Manual TMD-Display View EN v1.1 A

TMD-Display View is a KNX touch panel with an 8-button capacitive touch interface and 1.8" graphical display that provides versatile control of rooms. It has customizable buttons, pages, graphics, and LED indicators. The touch panel includes temperature and motion sensors, thermostat functionality, and inputs to integrate other devices. Users can configure multiple control interfaces by setting up different pages with unique button assignments and display content.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views

Manual TMD-Display View EN v1.1 A

TMD-Display View is a KNX touch panel with an 8-button capacitive touch interface and 1.8" graphical display that provides versatile control of rooms. It has customizable buttons, pages, graphics, and LED indicators. The touch panel includes temperature and motion sensors, thermostat functionality, and inputs to integrate other devices. Users can configure multiple control interfaces by setting up different pages with unique button assignments and display content.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 87

Capacitive Touch Panel with 8 Buttons

and Paged Graphical Display

ZVI-TMDV
USER MANUAL

Application Programme Version: [1.1]


User Manual Version: [1.1]_a

www.zennio.com
TMD-Display View

CONTENTS

Contents ........................................................................................................................................ 2

Document updates ........................................................................................................................ 4

1 Introduction ............................................................................................................................. 5

1.1 TMD-Display View ............................................................................................................ 5

1.2 Installation ........................................................................................................................ 7

2 Configuration ........................................................................................................................... 9

2.1 Default Configuration ....................................................................................................... 9

2.2 General ........................................................................................................................... 11

2.2.1 CONFIGURATION .................................................................................................... 11

2.2.2 Temperature Sensor ............................................................................................... 13

2.2.3 Screensaver............................................................................................................. 13

2.2.4 LEDs & Display ........................................................................................................ 14

2.2.5 Sounds .................................................................................................................... 18

2.2.6 Touch Locking ......................................................................................................... 20

2.2.7 Welcome Back Object ............................................................................................. 21

2.3 Pages .............................................................................................................................. 24

2.3.1 CONFIGURATION .................................................................................................... 24

2.4 Page n ............................................................................................................................. 26

2.4.1 CONFIGURATION .................................................................................................... 26

2.4.2 Disabled .................................................................................................................. 29

2.4.3 Pair .......................................................................................................................... 29

2.4.4 Individual ................................................................................................................ 53

2.5 Configuration pages ....................................................................................................... 67

http://www.zennio.com Technical Support: http://support.zennio.com


2
TMD-Display View

2.5.1 General Configuration ............................................................................................ 67

2.5.2 Display..................................................................................................................... 68

2.6 Inputs .............................................................................................................................. 69

2.6.1 Binary Input ............................................................................................................ 69

2.6.2 Temperature Probe ................................................................................................ 69

2.6.3 Motion Detector ..................................................................................................... 70

2.7 Thermostat ..................................................................................................................... 71

ANNEX I: LED Illumination Modes ............................................................................................... 72

ANNEX II. Button Icons ................................................................................................................ 75

ANNEX II: Communication Objects ............................................................................................. 76

http://www.zennio.com Technical Support: http://support.zennio.com


3
TMD-Display View

DOCUMENT UPDATES

Version Changes Page(s)

Changes in the application programme:


• Optimisation of the start-up process.
[1.1]_a -
• Minor optimisation in character representations.
• Update of the motion detector function.

http://www.zennio.com Technical Support: http://support.zennio.com


4
TMD-Display View

1 INTRODUCTION

1.1 TMD-DISPLAY VIEW


TMD-Display View is an evolution of TMD-Display One, the KNX multifunction
capacitive touch switch with graphical display from Zennio.

TMD-Display View provides eight capacitive buttons aligned in 2 columns of 4


buttons each, LEDs to indicate user presses or states, and a wide display on the top
of the front panel, as in ZAS and Roll-ZAS from Zennio.

TMD-Display View is a fully customisable solution for the room control, including
hotel rooms, offices or any other environment where the user needs to control climate
systems, lighting, blinds, scenes, etc.

The versatility of the above functions is enhanced by the built-in analogue/digital


inputs, the internal temperature sensor and the thermostat function, as well as an
elegant and fully customisable design of the front glass – customers can choose
their button icons, texts and colours and even personalise the background with their
pictures, logos, etc.

Moreover, the display offers the possibility to show useful information to the user about
the control states and object values, being possible to configure up to 4 different
pages. Unlike those in TMD-Display One, the capacitive buttons and the display in
TMD-Display View can perform different functions depending on the page selected,
thus providing the user a versatile interface with multitude of controls available.

The most outstanding features of TMD-Display View are:

1.8’’ back-lit display with a resolution of 128x64 pixels.

Fully customisable design of the front glass.

8 touch buttons which can operate as individual or pair controls.

Up to 4 different pages available.

Light indicator (LED) for every button, the state of which (on or off) can
depend on different factors according to the user’s needs.

http://www.zennio.com Technical Support: http://support.zennio.com


5
TMD-Display View

Buzzer for an audible acknowledgement of user actions (with the possibility


of disabling it either by parameter or by object).

Possibility of locking / unlocking the touch panel through binary orders or


scenes, and of setting a timed/automatic locking of the device (cleaning
function).

Welcome greeting on the display and Welcome Back object (binary or


scene).

Central touch area which allows browsing through the configured pages or
confirming certain actions.

Screensaver function.

Two analogue/digital inputs (temperature probes, additional switches, etc.).

Thermostat function.

Built-in temperature sensor.

Motion detection function, by connecting the corresponding accessory.

Figure 1 TMD-Display View.

http://www.zennio.com Technical Support: http://support.zennio.com


6
TMD-Display View

1.2 INSTALLATION

1 2 3 4

Figure 2 TMD-Display View. Installation Process.

To install the device, it is first necessary to mount the metallic plate into a square/round
standard appliance box through the suitable screws. Next, TMD-Display View is
connected to the KNX bus through the corresponding terminal on the rear side of the
device, and then the input terminal is as well connected to the rear of the device.

Once the input terminal and the KNX terminal are connected, the device can be easily
mounted on the metallic plate by the action of the built-in magnets. After that, it is
necessary to slide it downwards to fix it through the security anchorage system.

Finally, it is advisable to check that the device is properly installed, and that only its
profile becomes visible from above, from below and from both sides (the metallic plate
should be completely hidden).

This device does not need any external supply, as it is powered through the KNX bus.

1. Temperature Sensor.
2. KNX Bus Connector.
3. Analogue/Digital Inputs.
4. Test/Prog. Button.
5. Test/Prog. LED.
6. Magnet.
7. Display.
8. Status LED.
9. Main touch area.
10. Central Touch Area.

Figure 3 Element diagram.

http://www.zennio.com Technical Support: http://support.zennio.com


7
TMD-Display View

The programming button (4) can be pressed with the help of a thin screw to set the
device into the Programming Mode. After a short press, the programming LED (5) will
light in red. Note that if this button is held while plugging the device into the KNX bus,
the device will enter the Safe Mode. The LED will then blink in red.

Note: whenever the device recovers the bus power, an immediate self-calibration
process of the touch panel takes place. Please ensure to avoid touching the front glass
while powering the device. If undesired effects arise during normal use, please
disconnect the device from the bus and connect it again, making sure that the front
glass is not touched during this process.

For detailed information about the technical features of the device and for safety
instructions and on the installation process, please refer to the Datasheet bundled with
the original packaging of the device and also available at www.zennio.com.

http://www.zennio.com Technical Support: http://support.zennio.com


8
TMD-Display View

2 CONFIGURATION

2.1 DEFAULT CONFIGURATION


To make the device perform the desired functions, several options need to be
parameterised related to its general behaviour (screensaver, sounds, LEDs and
display brightness levels, lock procedure of the touch panel, welcome back object,
etc.).

Some of the above options are common to other Zennio devices such as Touch-
MyDesign, Roll-ZAS or Z41, while others are specific for TMD-Display View.

On the other hand, TMD-Display View features two opto-coupled inputs, each of which
may be independently configured as a switch/sensor, a push-button or a
temperature probe or motion detector, so that external accessories can be
connected to the device.

In the particular case of an external temperature probe (such as model ZN1AC-NTC68


from Zennio), it will be possible to use it with independence of the built-in temperature
sensor of the device, which implements its own communication objects and can be
enabled and disabled in parameters.

ETS PARAMETERISATION

Figure 4 General.

After importing the corresponding database in ETS and adding the device into the
topology of the project, the configuration process begins by right-clicking into the
device and selecting Edit parameters.

This will bring the window shown in Figure 4, which contains the following tabs:

General: contains the parameters that define the general behaviour of the
device and that enable/disable additional features such as the thermostat or
the external inputs. See section 2.2 for details.

http://www.zennio.com Technical Support: http://support.zennio.com


9
TMD-Display View

Pages: contains the parameters for enabling/disabling the different control


pages and some general parameters related to the touch buttons and the
navigation control. See section 2.3 for details.

Page 1: contains the parameters for enabling/disabling the controls contained


in page 1 (enabled by default). See section 2.4 for details.

Depending on the configuration, other tabs may show in the tab tree on the left.

These tabs will be explained in the next sections.

http://www.zennio.com Technical Support: http://support.zennio.com


10
TMD-Display View

2.2 GENERAL
As shown in Figure 5, the “General” tab only contains one sub-tab by default:
“Configuration”. However, it may include other tabs depending on the parameterisation.

2.2.1 CONFIGURATION

Figure 5. General - Configuration

This tab shows the following parameters:

Inputs: enables or disables the “Inputs” tab in the tree on the left, depending
on whether the device will or will not be connected any external accessories.
See section 2.6 for details.

Thermostat: enables or disables the “Thermostat” tab in the tree on the left.
See section 2.7 for details.

Internal temperature sensor: enables or disables the “Temperature Sensor”


tab in the tree on the left. See section 2.2.2 for details.

Screensaver: enables or disables the “Screensaver” tab in the tree on the


left. See section 2.2.3 for details.

LEDs and Display config.: sets whether the LEDs and display should make
use of the pre-defined brightness levels (“Default”) or of a user-defined
configuration (“Custom”).

http://www.zennio.com Technical Support: http://support.zennio.com


11
TMD-Display View

 “Default”: the LEDs will remain off while in the “off” state, and at the
maximum light level while in the “on” state. The display contrast level is set
to 7.

 “Custom”: a specific tab will be included in the tab tree on the left so the
integrator can set the desired light levels for the “off” and “on” states and
whether to use the Night Mode or not. The display contrast level will also
be configurable.

See section 2.2.4 for details.

Sounds: sets whether the sound functions (button beeps, alarm and
doorbell) should work according to the pre-defined configuration (“Default”) or
to a user-defined configuration (“Custom”). See section 2.2.5 for details.

Touch Locking: enables or disables the “Touch Locking” tab in the tree on
the left. See section 2.2.6 for details.

Welcome Back Object: enables or disables the “Welcome Back” tab in the
tree on the left. See section 2.2.7 for details.

Saved Scene Label: textbox to enter the string displayed when a scene is
being saved.

Hide explanation texts: displays or hides the explanation texts on the top of
the parameter screen of some functions. Experienced users may prefer to
hide these texts to have simpler parameter screens.

The project topology shows the following objects by default:

[General] Time of day: object for updating the time shown on the display.

Important: the time of day must be set through the bus by means of an
external reference. Note that in the absence of power, the clock will get
outdated.

[General] Scene: Receive and [General] Scene: Send: objects for


respectively receiving and sending scene values from/to the KNX bus
whenever it is necessary (e.g., when the user touches a button that has been
configured to send scene commands; see section 2.4.3 and section 2.4.4).

http://www.zennio.com Technical Support: http://support.zennio.com


12
TMD-Display View

2.2.2 TEMPERATURE SENSOR

TMD-Display View is equipped with one internal temperature probe which can
monitor the ambient temperature of the room, thus making the device capable of
reporting it to the KNX bus and of triggering certain actions when the temperature
reaches specific values.

Please refer to the specific manual “Temperature Sensor” (available in the TMD-
Display View section at the Zennio homepage, www.zennio.com) for detailed
information about the functionality and the configuration of the related parameters.

2.2.3 SCREENSAVER

The screensaver is a special page that will only be shown after a period of inactivity,
configurable by parameter.

It is possible to configure the screensaver to only show the current Time, the current
Temperature (selecting the desired measurement source: the internal temperature
sensor or an external value) or both (alternating every five seconds).

Notes:

 The temperature shown will be truncated to the range [-99ºC, 199ºC].

 The time of day must be set through the bus by an external reference.
Note that in the absence of power the clock will get outdated.

The screensaver disappears when any button is touched. It can be set by parameter
whether, while the screensaver is active, this press should simply cause the
screensaver interruption or, moreover –apart from hiding the screensaver–, the
execution of the action corresponding to the pressed button.

http://www.zennio.com Technical Support: http://support.zennio.com


13
TMD-Display View

ETS PARAMETERISATION

This screen is divided into three parts: Activation, Content and Exit, containing the
following parameters:

Activation timeout: time to automatically show the screensaver after the last
button touch. Range: 1 – 255 seconds, minutes or hours.

Time of Day: sets whether to show the current time or not.

Temperature: sets whether to show the current temperature or not. When


enabled, the following parameter will show up:

 Taken from: defines the source of the temperature value: “Internal sensor”
or “External reference”. The latter will bring a new two-byte object to the
project topology (“[General] Screensaver - External temperature”) so
that it the device can receive the required values from the bus.

Run button action on screensaver exit: sets whether touching a button


while the screensaver is active should cause the execution of the button
action, apart from hiding the screensaver.

Figure 6 General – Screensaver.

2.2.4 LEDs & DISPLAY

As anticipated in section 2.2, the integrator can configure the LEDs of the buttons to
make use of the pre-defined brightness levels or of user-defined levels.

http://www.zennio.com Technical Support: http://support.zennio.com


14
TMD-Display View

To begin with, each LED can commute between two states: off (which not necessarily
means “no light”) and on (which not necessarily means “light on”). They will switch their
states according to the options explained in ANNEX I: LED Illumination Modes.

Moreover, the LEDs and the display can also commute between two operation modes:
the normal mode and the night mode. The second one is optional. It is provided for
temporary situations and environments where an excess of brightness may disturb the
user. In such cases, it will be possible to switch the mode by means of a one-bit object
and/or a scene object.

Note: a general parameter is provided to make the ETS parameterisation easier in


case the night mode is not required and the integrator feels comfortable with the default
on/off brightness levels.

Regarding the display, it is possible to parameterise a contrast level in parameters. The


integrator can also enable an object to change the display contrast in real time.

ETS PARAMETERISATION

Figure 7 General – LEDs & Display config.

After selecting “Custom” for “LEDs and Display config.” (see section 2.2.1), a new tab
will be incorporated into the tree on the left.

The parameters shown in Figure 7 are equivalent to those for the “Default”
configuration of parameter “LEDs and Display config.”.

The upper section of this new screen is for the LED brightness configuration while the
lower is for the display brightness configuration.

http://www.zennio.com Technical Support: http://support.zennio.com


15
TMD-Display View

LED Brightness Levels

Figure 8 General – LEDs & Display – LED Brightness.

Normal Mode:

 LEDs: OFF level brightness: values between 0 (default) and 255.

 LEDs: ON level brightness: values between 0 and 255 (default).

 Display: Brightness: values between 0 and 10 (default).

Night Mode: in case of being this mode necessary, this checkbox needs to
be marked, which will incorporate some new parameters:

 LEDs: OFF level brightness: values between 0 and 255 (1 by default).

 LEDs: ON level brightness: values between 0 and 255 (8 by default).

 Display: Brightness: values between 0 and 10 (default).

http://www.zennio.com Technical Support: http://support.zennio.com


16
TMD-Display View

In case of enabling the night mode, some more options can be configured:

Control object: 1 bit: when marked, it will be possible to switch the mode by
writing to a binary object (“[General] LEDs & Disp - Brightness Mode”). A
specific drop-down list will show up to select which value should trigger which
mode (“0 = Normal; 1 = Night” or “0 = Night; 1 = Normal”).

Control object: Scene: when marked, it will be possible to switch the mode
by writing a certain scene value to “[General] Scene: Receive”. Two specific
textboxes will show up to enter what scenes (1 through 64) will trigger each
mode.

