Enhancing Differential Protection Stability During CT Saturation With Transient Bias
Enhancing Differential Protection Stability During CT Saturation With Transient Bias
Keywords: Current differential protection, transient biasing, The condition (1) essentially represents the equation 18 from
CT requirements, CT modelling. [2] when the inductive burden can be neglected.
The CT model employed in the paper has the following For internal faults the criteria to stop the test is non-operation
parameters: the CT ratio KCT = 10/1, the rated secondary of the protection or unacceptable tripping time.
current 1А, the knee-point voltage VK = 160V.
It is essential to test the protection with different CT
Figure 2 illustrates the CT saturation, the spurious operation remanence values. To achieve that, the initial remanence is
of the differential function without the transient bias and the set to zero and every fault is applied six times: three times
stabilizing effect of the transient bias. with a positive DC component (the remanence grows from
zero to its positive limit) and three times with a negative DC
60
40 component (the remanence drops from the positive limit to its
20
0 negative limit).
-20
a) The CT saturation
20 I DIFF .THR. Trip!!! After completing all the tests the RTDS system generates an
10
Trip!!! array of limiting CT burdens Rlim for external and internal
I DIFF
0 faults with different combinations of the following
b) The differential current and the tripping threshold without parameters:
the transient bias
30
20 I TR .BIAS 1. Knee-point voltage of the CT Vk : 40-320 V
10
0
2. Fault current If : 2-50 А secondary
c) The transient bias current 3. X/R ratio of the network: 5-120
40 I DIFF .THR. 4. Fault type: A-N, B-C, A-B-C
20
0
I DIFF 5. Point on wave (POW): 0°-150°
0.48 0.49 0.5 0.51 0.52 0.53 0.54 0.55 0.56 0.57 0.58 0.59 0.6
d) The differential current and the tripping threshold with the For the second slope setting K2 = 150% the number of tests
transient bias
totalled 3967 for external faults and 1915 – for internal,
where a single test comprises of the six-shot fault sequence
Figure 2: The stabilizing effect of transient biasing. described above.
Once the tests in the Simulink® environment had
2.4 Processing the results of the RTDS testing
demonstrated the merits of the transient bias algorithm, this
feature was implemented in the software of actual line The data produced by the RTDS system is processed in the
differential relays. MATLAB environment.
2.3 Testing relays with RTDS system and determining It should be noted that the limiting burden for internal faults
new CT requirements is much higher than for external ones owing to the external
fault detector and the fact that the transient biasing does not
The final tests of the differential relays with the transient slow the relay down during internal faults.
biasing feature, and the determining of the new CT
requirements, were carried out with the RTDS (Real Time A coefficient K is calculated from the limiting burden Rlim .
Digital Simulation) system. The set-up involved the This coefficient can be used as a dimensioning factor for an
following: arbitrary CT.
1. A protected line with settable X/R ratio and fault current
VK
(for internal and external faults). K= , (9)
2. Two models of three-phase CT with settable knee-point I n ⋅ (2 ⋅ Rlim + 0.5)
voltage Vk and burden. where
3. Several line differential relays connected to the CT models VK is the knee-point voltage of the CT used in the RTDS
through digital-to-analogue converters and amplifiers. test,
I n is the rated secondary current of the CT used in the RTDS
The stability check for external faults is done by applying
multiple faults with a pre-defined fault current and X/R ratio test (1А),
while incrementing the CT burden until one of the relays (2 ⋅ Rlim + 0.5) - the total CT burden including both forward
trips. The burden RL (one-way) is increased step by step from and return leads and the internal CT resistance (fixed at 0.5
0.1 Ohm to 16 Ohms (38 steps in total). Ohm).
(
If ( I f ⋅ X R) ≤ 1000 : K = max 65, (40 + 0.07 ⋅ ( I f ⋅ X R )) ,)
If 1000 < ( I f ⋅ X R) ≤ 1600 : K = 107 .
If X/R K K Effect
w/out trans. bias with trans. bias %
5 5 65 33.2 49
10 10 65 39.1 40
20 20 68 52.2 23
30 30 103 67.1 35
40 40 107 83.7 22
40 65 - 100.4 -
3 Conclusion
The transient biasing algorithm is proposed in the paper that
significantly increases the stability of Current Differential
protection during external faults. The algorithm is first tested
with CT and relay models in the MATLAB/SIMULINK®
environment and then with the RTDS® system.
The paper also describes in detail a testing technique used by
ALSTOM Grid to define CT requirements of Current
Differential protection. The results of the CT requirements