GE Infinity S CPB NES
GE Infinity S CPB NES
Applications
• Telecommunications Networks • Routers/Switches • Data Networks
• Digital Subscriber Line (DSL) • Fiber in the Loop • Distributed Antenna Systems
• Indoor/Outdoor Wireless • Transmission • Off-Grid/On-Grid Renewable
Energy Sites
Key Features
Specifications
INPUT NE100AC24ATEZ NE050AC48ATEZ NE075AC48ATEZ NE030DC48A NE040DC48A NE075DC24A
NE100ECO24ATEZ NE050ECO48ATEZ
Voltage Range 95-305Vac 95-305Vac 95-305Vac 21-30Vdc 21-30Vdc 42-60Vdc
Input Current 15-12A @ 100-120Vac 15-12A @ 100-120Vac 15-12A @ 100-120Vac 63A @ 27Vdc 94A @ 27Vdc 41A @ 54.5Vdc
15-12A @ 200-277Vac 15-12A @ 200-277Vac 22-15.5A @ 200-277Vac 81A @ 21Vdc 108A @ 21Vdc 54A @ 42Vdc
Input 45 – 66Hz 45 – 66Hz 45 - 66Hz - - -
Frequency
Power Factor 0.98 at>50% load 0.98 at>50% load 0.98 at>50% load - - -
Efficiency > 95% (Peak 95.6%) > 96% (Peak 96.9%) > 96% (Peak 96.9%) - - -
Total Harmonic <5% @loads over 50% <5% @loads over 50% <5% @loads over 50% - - -
Distortion
Heat Dissipation 174W / 594 BTU/hr 158W / 539 BTU/hr 249W / 850 BTU/hr 154W / 525 205W / 700 202W / 689
@ max out 1 BTU /hr BTU/ hr BTU/hr
1
Special room cooling may be required.
ENVIRONMENTAL
Operating Temperature -40°C to +75°C (-40°F to 167°F) Full capacity up to 55°C; output derates 2%/°C from 55°C to 75°C
Storage Temperature -40°C to +85°C (-40°F to 185°F)
Humidity < 95% non-condensing
Altitude 4000M (for altitudes above 2000M, peak operating temperature de-rates 0.656º C /100M;
4000M peak temperature rating is 62ºC
MECHANICAL
Length (inch/mm) 13.85 / 351.8
Width (inch/mm) 5.23 / 133
Height (inch/mm) 1.63 / 42
Weight (lb/Kg) 5.05 / 2.2
RoHS Compliant to RoHS EU Directive 2002/95/EC; RoHS 6/6 models with Z suffix (RoHS 5/6 all other models)
EMC European Directive 2014/30/EU; EN55032, Class A; EN55035; FCC, Class A; GR1089-CORE
ESD EN61000-4-2, Level 4
OUTLINE DRAWING
This controller utilizes standard network management protocols allowing for advanced network supervision. The GE Galaxy Manager*
software is the centralized visibility and control component of a comprehensive power management system designed to meet
engineering, operations and maintenance needs. The Galaxy Manager client-server architecture enables remote access to system
controllers across the power network, featuring ECO Priority advanced monitoring features which provides detailed energy source
analysis to help better customize your renewable energy resources.