Idle time to change to Night Mode (0=disabled): when the time set in this
parameter elapses, TMD-Display View will switch to Night Mode (provided
that it was not already in this mode). The range is 0 to 65535 seconds (0 by
default).

Brightness Mode after ETS download: sets which of the two modes
(“Normal” or “Night”) will be active after an ETS Download.

Once either Control object: 1-bit or Control object: scene have been activated, a
new parameter will be shown to allow a temporary transition to normal mode when a
button is pressed during the night mode:

Light up when any button is pressed: sets whether pressing on one of the
enabled buttons during the night mode should imply a temporary transition to
normal mode or not.

 Length of lighting: sets the time (1 to 65535 seconds) the device will
remain in normal mode before switching back to night mode. The default
value is 10 seconds.

Display

Figure 9 General – LEDs & Display – Display configuration.

http://www.zennio.com Technical Support: http://support.zennio.com


17
TMD-Display View

Display contrast level: value to set the display contrast level, from 1 to 10 (7
by default).

Object for changing the contrast level: enables a one-byte object


(“[General] Display - Contrast”) to change the display contrast level in real
time.

2.2.5 SOUNDS

Apart from the behaviour of the LEDs, it is possible to make TMD-Display View emit a
brief beep as an acoustic feedback in two situations:

When a button is pressed: short beep indicating that the user has pressed a
button. This only applies to step controls, i.e., controls that walk through a
certain range of values and that do not send a value after every touch, but
only the final value after the last press.

When an action has been triggered: sharper beep than the above one,
indicating that a value is being sent to the KNX bus.

Enabling and disabling the button sounds can be done in parameters or through an
object, being also possible to define in parameters whether the button sounds should
be initially enabled or not.

On the other hand, TMD-Display View can also emit the following sounds on request
(through the corresponding communication objects):

Doorbell sounds (a single beep),

Alarm sounds (a sequence of brief beeps with a higher pitch),

The alarm sequence will only stop when the alarm object gets deactivated or when the
user touches any of the buttons (this will not trigger any action, only the alarm
deactivation). Note that doorbell requests are ignored while the alarm is active.

A general parameter is provided to make the ETS parameterisation easier in case the
doorbell and alarm functions are not required and the user feels comfortable with the
default button beeps. On the contrary, customising the button, doorbell and alarm
sounds involves a set of parameters, as explained next.

http://www.zennio.com Technical Support: http://support.zennio.com


18
TMD-Display View

ETS PARAMETERISATION

In case the default button beep sound matches the requirements of the installation and
the doorbell and alarm functions are not necessary, the “Sounds” parameter in the
general Configuration tab (see section 2.2.1) can be set to “Default”. This will also
imply that the button beeps will be unconditional, as it will not be possible to disable
this function through an object.

On the other hand, if set to “Custom”, a specific tab named “Sounds” will show up in
the tab tree on the left. The initial configuration of this screen is equivalent to the
aforementioned default option. However, the following parameters will be configurable.

Figure 10 General – Sounds.

Disable button sound: enables or disables the button and action beeps. If
enabled (default option) the following parameters will also be available:

 Enable / Disable button sounds through a 1-bit object: makes it


possible to disable / resume the button beeping function in runtime by
writing to a specific object (“[General] Sounds – Disabling button
sound”).

The values (0 or 1) that will disable / resume it are parameterisable


through “Value”.

 Button sound after ETS Download: sets whether the button beeping
function should start up enabled (default option) or disabled after an ETS
download. This makes sense if the “Enable/Disable Button Sounds
Using 1-Bit Object” checkbox (see below) is enabled too.

http://www.zennio.com Technical Support: http://support.zennio.com


19
TMD-Display View

Object for doorbell: enables or disables the doorbell function. If enabled, a


specific object (“[General] Sounds: Doorbell”) will be included into the
project topology. The value that will trigger the sound (1 or 0) must be set in
“Value”.

Object for alarm bell: enables or disables the alarm function. If enabled, a
specific object (“[General] Sounds: Alarm”) will be included into the project
topology. The values (1 or 0) that will trigger the alarm sequence and then
stop it must be entered in “Value”.

2.2.6 TOUCH LOCKING

The touch panel of TMD-Display View can be optionally locked and unlocked anytime
by writing a configurable one-bit value to a specific object provided for this purpose. It
can also be done through scene values.

While locked, user presses on the touch buttons will be ignored: no actions will be
performed (and no LEDs will change their states) when the user presses on any of the
controls. However, if configured, a message will be shown on the display for three
seconds if the user touches a button during the lock state.

ETS PARAMETERISATION

After enabling “Touch Locking” (see section ¡Error! No se encuentra el origen de la


referencia.), a new tab will be incorporated into the tree on the left.

Figure 11 General - Touch Locking.

The screen contains two non-exclusive checkboxes to select how the touch panel
lock/unlock should be performed:

http://www.zennio.com Technical Support: http://support.zennio.com


20
TMD-Display View

Figure 12 General - Touch Locking: Control.

Upon the reception of a one-bit value (“1 bit object”).

When marked, a specific drop-down list will show up to select which value should
trigger which action (“0 = Unlock; 1 = Lock” or “0 = Lock; 1 = Unlock”). These values
are to be received through object “[General] Lock Touch”.

Upon the reception of a scene value (“Scene object”).

When marked, two specific textboxes will show up to enter the scene numbers (1 - 64)
that should trigger each action. These values are to be received through the general
“[General] Scene: Receive” object.

2.2.7 WELCOME BACK OBJECT

TMD-Display View can send a specific object (the welcome back object) to the KNX
bus when the user presses a touch button after a significant amount of time since the
last press. Sending it or not can also depend on an additional, configurable
condition consisting in the evaluation of up to five binary objects.

Any actions that in normal operation may be executed will not be if the welcome back
object is sent to the bus. Thus, if the user presses a button and this causes the
welcome back object to be sent, the normal action of that button will not be triggered.
On the other hand, if the additional condition is not evaluated to true, the device will
react normally. Hence, the action corresponding to the button touch will be executed.

The welcome back object can consist in a one-bit value or a scene value (or both),
depending on the parameterisation.

http://www.zennio.com Technical Support: http://support.zennio.com


21
TMD-Display View

ETS PARAMETERISATION

After enabling “Welcome Back Object” (see section ¡Error! No se encuentra el


origen de la referencia.), a new tab will be incorporated into the tree on the left.

This screen contains the following parameters:

Figure 13 General - Welcome Back Object.

Timeout (since last touch): sets the minimum time (1 to 255 seconds, 1 to
255 minutes, or 1 to 255 hours) that should elapse after the last button touch
before the next one triggers the execution of the welcome back function.

Additional Condition: sets if sending the welcome back object should also
depend on an external condition. The option by default is “No Additional
Condition”. The following are available too:

 Do not send unless all additional conditions are 0: the welcome back
object will only be sent if all the condition objects are found to have the
value “0”.

 Do not send unless all additional conditions are 1: the welcome back
object will only be sent if all the condition objects are found to have the
value “1”.

 Do not send unless at least one of the additional conditions is 0: the


welcome back object will only be sent if at least one of the condition
objects is found to have the value “0”.

http://www.zennio.com Technical Support: http://support.zennio.com


22
TMD-Display View

 Do not send unless at least one of the additional conditions is 1: the


welcome back object will only be sent if at least one of the condition
objects is found to have the value “1”.

Welcome Back Object (1 Bit): checkbox to enable the sending of a 1-bit


value (through “[General] Welcome back”) when the welcome back function
is triggered and the condition (if any) evaluates to true. The desired value (0
or 1) should to be set in “Value”.

Welcome Back Object (Scene): checkbox to enable the sending of a scene


run request (through “[General] Scene: send”) when the welcome back
function is triggered and the condition (if any) evaluates to true. The desired
scene number (1 through 64) should to be entered in “Value”.

Figure 14 General - Welcome Back Object - Custom Configuration.

http://www.zennio.com Technical Support: http://support.zennio.com


23
TMD-Display View

2.3 PAGES
The Pages tab contains a single screen, Configuration.

2.3.1 CONFIGURATION

The Configuration screen under Pages allows enabling/disabling the pages that will be
available on the screen and configuring some general parameters concerning the
buttons and the navigation control.

ETS PARAMETERISATION

Figure 15 Pages – Configuration

Page n: checkbox to enable page n. There is one checkbox for each general
purpose page (pages 1 to 4), and two more for the configuration pages:
General Configuration and Display. Page 1 is always enabled.

Action of the pair buttons: sets how the two-button controls should behave:

 Left = 0/Off//Decr./Down; Right = 1/On/Incr./Up,

 Right = 1/On/Incr./Up; Left = 0/Off//Decr./Down,

 Every button pair is configured separately, which will incorporate an


additional parameter to the configuration window of each pair control to
allow defining the action of each of the two buttons (unless the function of
the control has been set to “Enumeration” or “[Climate] Mode”).

http://www.zennio.com Technical Support: http://support.zennio.com


24
TMD-Display View

Navigation Control: sets how the central touch area will perform the
navigation between pages. The available options are:

 Slide: the pages switch by sliding the finger across the central area
between the buttons. The parameter Action sets the navigation direction:

• Upward = Next Page; Downward = Previous Page.

• Upward = Previous Page; Downward = Next Page.

 Single button: the pages switch by pressing on the central area between
the buttons. The parameter Action sets the navigation direction:

• Next Page.

• Previous Page.

 Two buttons: the pages change by pressing in the central area between
the buttons. In particular, pressing on the top central area will switch the
pages in one direction while pressing on the bottom area will do it in the
opposite direction. The parameter Action sets the navigation direction:

• Upper = Previous Page; Lower = Next Page

• Upper = Next Page; Lower = Previous Page..

http://www.zennio.com Technical Support: http://support.zennio.com


25
TMD-Display View

2.4 PAGE n
When any of the general-purpose pages is enabled from the Configuration screen
under the Menu tab, a new tab named Page n will appear, where n is the number of
the page.

Under this tab, one screen (Configuration) will be initially displayed to let the
integrator enable or disable any of the boxes in the page. Depending on that, more
parameter screens will appear.

Note: figures in this section will show the parameters of a certain page (for instance,
page 1). The parameters for other pages are totally analogous.

2.4.1 CONFIGURATION

TMD-Display View features eight capacitive buttons at the user’s disposal for the
execution of actions. Each can be configured to perform a different function per page.

Central touch area

Display

Pair A

Pair B
Buttons
Pair C
Pair D

1
2
Figure 16 Touch panel

As Figure 15Figure 16 shows, three areas can be distinguished in the front panel:

The buttons, grouped in pairs.

The display, at the top of the front panel.

The central touch area, between the two button columns.

http://www.zennio.com Technical Support: http://support.zennio.com


26
TMD-Display View

All the buttons are identical; this brings a high level of versatility for a wide variety of
applications. The following is a list of the functions that can be assigned to each pair of
buttons.

Disabled (none of the two buttons will react to user presses).

Pair Buttons (the two buttons will work jointly):

 Switch.
 Switch + Indicator.
 Two Objects (Short Press / Long Press).
 Counter.
 Scaling.
 Float.
 Enumeration.
 Shutter.
 Light dimmer.
 [Climate] Temperature setpoint.
 [Climate] Mode.
 [Climate] Fan.
 Multimedia
 Indicator

Individual Buttons (each button in the pair will work independently):

 Switch.
 Two Objects (short press / long press).
 Hold & Release.
 Scene.
 Counter constant.
 Scaling constant.
 Float constant.
 Enumeration.
 Dimmer.
 Shutter.
 Timer.
 LED indicator.

http://www.zennio.com Technical Support: http://support.zennio.com


27
TMD-Display View

Apart from the button function itself, the integrator can select the desired behaviour of
the button LEDs. The different illumination modes have been detailed in ANNEX I:
LED Illumination Modes.

The following sections will detail the involved configuration.

ETS PARAMETERISATION

Figure 17 Page n – Configuration.

As stated in section 2.1, an independent tab for the parameterisation of the buttons is
shown in ETS by default, initially containing only a sub-tab named Configuration.

One drop-down list with the following options is shown per pair of buttons:

Disabled. See section 0.

Pair. Selecting this option brings a new tab to the tree on the left (named
“Pair X”, where X depends on the button pair). See section 2.4.3.

Individual. Selecting this brings the checkboxes “Button X1” and “Button X2”
(where X depends on the button pair), which allow making each of the two
buttons functional or not. Depending on this, up to two new tabs (named
“Button Xn”) will be included in the tree on the left. See section 2.4.4.

Note: if a button pair is set to “Individual” but the “Button Xn” checkbox is left
unmarked, that button will behave as if the pair had been set to “Disabled”.

http://www.zennio.com Technical Support: http://support.zennio.com


28
TMD-Display View

2.4.2 DISABLED

While a button pair stays disabled, none of the two buttons will be functional: touching
them will not cause the execution of actions, nor will make the associated LED light.

ETS PARAMETERISATION

This function has no related parameters.

2.4.3 PAIR

Pair buttons configured to work jointly can be assigned the following control functions:

Switch: pressing one of the two buttons will make TMD-Display View send a
binary value to the bus, while pressing on the other will make it send the
inverse binary value. It is possible to configure which one does what.

Under a “state-dependent” LED illumination (see ANNEX I: LED Illumination


Modes), the LED of the corresponding button will remain on/off according to
the current state (on/off) of the switch. On the other hand, under a “state-
dependent (both LEDs)” LED illumination, both of them will remain on while
the switch is in the “on” state, and off while in the “off” state.

Switch + Indicator: the functionality of the buttons is analogous to that of the


the switch function although it is also possible to define a numerical indicator
(with a configurable type and size), whose value is shown on the display, in
parentheses, next to the name configured for the button pair.

Two Objects (Short Press / Long Press): permits sending specific binary
values both after a short or a long press on any of the two buttons (i.e., they
will work as a joint control; for independent buttons, please configure them as
individual). Different objects will be used for the short and long presses.

Moreover, it is possible (in parameters) to make the “state-dependent” and


“state-dependent (both LEDs)” LED illumination modes (see ANNEX I: LED
Illumination Modes) depend on either one object or the other. However, if
“LED Illumination Control (All Buttons)” (section 2.3.1) has been set to
“state-dependent (where available)” only the short press object will be
considered

http://www.zennio.com Technical Support: http://support.zennio.com


29
TMD-Display View

Scaling, Counter and Float: user touches over the buttons will trigger the
sending of a certain numerical value to the bus (this value will be
progressively increased or decreased every time the user touches one button
or the other) through the control object.

The display continuously shows the current numeric value. Moreover, it will
reflect the new values as the user interacts with the control, however values
are actually sent to the bus 1.5 seconds after the last press.

The “state-dependent” and “state-dependent (both LEDs)” LED


illumination modes are not available for this function (only the “regular” and
“dedicated object” LED illumination are available). See ANNEX I: LED
Illumination Modes for details.

Enumeration: pressing the buttons will make TMD-Display View send a one-
byte (unsigned) value to the bus. It is possible to distinguish up to 6 different
values. Successively pressing on the buttons will make TMD-Display View
walk through the different values, displaying on the screen the text associated
to each value.

As the above functions, this type of control provides parameter to link the
control with a box in the display in order to show the current value on the
display. Again, values are sent to the bus 1.5 seconds after the last press.

The “state-dependent” and “state-dependent (both LEDs)” LED


illumination modes are not available for this function (only the “regular” and
“dedicated object” LED illumination are available). See ANNEX I: LED
Illumination Modes for details.

Shutter: this option permits making use of the two buttons to control a shutter
actuator connected to the bus. Two alternative control methods are possible:

 Standard: a long press will make the device send to the KNX bus an order
to start moving the shutter (upwards or downwards, depending on the
button), while a short press will make it send a stop order (which will be
interpreted as an order to step up or to step down –depending on the
button– if the shutter was not in motion and such function is available).

 Hold & Release: as soon as the button is held, the device will send the
KNX bus an order to start moving the shutter (upwards or downwards,

http://www.zennio.com Technical Support: http://support.zennio.com


30
TMD-Display View

depending on the button). Once the button is released, it will send an order
to stop the shutter.

The “state-dependent” and “state-dependent (both LEDs)” LED


illumination modes are not available for this function (only the “regular” and
“dedicated object” LED illumination are available). See ANNEX I: LED
Illumination Modes for details.

