BEAM DESIGN & Column Design

The document provides design details for a reinforced concrete beam, stirrups, and column for the AMC Housing Project located in Bagumbong Road, Brgy. 171, Caloocan City. The beam design includes calculations for required tension and compression reinforcement areas. The stirrup design calculates required shear strength and spacing. The column design determines the required longitudinal bar area.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
100 views

BEAM DESIGN & Column Design

The document provides design details for a reinforced concrete beam, stirrups, and column for the AMC Housing Project located in Bagumbong Road, Brgy. 171, Caloocan City. The beam design includes calculations for required tension and compression reinforcement areas. The stirrup design calculates required shear strength and spacing. The column design determines the required longitudinal bar area.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

PROJECT NAME:

PROJECT LOCATION:
AMC HOUSING PROJECT
BAGUMBONG ROAD, BRGY.171,
WATER IMPOUNDING AREA
CALOOCAN CITY

DOUBLY REINFORCED CONCRETE BEAM DESIGN

DESIGN DATA:
width, 300 mm f'c, 21 MPa
depth, 400 mm fy, 275 MPa
FACTORED concrete cover, 50 mm
MOMENT,Mu: 290.98 KN.m main bar, dia. 25 mm
FACTORED SHEAR, stirrups, dia. 10 mm
Vu: 346.14 KN
Solve for ρmax and Mumax:
(0.75)(0.85)(f'c)(ᵝ₁)(600)
ρmax = = 0.02837 = ρ
fy (600 + fy)
ρfy
ω = = 0.3716
f'c
Mumax = φf'cωbd²(1-0.59ω) = KN.m 263.190
Since Mu > Mumax, compression reinforcement is necessary.
Solve for As₁:
As₁ = ρmax bd = 3404.9 mm²
Solve for Mu₁ and Mu₂:
Mu₁ = Mumax = 263.190 KN.m
Mu₂ = Mu - Mu₁ = 27.794 KN.m
Check if compression steel yields:
Solve for a and c:
[C₁ = T₁]
0.85f'c ab = As₁fy
a = 174.86 mm
[a = ᵝ₁ c]
c = 205.71 mm
600 (c- d') 388.54 MPa
f's = =
c
Since f's > fy, therefore compression steel yields and use A's =As2.
Mu₂ = φ T₂ (d-d')
Mu₂ = φ As₂ fy (d-d')
As₂ = 342.8989 mm²

Compression steel area, A's = As₂ = 342.8989 mm²


Therefore use 1 pcs, 25 mm dia. Reinforcing steel bar

Tension steel area, As = As1 + As₂ = 3747.8444 mm²


Therefore use 8 pcs, 25 mm dia. Reinforcing steel bar

DESIGNED BY: VEA ANNE A. GIRAY


CIVIL ENGINEER
PRC ID NO.: 0128826
PTR NO: 7537594
TIN: 317- 854- 120- 000
PROJECT NAME:
PROJECT LOCATION:
AMC HOUSING PROJECT
BAGUMBONG ROAD, BRGY.171,
WATER IMPOUNDING AREA
CALOOCAN CITY

VERTICAL STIRRUPS DESIGN

FACTORED SHEAR,
Vu: 346.14 KN
Calculate the shear strength provided by concrete, Vc:
Vc = 1/6 √f'c bωd = 91.652 KN
φVc = 77.904 KN
1/2 φVc = 38.952 KN
Since Vu > φVc, therefore stirrups are necessary.
Vn = Vu / φ = 407.22 KN
Vs = Vn - Vc = Vu φ -Vc = 315.57 KN
2/3 √ f'c bwd = 366.606 KN
Since Vs < 2/3 √ f'c bwd, spacing, s = Avfyd/ Vs.
Av = 2Ab
Avfyd
s = = 54.755 mm
Vs
1/3 √ f'c bwd = 183.303 KN
maximum spacing, s:
Since Vs > 1/3 √ f'c bwd , smax = d/4 or 300mm.
Use smax = 400/4 mm = 100mm

DESIGNED BY: VEA ANNE A. GIRAY


CIVIL ENGINEER
PRC ID NO.: 0128826
PTR NO: 7537594
TIN: 317- 854- 120- 000
PROJECT NAME:
PROJECT LOCATION:
AMC HOUSING PROJECT
BAGUMBONG ROAD, BRGY.171,
WATER IMPOUNDING AREA
CALOOCAN CITY

REINFORCED CONCRETE COLUMN DESIGN

DESIGN DATA:
width, 300 mm f'c, 21 MPa
depth, 400 mm fy, 275 MPa
height, 2250 mm concrete cover, 50 mm
main bar, dia. 25 mm
FACTORED lateral ties, dia. 10 mm
LOADS,Pu: 1393 KN

Calculate Ast:

Pu = φ0.80(0.85f'c(Ag-Ast)+fy(Ast)
φ = 0.70 for tied columns
1391600 = 0.70(0.80)(0.85(21)(300x400-Ast)+275(Ast))
Ast = 1333.6 mm²
Number of
reinforcing bars 4 pcs 25 mm dia. Bar
required =

Use 150 mm maximum spacing of lateral ties beyond confinement part


of column.

DESIGNED BY: VEA ANNE A. GIRAY


CIVIL ENGINEER
PRC ID NO.: 0128826
PTR NO: 7537594
TIN: 317- 854- 120- 000