Datasheet CS1-PR PDF
Datasheet CS1-PR PDF
CS2-VA
with high accuracy measurement, display and
communication of DC signal 0~10V and 4(0)~20mA.
They are also available 1 option of 1 Relay outputs, 1
Analogue output or 1 RS485(Modbus RTU Mode) interface
with versatile functions such as control, alarm,
CS1-PR
− − −
Input Optional Excitation Aux.
CS1−PR− Signal Output Supply Powered
OPTION
CODE INPUT RANGE CODE OPTIONAL O/P CODE EXCIT. SUPPLY CODE AXU. POWER
A1 0(4) ~ 20mA / 0 ~ 10mA N None N None A AC115/230V
V1 0 ~ 10V / 0(1) ~ 5V R1 1 Relay E24 DC 24V OPTION 4
C1-01-1/7-2007-11-07
CSM-321S
RS 485 Communication(option)
Protocol: Modbus RTU mode INSTALLATION
Baud rate: 1200/2400/4800/9600/19200/38400 programmable The meter should be installed in a location that dose not exceed the
8 bits
CS2-VA
Data bits: maximum operating temperature and provides good air circulation.
Parity: Even, odd or none (with 1 or 2 stop bit) programmable
Address: 1 ~ 255 programmable
Remote display: to show the value from RS485 command of master
Distance: 1200M RL COM
CI1
ENT/FN
RS 485 port
Panel cutout: 92mm(W) x 44mm(H)
Case materiel: ABS fire-resistance (UL 94V-0) Please check the voltage of power supplied first, and then connect
Mounting: Panel flush mounting to the specified terminals. It is recommended that power supplied to
Terminal block: Plastic NYLON 66 (UL 94V-0) the meter be protected by a fuse or circuit breaker.
10A 300Vac, M2.6, 1.3~2.0mm2(16~12AWG) Power Supply
Weight: 350g / 300g(Aux. Power Code: ADH or ADL)
6 7 8 9 10
CSM-321S CSM- CSM-321S CSM- CSM-321S CSM-
Power 1A Fuse
Power supply: AC115/230V,50/60Hz; L L AC115/230V
Optional: AC/DC 85~264V or 20~90V(RoHS version)
N N AC85~264V
G G
Excitation supply: DC24V/30mA maximum in standard
Filter or Transformer
Power Consumption: 4.5VA maximum
Back up memory: By EEPROM 2 wire Transmitter connection RS485 Communication Port
4~20mA 24Vdc
Input Excit.S
FRONT PANEL 11 12 13 14 15
Max. Distance: 1200M
Terminate Resistor
(at latest unit):
A B 120~300ohm/0.25W
Max. Hold status (typical: 150ohm)
Relay status
Indication RL1 COM
M.H
Comm. status 4 5 6
CI11
Front Key
RS485 Port
M.H function status
Display screen
ENT/FN ? ? ? Kg/cm 2 Mini. Hold status
Operation Key
Engineer Unit
FUNCTION DESCRIPTION
DIMENSIONS Input & Scaling Functions
Dual input types: (Option Code: AV)
Voltage and Current Type are in one unit available in option. If the
customer specify the input coding for AV, the meter will be calibrated for
FRONT VIEW 48.0 0~10V and 0~20mA in factory. The user can use in 0~10V or4(0)~20mA
by difference terminals connection(#11 & #13 for 0~10V or #12 & #13 for
4(0)~20mA) and programming in 【Ai.tYP】of【inPUt GroUP】.
96.0 8.0 60.0
12.0 Scaling function:
Setting the Lo.SC(Low scale) and Hi.SC(High scale) in【inPUt
Dimensions: 96mm x 48mm x 72mm GroUP】to relative input signal. Reverse scaling will be done too.