Dimmer: short-pressing one of the two buttons will make TMD-Display View
send a switch-on order to the bus, while doing so on the other button will
make it send a switch-off order.

Long presses will make it send a step dimming order (the value of which is
configurable) to make a dimmer increase or decrease the light level (and a
stop order as soon as the user releases the push button). It is possible to
configure which button does what.

Under a “state-dependent” LED illumination (see ANNEX I: LED Illumination


Modes), the LED of the corresponding button will remain on/off according to
whether the current value of the light level status object (which should be
updated by the actual dimmer) is greater than 0% or not. On the other hand,
under a “state-dependent (both LEDs)” LED illumination, both LEDs
together will remain on or off depending on such value.

[Climate] Temperature setpoint: permits controlling the temperature


setpoint of an external thermostat by means of a button pair and the display.

This function can also be linked to a box in the display in order to show the
current setpoint value. The box will reflect the value (in ºC) of the status
object, which gets automatically updated after sending control orders (that is,
after pressing the buttons), being even possible to receive values from the
bus, for example, from the corresponding setpoint status object from the
external thermostat.

The “state-dependent” and “state-dependent (both LEDs)” LED


illumination modes are not available for this function (only the “regular” and
“dedicated object” LED illumination are available). See ANNEX I: LED
Illumination Modes for details.

http://www.zennio.com Technical Support: http://support.zennio.com


31
TMD-Display View

[Climate] Mode: pressing one of the two buttons will make TMD-Display
View send climate mode values to the bus. Two mode control types are
possible: Heat / Cool and Extended (HVAC).

As in previous functions, the current mode is shown in the display.

The “state-dependent” and “state-dependent (both LEDs)” LED


illumination modes are not available for the Extended mode (only the
“regular” and “dedicated object” LED illumination are available). For the
Heat / Cool mode all the illumination options are available. See ANNEX I:
LED Illumination Modes for details.

[Climate] Fan: pressing one of the two buttons will make TMD-Display View
send a binary value to the bus that allows changing the fan speed (up to five
levels available). This value can be either binary (increase / decrease
orders), scaling (0% - 100%) or enumerated.

Furthermore, it is possible to configure the speed 0 as an additional fan level,


and/or another level to activate the Auto mode.

The order to activate the auto mode can be sent over a one-bit object,
independent from the fan control object, or alternatively consist in the speed
level 0. In the latter case, level 0 will imply triggering the Auto mode.

The three available control types are:

 “1 bit (decrease/increase)”: one-bit values (increase or decrease) will be


sent according to the action configured for each button.

In this case, switching from the current fan level to a non-consecutive level
involves going through each of the intermediate levels.

 “Scaling”: button presses will make the device send percentage values
through the corresponding one-byte object.

Every press will activate the subsequent (or preceding) fan level,
depending on the current one. Therefore, the percentage values sent will
depend on the number of the available levels and on whether the Auto
mode and the speed level 0 are available or not.

http://www.zennio.com Technical Support: http://support.zennio.com


32
TMD-Display View

 “Enumeration”: this control is similar to the one above, although integer


values are sent instead of scaling values.

Table 1 shows the relation between the scaling values and the
enumeration values, depending on the number of speed levels configured
(note that if the Auto mode or the speed level 0 are allowed one more level
is added, corresponding to value 0).

% Values based on fan levels


Speed Levels 1 2 3 4 5
1 100 50,2 33,3 25,1 20
Enumeration value

2 - 100 66,7 50,2 40


3 - - 100 75,3 60
4 - - - 100 80
5 - - - - 100
Table 1 Fan levels.

For the scaling and enumeration controls, the object is sent to the bus
slightly delayed, once the desired value has been set by the user. The
current value is continuously shown on the display.

Under a “state-dependent” LED illumination, the LED of the


corresponding button will remain on/off according to the current state of
the fan. On the other hand, under a “state-dependent (both LEDs)” LED
illumination, both of them will remain on or off while the fan level is greater
than 0 or not, respectively. The “regular” and “dedicated object” LED
illumination modes are also available. See ANNEX I: LED Illumination
Modes for details.

Multimedia: tapping on one of the two buttons will make TMD-Display View
send a binary value to the bus, while pressing on the other will make it send
the inverse binary value. It is possible to configure which one does what.
Also, this control has a 14-byte object associated, whose value is displayed
on the screen between the icons of the buttons.

Note: after a failure of the KNX bus, any value that may have been received
through the 14-byte object will be lost.

http://www.zennio.com Technical Support: http://support.zennio.com


33
TMD-Display View

Indicator: in this case, the two push buttons are functionless, although the
display will show the value of an indicator (with a configurable type and size)
on the right size.

ETS PARAMETERISATION

When a button pair has been configured to work as a joint control, a specific tab (“Pair
X”) becomes available under “Buttons” in the tree on the left.

Figure 18 Buttons - Pair A.

Parameters common to all types of controls are:

Function: sets the desired function for the button pair: “Switch”, “Switch +
Indicator”, “Two objects (short press / long press)”, “Counter”, “Scaling”,
“Float”, “Enumeration”, “Shutter”, “Dimmer”, “[Climate] Temperature Setpoint”,
“[Climate] Mode” or “[Climate] Fan”, “Multimedia” or “Indicator”.

Label: textbox to enter a string (up to 10 characters) which is displayed on


the screen between the icons of the buttons, in order to identify the control.

Icon: allows selecting the icon that is drawn on each button on the display.
Please refer to ANNEX II. Button Icons for a list of available icons.

Depending on the function, some more parameters are shown, as described next.
Please note that in the next pages the general notation “[Pn] [X]” is used for the name
of the communication objects, as “X” depends on the button pair (A, B, etc.). On the
other hand, “Pn” will refer to the page number.

http://www.zennio.com Technical Support: http://support.zennio.com


34
TMD-Display View

Switch

Figure 19 Pair Buttons – Switch.

Action: assigns each of the two buttons the value to be sent through “[Pn]
[X] Switch” (which has the Write flag enabled, so the state of the switch can
be updated from external devices). The options are “Left=0; Right=1” and
“Left=1; Right=0”.

Note: this parameter will remain hidden unless having selected “Every button
pair is configured separately” in Action of the pair buttons (see section
2.3.1).

Text for ‘0’ and Text for ‘1’: sets the text to be displayed between the icons
of the buttons when the values ‘0’ and ‘1’ are sent, respectively.

LED illumination control: sets the behaviour of the LEDs on the buttons.
The options are “Regular”, “State-dependent”, “State-dependent (both LEDs)”
and “Dedicated Object”.

In case of selecting the latter, the object “[Pn] [X] Led On/Off” will be
included in the project topology and a new parameter to select the value to
switch off and on the LED shows up:

http://www.zennio.com Technical Support: http://support.zennio.com


35
TMD-Display View

Figure 20 LED illumination control - Dedicated object.

Switch + Indicator

Figure 21 Pair buttons – Switch + Indicator.

Action: assigns each of the two buttons the value to be sent through “[Pn]
[X] Switch” (which has the Write flag enabled, so the state of the switch can
be updated from external devices). The options are “Left=0; Right=1” and
“Left=1; Right=0”.

Note: this parameter will remain hidden unless having selected “Every button
pair is configured separately” in Action of the pair buttons (see section
2.3.1).

Indicator Type: sets the type and size of the object that receives the value of
the indicator to be shown on the display. The options are:

 “Counter”: the value is received through the communication object “[Pn]


[X] 1-byte / 2-byte / 4-byte Signed / Unsigned Int Indicator”. After
selecting Counter, the following parameters appear:

• Size: sets the size of the object, “1 byte”, “2 bytes” or “4 bytes Signed
Int”

http://www.zennio.com Technical Support: http://support.zennio.com


36
TMD-Display View

• Signed: checkbox to set if the values will be signed or unsigned.

• Units: text that will be displayed next to the indicator to identify the units
of the value. Up to 4 characters are available.

 “Scaling”: the value is received through the communication object “[Pn] [X]
1-byte Indicator (Scaling)”

 “Temperature”: the value is received through the communication object


“[Pn] [X] Temperature Indicator”.

LED illumination control: sets the behaviour of the LEDs on the buttons. The
options are “Regular”, “State-dependent”, “State-dependent (both LEDs)” and
“Dedicated Object”.

Two Objects (short Press / long press)

Figure 22 Pair Buttons - Two Objects (Short Press / Long Press).

Action on short press: sets the value that will be sent through “[Pn] [X] Two
switches - Short press” after the user short-presses one of the two buttons.

 “Left=0; Right=1”.

 “Left=1; Right=0”.

http://www.zennio.com Technical Support: http://support.zennio.com


37
TMD-Display View

Note: this parameter will remain hidden unless having selected “Every button
pair is configured separately” in Action of the pair buttons (see section
2.3.1).

Text for ‘0’ and Text for ‘1’: sets the text to be displayed between the icons
of the buttons when the values ‘0’ and ‘1’ are sent (respectively) after short-
pressing them.

Action on long press: sets the value that will be sent through “[Pn] [X] Two
switches: Long press” after the user long-presses one of the two buttons.

 “Left=0; Right=1”.

 “Left=1; Right=0”.

Note: this parameter will remain hidden unless having selected “Every button
pair is configured separately” in Action of the pair buttons (see section
2.3.1).

Long press threshold time: sets the minimum time the user should hold the
button in order to consider it a long press. The available range is 5 to 50
tenths of a second, being 6 tenths the default value.

LED illumination control: analogous to the homonymous parameter for the


Switch function (see above). In this case, however, selecting “State-
dependent” or “State-dependent (both LEDs)” brings an additional parameter,
“State Object”, to make the state of the LEDs correspond either to object
“[Pn] [X] Two switches: Short press” (“Short Press Object”) or to object
“[Pn] [X] Two switches: Long press” (“Long Press Object”).

Figure 23 Pair Buttons - Two objects (short press / long press) - LED illumination control.

http://www.zennio.com Technical Support: http://support.zennio.com


38
TMD-Display View

Counter

Figure 24 Pair Buttons – Counter.

Action: assigns each of the two buttons the order to be sent:

 “Left=Decrease; Right=Increase”.

 “Left=Increase; Right=Decrease”.

Note: this parameter will remain hidden unless having selected “Every button
pair is configured separately” in Action of the pair buttons (see section
2.3.1).

Size: sets the desired size of the object, “1 byte” or “2 bytes”.

Signed: checkbox to set whether the object will be signed or unsigned.

The value ranges depend on the above two parameters:

 1 byte unsigned: 0 – 255.

 1 byte signed: -128 – 127.

 2 bytes unsigned: 0 – 65535.

 2 bytes signed: -32768 – 32767.

http://www.zennio.com Technical Support: http://support.zennio.com


39
TMD-Display View

Minimum Value: sets which value from the available range will be the
minimum value permitted by the control.

Maximum Value: sets which value from the available range will be the
maximum value permitted by the control.

Increment on Short Press: sets the increase or decrease to be applied to


the current value on every short press over the increase or decrease buttons,
respectively (i.e., the smaller the increment, the more presses will be
required).

Increment on Long Press: sets the increase or decrease to be applied to


the current value on every long press over the increase or decrease buttons,
respectively (i.e., the smaller the increment, the more presses will be
required).

LED illumination control: analogous to the homonymous parameter for the


previous functions (see above). In this case, the only options are “Regular”
and “Dedicated Object”.

The counter values will be sent to the bus through the objects “[Pn] [X] [size]
Unsigned Int Value” or “[Pn] [X] [size] Signed Int Value”.

Scaling

Figure 25 Pair Buttons – Scaling.

http://www.zennio.com Technical Support: http://support.zennio.com


40
TMD-Display View

Action: assigns each of the two buttons the order to be sent:

 “Left=Decrease; Right=Increase”.

 “Left=Increase; Right=Decrease”.

Note: this parameter will remain hidden unless having selected “Every button
pair is configured separately” in Action of the pair buttons (see section
2.3.1).

Minimum Value: sets which value from the available range will be the
minimum value permitted by the control. The available range is 0-100.

Maximum Value: sets which value from the available range will be the
maximum value permitted by the control after. The available range is 0-100.

Increment on Short Press: sets the increase or decrease to be applied to


the current value on every short press over the increase or decrease buttons,
respectively (i.e., the smaller the increment, the more presses will be
required). The available range is 0-100.

Increment on Long Press: sets the increase or decrease to be applied to


the current value on every long press over the increase or decrease buttons,
respectively (i.e., the smaller the increment, the more presses will be
required). The available range is 0-100.

LED illumination control: analogous to the homonymous parameter for the


previous functions (see above). In this case, the only options are “Regular”
and “Dedicated Object”.

The percentage values will be sent to the bus through “[Pn] [X] 1-byte Scaling Value”.

Float

Action: assigns each of the two buttons the order to be sent:

 “Left=Decrease; Right=Increase”.

 “Left=Increase; Right=Decrease”.

Note: this parameter will remain hidden unless having selected “Every button
pair is configured separately” in Action of the pair buttons (see section
2.3.1).

http://www.zennio.com Technical Support: http://support.zennio.com


41
TMD-Display View

Figure 26 Pair Buttons – Float.

Minimum Value: sets which value from the available range (-671088.625 to
670760.9375) will be the minimum value permitted by the control.

Maximum Value: sets which value from the available range (-671088.625 to
670760.9375) will be the maximum value permitted by the control.

Increment on Short Press: sets the increase or decrease to be applied to


the current value on every short press over the increase or decrease buttons,
respectively (i.e., the smaller the increment, the more presses will be
required). The available range is 0.1 – 670760.93750 (0.5 by default).

Increment on Long Press: sets the increase or decrease to be applied to


the current value on every long press over the increase or decrease buttons,
respectively (i.e., the smaller the increment, the more presses will be
required). The available range is 0.1 – 670760.93750 (1 by default).

LED illumination control: analogous to the homonymous parameter for the


previous functions (see above). In this case, the only options are “Regular”
and “Dedicated Object”.

The values will be sent to the bus through object “[Pn] [X] 2-byte Float Value”.

http://www.zennio.com Technical Support: http://support.zennio.com


42
TMD-Display View

Enumeration

Figure 27 Pair Buttons – Enumeration.

# Enums: number of states (up to 6) that will be distinguished. For every


distinguished state, one parameter named Value j will become available, in
order to set the value sent through the communication object.

Value j: numerical value (0 – 255) that will be sent through the control object
when the user, after pressing the buttons, sets the control to state j. The
actual sending will not be performed until 1.5 seconds after the last press.

Text j: text to be displayed between the icons of the buttons, to indicate the
current enumeration value.

LED illumination control: analogous to the homonymous parameter for the


previous functions (see above). In this case, the only options are “Regular”
and “Dedicated Object”.

The values will be sent to the bus through object “[Pn] [X] Enumeration”.

Shutter

The move orders will be sent through “[Pn] [X] Move Shutter”, while the stop orders
will be sent through “[Pn] [X] Stop Shutter/Step” (for Standard type) or “[Pn] [X] Stop
Shutter” (for Hold & Release type).

The parameters for this function are:

http://www.zennio.com Technical Support: http://support.zennio.com


43
TMD-Display View

Figure 28 Pair Buttons – Shutter.

Action: assigns each of the two buttons the order to be sent:

 “Left=Down; Right=Up”.

 “Left=Up; Right=Down”.

Note: this parameter will remain hidden unless having selected “Every button
pair is configured separately” in Action of the pair buttons (see section
2.3.1).

Type: sets the desired behaviour of the buttons, “Standard” or “Hold &
Release” (the differences between them have been explained in previous
pages).

LED illumination control: analogous to the homonymous parameter for the


previous functions (see above). In this case, the only options are “Regular”
and “Dedicated Object”.

Dimmer

Figure 29 Pair Buttons – Dimmer.

http://www.zennio.com Technical Support: http://support.zennio.com


44
TMD-Display View

The switch orders will be sent through the “[Pn] [X] Light On/Off” one-bit object, while
the increase/decrease orders will be through the “[Pn] [PX] Light Dimming” four-bit
object.

On the other hand, the “[Pn] [X] Light Indicator” one-byte object may be linked to the
light level status object of the dimmer (in fact, this object is only intended to receive
values from the bus, not to send them). As explained in 2.4.3, the state-dependent LED
lighting will be determined by the value of this object (LED off at 0% and on at any
other level).