Applications
• Telecommunications Networks • Fiber in the Loop • Data Networks
• Digital Subscriber Line (DSL) • Transmission • PBX
• Indoor/Outdoor Wireless • Off-Grid/On-Grid Renewable
• Routers/Switches Energy Sites
Key Features
Remote Access and Features • ECO Priority controls and features • Multiple Low Voltage Load and Low
• Integrated 10/100Base-T - Advanced generator controls to Voltage Battery Disconnect thresholds
Ethernet Network help minimize fuel consumption • Configuration, statistics, and history
- TCP/IP with IPV6 Capability for off grid applications - All stored in non-volatile memory
- SNMP V3 for management - ECO Energy Management allowing - Remote/local backup and restore
- SMTP for email for non-ECO sources outputs to be of configuration data
- Telnet for command line interface minimized while ECO resources
are available • Industry standard defaults
- DHCP for plug-n-play - Customer specific
- FTPS for rapid backup and upgrades - Source and load trend logging
configurations available
- HTTPS for standard web pages Standard System Features
and browsers • Remote/local software upgrade
• Monitor and control of more than 40
- Compatible with Galaxy Manager connected devices • Basic, busy hour, and trend statistics
and other management packages - Robust RS485 system bus • Detailed event history
- Shielded RJ-45 interface
referenced to chassis ground • Standard and user defined alarms • User defined events and
- Alarm test derived channels
• Password protected security levels: - Assignable alarm severity:
User, Super-User, Administrator Standard Battery Management Features
Critical, Major, Minor, Warning,
for all access and record-only • Float/boost mode control
• Ground-referenced RS232 system port - 10 alarm relays (7 user assigned) - Manual boost
- Manual timed boost locally, T1.317,
• ANSI T1.317 command-line interface • Rectifier management features
and remotely initiated
• Modem access support - Automatic rectifier restart
- Auto boost terminated by time
- Remote via external modem - Active Rectifier Management
or current
- Callback security ARM (energy efficiency)
- Remote rectifier (on/off) • Battery discharge testing
• EasyView2, Windows-based GUI - Reserve Operation - Manual (local/remote)
software for local terminal or - Automatic rectifier sequence control - Periodic
Modem access - N + X redundancy check - Plant Battery Test (PBT)
input driven
Specifications
GENERAL
Operating Voltage ±24 Vdc, ±48 Vdc
(Range: ±18 to ±60 Vdc)
Input Power Less than 7W
Operating Temperature Range -40°C to +75°C (-40°F to 167°F)
No Alarms Menu 1
Operating Relative Humidity 0 - 95% (non-condensing)
Storage Temperature Range -40°C to +85°C (-40°F to 185°F) No Alarms Menu 1
AGENCY CERTIFICATIONS
NEBs Level 3 Evaluated by independent NRTL test lab to Telcordia GR63, Issue 3 and GR1089-CORE, Issue 6
EMC European Directive 2014/30/EU; EN55032, (CISPR22) Class A, EN55035 (CISPR24)
Safety Underwriters Laboratories (UL) Listed per Subject Letter 1801: Power Distribution Center for (CSA 22.2 950):
Safety of Information Technology Equipment
The controller is utilized in bulk power applications in data centers and enterprise
applications. Ethernet connectivity with SNMP V3 facilitates secure remote network
management. Access through its front-accessible RS232 or USB port and aided by the EasyView2 graphical enables full user
interface locally. Optional 1U display version allows convenient access to all controller functions without requiring external cable
connections. The display also features alarm context sensitive backlighting for at-a-glance system status.
As a battery plant controller, it provides a complete set of features to monitor and control rectifiers, batteries, and distribution. A
flexible set of configurable inputs allow the Pulsar Edge controller to monitor a wide variety of system equipment and incorporate
appropriate state information enabling a centralized point of management . The controller utilizes standard network management
protocols allowing for advanced network supervision. GE Galaxy Manager* software is the centralized visibility and control
component of a comprehensive power management system designed to meet engineering, operations and maintenance needs.
The Galaxy Manager client-server architecture enables remote access to system controllers across the power network.