PANEL CUT-OUT 44.0+0.2 Panel Cutout: 93mm x 45mm (advise) Please refer to the figure as below,
SC ALE D e fa u lt: L o .S C : 0 .0 0 , H i.S C : 1 0 0 .0 0
Unit: mm C h a n g e to L o .S C : 5 0 .0 0 , H i.S C : 1 9 9 .9 9
92.0+0.2 1 9 9 .9 9
R e ve rs e s lo p
1 0 0 .0 0
5 0 .0 0
0 .0 0 IN P U T
0 .0 0 % 5 0 .0 0 % 1 0 0 .0 0 %
*Too narrow scale may course display lower resolution.
C1-01-2/7-2007-11-07
Display & Functions Digital fine adjustment:
Max / Mini recording: The meter will storage the maximum and minimum value in Users can get Fine Adjustment for Zero & Span of PV by front key of
【User Level】during power on in order to review drifting the meter, and “Just Key In” the value which user want to show in
the current input signals.
CS2-VA
of PV.
Display functions: PV / Max(Mini) Hold / RS 485 programmable in Especially, the【Pv.Zro】&【Pv.SPn】are not only in zero & span of
(Please refer to step A-07) 【dSPLY】function of【inPUt GroUP】 PV, but also any lower point for
【Pv.Zro】& higher point for
【Pv.SPn】.
Present Value Pv: The display will show the value that The meter will be linearization for full scale.
Relative to Input signal. The adjustment can be clear in function【Z.S.CLr】.
Maximum Hold Max.H / Minimum Hold Mini.H : D e fa u lt In p u t: L o .S C : 0.0 0 , H i.S C : 1 9 9 .9 9
The meter will keep display in maximum(minimum) D ig ita l fin e ad ju t.: in p u t 2 .7 5 V ,
CS1-PR
sending. In past, The meter normally receive Average set to be 3
or 0~10V from AO or digital output from BCD module Sample 1 Sample 2 Sample 3 Sample 4 Sample 5 Sample 6 …….
of PLC .We support a new solution that PV shows
the value from RS485 command of master can so Display Update Value = Display Update Value =
(Sample 1 + Sample 2 + Sample 3)/3 (Sample 4 + Sample 5 + Sample 6)/3
that can be save cost and wiring from PLC.
Remark: The higher average setting will cause the response time of Relay and Analogue output slower.
Front key functions: Relative PV / PV Hold / Reset for maxi(mini) hold /
be Pv. HLd function. When user press the key, Display Update Value = (Sample 4 + Sample 5 + Sample 6)/3
the display will be hold until press the key again. Remark: The higher moving average setting wouldn’t cause the response time of Relay and Analogue
output slower after first 3 samples.
¾ Please find the PV.H sticker to stick on the right
side of square red LED. Digital filter: The digital filter can reduce the magnetic noise in field.
PV Hold & Reset
Present PV Hold Control functions(option)
Value Relay energized mode: Hi / Lo / Hi.HLd / Lo.HLd programmable
Hi: Relay will energize when PV > Set-Point
Lo: Relay will energize when PV < Set-Point
Reset PV Hold
Hi / Lo Relay Energized
O ON Edge ON
by Front
DownKey N Trigger Hi Setting
Low Cut is set for 0.50, if the PV is Low Cut is set for -0.10, if the PV is under
from -0.50~+0.50, that display will be 0. (< = -0.10), that display will be -0.10.
C1-01-3/7-2007-11-07
Energized functions: Start delay / Energized & De-energized delay / Hysteresis RS 485 Communication(option)
Start Delay Energized / De-energized The RS485’s protocol is Modbus RTU mode, and baud rate up to
Delay & Hysteresis 38400 bps. It’s convenience to remote monitoring, display for
CS2-VA
Inhibit
Hi Setting
reading.