The parameters for this function are:

Action: assigns each of the two buttons the order to be sent:

 “Left=Off; Right=On”.

 “Left=On; Right=Off”.

Note: this parameter will remain hidden unless having selected “Every button
pair is configured separately” in Action of the pair buttons (see section
2.3.1).

Step: defines the dimming step (“100%”, “50%”, “25%”, “12.5%”, “6.25%”,
“3.1%” or “1.5%”) to be sent to the light dimmer with every increase /
decrease order.

Note: since dimmers typically do not apply the new light level immediately
(i.e., the step regulation is performed progressively) and since TMD-Display
View sends an order to interrupt the step dimming once the user releases the
button, it is advisable to configure a step of 100%. This way, the user can
perform any dimming step by simply leaving the button pressed and then
releasing it without needing to make successive button presses.

LED illumination control: analogous to the homonymous parameter for the


“Switch” and “Two Objects (short press / long press)” function (see above).

http://www.zennio.com Technical Support: http://support.zennio.com


45
TMD-Display View

[Climate] Temperature Setpoint

Figure 30 Pair Buttons – [Climate] Temperature Setpoint.

Action: assigns each of the two buttons the order to be sent:

 “Left=Decrease; Right=Increase”.

 “Left=Increase; Right=Decrease”.

Note: this parameter will remain hidden unless having selected “Every button
pair is configured separately” in Action of the pair buttons (see section
2.3.1).

Minimum Value: sets which value from the available range (-273 to
670760.9375; 10 by default) will be the minimum value permitted by the
control.

Maximum Value: sets which value from the available range (-273 to
670760.9375; 30 by default) will be the maximum value permitted by the
control after.

LED illumination control: analogous to the homonymous parameter for the


previous functions (see above). In this case, the only options are “Regular”
and “Dedicated Object”.

The values are sent to the bus through “[Pn] [X] (Climate) Temperature setpoint”.

http://www.zennio.com Technical Support: http://support.zennio.com


46
TMD-Display View

[Climate] Mode

Figure 31 Pair Buttons – [Climate] Mode.

Mode Type: sets mode control type: “Heat/Cool” or “Extended” (HVAC).

 “Heat/Cool”: pressing one of the two buttons will make TMD-Display View
send a one-bit value to the bus (Left=Cool, value “0”; Right=Heat, value
“1”).

 “Extended”: pressing on the two buttons will make TMD-Display View walk
through the different HVAC modes and send a one-byte value to the bus
according to the selected mode. Which of the modes should be available
can be set through five specific checkboxes.

Figure 32 Pair Buttons – [Climate] Mode – Mode Type: Extended.

http://www.zennio.com Technical Support: http://support.zennio.com


47
TMD-Display View

Text for ‘[mode]’: text displayed between the icons of the buttons to indicate
the current mode.

LED illumination control: sets the behaviour of the LEDs on the buttons.
The options are “Regular”, “State-dependent”, “State-dependent (both LEDs)”
and “Dedicated Object”.

The values will be sent to the bus through objects “[Pn] [X] (Climate) Mode” or “[Pn]
[X] (Climate) Mode - Extended”.

[Climate] Fan

Figure 33 Pair Buttons – [Climate] Fan.

Action: assigns each of the two buttons the order to be sent:

 “Left = Decrease; Right = Increase”.

 “Left = Increase; Right = Decrease”.

Note: this parameter will remain hidden unless having selected “Every button
pair is configured separately” in Action of the pair buttons (see section
2.3.1).

Control Type: sets the type of the communication objects that will control the
fan level.

http://www.zennio.com Technical Support: http://support.zennio.com


48
TMD-Display View

 “1 bit (decrease/increase)”: orders of speed increase/decrease are sent


through the one-bit object “[Pn] [X] Fan control (Type: 1 bit)”.

 “Scaling”: scaling values are sent through the one-byte object “[Pn] [X]
Fan control (Type: scaling)”.

 “Enumeration”: integer values are sent through the one-byte object “[Pn]
[X] Fan control (Type: Enumeration)”. When selecting this type of
control the following parameter appears:

• Text Before Each Level: text displayed, between the icons of the
buttons, preceding the selected level.

For either type of control an indicator object is added to show its value on the
display: “[Pn] [X] Fan Indicator”.

Speed levels: sets how many speed levels will be available in the control. 1
to 5 levels.

Cyclical: sets whether scrolling through the speed levels is circular or not. If
checked, an increase order in the maximum level switches to the minimum
and vice versa (in the minimum level a decrease order switches to the
maximum).

Auto Mode: sets whether the fan Auto mode will be available or not. If
checked, the following parameters are also shown.

 Text for ‘Auto’: text displayed between the icons of the buttons to indicate
that the ‘Auto’ mode has been selected.

 Dedicated Object for Auto Mode: sets how the Auto mode should be
activated. In the absence of a dedicated object, the Auto fan mode will be
activated by switching to fan level 0.

Figure 34 Pair Buttons – [Climate] Fan – Auto Mode.

http://www.zennio.com Technical Support: http://support.zennio.com


49
TMD-Display View

In this case the fan levels activated by short presses are:

Auto Mode ( 0 ) Minimum Medium Maximum

On the other hand, marking the checkbox enables the one-bit object “[Pn]
[X] Fan control – Auto mode”, which will trigger the Auto mode when it
receives the value “1” (or “0”, depending on the subsequent parameter,
“Value to Set the Auto Mode”).

Figure 35 Pair Buttons – [Climate] Fan – Dedicated Object for Auto Mode.

However, two alternative (and mutually exclusive) methods are possible to


activate this mode:

o By short press: the Auto mode can be reached as a further level above
the maximum one. In this case the fan levels activated by short presses
are (note that speed 0 is optional):

(0) Minimum Medium Maximum Auto Mode

o By long press on any of the buttons of the control (requires checking


Long Press to Activate Auto Mode).

A further long press deactivates back the Auto mode and resumes the
previous fan level. Instead, a short press deactivates the Auto mode
and switches to the next level (or previous, depending on the button). In
this case the fan levels reachable through short presses are (speed 0
is optional):

(0) Minimum Medium Maximum

(Here, the Auto mode is only activated by long press).

http://www.zennio.com Technical Support: http://support.zennio.com


50
TMD-Display View

Allow speed 0: sets whether the speed level 0 will be present or not. When
the Auto Mode without a dedicated object has been configured, this option
will be necessarily activated.

LED illumination control: analogous to the homonymous parameter for the


previous functions (see above). The options are “Regular”, “State-
dependent”, “State-dependent (both LEDs)” and “Dedicated Object”.

Multimedia

Figure 36 Pair Buttons – Multimedia.

Action: assigns each of the two buttons the order to be sent:

 “Left = Stop/Backward; Right = Start/Forward”.

 “Left = Start/Forward; Right = Stop/Backward”.

Note: this parameter will remain hidden unless having selected “Every button
pair is configured separately” in Action of the pair buttons (see section
2.3.1).

The orders will be sent to the bus through the object “[Pn] [X] 1-bit Multimedia
Control”, while the indicator values should be received through the object “[Pn] [X]
Multimedia Text Indicator”.

http://www.zennio.com Technical Support: http://support.zennio.com


51
TMD-Display View

Indicator

Figure 37 Pair Buttons – Indicator

Indicator Type: sets the type and size of the object that receives the value of
the indicator to be shown on the display. The options are:

 “Binary”: the value is received through the object “[Pn] [X] Binary
Indicator”. When selecting Counter, the following parameter appears:

• Text for ‘0’ and Text for ‘1’: set the text displayed, between the icons
of the buttons, after receiving the value ‘0’ or the value ‘1’, respectively.

 “Counter”: the value is received through the communication object “[Pn]


[X] 1-byte/2-byte/4-byte Signed/Unsigned Int Indicator”. When
selecting Counter, the following parameters appear:

• Size: sets the desired size of the object, “1 byte”, “2 bytes” or “4 bytes
Signed Int”

• Signed: checkbox to set if the allowed values are signed or unsigned.

• Units: text that will be displayed next to the indicator to identify the units
of the value. Up to 4 characters are available.

 “Scaling”: the value is received through the “[Pn] [X] 1-byte Indicator
(Scaling)” communication object.

 “Enumeration”: the value is received through the “[Pn] [X] Enumerated


Indicator” communication object. When selecting the type Enumeration,
the following parameters appear:

• Value j: numeric value (0 – 255) that corresponds to element j.

http://www.zennio.com Technical Support: http://support.zennio.com


52
TMD-Display View

• Text j: text to be displayed between the icons of the buttons to indicate


that element j is currently selected.

 “Float”: the value is received through the “[Pn] [X] 2-byte Float Indicator”
object. When selecting the type Float, the following parameter appears:

• Units: text that will be displayed next to the indicator to identify the units
of the value. Up to 4 characters are available.

2.4.4 INDIVIDUAL

Buttons configured to work as individual (separate) controls can be assigned any of the
following control functions from the corresponding Button Xn tab:

Switch: whenever the user touches the button, a binary value will be sent to
the KNX bus. This value is configurable and may be 0 or 1, or alternate with
every touch according to the sequence 1  0  1  …

Under a “state-dependent” LED illumination, the LED will remain on/off


according to the current state (on/off) of the object.

Two Objects (Short Press / Long Press): specific binary values will be sent
both after a short or a long press (a different object will be used in each
case). Under a “state-dependent” LED illumination, the LED will remain
on/off according to the current state (on/off) of either one object or the other,
which can be configured in parameters. However, if “LED Illumination
Control (All Buttons)” (see section 2.3.1) has been set to “state-dependent
(where available)”, only the short press object will apply.

Hold & Release: as soon as the user touches the button, a binary value (“0”
or “1”, configurable) will be sent to the KNX bus. And as long as the user
releases the button, another value (“0” or “1”, also configurable) will be sent
through the same object.

The “state-dependent” LED illumination mode is not available for this


function.

Scene: after the user touches the button, an order to run a specific scene
(configurable) will be sent to the bus. If enabled in parameters, orders to save

http://www.zennio.com Technical Support: http://support.zennio.com


53
TMD-Display View

the scene can also be sent to the bus after a three-second press on the
button. The “state-dependent” LED mode is not available for this function.

Counter Constant: sends an integer value (configurable) to the bus when


the user touches the button. This value can be one-byte or two-byte sized, as
well as signed or unsigned. The available ranges are shown next.

1-byte 2-byte

Unsigned 0 – 255. 0 – 65535

Signed -128 – 127. -32768 – 32768.

Table 2 Counter Constant values

The “state-dependent” LED illumination mode is analogous as for the


Scaling Constant function.

Scaling Constant: sends a percentage value (configurable) to the bus when


the user touches the button. Under a “state-dependent” LED illumination, the
LED will remain on/off depending on whether the current value of the object
matches the one parameterised. This object can also be written from the bus,
which will update the LED according to the new value.

Float Constant: sends a two-byte floating point value (configurable) to the


bus when the user touches the button. The available range is -671088.625 to
670760.9375.

The “state-dependent” LED illumination mode is analogous as for the


Scaling Constant and Counter Constant functions.

Enumeration: implements a one-button enumeration control that sends one-


byte (unsigned) values to the KNX bus. This control is completely analogous
to the Enumeration control in pair buttons (see section 2.4.3), however the
object is sent to the bus when the button is pressed (not 1.5 seconds later).
Moreover, in this case there is no option to link it to the display.

The “state-dependent” LED mode is not available for this function.

Dimmer: implements a one-button light control that sends orders to the KNX
bus, which can then be executed by light dimmers. These orders consist in:

http://www.zennio.com Technical Support: http://support.zennio.com


54
TMD-Display View

 Switch-on / Switch-off orders (on short presses).

 Step dimming orders (on long presses) and the subsequent stop order
once the button is released.

Being a one-button control, the switch orders will alternate (on / off) for
every short press, and so will do the step dimming orders (increase /
decrease) for every long press. However, there are some exceptions to this
alternation:

 On a long press: an increase dimming order will be sent if the light is found
to be off (according to the status object). On the other hand, a decrease
order will be sent if it is found to be 100%.

 On a short press: a switch-on order will be sent if the light is found to be off
(according to the status object). On the other hand, a switch-off order will
be sent if it is found to be on (value greater than 0%).

Note that the device considers that the current light level is the value of a
specific one-byte object provided to be written from the KNX bus (i.e., to
receive feedback from the dimmer). This object is internally updated after a
short or long press, but linking it to the real dimmer status is highly advisable.

Under a “state-dependent” LED illumination, the LED will remain on/off


according to the value of the aforementioned status object (i.e., off when the
value is 0% and on in any other case).

Note: after a bus recovery, the light dimmer should send back the status
object so the control and the LED update their own state, instead of simply
recovering the previous one.

Shutter: implements a one-button shutter control that sends orders to the


KNX bus, which can then be executed by an actuator.

Two control types can be configured:

 Standard: the device will react to both long and short presses, being
possible to send the bus the following commands:

• Move (raise / lower) orders (on long presses).

http://www.zennio.com Technical Support: http://support.zennio.com


55
TMD-Display View

• Stop / Step orders (on short presses).

Being a one-button control, the direction of the motion will alternate


(upwards / downwards) for both the move and the step orders after every
long press. However, there are some exceptions to this alternation:

• On a short press: a step-up order will be sent if the last long press
made the shutter move up, or if the current position is found to be
100%. On the other hand, a step-down order will be sent if the last
long press made the shutter move down or if the current position is
found to be 0%.

• On a long press: a move-up order will be sent if the last short press
caused a step-down order or if the current position is found to be
100%. On the other hand, a move-down order will be sent if the last
short press caused a step-up order or if the current position is found
to be 0%.

As usual in the KNX standard, stop/step orders are interpreted by the


actuators as a request to move the slats one step up or down (in case the
shutter is still) or as a request to interrupt the motion of the shutter (in case
it is already moving up or down).

TMD-Display View is aware of the current position of the shutter through


a specific object which should be linked to the analogous object of the
shutter actuator in order to receive feedback.

 Hold & Release: the device will send an order to move the shutter as soon
as the button is touched, and the order to stop it as soon as it is released.
Hence, short or long touches have the same effect: the shutter will remain
in motion as long as the user keeps holding the button.

The direction of this motion (upwards or downwards) will alternate with


every touch, according to the following sequence: downwards  upwards
 downwards  …

However, there are some exceptions to this alternation:

• If the position of the shutter is found to be 0%, the next order will
lower the shutter.

http://www.zennio.com Technical Support: http://support.zennio.com


56
TMD-Display View

• If the position of the shutter is found to be 100%, the next order will
raise the shutter.

TMD-Display View is aware of the current position of the shutter through


a specific object which should be linked to the analogous object of the
shutter actuator, in order to receive feedback. This object is initialised with
value “50%” after a download or a bus failure; therefore, the actuator is
required to update it with the real value after the bus recovery.

The “state-dependent” LED illumination mode is not available for this


function.

Timer: this function allows sending a binary value ("1" or "0") or a scene
command to the KNX bus at a certain time, either as a single sending (one-
time execution), as a periodic sending or after a countdown time.

LED indicator: user presses will not trigger any function although the LED
will turn on or off depending on the values received from the bus.

ETS PARAMETERISATION

When an individual button has been enabled, a specific tab (“Button Xn”) becomes
available under “Buttons” in the tree on the left.

Figure 38 Individual Button.

Parameters common to all types of controls are:

Function: sets the desired function for the button: “Switch”, “Two Objects
(short press / long press)”, “Hold & Release”, “Scene”, “Counter constant”,

http://www.zennio.com Technical Support: http://support.zennio.com


57
TMD-Display View

“Scaling constant”, “Float constant”, “Enumeration”, “Dimmer”, “Shutter”,


“Timer” or “LED Indicator”.

Label: text (up to 10 characters) to be displayed to identify the control.

Icon: icon to be displayed over each button in the display. For a list of the
available icons, please refer to ANNEX II. Button Icons.

Depending on the function, some more parameters are involved (as described next).
Please note that in the next pages “[Pn] [Xj]” is used as a general notation for the
communication objects, where “Xj” depends on the button (A1, A2, B1, etc.) and “Pn”
depends on the page number.

Switch

Figure 39 Individual Button - Switch.

Action: sets the value to be sent to the bus (through object “[Pn] [Xj]
Switch“) when the user touches the button. The options are “Send 0”, “Send
1” and “Toggle 0/1”.

