Current chopping
• It is the phenomenon of current interruption before the natural current
zero is reached.
• Current chopping mainly occurs in air-blast circuit breakers because
they try extinguishing high power irrespective of the magnitude of the
current to be interrupted.
• When breaking low currents (e.g., transformer magnetising current)
with such breakers, the powerful de-ionizing effect of air-blast causes
the current to fall abruptly to zero well before the natural current zero
is reached.
Current chopping
Circuit Breaker Ratings
• Under fault conditions, a circuit breaker is required to perform the
following three duties :I
a. It must be capable of opening the faulty circuit.
b. It must be capable of breaking the fault current.
c. It must be capable of carrying fault current for a short time while another circuit
breaker (in series) is clearing the fault.
• Corresponding to the above mentioned duties, the circuit
breakers have three ratings viz.
(i) breaking capacity (ii) making capacity and (iii) short-time capacity
(i) Breaking capacity. It is current (r.m.s.) that a circuit breaker is capable of
breaking at given recovery voltage and under specified conditions (e.g., power
factor, rate of rise of restriking voltage).
(ii) Making capacity: There is always a possibility of closing or making the circuit
under short circuit conditions. The capacity of a breaker to “make” current
depends upon its ability to withstand and close successfully against the effects of
electromagnetic forces. These forces are proportional to the square of maximum
instantaneous current on closing.