Applications
• Telecommunications Networks • Routers/Switches • Data Networks
• Digital Subscriber Line (DSL) • Fiber in the Loop • PBX
• Indoor/Outdoor Wireless • Transmission
Key Features
Remote Access and Features • EasyView2, Windows- - Automatic rectifier
• Integrated 10/100Base-T Ethernet based GUI software for local sequence control
Network terminal or Modem access - N + X redundancy check
- TCP/IP with IPV6 Support • Optional 1U display with alarm • Multiple Low Voltage Load
- SNMP V3 for management indicating backlight feature and Low Voltage Battery
- SMTP for email Standard System Features Disconnect thresholds (4)
- Telnet for command line interface • Configuration, statistics, and history
- DHCP for plug-n-play • Monitor and control of more than 40
connected devices - All stored in non-volatile memory
- FTPS for rapid backup and upgrades - Remote/local backup and
- HTTPS for standard web pages - Maximum of 32 rectifiers
- Maximum of 6 distribution restore of configuration data
and browsers
- Compatible with Galaxy Manager control cards • Industry standard defaults
and other management packages - Robust RS485 system bus - Customer specific
- Shielded RJ-45 interface • Standard and user defined alarms configurations available
referenced to chassis ground - Alarm test • Remote/ local software upgrade
• Password protected security - Assignable alarm severity: • Basic, busy hour, and trend statistics
levels: User, Super-User, Critical, Major, Minor,
Warning, and record-only • Detailed event history
Administrator for all access
• Rectifier management features • User defined events and
• Ground-referenced
- Automatic rectifier restart derived channels
RS232 system port
- Adaptive Rectifier Management
• ANSI T1.317 command-line interface (energy efficiency)
• Modem access support - Remote rectifier (on/off)
- Remote via external modem - Reserve Operation
- Callback security
Specifications
GENERAL
Operating Voltage ±24 Vdc, ±48 Vdc (Range: ±18 to ±60 Vdc)
Input Power Less than 7W
Operating Temperature Range -40°C to +70°C (-40°F to 167°F)
Operating Relative Humidity 0 - 95% (non-condensing)
Storage Temperature Range -40°C to +85°C (-40°F to 185°F)
Physical Specifications 1.75 in. H, 0.75 in. W, 8.00 in. D; 0.5lb
Display 8-line by 40-character backlit LCD
EMC FCC/EN55032 Class A, CISPR22 Level A
AGENCY CERTIFICATIONS
Applications
• Wireless Telecom Networks • Transmission • Off-Grid/On-Grid
• Indoor/Outdoor Wireless • Data Networks Renewable Energy Sites
Key Features
• Dual Voltage Flexibility • 1U Height, Hi Power Density • Hot Pluggable
• Redundant Fan Cooling • 220/110 V AC Input • RoHS Compliant
• Front Panel LED Indicators • Digital Load Sharing • ECO Priority Ready
Specifications
INPUT MIN TYP MAX
Voltage Range
- High-Line 175Vac 220Vac 305Vac
- Low-Line 85Vac 110Vac 140Vac
Frequency 45Hz 60Hz 66Hz
Power Factor 98% 99.5%
Total Harmonic Distortion 5%
PRIMARY OUTPUT
Nominal Voltage 24Vdc -48Vdc
Output Current 1,200A 800A
Vo Setpoint (factory) 27.2Vdc±1% -54.5Vdc±1%
Vo Range +21Vdc to +29Vdc -42Vdc to -58Vdc
Regulation ±0.5%
SECONDARY OUTPUT
Nominal Voltage -48Vdc +24Vdc
Output Current 120A 300A
Vo Setpoint (factory) -54.5Vdc±1% 27.25Vdc±1%
Vo Range -42Vdc to -58Vdc +21Vdc to +29Vdc
Regulation ±0.5%
ENVIRONMENTAL
Operating Temperature -40°C to +75°C (-40°F to 167 °F)