Inhibit
De-energized
Hi Setting
delay time
Hysteresis RS 485 Modbus RTU Mode (up to 38400bps)
Relay Relay
Energized Start Delay Time ON Energized ON 1 Relay Output:
Mode: High or Low Energized
Functions: Start delay / Energized &
De-energized delay / Hysteresis
CSM- CSM-321S CSM-
COM COM
RL1 RL1
Display:
Analogue output(option) ENT/FN ◄ ▲ ▼ RPM
EN ◄ ▲ ▼
Kg/cm
Mode: Measuring Value / Maximum Hold /
Minimum Hold / Reading value from
RS485 command
2
ENT/FN ◄ ▲ ▼ Kg/cm
M.H
ERROR MASAGE
DESCRIPTION DISPLAY FLASH REMARK
BEFORE POWER ON, PLEASE CHECK THE SPECIFICATION AND
CONNECTION AGAIN.
SELF-DIAGNOSIS AND ERROR CODE:
: Display is positive-overflow (Signal is over display range) (Please check the input signal)
: Display is negative-overflow (Signal is under display range) (Please check the input signal)
: ADC is positive-overflow (Signal is higher than input 120%) (Please check the input signal)
: ADC is negative-overflow (Signal is lower than input -120%) (Please check the input signal)
: EEPROM occurs error (Please send back to
/ manufactory for repaired)
: Calibrating Input Signal do not process (Please process Calibrating
/ Input Signal)
: Calibrating Input Signal error (Please check Calibrating Input
/ Signal)
(Please process Calibrating
/ : Calibrating Output Signal do not process Output Signal)
(Please check Calibrating
/ : Calibrating Output Signal error Output Signal)
C1-01-4/7-2007-11-07
FRONT PANEL:
Operating Key: 4 keys for Enter(Function) /
CS2-VA
Relay status Max. Hold status
Indication RL1 COM
M.H
Comm. status Shift(Escape) / Up key / Down key
CI11
CS1-PR
Stickers: z User Level: User Level lock. User can get into User Level for
Each meter has a sticker what are functions and engineer checking but setting.
label enclosure. z Programming Level: Programming level lock. User can get
into programming level for checking but setting.
z Relay energized mode: H H H i L o L L D O
z ALL: All lock. User can get into all level for checking but
z Down key functions mode:
setting.
C1-01-5/7-2007-11-07
OPERATING DIAGRAM (The detail description of operation, please refer to operating manual.)
Power ON
CS2-VA
Self-diagnosis
User Level
Press for 1 sec. can back to Measuring
Show the This page will Min:PV model number
0−0−1
0−3
0−6
model number show out, Minimum firmware
CSM- CSM-321S CSM-
0−4
0−0−1
the firmware 1 Set-point Maximum page
version setting storage
-19999~+29999 Checking only
MEASURING rY.rSt: Reset M.rSt: Reset
0−2
0−5
PAGE for energized for Maximum &
Press 1sec Latch of Relay Minimum
YES no storage
Press 1sec
ENT YES no
Enter the
password to
access
CS1-PR
ENT
programming
Level
NO
Pass Code
Programming Level
YES
▼
▲
CSM-321S CSM- CSM-321S CSM- CSM-321S CSM-
▼
INPUT RELAY ANALOGUE RS485
GROUP GROUP OUTPUT GROUP
▲
B−1
D−1
E−1
D−2
E−2
B−3
D−3
E−3
B−4
D−4
B−5
D−5
B−6
D−6
C1-01-6/7-2007-11-07
Z.S.CLr: Clear
A−6
CS2-VA
PV display
nonE Pv.Zro
Pv.SPn botH
dSPLY:
A−7
Display
Function
Pv Mini.H
Cut Function
-19999~+29999
AvG: Average
A−9
update for PV
1(None)~
99 times
M.AvG:
A−10
Moving
Average
update for PV
1(None)~
10 times
d.FiLt: Digital
A−11
filter
0(None)/1~99
CS1-PR
times
dn.KEY:
A−12
Down key
function
nonE rEL.Pv
Pv.HLd M.rSt
Function Level
Lock
nonE USEr
EnG ALL
C1-01-7/7-2007-11-07