Text for ‘0’ and Text for ‘1’: sets the text to be displayed between the icons
of the buttons when the values ‘0’ and ‘1’ are sent, respectively.

LED illumination control: sets the behaviour of the LEDs on the buttons.
The options are “Regular”, “State-dependent” and “Dedicated Object”.

In case of selecting the latter, the object “[Pn] [Xj] LED On/Off” will be
included in the project topology (the desired values to turn on or turn off the
LED are set by the parameter Object Value).

http://www.zennio.com Technical Support: http://support.zennio.com


58
TMD-Display View

Two Objects (Short Press / Long Press)

Figure 40 Individual Button – Two Objects (short press / long press).

Action on Short press: sets the value to be sent to the bus (through “[Pn]
[Xj] Two switches - Short press”) when the user short-presses the button.
The options are “Send 0”, “Send 1”, “Toggle 0/1” and “Send 1-byte Unsigned
Int Value”. In case of selecting the latter, an additional parameter (“Value”)
will be displayed to enter the desired one-byte value (0 - 255).

 Text for ‘0’ and Text for ‘1’: sets the text to be displayed between the
icons of the buttons when the values ‘0’ and ‘1’ are sent, respectively.

Action on Long press: sets the value to be sent to the bus (through “[Pn]
[Xj] Two switches - Long press”) when the user long-presses the button.
The options are the same as for the short press.

Long Press Threshold Time: sets the minimum time the user should hold
the button in order to consider it a long press. The available range is 5 to 50
tenths of a second, being 5 tenths the default value.

LED illumination control: analogous to the homonymous parameter for the


“LED Indicator”, “Switch” and “Hold & Release” functions (see previous
pages). The options in this case are “Regular”, “State dependent” and
“Dedicated object”.

http://www.zennio.com Technical Support: http://support.zennio.com


59
TMD-Display View

Selecting “State dependent” brings an additional parameter, “LED


Illumination State Object”, to make the state of the LED correspond either
to object “[Pn] [Xj] Two objects - Short press” (“Short Press Object”) or to
object “[Pn] [Xj] Two objects - Long press” (“Long Press Object”).

Hold & Release

Figure 41 Individual Button – Hold & Release.

Action on Hold: sets the value to be sent to the bus (through “[Pn] [Xj] Hold
& Release”) when the user touches the button. The options are “Send 0” and
“Send 1” (default).

Action on Release: sets the value to be sent to the bus (again, through “[Pn]
[Xj] Hold & Release”) when the user stops touching the button. The options
are “Send 0” (default) and “Send 1”.

LED illumination control: analogous to the homonymous parameter for the


“LED Indicator” and “Switch” functions (see above). The options in this case
are “Regular” and “Dedicated object”.

Scene

Action: sets whether the value to be sent to the KNX bus (through “[General]
Scene: send”) when the user touches the button will always be a scene run
request (“Run scene”) or –depending on the length of button press– a scene
run or save request (“Run (Short Press) + Save (3s Press) Scene”).

Scene number: number of the scene (1 – 64) to be sent to the bus, both in
the case of the run requests and the save requests.

http://www.zennio.com Technical Support: http://support.zennio.com


60
TMD-Display View

LED illumination control: analogous to the homonymous parameter for all


the above functions (see previous pages). The options in this case are
“Regular”, and “Dedicated object”.

Figure 42 Individual Button – Scene.

Counter Constant / Scaling Constant / Float Constant

Figure 43 Individual Button - Scaling Constant.

Object Value: sets the value to be sent to the KNX bus when the user
touches the button. The available range and the object through which the
value is sent depends for each as the table below shows.

In case of selecting Counter Constant, two specific parameters (“Size” and


“Signed”) will be displayed to respectively define the size of the constant (“1
byte” or “2 bytes”) and whether it is a signed value or an unsigned value.
Depending on that, the range and the name of the object will vary.

http://www.zennio.com Technical Support: http://support.zennio.com


61
TMD-Display View

Available Values Name of the Object

Scaling
0% – 100% [Pn] [Xj] 1-byte Scaling Value
Constant

0 – 255 [Pn] [Xj] 1-byte Unsigned Int Value


Counter -128 – 127 [Pn] [Xj] 1-byte Signed Int Value
Constant 0 – 65535 [Pn] [Xj] 2-byte Unsigned Int Value
-32768 – 32767 [Pn] [Xj] 2-byte Signed Int Value

-671088.64 –
Float Constant [Pn] [Xj] 2-byte Float Value
670760.96

Table 3 Constant – Object Value

LED illumination control: analogous to the homonymous parameter for all


the above functions (see previous pages). The options in this case are
“Regular”, “State dependent” and “Dedicated object”.

Enumeration

Figure 44 Individual Buttons – Enumeration.

This control is completely analogous to the Enumeration control in pair-button controls


(see section 2.4.3), but without the parameter to link the control to the display (in this
case, the value is sent to the bus when the button is pressed).

# Enums: number of states (up to 6) that will be distinguished. For every


distinguished state, one parameter Value j and Text j will become available,
in order to set the value sent through the communication object.

http://www.zennio.com Technical Support: http://support.zennio.com


62
TMD-Display View

Value j: numerical value (0 – 255) that will be sent through the object “[Pn]
[Xj] Enumeration” when the user, after pressing the buttons, sets the control
box to state j.

Text j: text to be displayed, between the icons of the buttons, to indicate the
selected enumeration value.

LED illumination control: analogous to the homonymous parameter for all


the previous functions (see previous pages). The options in this case are
“Regular” and “Dedicated object”.

Dimmer

Figure 45 Individual Button - Dimmer.

The (alternating) switch orders will be sent through the “[Pn] [Xj] Light On/Off” one-bit
object, while the (alternating) increase/decrease/stop orders will be through the “[Pn]
[Xj] Light Dimming” four-bit object.

On the other hand, the “[Pn] [Xj] Light Indicator” one-byte object may be linked to the
light level status object of the dimmer (in fact, this object is only intended to receive
values from the bus, not to send them). As explained in 2.4.4, the state-dependent LED
lighting will be determined by the value of this object (LED off at 0% and on at any
other level).

The parameters for this function are:

Step: defines the dimming step (“100%”, “50%”, “25%”, “12.5%”, “6.25%”,
“3.1%” or “1.5%”) to be sent (through “[Pn] [Xj] Light Dimming”) to the light
dimmer with every long press.

Note: since dimmers typically do not apply the new light level immediately
(i.e., the step is performed progressively) and since TMD-Display View sends

http://www.zennio.com Technical Support: http://support.zennio.com


63
TMD-Display View

an order to interrupt the step dimming once the user releases the button, it is
advisable to configure a step of 100%. This way, the user can perform any
dimming step by simply leaving the button pressed and then releasing it,
without needing to make successive button presses.

LED illumination control: analogous to the homonymous parameter for all


the above functions (see previous pages). The options in this case are
“Regular”, “State dependent” and “Dedicated object”.

Shutter

Figure 46 Individual Button - Shutter.

The (alternating) move up/down orders will be sent through the “[Pn] [Xj] Move
Shutter (Toogle Direction)” one-bit object, while the (alternating) step up/down orders
will be through the “[Pn] [Xj] Stop Shutter/Step” one-bit object.

Additionally, a one-byte object (“[Pn] [Xj] Shutter Position”) is provided to link it to the
position status object of the shutter actuator (in fact, this object is only intended to
receive values from the bus, not to send them). As explained in , the alternation of the
move up/down and the step up/down requests will be conditioned to these statuses, to
prevent sending ineffective requests.

The parameters for this function are:

Type: sets the desired control type: “Standard” or “Hold & Release”, which
have been described in section 2.4.4.

LED illumination control: analogous to the homonymous parameter for all


the previous functions (see previous pages). The options in this case are
“Regular” and “Dedicated object”.

http://www.zennio.com Technical Support: http://support.zennio.com


64
TMD-Display View

Timer

Figure 47 Individual Buttons – Timer.

Action: sets the value to send to the bus when the configured time elapses.
The options are “Send 0”, “Send 1” and “Send Scene”. The binary values are
sent through the 1-bit object “[Pn] [Xj] Timer Control: “0/1””, but the scene
values through the generic scene object “[Pn] [Xj] Scene: Receive”.

Timer type: sets the timer type.

 “Without Repetition”: The parameterised value ("0", "1" or a scene) will be


sent once through the corresponding object.

 “Periodic” The parameterised value ("0", "1" or a scene) will be sent daily
through the corresponding object.

 “Countdown” The parameterised value ("0", "1" or a scene) will be sent


through the corresponding object once the countdown expires.

The values are sent when the user enables the timer and sets when the
sending must take place. This can be done by short pressing the
corresponding button (each press switches the state: disabled/enabled) or by
sending the value "1" through the "[Px][By] Enable Timer" object. If the timer
has been enabled, the timer label and the trigger time will flash on the screen.
Besides, the LED of the button will stay on. If the timer is disabled, just the
name of the button will be shown, while the associated LED stays off. The
same applies to the countdown timers, although the time is shown preceded
by the "-" sign, thus indicating that it is a decreasing value.

Once enabled, it is necessary to set the time (or the countdown interval) for
the sending. This is done from the device itself by long-pressing on the button

http://www.zennio.com Technical Support: http://support.zennio.com


65
TMD-Display View

(in the case of the countdown, the button can also be short-pressed). Then a
virtual clock shows up in order to set the desired time by making use of the
arrow buttons. To confirm the selection, just short press on the central area.

LED Indicator

Figure 48 Individual Buttons – Timer.

LED Illumination Control Object Value: sets the value to switch off and
switch on the LED. The options are: “0 = Off; 1 = On” or “0 = On; 1 = Off”.

http://www.zennio.com Technical Support: http://support.zennio.com


66
TMD-Display View

2.5 CONFIGURATION PAGES


When marking the checkbox corresponding to one of the configuration pages in the
Configuration screen under the Pages tab, a new tab is added on the menu on the left.

2.5.1 GENERAL CONFIGURATION

From this ETS window it is possible to enable and to assign a name to certain
parameters of TMD-Display View adjustable by the end user at runtime, from the
Configuration page.

ETS PARAMETERISATION

Figure 49 Configuration pages – General Configuration.

Title: a text string of up to 10 characters that identifies the General


Configuration page and that will be shown in the upper left side of the display
when accessing this page.

Label: textbox to enter the string (up to 10 characters) that is displayed on


the screen next to the button, in order to identify the control.

Time: allows setting the time of the clock (with format "hh:mm"). To do so,
please press on the corresponding button and make use of the arrow buttons
(long presses cause ten-minute steps, while short presses imply one-minute
steps). To confirm, just press on the central area between the buttons.

Note: bus power failures may introduce delays, as the internal clock needs
power to work. In such case, the clock should be set to the correct time once
the bus power returns.

Programming LED: when the physical address of the device needs to be


downloaded, it is possible to enter the programming mode directly by short-
pressing this button. This feature overcomes the need for accessing the rear

http://www.zennio.com Technical Support: http://support.zennio.com


67
TMD-Display View

side of the panel to physically press the programming button. While the
programming mode is active, the LED associated to this button in the
Configuration page will stay on. To leave the programming mode, just short-
press this button again (the programming LED and the button LED will be
switched off).

Reset: a long press of at least 3 seconds reset all the stored values and set
TMD-Display View to the initial state it had after the last download performed.

2.5.2 DISPLAY

Figure 50 Configuration pages – Display.

Title: a text string of up to 10 characters that identifies the Display page and
that will be shown in the left upper side of the display when accessing this
page.

Label: textbox to enter the string (up to 10 characters) that is displayed on


the screen next to the button, in order to identify the control.

Brightness (Normal Mode): allows setting the display brightness level for
the normal mode (values from 1 to 10). Press the button corresponding to the
brightness and simply make use of the arrow buttons to modify this level.

Brightness (Night Mode): analogous to the above one, but referred to the
night mode. This parameter is only available after enabling the night mode in
the LEDs and Display tab (see section 2.2.4).

Contrast: allows setting the display contrast level (values from 1 to 10).
Press the button corresponding to the Contrast and simply make use of the
arrow buttons to modify this level.

http://www.zennio.com Technical Support: http://support.zennio.com


68
TMD-Display View

2.6 INPUTS
TMD-Display View incorporates two analogue/digital inputs, each configurable as a:

Binary Input, for the connection of a pushbutton or a switch/sensor.

Temperature Probe, for the connection of a temperature sensor (such as


models ZN1AC-NTC68 S/E/F and SQ-AmbienT from Zennio).

Motion Detector, for the connection of a motion detector (models ZN1IO-


DETEC-P and ZN1IO-DETEC-X from Zennio).

Important: older models of the Zennio motion detector (e.g., ZN1IO-DETEC


and ZN1IO-DETEC-N) will not work properly with TMD-Display View.

ETS PARAMETERISATION

When Inputs has been activated in the General parameters screen, the following drop-
lists will be available for the selection of the specific functions required.

Figure 51. Inputs - Configuration

All inputs are disabled by default. Depending on the function selected for each input,
additional tabs will be included in the menu on the left.

2.6.1 BINARY INPUT

Please refer to the specific user manual “Binary Inputs”, available in the TMD-Display
View section, at the Zennio website (www.zennio.com).

2.6.2 TEMPERATURE PROBE

Please refer to the specific user manual “Temperature Probe”, available in the TMD-
Display View section, at the Zennio website (www.zennio.com)..

http://www.zennio.com Technical Support: http://support.zennio.com


69
TMD-Display View

2.6.3 MOTION DETECTOR

It is possible to connect motion detectors (models ZN1IO-DETEC-P and ZN1IO-


DETEC-X from Zennio) to the input ports of TMD-Display View.

Please refer to the specific user manual “Motion Detector”, available in the TMD-
Display View section, at the Zennio website (www.zennio.com).

Notes:

This device does not include luminosity measurement capabilities (only


motion detection). Therefore, the two models mentioned offer equivalent
functionality when connected to this device

Motion detectors with references ZN1IO-DETEC and ZN1IO-DETEC-N are


not compatible with TMD-Display View (may report inaccurate
measurements if connected to this device).

When connected to TMD-Display View, the rear micro-switch of model


ZN1IO-DETEC-P should be set to position “Type B”.

http://www.zennio.com Technical Support: http://support.zennio.com


70
TMD-Display View

2.7 THERMOSTAT
TMD-Display View implements one Zennio thermostat which can be enabled and fully
customised.

For details please refer to the specific manual “Zennio Thermostat” available in the
TMD-Display View section at the Zennio homepage (www.zennio.com).

http://www.zennio.com Technical Support: http://support.zennio.com


71
TMD-Display View

ANNEX I: LED ILLUMINATION MODES

The central LED indicator of every button, by default (in most functions), will turn on for
a brief instant whenever the button is touched. This behaviour is referred to as the
“Regular Illumination”.

However, in most cases it is possible to assign different behaviours to the LEDs. Which
options are available will depend on the function parameterised for the button, but will
always include some of the following:

Regular Illumination: the LED will light for an instant once the button is
touched.

State-Dependent Illumination: the LED will or will not light, depending on


the value of the communication object that corresponds to the function
implemented by the button. The exact correspondence between the different
values of the object and the different states of the LED may be slightly
different from one type of control to another, and is detailed for each function.

State-Dependent Illumination (both LEDs): only applies to buttons


configured as pair controls. The two LEDs of the control will light or not,
depending on the value of the related object and on the particular control type
parameterised for that pair of buttons. The only difference compared to the
previous case is that, under “both LEDs”, the two LEDs will always turn off or
on simultaneously, as if it were a unique indicator consisting of two LEDs.

Dedicated Object: the LED will light or not depending on the value (“0” or
“1”, configurable) of a binary, independent object. In the case of the pair
controls, the value “0” will make one of the LEDs light (leaving the other one
off), while the value “1” will make them switch their states.

Note:

Regarding the LEDs, it is interesting to distinguish the following cases:

Disabled button: the LED will remain off, and the button will have no function.

Button configured as “Individual” with “LED Indicator” function: the button will
still have no function. The LED may be turned on/off through a binary object.

http://www.zennio.com Technical Support: http://support.zennio.com


72
TMD-Display View

Button configured as any other control type: the behaviour of the LED will be
configurable according to the following table (being also possible to leave it
turned off).