Storage Temperature -40°C to +85°C (-40°F to 185 °F)
Relative Humidity 95% max, non-condensing
Altitude 4000M (for altitudes above 2000M, peak operating temperature de-rates 0.656º C /100M; 4000M peak temperature rating is 62º C
AGENCY CERTIFICATIONS
CSA ANSI/UL60950-1-2014 and CAN/CSA C22.2 No. 60950-1-07, Second Edition + A2:2014 (MOD), dated October 14, 2014
EMI/EMC European Directive 2014/30/EU; EN55032 (CISPR22) Class A; EN55035 (CISPR24)
NEBS LEVEL 3 GR1089-CORE
Special equipment room cooling may be needed - heat dissipation exceeds values of GR-63 Table 4-5
ENVIRONMENTAL
NEBs Evaluated by independent NRTL test lab to Telcordia GR63-CORE and GR1089-CORE ISSUE 6 [Level 3]
Safety ANSI/UL60950-1-2014 and CAN/CSA C22.2 No. 60950-1-07, Second Edition + A2:2014 (MOD), dated October 14, 2014
RoHS Compliant to RoHS EU Directive 2002/95/EC RoHS 6/6
EMC European Directive 2014/30/EU; EN55032, Class A; EN55035; FCC, Class A; GR1089-CORE ISSUE 6
AGENCY CERTIFICATIONS
UL ISSUE 6
EMI/EMC European Directive 2014/30/EU; EN55032 (CISPR22) Class A; EN55035 (CISPR24)
NEBS LEVEL 3 GR1089-CORE ISSUE 6
Additional Information
Product Documentation
CC848815341 Advanced Features User Guide for the Pulsar Plus Controller, 167-792-183
CC848908475 Infinity S Quick Start Guide
850022389 Infinity S Quick Start Guide, Dual Voltage Systems
CC848836981 User Guide for the Galaxy Pulsar Edge Family of System Controllers
Ordering Guide
Infinity S may be configured as a +24V or -48V single voltage power system or as a
“dual voltage” power system that supports rectifiers and converters. The primary
voltage is supported by +24V or -48V rectifiers and battery reserve, while secondary
voltage is supported by DC-DC converters. The primary voltage capacity is 1,200A at
24V and 800A at 48V. Secondary voltage capacity is up to 120A (-48V), 300A (24V).
Infinity S systems may be equipped in a 7ft framework, a half height (42”) frame
for mounting on battery stands, integrated into cabinet applications, or supplied
frameless for field install applications.
Features
• Infinity Series Rectifiers for +24V and • Temperature hardened harsh • Battery connections, LVBD and
-48V applications. environments. (-40ºC to +75ºC) LVLD options.
• Dual Voltage Bus architecture for easy • Compact size: Base System with 1 • Plug-N-Play Pulsar Plus controller with
growth and voltage migration power shelf occupies 5 RU (8.75 in) of Web based interface for local and
• DC-DC Converter support for dual 19” or 23” rack space (18”-21” depth) remote (LAN) access.
voltage systems • Frame options – Factory installed in • Distribution options include 3A-250A
• DC Distribution for both voltages, with 7ft or 42” tall, 19” or 23” wide frame or bullet style circuit breakers, and
Selectable Voltage panel availability field installed in user supplied frame GMT fuses
AC Input Types
TYPE DESCRIPTION SCHEMATIC
AC1 Dual Feed, Molex Mini-fit Sr
23” Shelves
23” Shelves
23” Shelves 19” Shelves
AC6 Three Phase, terminal strip input Rear cover is equipped with a 1” conduit knockout
19” Shelves
400A Infinity S Power Dual Molex No CC109163705 NES48 -23 -AC1 -PS8 -DC1E
system equipped with
-48V 8 rectifier positions and
26 distribution positions
400A selectable between -48V Dual Molex LVBD CC109165998 NES48 -23 -AC1 -PS8 -DC1E -LVBD
Load and Battery
System - 6RU
600A Infinity S Power Dual Molex No CC109163713 NES48 -23 -AC1 -PS12 -DC1E
