the necessary information.
Any agreements, commitments, and legal relationships and any obligations on the part of AREVA including
settlements of warranties, result solely from the applicable purchase contract, which is not affected by the
contents of the technical manual.
This device MUST NOT be modified. If any modification is made without the express permission of
AREVA, it will invalidate the warranty, and may render the product unsafe.
The AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.
MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered or not,
are the property of their owners.
This manual is provided for informational use only and is subject to change without notice.
CONTENTS
1.1 Introduction
This specification is the Protocol Implementation Conformance Statement (PICS) and
presents the ACSI conformance statements as defined in Annex A of Part 7-2 of the
IEC61850 standard specifications.
1.2 ACSI basic conformance statement
The basic conformance statement shall be as defined in Table A.1.
Table A.1 - Basic conformance statement
Client-Server Roles
SCSMs Supported
M1 Logical device c2 Y c2 Y
M2 Logical node c3 Y c3 Y
M3 Data c4 Y c4 Y
M4 Data set c5 Y c5 Y
M5 Substitution O N O N
M6 Setting group control O N O N
Reporting
M7 Buffered report control O N O N
M7-1 sequence-number
M7-2 report-time-stamp
M7-3 reason-for-inclusion
M7-4 data-set-name
M7-5 data-reference
M7-6 buffer-overflow
M7-7 entryID
M7-8 BufTim
M7-9 IntgPd
M7-10 GI
M8 Unbuffered report control O N O Y
M8-1 sequence-number N Y
M8-2 report-time-stamp N Y
M8-3 reason-for-inclusion N Y
M8-4 data-set-name N Y
M8-5 data-reference N Y
M8-6 BufTim N Y
M8-7 IntgPd N Y
M8-8 GI N Y
Logging O N O N
M9 Log control O N O N
M9-1 IntgPd N N
M10 Log O N O N
M11 Control M N M N
GOOSE O N O Y
M12-1 entryID ?
M12-2 dataRefInc ?
PICS & MICS P44x/EN PM/A11
Time (5.5)
T1 Time resolution of internal clock 1ms Nearest
negative power
of 2 in seconds
T2 Time accuracy of internal clock 1ms T0
T1
T2
T3
T4
T5
T3 Supported TimeStamp resolution 1ms Nearest value
of 2**-n in
seconds
according to
5.5.3.7.3.3
PICS & MICS P44x/EN PM/A11
2.1 Introduction
This specification is the Model Implementation Conformance Statement (MICS) and presents
the top-level IEC61850 data model that has been implemented. The definitions of all used
Logical Nodes and their associated Common Data Classes, components and associated
enumerated values are also included for completeness.
The reader is expected to be conversant with the terminology presented within the IEC61850
part 7 series of specifications.
2.2 Objective
To provide comprehensive details of the standard data object model elements supported by
the device. The MICS is conformant to the devices associated ICD (Substation Configuration
Language) file, according to part 6 of the IEC61850 standards. The layout of the presented
tables within this document are conformant to the part 7 series of the IEC61850 standard
specifications with the following exceptions:
• The "M/O" field is not present as the definitions are as deployed within the model.
Control
Swing Blocking
Measurements
Protection
Records
System
Description: Metering Statistics (w.r.t Real + Reactive Power - Average + Max values)
LN Class: MSTA
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN_PRIV Name Plate
AvW MV_FLOAT_D Average real power
MaxW MV_FLOAT_D Maximum real power
AvVAr MV_FLOAT_D Average reactive power
MaxVAr MV_FLOAT_D Maximum reactive power
Description: Synchronism-check / Synchronising (w.r.t Calculated for Manual and automatic close)
LN Class: RSYN
Attribute Attr. Type Explanation T X
Mod INC_MOD Mode
Beh INS_BEH Behaviour
Health INS_HEALTH Health
NamPlt LPL_LN Name Plate
Rel SPS_WD Release
DifHzClc MV_FLOAT Calculated difference in frequency
Description: Complex Measured value (w.r.t Floating Point Magnitude and Angle)
CDC Class: CMV
Attribute Type FC Enumeration Comment X
Deadbanded complex
measured vector. Updated
to the current value of
Vector_Magnitude
cVal MX instCVal when the value
Angle_ Float
has changed according to
the configuration
parameter db
Quality of the
q Quality MX
measurement value
Time deadbanded
magnitude last exceeded
t TimeStamp MX
its db configuration
parameter
Unit of the attribute
units Unit_No_Multiplier CF
representing the data
db INT32U CF Measurement deadband
Description: Phase to phase measurements for a 3-Phase system (w.r.t Phase Seggregation
Angle)
CDC Class: DEL
Attribute Type FC Enumeration Comment X
Measurement values for
phsAB CMV_MAG_ANG_FLOAT --
Phase A to Phase B
Measurement values for
phsBC CMV_MAG_ANG_FLOAT --
Phase B to Phase C
Measurement values for
phsCA CMV_MAG_ANG_FLOAT --
Phase C to Phase A
P44x/EN PM/A11 PICS & MICS
Description: Phase to ground measurements for a 3-Phase system (w.r.t Phase Seggregation)
CDC Class: WYE
Attribute Type FC Enumeration Comment X
Measurement values for
phsA CMV_MAG_FLOAT --
Phase A
Measurement values for
phsB CMV_MAG_FLOAT --
Phase B
PICS & MICS P44x/EN PM/A11
Comment: Complex vector (w.r.t Floating Point Magnitude and Angle values)
Parent Type: Vector
Attribute Type Enumeration Comment X
mag AnalogueValue_Float The magnitude of the
complex value
ang AnalogueValue_Float The angle of the
complex value (the
unit is degrees)
PICS & MICS P44x/EN PM/A11
Ordinal Semantic
1 Ready
2 In Progress
3 Successful
Description: Behaviour/Mode
Ordinal Semantic
1 On
2 Blocked
3 Test
4 Test / Blocked
5 Off
Description: Health
Ordinal Semantic
1 OK
2 Warning
3 Alarm
P44x/EN PM/A11 PICS & MICS
Description: CB position
Ordinal Semantic
0 Intermediate
1 Off
2 On
3 Bad-state
Ordinal Semantic
52 ppm
53 s¯¹
54 rads¯¹
61 VA
62 W
63 VAr
64 theta
65 cos(theta)
66 Vs
67 V²
68 As
69 A²
70 A²t
71 VAh
72 Wh
73 VArh
74 V/Hz
P44x/EN PM/A11 PICS & MICS