State-dep. Dedicated
Regular State-dep.
(both LEDs) object

Switch
Switch + Indicator
Two Objects
Counter - -

Scaling - -

Float - -

Enumeration - -
PAIR Shutter - -

Dimmer
[Climate]
Temperature
[Climate] Mode
[Climate] Fan
Multimedia - - - -

Indicator - - - -

Binary -

Two Objects -

Hold & Rel. - -

Scene - -

Constants -
INDIVIDUAL
Enumeration - -

Dimmer -

Shutter - -

Timer - - - -

LED Indicator - - -

Table 4 Functions vs. LED Illumination Options.

Although the behaviour of the LEDs can be configured independently for each control
(see section 2.3.1), it is also possible to define a general behaviour for all of them
thus not being then necessary to configure the same option multiple times. In case of
opting for a general configuration, the options are:

http://www.zennio.com Technical Support: http://support.zennio.com


73
TMD-Display View

Regular Illumination.

State-Dependent (when available). Functions where “state-dependent” is


not available will use the regular illumination.

State-Dependent (when available) (both LEDs). Functions where “state-


dependent” is not available will use the regular illumination.

Dedicated Object. One binary communication object per control will be


included in the project topology so that the LED of every control turns on/off
depending on its own object.

ETS PARAMETERISATION

For details on the parameterisation of the LED illumination modes please refer to the
pages that cover the specific function being assigned to the button (section 2.4).

http://www.zennio.com Technical Support: http://support.zennio.com


74
TMD-Display View

ANNEX II. BUTTON ICONS


Icons for individual buttons:

Name Icon
Default
Off
On
0
1
Minus
Plus
Down
Up
Left
Right
Stop
Play

Icons for pair buttons: they are similar to those for the individual buttons; however
they are grouped into pairs. The one on the left will be shown on the left button of the
pair, while the one on the right will be drawn on the right button.

Name Icon
Default
Off/On
0/1
Minus/Plus
Down/Up
Left/Right
Stop/Play

http://www.zennio.com Technical Support: http://support.zennio.com


75
TMD-Display View

ANNEX II: COMMUNICATION OBJECTS


“Functional range” shows the values that, with independence of any other values permitted by the bus according to the object size,
may be of any use or have a particular meaning because of the specifications or restrictions from both the KNX standard or the
application programme itself.

Number Size I/O Flags Data type (DPT) Functional Range Name Function
1 3 Bytes I C--W- DPT_TimeOfDay 00:00:00 - 23:59:59 [General] Time of Day Time of Day External Reference
2 1 Byte I C--W- DPT_SceneNumber 0-63 [General] Scene: Receive 0-63 (Run Scene 1-64)
3 1 Byte CT--- DPT_SceneControl 0-63; 128-191 [General] Scene: Send 0-63 / 128-191 (Run/Save Scene 1-64)
4 2 Bytes I C--W- DPT_Value_Temp -273,00 - 670760,00 [General] Screensaver - External Temperature Temperature to be shown on the screensaver
1 Bit I C--W- DPT_Switch 0/1 [General] LEDs & Disp - Brightness Mode 0 = Normal; 1 = Night
5
1 Bit I C--W- DPT_Switch 0/1 [General] LEDs & Disp - Brightness Mode 0 = Night; 1 = Normal
6 1 Byte I C--W- DPT_SceneNumber 0-10 [General] Display - Contrast 0 = Level 1; ... ; 10 (Scene Format)
1 Bit I C--W- DPT_Enable 0/1 [General] Sounds - Disabling Button Sound 0 = Disable Sound; 1 = Enable Sound
7
1 Bit I C--W- DPT_Enable 0/1 [General] Sounds - Disabling Button Sound 0 = Enable Sound; 1 = Disable Sound
1 Bit I C--W- DPT_Trigger 0/1 [General] Sounds - Doorbell 0 = No Action; 1 = Doorbell
8
1 Bit I C--W- DPT_Trigger 0/1 [General] Sounds - Doorbell 0 = Doorbell; 1 = No Action
1 Bit I C--W- DPT_Alarm 0/1 [General] Sounds - Alarm 0 = Stop Alarm; 1 = Start Alarm
9
1 Bit I C--W- DPT_Alarm 0/1 [General] Sounds - Alarm 0 = Start Alarm; 1 = Stop Alarm
1 Bit I C--W- DPT_Enable 0/1 [General] Touch Locking 0 = Unlock; 1 = Lock
10
1 Bit I C--W- DPT_Enable 0/1 [General] Touch Locking 0 = Lock; 1 = Unlock
1 Bit O CTR-- DPT_Switch 0/1 [General] Welcome Back Object: "1" 1-bit Generic Control
11
1 Bit O CTR-- DPT_Switch 0/1 [General] Welcome Back Object: "0" 1-bit Generic Control
12 1 Bit I C--W- DPT_Bool 0/1 [General] Welcome back - Additional Condition Additional Condition Object 1
13 1 Bit I C--W- DPT_Bool 0/1 [General] Welcome back - Additional Condition Additional Condition Object 2
14 1 Bit I C--W- DPT_Bool 0/1 [General] Welcome back - Additional Condition Additional Condition Object 3
15 1 Bit I C--W- DPT_Bool 0/1 [General] Welcome back - Additional Condition Additional Condition Object 4
16 1 Bit I C--W- DPT_Bool 0/1 [General] Welcome back - Additional Condition Additional Condition Object 5
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X1] Switch: "0" 1-bit Generic Control
17, 30, 43, 56, 1 Byte I/O C T R W - DPT_Value_1_Ucount 0 - 255 [Pn] [X1] Two Objects - Short Press: (1-byte) Send selected 1-byte value on short press
69, 82, 95, 108, 1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X1] Switch: "1" 1-bit Generic Control
121, 134, 147,
160, 173, 186, 1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X1] Switch: "0/1" 1-bit Generic Control
199, 212 1 Bit O CTR-- DPT_Switch 0/1 [Pn] [X1] Hold & Release 1-bit Generic Control
1 Bit O CTR-- DPT_Switch 0/1 [Pn] [X] Light On/Off 0 = Off; 1 = On

http://www.zennio.com Technical Support: http://support.zennio.com


76
TMD-Display View

1 Bit O CTR-- DPT_Switch 0/1 [Pn] [X1] Light On/Off (Toggle) 0 = Off; 1 = On
0 = Stop Shutter/Step Up; 1 = Stop
1 Bit O CTR-- DPT_Step 0/1 [Pn] [X] Stop Shutter/Step
Shutter/Step Down
0 = Stop Shutter/Step Up; 1 = Stop
1 Bit O CTR-- DPT_Step 0/1 [Pn] [X1] Stop Shutter/Step
Shutter/Step Down
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X] Two Objects - Short Press 1-bit Generic Control
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X1] Two Objects - Short Press: "0" 1-bit Generic Control
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X1] Two Objects - Short Press: "1" 1-bit Generic Control
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X1] Two Objects - Short Press: "0/1" 1-bit Generic Control
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X] Switch 1-bit Generic Control
1 Bit O CTR-- DPT_Trigger 0/1 [Pn] [X] Stop Shutter 0, 1 = Stop Shutter
1 Bit O CTR-- DPT_Trigger 0/1 [Pn] [X1] Stop Shutter 0, 1 = Stop Shutter
1 Bit I/O C T R W - DPT_Heat_Cool 0/1 [Pn] [X] (Climate) Mode Left = Cool; Right = Heat
0 = Auto
1 = Calor
Rotating change of selected modes on short
1 Byte I/O C T R W - DPT_HVACContrMode 3 = Frío [Pn] [X] (Climate) Mode - Extended
press
9 = Viento
14 = Seco
1 Bit O CTR-- DPT_Start 0/1 [Pn] [X] 1-bit Multimedia Control 1 = Start/Forward; 0 = Stop/Backward
1 Bit I/O C T R W - DPT_Enable 0/1 [Pn] [X1] Enable Timer 0 = Disabled; 1 = Enabled
1 Bit O CTR-- DPT_Step 0/1 [Pn] [X] Fan Control (Type: 1-bit) 0 = Decrease; 1 = Increase
1 Byte O CTR-- DPT_Scaling 0% - 100% [Pn] [X] Fan Control (Type: Scaling) 0%, 33%, 67%, 100%
1 Byte O CTR-- DPT_Scaling 0% - 100% [Pn] [X] Fan Control (Type: Scaling) 0%, 50%, 100%
1 Byte O CTR-- DPT_Scaling 0% - 100% [Pn] [X] Fan Control (Type: Scaling) Auto, 50%, 100%
1 Byte O CTR-- DPT_Scaling 0% - 100% [Pn] [X] Fan Control (Type: Scaling) 50%, 100%
1 Byte O CTR-- DPT_Scaling 0% - 100% [Pn] [X] Fan Control (Type: Scaling) 33%, 67%, 100%
1 Byte O CTR-- DPT_Scaling 0% - 100% [Pn] [X] Fan Control (Type: Scaling) Auto, 33%, 67%, 100%
1 Byte O CTR-- DPT_Scaling 0% - 100% [Pn] [X] Fan Control (Type: Scaling) 25%, 50%, 75%, 100%
1 Byte O CTR-- DPT_Scaling 0% - 100% [Pn] [X] Fan Control (Type: Scaling) 0%, 25%, 50%, 75%, 100%
1 Byte O CTR-- DPT_Scaling 0% - 100% [Pn] [X] Fan Control (Type: Scaling) Auto, 25%, 50%, 75%, 100%
1 Byte O CTR-- DPT_Scaling 0% - 100% [Pn] [X] Fan Control (Type: Scaling) 100%
1 Byte O CTR-- DPT_Scaling 0% - 100% [Pn] [X] Fan Control (Type: Scaling) Auto, 20%, 40%, 60%, 80%, 100%
1 Byte O CTR-- DPT_Scaling 0% - 100% [Pn] [X] Fan Control (Type: Scaling) 0%, 20%, 40%, 60%, 80%, 100%
1 Byte O CTR-- DPT_Scaling 0% - 100% [Pn] [X] Fan Control (Type: Scaling) 20%, 40%, 60%, 80%, 100%
1 Byte O C T R - - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Control (Type: Enumeration) Auto, 1
1 Byte O C T R - - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Control (Type: Enumeration) 1, 2
1 Byte O C T R - - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Control (Type: Enumeration) 1
1 Byte O C T R - - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Control (Type: Enumeration) 0, 1
1 Byte O CTR-- DPT_Scaling 0% - 100% [Pn] [X] Fan Control (Type: Scaling) Auto, 100%
1 Byte O C T R - - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Control (Type: Enumeration) 0, 1, 2
1 Byte O C T R - - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Control (Type: Enumeration) Auto, 1, 2

http://www.zennio.com Technical Support: http://support.zennio.com


77
TMD-Display View

1 Byte O C T R - - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Control (Type: Enumeration) Auto, 1, 2, 3
1 Byte O C T R - - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Control (Type: Enumeration) 0, 1, 2, 3, 4, 5
1 Byte O C T R - - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Control (Type: Enumeration) 1, 2, 3, 4, 5
1 Byte O C T R - - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Control (Type: Enumeration) Auto, 1, 2, 3, 4, 5
1 Byte O C T R - - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Control (Type: Enumeration) Auto, 1, 2, 3, 4
1 Byte O C T R - - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Control (Type: Enumeration) 0, 1, 2, 3, 4
1 Byte O C T R - - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Control (Type: Enumeration) 1, 2, 3, 4
1 Byte O C T R - - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Control (Type: Enumeration) 1, 2, 3
1 Byte O C T R - - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Control (Type: Enumeration) 0, 1, 2, 3
1 Byte O CTR-- DPT_Scaling 0% - 100% [Pn] [X] Fan Control (Type: Scaling) 0%, 100%
1 Byte I C--W- DPT_Scaling 0% - 100% [Pn] [X] Fan Indicator 0 - 100%
1 Byte I C - - W - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Fan Indicator Enumerated Value
1 Bit I C--W- DPT_Switch 0/1 [Pn] [X] [Status] Switch Value of 1-bit Generic Control
1 Bit I C--W- DPT_Switch 0/1 [Pn] [X] [Status] Two Objects - Short Press Value of 1-bit Generic Control
1 Bit I C--W- DPT_Heat_Cool 0/1 [Pn] [X] [Status] (Climate) Mode Left = Cool; Right = Heat
0 = Auto
1 = Calor
Rotating change of selected modes on short
1 Byte I C - - W - DPT_HVACContrMode 3 = Frío [Pn] [X] [Status] (Climate) Mode - Extended
18, 31, 44, 57, press
9 = Viento
70, 83, 96, 109, 14 = Seco
122, 135, 148, 1 Bit I C--W- DPT_Switch 0/1 [Pn] [X1] [Status] Switch Value of 1-bit Generic Control
161, 174, 187,
200, 213 1 Bit I C--W- DPT_Switch 0/1 [Pn] [X1] [Status] Hold & Release Value of 1-bit Generic Control
1 Bit I C--W- DPT_BinaryValue 0/1 [Pn] [X1] [Status] Two Objects - Short Press: (1-bit) Value of short press object: (1-bit)
[Pn] [X1] [Status] Two Objects - Short Press: (1-
1 Byte I C - - W - DPT_Value_1_Ucount 0 - 255 Value of short press object: (1-byte)
byte)
0 = Stop Shutter/Step Up; 1 = Stop
1 Bit I C--W- DPT_Step 0/1 [Pn] [X1] [Status] Stop Shutter/Step
Shutter/Step Down
1 Bit I C--W- DPT_Trigger 0/1 [Pn] [X1] [Status] Stop Shutter 0, 1 = Stop Shutter
1 Bit I C--W- DPT_Switch 0/1 [Pn] [X] [Status] Switch 1-bit Generic Control
1 Bit I C--W- DPT_Start 0/1 [Pn] [X] [Status] 1-bit Multimedia Control 1 = Start/Forward; 0 = Stop/Backward
0x0 (Detener)
0x1 (Reducir 100%)

0x7 (Reducir 1%)
4 Bit O C T R - - DPT_Control_Dimming [Pn] [X] Light Dimming 4-bit Dimming Control
0x8 (Detener)
19, 32, 45, 58, 0x9 (Subir 100%)
71, 84, 97, 110, …
123, 136, 149, 0xF (Subir 1%)
162, 175, 188,
201, 214 0x0 (Detener)
0x1 (Reducir 100%)