system equipped with
-48V 12 rectifier positions and Ind. Term Block No 150045733 NES48 -23 -AC5H -PS12 -DC1E
26 distribution positions
600A selectable between -48V Ind. Term Block No 150045732 NES48-23-AC5H-PS8-DC1E
Load and Battery
System - 7RU Dual Molex LVBD CC109167920 NES48 -23 -AC1 -PS12 -DC1E -LVBD
Ind. Term Block LVBD 150045739 NES48 -23 -AC5H -PS12 -DC1E -LVBD
600A Infinity S Power Dual Molex No CC109171286 NES48 -23 -AC1 -PS12 -DC2E
system equipped with 12
-48V rectifier positions and 52
total distribution positions,
600A 26 of which are selectable
Dual Molex LVBD CC109171278 NES48 -23 -AC1 -PS12 -DC2E -LVBD
between -48V Load
and Battery
System - 11RU
600A Infinity S Power Ind. Term Block No 150045735 NES48 -23 -AC5H -PS16 -DC1E
system equipped with
-48V 16 rectifier positions and
26 distribution positions
600A selectable between -48V Ind. Term Block LVBD 150045742 NES48 -23 -AC5H -PS16 -DC1E -LVBD
Load and Battery
System - 8RU
800A Infinity S Power Ind. Term Block No 150045734 NES48-23-AC5H-PS12-DC2E
system equipped with
-48V 16 rectifier positions Ind. Term Block LVBD 150045740 NES48-23-AC5H-PS12-DC2E-LVBD
and 52 total distribution
800A positions, 26 of which Ind. Term Block No 150045736 NES48 -23 -AC5H -PS16 -DC2E
are selectable between
-48V Load and Battery Ind. Term Block LVBD 150045741 NES48-23-AC5H-PS12-DC2E-LVLD
System - 12RU
Ind. Term Block LVBD 150045743 NES48 -23 -AC5H -PS16 -DC2E -LVBD
850022254 Bus Kit to expand battery bulk connections on battery buses to 2 - 3/8” on 1” .50
1.00
through hole connections. (One bus per kit, order two for paired connections) .60
(2) .35
1.60
R.19
(4) .434
3.50
1.30
.70
SCALE 2/1
Note: Adding these shelves does not increase the overall rating of the distribution.
Rectifiers
OUTPUT ORDERING CODE MODEL PHOTO
RATING
CC109160834 95 - 145Vac input, 24V, 44A output (max. 50A@24V)
175 - 305Vac input, 24V, 100A output (max. 114A @24V)
145 - 175 linear output increase from 44A to 100A
NE100AC24ATEZ
100A
150025075 95 - 145Vac input, 24V, 44A output (max. 50A@24V)
175 - 305Vac input, 24V, 100A output (max. 114A @24V)
145 - 175 linear output increase from 44A to 100A
100 - 310 VDC input from Solar resource with full power above 250VDC.
100A NE100ECO24ATEZ
CC109158878 95 - 145Vac input, 48V, 22A output (max. 25A @48V)
175 - 305Vac input, 48V, 50A output (max. 57A @48V)
145 - 175 linear output increase from 22A to 50A
NE050AC48ATEZ
50A
150025074 95 - 145Vac input, 48V, 22A output (max. 25A @48V)
175 - 305Vac input, 48V, 50A output (max. 57A @48V)
145 - 175 linear output increase from 22A to 50A
100 - 310 VDC input from Solar resource with full power above 250VDC.
50A NE050ECO48ATEZ
CC109163473 95 - 145Vac input, 48V, 22A output (max. 25A@48V)
175 - 305Vac input, 48V, 75A output (max. 82A@48V)
145 - 175 linear output increase from 22A to 75A
Note: for use in 19” or AC5H 23” systems only
75A NE075AC48ATEZ
Converters
OUTPUT ORDERING CODE MODEL PHOTO
RATING
CC109112471 21-30Vdc input, 48V, 30A output
NE030DC48A
30A
NE040DC48AZ
40A
75A
Miscellaneous
ORDERING CODE MODEL
CC109170668 Infinity Rectifier/Converter slot filler (full chassis)
CC848798702 Blank panel for use in empty rectifier / converter positions
ORDERING AC GAUGE SHELF ORDER # OF CORDS CORD LENGTH USER 120 VAC 208/240
CODE TYPE TERMINATION TYPE TERMINATION VAC
SHELF DUAL INDIV.
