NETSURE™ 7100 & NETSURE™ 8100

Technical Specifications
AC INPUT NETSURE™ 7100 NETSURE™ 8100

Range Single phase: 85 VAC to 300 VAC 3 phase: 260 VAC to 530 VAC OVERVIEW
(Nominal: 200 VAC to 240 VAC) (Nominal: 346 VAC to 415 VAC)
Line Frequency 50 or 60 Hz (45 Hz to 65 Hz)
Connections Terminal or distribution for up to 12 circuit breakers
Surge Protection Optional 1 2 1 2

DC OUTPUT
Adjustable Range -42 VDC to -58 VDC (Nominal: -48 VDC)
42 kW (12 x 3,5 kW 46,4 kW (8 x 5,8 kW 3 4 3 4
Power, Maximum rectifier modules per cabinet) rectifier modules per cabinet)
Total system power up to 2,8 MW
Efficiency, Peak 96,5% eSure™ R48-3500 rectifier 96,2% eSure™ R48-5800 rectifier
5 5
DC SYSTEM UNITS
Distribution Units Available for circuit breakers, cartridge fuses, NH00 fuses, NH2 fuses
Circuit Breakers From 2 A up to 200 A
Fuses NH00-80V (up to 600 A) and NH2 (up to 400 A) 6 6
Intelligent Load Management Optional, equipment for all distribution units
Up to 5 x 300 A or 4 x 400 A circuit breakers,
Battery Connections 7 7
Up to 4 x (500 A to 630 A) fuses

PHYSICAL CHARACTERISTICS
Mounting Top and bottom cabling
Dimensions (H x W x D) 1800 or 2020 mm x 600 mm x 600 mm (per cabinet)
Weight 155 kg per cabinet (fully equipped) NetSure 8100
Access and Security Front access, IP20, door with lock as option on front and back Multi Cabinet System

ENVIRONMENTAL 1 Battery Connection Unit


Temperature Range, Operating -5 °C to +60 °C (full power up to 40 °C) 2 Cabinet Interconnection
Relative Humidity, Operating <90%
Altitude 2000 m
3 Customer Connections
Audible Noise 59dB for R48-3500e 60dB for R48-5800e 4 Control Unit
Ventilation Forced ventilated (rectifier fans) 5 Load Distribution Units

SAFETY AND STANDARDS COMPLIANCE


6 AC Distribution Unit
Electrical CE EN60950-1 7 eSure 5800 W Rectifiers
EMC EN 300 386-2, Class B
Environmental REACH, RoHS 6

Ordering Information
MODEL PART
NUMBER NUMBER DESCRIPTION
Multi cabinet NetSure 7100 DC power system or
— BMK220A01 Multi cabinet NetSure 8100 DC power system
1R485800E BML403123/1 5,8 kW eSure rectifier, high efficiency
1R483500E2 BML440066/1 3,5 kW eSure rectifier, high efficiency
M830D BMP903100/2 NetSure Control Unit

VertivCo.com | Vertiv Infrastructure Limited, George Curl Way, Southampton, SO18 2RY, VAT Number: GB188146827
© 2016 Vertiv Co. All rights reserved. Vertiv™, the Vertiv logo, NetSure™ Advanced Remote Distribution Cabinet and NetSure Control Unit (NCU) are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names,
trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this
information or for any errors or omissions. Specifications are subject to change without notice.

EN329DRD-NS7100M / Apr 2017

You might also like