4 Bit O C T R - - DPT_Control_Dimming [Pn] [X1] Light Dimming (Toggle) 4-bit Dimming Control
0x7 (Reducir 1%)
0x8 (Detener)
0x9 (Subir 100%)

http://www.zennio.com Technical Support: http://support.zennio.com


78
TMD-Display View


0xF (Subir 1%)
1 Byte I C--W- DPT_Scaling 0% - 100% [Pn] [X] Light Indicator 0 - 100%
1 Byte I C--W- DPT_Scaling 0% - 100% [Pn] [X1] Light Indicator 0 - 100%
1 Byte I C--W- DPT_Scaling 0% - 100% [Pn] [X1] Shutter Position 0 - 100%
2 Bytes I C - - W - DPT_Value_2_Ucount 0 - 65535 [Pn] [X] 2-byte Unsigned Int Indicator 0 – 65535
2 Bytes I C - - W - DPT_Value_2_Count -32768 - 32767 [Pn] [X] 2-byte Signed Int Indicator -32768 - 32767
1 Byte I C - - W - DPT_Value_1_Ucount 0 - 255 [Pn] [X] 1-byte Unsigned Int Indicator 0 – 255
1 Byte I C - - W - DPT_Value_1_Count -128 - 127 [Pn] [X] 1-byte Signed Int Indicator -128 - 127
1 Byte I C--W- DPT_Scaling 0% - 100% [Pn] [X] 1-byte Indicator (Scaling) 0 - 100%
2 Bytes I C--W- DPT_Value_Temp -273,00 - 670760,00 [Pn] [X] Temperature Indicator -273.00°C – 670760.96°C
4 Bytes I C--W- 13.xxx [Pn] [X] 4-byte Signed Int Indicator -2147483648 - 2147483647
-671088.64 -
2 Bytes I C--W- 9.xxx [Pn] [X] 2-byte Float Indicator -671088.64 – 670760.96
670760.96
1 Bit I C--W- DPT_Switch 0/1 [Pn] [X] Binary Indicator 1-bit Generic Indicator
1 Byte I C - - W - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Enumerated Indicator 1-byte Enumeration
1 Byte I C--W- DPT_Scaling 0% - 100% [Pn] [X] Shutter Position 0 - 100%
1 Bit I C--W- DPT_Switch 0/1 [Pn] [X] [Status] Two Objects - Long Press Value of 1-bit Generic Control
20, 33, 46, 59, 1 Byte I C--W- DPT_Scaling 0% - 100% [Pn] [X] [Status] 1-byte Scaling Value 0 - 100%
72, 85, 98, 111, 1 Byte I C - - W - DPT_Value_1_Ucount 0 - 255 [Pn] [X] [Status] 1-byte Unsigned Int Value 0 – 255
124, 137, 150, 1 Byte I C - - W - DPT_Value_1_Count -128 - 127 [Pn] [X] [Status] 1-byte Signed Int Value -128 - 127
163, 176, 189, 2 Bytes I C - - W - DPT_Value_2_Count -32768 - 32767 [Pn] [X] [Status] 2-byte Signed Int Value -32768 - 32767
202, 215
2 Bytes I C - - W - DPT_Value_2_Ucount 0 - 65535 [Pn] [X] [Status] 2-byte Unsigned Int Value 0 – 65535
1 Byte I C - - W - DPT_Value_1_Ucount 0 - 255 [Pn] [X] [Status] Enumeration Rotating value change
-671088.64 -
2 Bytes I C--W- 9.xxx [Pn] [X] [Status] 2-byte Float Value -671088.64 – 670760.96
670760.96
2 Bytes I C--W- DPT_Value_Temp -273,00 - 670760,00 [Pn] [X] [Status] (Climate) Temperature Setpoint -273.00°C – 670760.96°C
1 Bit I C--W- DPT_Switch 0/1 [Pn] [X] [Status] Fan Control - Auto Mode Auto Mode Status
1 Bit I C--W- DPT_BinaryValue 0/1 [Pn] [X1] [Status] Two Objects - Long Press: (1-bit) Value of long press object: (1-bit)
1 Byte I C - - W - DPT_Value_1_Ucount 0 - 255 [Pn] [X1] [Status] Two Objects - Long Press: (1-byte) Value of long press object: (1-byte)
1 Byte I C--W- DPT_Scaling 0% - 100% [Pn] [X1] [Status] 1-byte Scaling Value 0 - 100%
1 Byte I C - - W - DPT_Value_1_Ucount 0 - 255 [Pn] [X1] [Status] 1-byte Unsigned Int Value 0 – 255
1 Byte I C - - W - DPT_Value_1_Count -128 - 127 [Pn] [X1] [Status] 1-byte Signed Int Value -128 - 127
2 Bytes I C - - W - DPT_Value_2_Ucount 0 - 65535 [Pn] [X1] [Status] 2-byte Unsigned Int Value 0 – 65535
2 Bytes I C - - W - DPT_Value_2_Count -32768 - 32767 [Pn] [X1] [Status] 2-byte Signed Int Value -32768 - 32767
-671088.64 -
2 Bytes I C--W- 9.xxx [Pn] [X1] [Status] 2-byte Float Value -671088.64 – 670760.96
670760.96
1 Byte I C - - W - DPT_Value_1_Ucount 0 - 255 [Pn] [X1] [Status] Enumeration Rotating value change
1 Bit I C--W- DPT_Switch 0/1 [Pn] [X1] [Status] Timer Control 1-bit Generic Control
21, 34, 47, 60, 1 Bit I/O C T R W - DPT_UpDown 0/1 [Pn] [X1] Move Shutter (Toggle Direction) 0 = Up; 1 = Down
73, 86, 99, 112, 1 Bit I/O C T R W - DPT_UpDown 0/1 [Pn] [X] Move Shutter 0 = Up; 1 = Down

http://www.zennio.com Technical Support: http://support.zennio.com


79
TMD-Display View

125, 138, 151, 2 Bytes I/O C T R W - DPT_Value_2_Ucount 0 - 65535 [Pn] [X1] 2-byte Unsigned Int Value 0 – 65535
164, 177, 190, 1 Byte I/O C T R W - DPT_Value_1_Ucount 0 - 255 [Pn] [X1] 1-byte Unsigned Int Value 0 – 255
203, 216
1 Byte I/O C T R W - DPT_Scaling 0% - 100% [Pn] [X1] 1-byte Scaling Value 0 - 100%
-671088.64 -
2 Bytes I/O C T R W - 9.xxx [Pn] [X1] 2-byte Float Value -671088.64 – 670760.96
670760.96
1 Byte I/O C T R W - DPT_Value_1_Count -128 - 127 [Pn] [X1] 1-byte Signed Int Value -128 - 127
2 Bytes I/O C T R W - DPT_Value_2_Count -32768 - 32767 [Pn] [X1] 2-byte Signed Int Value -32768 - 32767
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X] Two Objects - Long Press 1-bit Generic Control
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X1] Two Objects - Long Press: "0" 1-bit Generic Control
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X1] Two Objects - Long Press: "1" 1-bit Generic Control
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X1] Two Objects - Long Press: "0/1" 1-bit Generic Control
2 Bytes I/O C T R W - DPT_Value_2_Count -32768 - 32767 [Pn] [X] 2-byte Signed Int Value -32768 - 32767
1 Byte I/O C T R W - DPT_Value_1_Count -128 - 127 [Pn] [X] 1-byte Signed Int Value -128 - 127
-671088.64 -
2 Bytes I/O C T R W - 9.xxx [Pn] [X] 2-byte Float Value -671088.64 – 670760.96
670760.96
1 Byte I/O C T R W - DPT_Scaling 0% - 100% [Pn] [X] 1-byte Scaling Value 0 - 100%
1 Byte I/O C T R W - DPT_Value_1_Ucount 0 - 255 [Pn] [X] 1-byte Unsigned Int Value 0 – 255
2 Bytes I/O C T R W - DPT_Value_2_Ucount 0 - 65535 [Pn] [X] 2-byte Unsigned Int Value 0 – 65535
1 Byte I/O C T R W - DPT_Value_1_Ucount 0 - 255 [Pn] [X1] Enumeration Rotating value change
1 Byte I/O C T R W - DPT_Value_1_Ucount 0 - 255 [Pn] [X] Enumeration Rotating value change
2 Bytes I/O C T R W - DPT_Value_Temp -273,00 - 670760,00 [Pn] [X] (Climate) Temperature Setpoint -273.00°C – 670760.96°C
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X1] Timer Control: "0" 1-bit Generic Control
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X1] Timer Control: "1" 1-bit Generic Control
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X] Fan Control - Auto Mode Switch Auto Mode on Long Press
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X] Fan Control - Auto Mode Switch Auto Mode on Short Press
1 Byte I/O C T R W - DPT_Value_1_Ucount 0 - 255 [Pn] [X1] Two Objects - Long Press: (1-byte) Send selected 1-byte value on long press
22, 35, 48, 61, 1 Bit I C--W- DPT_Switch 0/1 [Pn] [X] LED On/Off 0 = Off; 1 = On
74, 87, 100, 113, 1 Bit I C--W- DPT_Switch 0/1 [Pn] [X1] LED On/Off 0 = On; 1 = Off
126, 139, 152,
1 Bit I C--W- DPT_Switch 0/1 [Pn] [X1] LED On/Off 0 = Off; 1 = On
165, 178, 191,
204, 217 1 Bit I C--W- DPT_Switch 0/1 [Pn] [X] LED On/Off 0 = On; 1 = Off
23, 36, 49, 62,
75, 88, 101, 114,
127, 140, 153, 14 Bytes I C--W- DPT_String_ASCII [Pn] [X] Multimedia Text Indicator 14-byte String
166, 179, 192,
205, 218
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X2] Switch: "0" 1-bit Generic Control
24, 37, 50, 63, 1 Byte I/O C T R W - DPT_Value_1_Ucount 0 - 255 [Pn] [X2] Two Objects - Short Press: (1-byte) Send selected 1-byte value on short press
76, 89, 102, 115, 1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X2] Switch: "1" 1-bit Generic Control
128, 141, 154,
167, 180, 193, 1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X2] Switch: "0/1" 1-bit Generic Control
206, 219 1 Bit O CTR-- DPT_Switch 0/1 [Pn] [X2] Hold & Release 1-bit Generic Control
1 Bit O CTR-- DPT_Switch 0/1 [Pn] [X2] Light On/Off (Toggle) 0 = Off; 1 = On

http://www.zennio.com Technical Support: http://support.zennio.com


80
TMD-Display View

0 = Stop Shutter/Step Up; 1 = Stop


1 Bit O CTR-- DPT_Step 0/1 [Pn] [X2] Stop Shutter/Step
Shutter/Step Down
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X2] Two Objects - Short Press: "0" 1-bit Generic Control
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X2] Two Objects - Short Press: "1" 1-bit Generic Control
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X2] Two Objects - Short Press: "0/1" 1-bit Generic Control
1 Bit O CTR-- DPT_Trigger 0/1 [Pn] [X2] Stop Shutter 0, 1 = Stop Shutter
1 Bit I/O C T R W - DPT_Enable 0/1 [Pn] [X2] Enable Timer 0 = Disabled; 1 = Enabled
1 Bit I C--W- DPT_Switch 0/1 [Pn] [X2] [Status] Switch Value of 1-bit Generic Control
1 Bit I C--W- DPT_Switch 0/1 [Pn] [X2] [Status] Hold & Release Value of 1-bit Generic Control
25, 38, 51, 64, 1 Bit I C--W- DPT_BinaryValue 0/1 [Pn] [X2] [Status] Two Objects - Short Press: (1-bit) Value of short press object: (1-bit)
77, 90, 103, 116,
129, 142, 155, [Pn] [X2] [Status] Two Objects - Short Press: (1-
1 Byte I C - - W - DPT_Value_1_Ucount 0 - 255 Value of short press object: (1-byte)
168, 181, 194, byte)
207, 220 0 = Stop Shutter/Step Up; 1 = Stop
1 Bit I C--W- DPT_Step 0/1 [Pn] [X2] [Status] Stop Shutter/Step
Shutter/Step Down
1 Bit I C--W- DPT_Trigger 0/1 [Pn] [X2] [Status] Stop Shutter 0, 1 = Stop Shutter
0x0 (Detener)
0x1 (Reducir 100%)
26, 39, 52, 65,

78, 91, 104, 117,
0x7 (Reducir 1%)
130, 143, 156, 4 Bit O C T R - - DPT_Control_Dimming [Pn] [X2] Light Dimming (Toggle) 4-bit Dimming Control
0x8 (Detener)
169, 182, 195,
0x9 (Subir 100%)
208, 221

0xF (Subir 1%)
1 Bit I C--W- DPT_Switch 0/1 [Pn] [X2] [Status] Timer Control 1-bit Generic Control
1 Byte I C--W- DPT_Scaling 0% - 100% [Pn] [X2] Light Indicator 0 - 100%
1 Byte I C--W- DPT_Scaling 0% - 100% [Pn] [X2] Shutter Position 0 - 100%
1 Bit I C--W- DPT_BinaryValue 0/1 [Pn] [X2] [Status] Two Objects - Long Press: (1-bit) Value of long press object: (1-bit)
27, 40, 53, 66, 1 Byte I C - - W - DPT_Value_1_Ucount 0 - 255 [Pn] [X2] [Status] Two Objects - Long Press: (1-byte) Value of long press object: (1-byte)
79, 92, 105, 118, 1 Byte I C--W- DPT_Scaling 0% - 100% [Pn] [X2] [Status] 1-byte Scaling Value 0 - 100%
131, 144, 157, 1 Byte I C - - W - DPT_Value_1_Ucount 0 - 255 [Pn] [X2] [Status] 1-byte Unsigned Int Value 0 – 255
170, 183, 196, 1 Byte I C - - W - DPT_Value_1_Count -128 - 127 [Pn] [X2] [Status] 1-byte Signed Int Value -128 - 127
209, 222
2 Bytes I C - - W - DPT_Value_2_Ucount 0 - 65535 [Pn] [X2] [Status] 2-byte Unsigned Int Value 0 – 65535
2 Bytes I C - - W - DPT_Value_2_Count -32768 - 32767 [Pn] [X2] [Status] 2-byte Signed Int Value -32768 - 32767
-671088.64 -
2 Bytes I C--W- 9.xxx [Pn] [X2] [Status] 2-byte Float Value -671088.64 – 670760.96
670760.96
1 Byte I C - - W - DPT_Value_1_Ucount 0 - 255 [Pn] [X2] [Status] Enumeration Rotating value change
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X2] Timer Control: "0" 1-bit Generic Control
28, 41, 54, 67, 1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X2] Timer Control: "1" 1-bit Generic Control
80, 93, 106, 119, 1 Bit I/O C T R W - DPT_UpDown 0/1 [Pn] [X2] Move Shutter (Toggle Direction) 0 = Up; 1 = Down
132, 145, 158,
171, 184, 197, 2 Bytes I/O C T R W - DPT_Value_2_Ucount 0 - 65535 [Pn] [X2] 2-byte Unsigned Int Value 0 – 65535
210, 223 1 Byte I/O C T R W - DPT_Value_1_Ucount 0 - 255 [Pn] [X2] 1-byte Unsigned Int Value 0 – 255
1 Byte I/O C T R W - DPT_Scaling 0% - 100% [Pn] [X2] 1-byte Scaling Value 0 - 100%

http://www.zennio.com Technical Support: http://support.zennio.com


81
TMD-Display View

-671088.64 -
2 Bytes I/O C T R W - 9.xxx [Pn] [X2] 2-byte Float Value -671088.64 – 670760.96
670760.96
1 Byte I/O C T R W - DPT_Value_1_Count -128 - 127 [Pn] [X2] 1-byte Signed Int Value -128 - 127
2 Bytes I/O C T R W - DPT_Value_2_Count -32768 - 32767 [Pn] [X2] 2-byte Signed Int Value -32768 - 32767
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X2] Two Objects - Long Press: "0" 1-bit Generic Control
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X2] Two Objects - Long Press: "1" 1-bit Generic Control
1 Bit I/O C T R W - DPT_Switch 0/1 [Pn] [X2] Two Objects - Long Press: "0/1" 1-bit Generic Control
1 Byte I/O C T R W - DPT_Value_1_Ucount 0 - 255 [Pn] [X2] Enumeration Rotating value change
1 Byte I/O C T R W - DPT_Value_1_Ucount 0 - 255 [Pn] [X2] Two Objects - Long Press: (1-byte) Send selected 1-byte value on long press
29, 42, 55, 68, 1 Bit I C--W- DPT_Switch 0/1 [Pn] [X2] LED On/Off 0 = On; 1 = Off
81, 94, 107, 120,
133, 146, 159,
172, 185, 198, 1 Bit I C--W- DPT_Switch 0/1 [Pn] [X2] LED On/Off 0 = Off; 1 = On
211, 224
225 1 Byte I C--W- DPT_SceneControl 0-63; 128-191 [Thermostat] Scene Input Scene Value
226 2 Bytes I C--W- DPT_Value_Temp -273,00 - 670760,00 [T1] Temperature Source 1 External Sensor Temperature
227 2 Bytes I C--W- DPT_Value_Temp -273,00 - 670760,00 [T1] Temperature Source 2 External Sensor Temperature
228 2 Bytes O CTR-- DPT_Value_Temp -273,00 - 670760,00 [T1] Effective Temperature Effective Control Temperature
1=Confort
2=Standby
229 1 Byte I C--W- DPT_HVACMode [T1] Special Mode 1-byte HVAC Mode
3=Económico
4=Protección
1 Bit I C--W- DPT_Trigger 0/1 [T1] Special Mode: comfort 0 = Nothing; 1 = Trigger
230
1 Bit I C--W- DPT_Switch 0/1 [T1] Special Mode: comfort 0 = Off; 1 = On
1 Bit I C--W- DPT_Trigger 0/1 [T1] Special Mode: standby 0 = Nothing; 1 = Trigger
231
1 Bit I C--W- DPT_Switch 0/1 [T1] Special Mode: standby 0 = Off; 1 = On
1 Bit I C--W- DPT_Trigger 0/1 [T1] Special Mode: economy 0 = Nothing; 1 = Trigger
232
1 Bit I C--W- DPT_Switch 0/1 [T1] Special Mode: economy 0 = Off; 1 = On
1 Bit I C--W- DPT_Trigger 0/1 [T1] Special Mode: protection 0 = Nothing; 1 = Trigger
233
1 Bit I C--W- DPT_Switch 0/1 [T1] Special Mode: protection 0 = Off; 1 = On
234 1 Bit I C--W- DPT_Window_Door 0/1 [T1] Window Status (input) 0 = Closed; 1 = Open
235 1 Bit I C--W- DPT_Trigger 0/1 [T1] Comfort Prolongation 0 = Nothing; 1 = Timed Comfort
1=Confort
2=Standby
236 1 Byte O CTR-- DPT_HVACMode [T1] Special Mode Status 1-byte HVAC Mode
3=Económico
4=Protección
2 Bytes I C--W- DPT_Value_Temp -273,00 - 670760,00 [T1] Setpoint Thermostat Setpoint Input
237
2 Bytes I C--W- DPT_Value_Temp -273,00 - 670760,00 [T1] Basic Setpoint Reference Setpoint
238 1 Bit I C--W- DPT_Step 0/1 [T1] Setpoint Step 0 = -0.5ºC; 1 = +0.5ºC
-670760,00 -
239 2 Bytes I C--W- DPT_Value_Tempd [T1] Setpoint Offset Float Offset Value
670760,00
240 2 Bytes O CTR-- DPT_Value_Temp -273,00 - 670760,00 [T1] Setpoint Status Current Setpoint