CC848801977 AC1 8 Molex 1 x Sleeved 3' Unterminated x x
CC848830522 Molex 1 x Sleeved 4' Unterminated
848710711 Molex 1 x Sleeved 10' Unterminated
CC848906586 Molex 2 x SO 10' Unterminated
CC848773515 10 Molex 2 x SO 15' Unterminated
850031034 8 Molex 2 x SO Unterminated
CC848847368 AC3 12 IEC - No Plug 4 x SO 8’ Unterminated x x
CC848850801 12 IEC 5 - 20P 4 x SO 8’ 5 -20P x
CC848850834 12 IEC 6 - 20P 4 x 8’ 6 -20P x
CC848850842 12 IEC L6 - 20P 4 x 8’ L6 -20P x
The following AC Covers can be used to replace the individual AC Covers on the 23” AC5 or AC5H shelf with a single larger
cover to allow for fewer conduit runs to the system. Each Kit comes with 2 covers, one for each side of the system.
Alarm Cables
ORDERING CODE MODEL PHOTO
CC848865980 15ft Auxiliary input alarm cable for Pulsar Plus Controller
CC848817651 50ft Auxiliary input alarm cable for Pulsar Plus Controller
CC848817668 150ft Auxiliary input alarm cable for Pulsar Plus Controller
CC109157442 15ft alarm cable for Pulsar Plus Controller
CC848817635 50ft alarm cable for Pulsar Plus Controller
CC848817643 150ft alarm cable for Pulsar Plus Controller
CC848890161 5ft alarm cable for Pulsar Edge Controller
CC848890178 15ft alarm cable for Pulsar Edge Controller
CC848890186 50ft alarm cable for Pulsar Edge Controller
408185353 125 2 2
CC848756916 2-pole Adapter bus for 100-150A breakers; used for ¼”-20 on 5/8” lugs
(order 2 per 2 pole breaker to accommodate load and return lugs)
850021775 2-pole Adapter bus for 100-150A breakers; used for 3/8” on 1” lugs
(order 2 per 2 pole breaker to accommodate load and return lugs)
CC848756924 3-pole Adapter bus for 200-250A breakers; used for 3/8” on 1” lugs;
off-center connection
(order 2 per 3 pole breaker to accommodate load and return lugs)
850021955 3-pole Adapter bus for 200-250A breakers; used for 3/8” on 1” lugs;
center connection
(order 2 per 3 pole breaker to accommodate load and return lugs)
Note: For 70-100A single pole breakers, one breaker space must be left open in the adjacent position when powering breaker above 80% capacity under normal loading conditions
CC408612758 30
CC408612766 40
CC408612774 45
CC408574370 50
408560123 60
CC408574387 70
CC408574395 100
CC408574404 125 (2-pole)
CC408574412 150 (2-pole)
CC408574420 200 (2-pole)
CC408645295 250A (3-pole)
CC109106548 100A battery bullet bus strap (substitute for battery breaker)
Terminal Lugs for Bullet Style Breakers and TPS Fuses (1/4” Bolt on 5/8” Centers)
ORDERING CODE STR WIRE GA (CLASS B) FLEX WIRE GA (CLASS I) WP-91412 LIST PHOTO
406021626 8 8 75
405347519 6 6 3
405347576 4 4 5
405348202 2 - 54
405347683 - 2 8
Terminal Lugs for Battery and Large Breakers (3/8” Bolt on 1” Centers)
PEOPLESOFT NUMBER STR WIRE GA (CLASS B) FLEX WIRE GA (CLASS I) WP-91412 LIST PHOTO
406338665 2 - -
405348228 1/0 - -
405348236 2/0 1/0 -
406021725 - 2/0 -
405348251 4/0 - -
405347923 - 4/0 -
Temperature/Voltage probes are needed for battery monitoring. They are connected to each battery or battery string to provide slope thermal compensation,
temperature alarms and voltage imbalance alarms.
Temperature Measurement
Warranty
GE is committed to providing quality products and solutions. We have
developed a comprehensive warranty that protects you and provides a
simple way to get your products repaired or replaced as soon as possible.