SE6166 / SE6104a

Single Equipment Controller

Automated Logic’s powerful SE line provides a rugged solution for single equipment applications. Designed to
operate in a wide range of environmental conditions, SE controllers can be used in rooftop units, mechanical
rooms, equipment closets, or almost any other weather tight location. Fully programmable using the EIKON®-
LogicBuilder graphic programming language, SE controllers use native BACnet communications over either a
high-speed ARCNET 156 Kbps network or a medium speed MS/TP network to provide maximum flexibility and
interoperability.

Key Features and Benefits


• Native BACnet communications to field devices over a high-speed ARCNET 156 Kbps or BACnet MS/TP
network.
• 12-bit Analog to Digital converter provides extreme precision on all inputs. Pulse counting capability up to 40
Hz is available on selected inputs.
• Uses a high-speed microprocessor with 1 MByte Flash memory and 1 MByte of RAM for unparalleled
programmability. Firmware upgrades can be downloaded remotely – no chip replacement necessary.
• Battery backed real-time clock provides true stand-alone capabilities. Control modules recover from power
failures providing full continuity of scheduled operations, even when communications are disrupted.
• Rnet port supports Automated Logic’s line of RS room sensors and BACview6 local operator interface, and
provides local access to the system.
• SE line controllers are fully graphically programmable and offer full peer-to-
peer communications with
other SE line, ME line or ZN line controllers. Graphical programs are
universally understood and provide
self-documenting control sequences. 1150 Roberts Boulevard
• Tough construction delivers superior performance and reliability. Control Kennesaw, Georgia 30144
modules are constructed with a rugged aluminum cover, which provides 770/429-3000
Fax 770/429-3001
optimum electrical protection and noise immunity. www.automatedlogic.com
SE6166 / SE6104a
Specif ications

BACnet® Support: Conforms to the Advanced Application Controller (B-AAC) Standard Device Profile as defined in ANSI-ASHRAE Standard
135-2004 (BACnet) Annex L. Tested to Protocol Revision 9
Communication: The following ports are available on the SE control modules:
EIA-485 port for ARCNET 156 Kbps or MS/TP (9600 bps – 76.8 kbps).
Rnet Port supports:
1. Local access for system start-up and troubleshooting.
2. Local operator interface BACview6.
3. RS Room Sensors - one RS Pro and up to four RS room sensors for averaging or high/low select control.
Binary Outputs: SE6166 and SE6104a have six binary outputs, relay contact rated at 3A max @ 24 V-ac, configured normally open with
hand-off auto switches.
Universal Inputs: SE6166 - 16 configurable universal inputs, SE6104a - 10 configurable universal inputs, both with 12-bit A/D resolution.
Supported input types include: 0-5 V-dc, 0-10 V-dc, 0-20 mA, Thermistor (10k Ohm Type II), 1k Ohm RTD (Platinum, Nickel
or Balco), and Dry Contact.
NOTE: Inputs 1 and 2 support pulse counting up to 40 cycles per second (40 Hz).
Analog Outputs: SE6166 - six analog outputs, SE6104a - four analog outputs, both with 0-10 V-dc or 0-20mA selectable with 8-bit resolution.
Microprocessor: High speed microprocessor with ARCNET communication co-processor.
Memory: 1 MByte non-volatile battery-backed RAM, 1 MByte Flash memory, 16-bit memory bus. (Shelf life of the battery is 10 years
with 10,000 hours of continuous operation.)
Real-time Clock: Battery-backed real-time clock.
Status Indicators: LED status indicators for EIA-485 communication, running, error, power and all digital outputs.
Module Addressing: Rotary dip switches for intuitive network addressing of modules.
Protection: Built-in surge and transient protection circuitry for power, communications, inputs and outputs.
Listed by: UL916 (Canadian Std C22.2 No. 205-M1983), CE, FCC Part 15 – Subpart B – Class A.
Environmental Operating Range: -20ºF to 140ºF (-29ºC to 60ºC); 10 to 90% relative humidity, non-condensing.
NOTE: Control modules should be mounted in protective enclosures.
Power Requirements: 24 V-ac ± 10%, 50 to 60Hz, 20VA.
NOTE: Power consumption will increase when BACview or other accessories are attached.
Physical: Rugged aluminum cover. Removable screw terminal blocks.
Weight: 0.6 lb. (0.27 kg).
Dimensions:
Overall Mounting
Width: 8.3” (211mm) Width: 7.835”(199mm)
Height: 7” (178mm) Height: 5” (127mm)
Depth: 1.5” (38mm) min. panel depth 5” mounting hole spacing

Automated Logic Corporation . 1150 Roberts Boulevard . Kennesaw, Georgia 30144 . 770/429-3000 . Fax 770/429-3001 . www.automatedlogic.com
© United Technologies Corporation 2013. All rights reserved. Copyright Policy
BACnet is a registered trademark of ASHRAE. All other trademarks are the property of their respective owners. Specifications are subject to change without prior notice.
Automated Logic is a part of UTC Building & Industrial Systems, a unit of United Technologies Corp
Made in the USA SE_CS_11062014