http://www.zennio.com Technical Support: http://support.zennio.com


82
TMD-Display View

241 2 Bytes O CTR-- DPT_Value_Temp -273,00 - 670760,00 [T1] Basic Setpoint Status Current Basic Setpoint
-670760,00 -
242 2 Bytes O CTR-- DPT_Value_Tempd [T1] Setpoint Offset Status Current Setpoint Offset
670760,00
1 Bit I C--W- DPT_Reset 0/1 [T1] Setpoint Reset Reset Setpoint to Default
243
1 Bit I C--W- DPT_Reset 0/1 [T1] Offset Reset Reset offset
244 1 Bit I C--W- DPT_Heat_Cool 0/1 [T1] Mode 0 = Cool; 1 = Heat
245 1 Bit O CTR-- DPT_Heat_Cool 0/1 [T1] Mode Status 0 = Cool; 1 = Heat
246 1 Bit I C--W- DPT_Switch 0/1 [T1] On/Off 0 = Off; 1 = On
247 1 Bit O CTR-- DPT_Switch 0/1 [T1] On/Off Status 0 = Off; 1 = On
248 1 Byte O CTR-- DPT_Scaling 0% - 100% [T1] Control Variable (Cool) PI Control (Continuous)
249 1 Byte O CTR-- DPT_Scaling 0% - 100% [T1] Control Variable (Heat) PI Control (Continuous)
1 Bit O CTR-- DPT_Switch 0/1 [T1] Control Variable (Cool) 2-Point Control
250
1 Bit O CTR-- DPT_Switch 0/1 [T1] Control Variable (Cool) PI Control (PWM)
1 Bit O CTR-- DPT_Switch 0/1 [T1] Control Variable (Heat) 2-Point Control
251
1 Bit O CTR-- DPT_Switch 0/1 [T1] Control Variable (Heat) PI Control (PWM)
252 1 Bit O CTR-- DPT_Switch 0/1 [T1] Additional Cool Temp >= (Setpoint+Band) => "1"
253 1 Bit O CTR-- DPT_Switch 0/1 [T1] Additional Heat Temp <= (Setpoint-Band) => "1"
0 = PI signal 0%; 1 = PI signal greater than
254 1 Bit O CTR-- DPT_Switch 0/1 [T1] PI State (Cool)
0%
0 = PI signal 0%; 1 = PI signal greater than
255 1 Bit O CTR-- DPT_Switch 0/1 [T1] PI State (Heat)
0%
256, 260 2 Bytes O CTR-- DPT_Value_Temp -273,00 - 670760,00 [I1] Current Temperature Temperature sensor value
257, 261 1 Bit O CTR-- DPT_Alarm 0/1 [I1] Overcooling 0 = No Alarm;1 = Alarm
258, 262 1 Bit O CTR-- DPT_Alarm 0/1 [I1] Overheating 0 = No Alarm;1 = Alarm
259, 263 1 Bit O CTR-- DPT_Alarm 0/1 [I1] Probe Error 0 = No Alarm;1 = Alarm
264 2 Bytes O CTR-- DPT_Value_Temp -273,00 - 670760,00 [Internal Probe] Current Temperature Temperature sensor value
265 1 Bit O CTR-- DPT_Alarm 0/1 [Internal Probe] Overcooling 0 = No Alarm;1 = Alarm
266 1 Bit O CTR-- DPT_Alarm 0/1 [Internal Probe] Overheating 0 = No Alarm;1 = Alarm
267 1 Byte I C--W- DPT_SceneControl 0-63; 128-191 [Motion Detector] Scene Input Scene Value
268 1 Byte CT--- DPT_SceneControl 0-63; 128-191 [Motion Detector] Scene Output Scene Value
269, 298 1 Byte O CTR-- DPT_Scaling 0% - 100% [In] Luminosity 0-100%
270, 299 1 Bit O CTR-- DPT_Alarm 0/1 [In] Open Circuit Error 0 = No Error; 1 = Open Circuit Error
271, 300 1 Bit O CTR-- DPT_Alarm 0/1 [In] Short Circuit Error 0 = No Error; 1 = Short Circuit Error
272, 301 1 Byte O CTR-- DPT_Scaling 0% - 100% [In] Presence State (Scaling) 0-100%
1=Confort
2=Standby Auto, Comfort, Standby, Economy, Building
273, 302 1 Byte O CTR-- DPT_HVACMode [In] Presence State (HVAC)
3=Económico Protection
4=Protección
1 Bit O CTR-- DPT_Occupancy 0/1 [In] Presence State (Binary) Binary Value
274, 303
1 Bit O CTR-- DPT_Trigger 0/1 [In] Presence: Slave Output 1 = Motion Detected
275, 304 1 Bit I C--W- DPT_Window_Door 0/1 [In] Presence Trigger Binary Value to Trigger the Presence Detection

http://www.zennio.com Technical Support: http://support.zennio.com


83
TMD-Display View

276, 305 1 Bit I C--W- DPT_Trigger 0/1 [In] Presence: Slave Input 0 = Nothing; 1 = Detection from slave device
277, 306 2 Bytes I C--W- DPT_TimePeriodSec [In] Presence: Waiting Time 0-65535 s.
278, 307 2 Bytes I C--W- DPT_TimePeriodSec [In] Presence: Listening Time 1-65535 s.
279, 308 1 Bit I C--W- DPT_Switch 0/1 [In] Presence: Enable According to parameters
280, 309 1 Bit I C--W- DPT_Switch 0/1 [In] Presence: Day/Night According to parameters
281, 310 1 Bit O CTR-- DPT_Occupancy 0/1 [In] Presence: Occupancy State 0 = Not Occupied; 1 = Occupied
0 = Nothing; 1 = Motion detected by an
282, 311 1 Bit I C--W- DPT_Trigger 0/1 [In] External Motion Detection
external sensor
283, 288, 293,
1 Byte O CTR-- DPT_Scaling 0% - 100% [In] [Cj] Detection State (Scaling) 0-100%
312, 317, 322
1=Confort
284, 289, 294, 2=Standby Auto, Comfort, Standby, Economy, Building
1 Byte O CTR-- DPT_HVACMode [In] [Cj] Detection State (HVAC)
313, 318, 323 3=Económico Protection
4=Protección
285, 290, 295,
1 Bit O CTR-- DPT_Switch 0/1 [In] [Cj] Detection State (Binary) Binary Value
314, 319, 324
286, 291, 296,
1 Bit I C--W- DPT_Switch 0/1 [In] [Cj] Enable Channel According to parameters
315, 320, 325
287, 292, 297,
1 Bit I C--W- DPT_Switch 0/1 [In] [Cj] Force State 0 = No Detection; 1 = Detection
316, 321, 326
327, 333 1 Bit I C--W- DPT_Switch 0/1 [In] Input Lock 1 = Locked; 0 = Unlocked
1 Bit CT--- DPT_Switch 0/1 [In] [Short Press] 0 Sending of 0
1 Bit CT--- DPT_Switch 0/1 [In] [Short Press] 1 Sending of 1
1 Bit I CT-W- DPT_Switch 0/1 [In] [Short Press] 0/1 Switching Switching 0/1
1 Bit CT--- DPT_UpDown 0/1 [In] [Short Press] Move Up Shutter Sending of 0 (Up)
1 Bit CT--- DPT_UpDown 0/1 [In] [Short Press] Move Down Shutter Sending of 1 (Down)
1 Bit CT--- DPT_UpDown 0/1 [In] [Short Press] Move Up/Down Shutter Switching 0/1 (Up/Down)
1 Bit CT--- DPT_Step 0/1 [In] [Short Press] Stop/Step Up Shutter Sending of 0 (Stop/Step Up)
1 Bit CT--- DPT_Step 0/1 [In] [Short Press] Stop/Step Down Shutter Sending of 1 (Stop/Step Down)
1 Bit CT--- DPT_Step 0/1 [In] [Short Press] Stop/Step Shutter (Switched) Switching of 0/1 (Stop/Step Up/Down)
0x0 (Detener)
328, 334 0x1 (Reducir 100%)

0x7 (Reducir 1%)
4 Bit C T - - - DPT_Control_Dimming [In] [Short Press] Brighter Increase Brightness
0x8 (Detener)
0x9 (Subir 100%)

0xF (Subir 1%)
0x0 (Detener)
0x1 (Reducir 100%)

4 Bit C T - - - DPT_Control_Dimming [In] [Short Press] Darker Decrease Brightness
0x7 (Reducir 1%)
0x8 (Detener)
0x9 (Subir 100%)

http://www.zennio.com Technical Support: http://support.zennio.com


84
TMD-Display View


0xF (Subir 1%)
0x0 (Detener)
0x1 (Reducir 100%)

0x7 (Reducir 1%)
4 Bit C T - - - DPT_Control_Dimming [In] [Short Press] Brighter/Darker Switch Bright/Dark
0x8 (Detener)
0x9 (Subir 100%)

0xF (Subir 1%)
1 Bit CT--- DPT_Switch 0/1 [In] [Short Press] Dimmer ON Sending of 1 (ON)
1 Bit CT--- DPT_Switch 0/1 [In] [Short Press] Dimmer OFF Sending of 0 (OFF)
1 Bit I CT-W- DPT_Switch 0/1 [In] [Short Press] Dimmer ON/OFF Switching 0/1
1 Byte CT--- DPT_SceneControl 0-63; 128-191 [In] [Short Press] Run Scene Sending of 0 - 63
1 Byte CT--- DPT_SceneControl 0-63; 128-191 [In] [Short Press] Save Scene Sending of 128 - 191
1 Bit I/O C T R W - DPT_Switch 0/1 [In] [Switch/Sensor] Edge Sending of 0 or 1
1 Byte C T - - - DPT_Value_1_Ucount 0 - 255 [In] [Short Press] Constant Integer Value 0 - 255
1 Byte CT--- DPT_Scaling 0% - 100% [In] [Short Press] Constant Percentage Value 0% - 100%
2 Bytes C T - - - DPT_Value_2_Ucount 0 - 65535 [In] [Short Press] Constant Integer Value 0 - 65535
-671088.64 -
2 Bytes CT--- 9.xxx [In] [Short Press] Constant Float Value Float value
670760.96
1 Byte I C--W- DPT_Scaling 0% - 100% [In] [Short Press] Shutter Status (Input) 0% = Top; 100% = Bottom
329, 335
1 Byte I C--W- DPT_Scaling 0% - 100% [In] [Short Press] Dimming Status (Input) 0% - 100%
1 Bit CT--- DPT_Switch 0/1 [In] [Long Press] 0 Sending of 0
1 Bit CT--- DPT_Switch 0/1 [In] [Long Press] 1 Sending of 1
1 Bit I CT-W- DPT_Switch 0/1 [In] [Long Press] 0/1 Switching Switching 0/1
1 Bit CT--- DPT_UpDown 0/1 [In] [Long Press] Move Up Shutter Sending of 0 (Up)
1 Bit CT--- DPT_UpDown 0/1 [In] [Long Press] Move Down Shutter Sending of 1 (Down)
1 Bit CT--- DPT_UpDown 0/1 [In] [Long Press] Move Up/Down Shutter Switching 0/1 (Up/Down)
1 Bit CT--- DPT_Step 0/1 [In] [Long Press] Stop/Step Up Shutter Sending of 0 (Stop/Step Up)
1 Bit CT--- DPT_Step 0/1 [In] [Long Press] Stop/Step Down Shutter Sending of 1 (Stop/Step Down)
1 Bit CT--- DPT_Step 0/1 [In] [Long Press] Stop/Step Shutter (Switched) Switching of 0/1 (Stop/Step Up/Down)
330, 336 0x0 (Detener)
0x1 (Reducir 100%)

0x7 (Reducir 1%)
4 Bit C T - - - DPT_Control_Dimming [In] [Long Press] Brighter Long Pr. -> Brighter; Release -> Stop
0x8 (Detener)
0x9 (Subir 100%)

0xF (Subir 1%)
0x0 (Detener)
0x1 (Reducir 100%)
4 Bit C T - - - DPT_Control_Dimming [In] [Long Press] Darker Long Pr. -> Darker; Release -> Stop

0x7 (Reducir 1%)

http://www.zennio.com Technical Support: http://support.zennio.com


85
TMD-Display View

0x8 (Detener)
0x9 (Subir 100%)

0xF (Subir 1%)
0x0 (Detener)
0x1 (Reducir 100%)

0x7 (Reducir 1%)
4 Bit C T - - - DPT_Control_Dimming [In] [Long Press] Brighter/Darker Long Pr. -> Brighter/Darker; Release -> Stop
0x8 (Detener)
0x9 (Subir 100%)

0xF (Subir 1%)
1 Bit CT--- DPT_Switch 0/1 [In] [Long Press] Dimmer ON Sending of 1 (ON)
1 Bit CT--- DPT_Switch 0/1 [In] [Long Press] Dimmer OFF Sending of 0 (OFF)
1 Bit I CT-W- DPT_Switch 0/1 [In] [Long Press] Dimmer ON/OFF Switching 0/1
1 Byte CT--- DPT_SceneControl 0-63; 128-191 [In] [Long Press] Run Scene Sending of 0 - 63
1 Byte CT--- DPT_SceneControl 0-63; 128-191 [In] [Long Press] Save Scene Sending of 128 - 191
1 Bit O CTR-- DPT_Alarm 0/1 [In] [Switch/Sensor] Alarm: Breakdown or sabotage 1 = Alarm; 0 = No Alarm
-671088.64 -
2 Bytes CT--- 9.xxx [In] [Long Press] Constant Float Value Float value
670760.96
2 Bytes C T - - - DPT_Value_2_Ucount 0 - 65535 [In] [Long Press] Constant Integer Value 0 - 65535
1 Byte CT--- DPT_Scaling 0% - 100% [In] [Long Press] Constant Percentage Value 0% - 100%
1 Byte C T - - - DPT_Value_1_Ucount 0 - 255 [In] [Long Press] Constant Integer Value 0 - 255
331, 337 1 Bit CT--- DPT_Trigger 0/1 [In] [Long Press/Release] Stop Shutter Release -> Stop Shutter
1 Byte I C--W- DPT_Scaling 0% - 100% [In] [Long Press] Dimming Status (Input) 0% - 100%
332, 338
1 Byte I C--W- DPT_Scaling 0% - 100% [In] [Long Press] Shutter Status (Input) 0% = Top; 100% = Bottom

http://www.zennio.com Technical Support: http://support.zennio.com


86
Join and send us your inquiries
about Zennio devices:
http://support.zennio.com

Zennio Avance y Tecnología S.L.


C/ Río Jarama, 132. Nave P-8.11
45007 Toledo (Spain).

Tel. +34 925 232 002

www.zennio.com
[email protected]

You might also like