100% found this document useful (1 vote)
362 views4 pages

Model:KM2800: Rating Range

This document summarizes the specifications of a 2750kVA diesel generator set. It includes: 1) Key features such as one-source responsibility from Kohler Co., prototyped testing, and a one-year warranty. 2) Technical specifications of the generator including a Mitsubishi engine, Marathon alternator, 400V output, and 95.5% efficiency. 3) Dimensions and weights of 7062x2859x3072mm and 17550kg dry weight.

Uploaded by

T.S. Anklesaria
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
362 views4 pages

Model:KM2800: Rating Range

This document summarizes the specifications of a 2750kVA diesel generator set. It includes: 1) Key features such as one-source responsibility from Kohler Co., prototyped testing, and a one-year warranty. 2) Technical specifications of the generator including a Mitsubishi engine, Marathon alternator, 400V output, and 95.5% efficiency. 3) Dimensions and weights of 7062x2859x3072mm and 17550kg dry weight.

Uploaded by

T.S. Anklesaria
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Model:KM2800

380 - 415V

Standard Features:
Rating Range • Kohler Co. provides one-source responsibility for the
generating system and accessories
KM2800
• The generator set and its components are prototyped-tested,
50Hz
factory-built and production tested
kW 2200 • The generator set complies with ISO8528-5, G3 requirement
Standby
kVA 2750 for transient performance
kW 2000 • A one-year limited warranty covers all systems and
Prime components.
kVA 2500
• 100% one step load
• MHI engine
• Marathon alternator
• Operation manual

Generator Rating
Standby Rating Prime Rating

Alternator Voltage Ph Hz kW/kVA Amps kW/kVA Amps

MXL-2000-4 400 3 50 2200/2750 3969 2000/2500 3609

380 3 50 2200/2750 4178 2000/2500 3609


MXL-2000-4J
415 3 50 2200/2750 3826 2000/2500 3478
Alternator Specification
• NMEA MG1,IEEE and ANSI standards compliance for
temperature rise and motor starting Specification Alternator

• IP23 Manufacturer Marathon


• Insulation: Class H Type 4 Pole
• 2/3 Winding Pitch Leading Wire 6
Specification 50Hz AVR DVR2000E+
Voltage 400V Excitation system PMG
Standby (27℃),kVA 2750 Insulation/Temp rise H/H
Continuous (40℃), kVA 2625 Bearing Double
Efficiency (100% load) 95.5% Voltage regulation ±0.25%

Specification
Engine Engine Electrical
Engine Specification Engine electrical
Manufacturer Mitsubishi System Voltage (DC) 24
Model S16R2-PTAW2-E Battery ,CCA 4,1200
Engine Type Turbocharged Battery voltage (DC) 12
Cylinder 16V
Displacement, L 79.9 Lubrication
Bore and stroke, mm 170 x 220 Lubrication system
Compression ratio 14:1 Oil capacity (L) 200~260
Piston speed, m/s 11 Total Oil capacity (include filter) (L) 290
Rated speed (r/min) 1500 Min. oil pressure (bar) 2~3
Max standby power, kW 2430 Max. oil pressure (bar) 4~6
Governor Type Electrical
Frequency regulation ±0.25%
Air cleaner type Dry

Exhaust
Exhaust system
Exhaust flow at rated power, 𝑚3 /𝑚𝑖𝑛 506
Max back pressure, mm𝐻2 𝑂 600
Exhaust outlet size, mm See ADV
Controller
Specification
Cooling System
Cooling System
Ambient temperature (standby) ℃ 40
Decision-𝐌𝐚𝐫𝐤𝐞𝐫 𝐓𝐌 4000
Coolant capacity (only engine) L 190
Standard Feature
Coolant capacity (radiator), L 665 • Large LCD Display
Heat rejected to jacket water (kW) 960 • Unique control wheel for system access
Heat rejected to charge cooling water (kW) 692 • User buttons for start, stop, menu and escape
Fan diameter (mm) 2134 • Emergency stop button
• On/off key switch
Fan loss (kW) 100
• Panel-mounted battery fuse
Max. restriction of cooling air, intake and • Panel-mounted USB ports for PC access and software
150
discharge side of radiator (kPa) upgrade
Radiator cooling air flow 𝑚3 /𝑚𝑖𝑛 3300 • Password-protected access to control parameter
• Upgradeable software for future enhancements
LCD Panel Feature
Air requirement • 600 x 800 resolution
3
Combustion, 𝑚 /𝑚𝑖𝑛 191 • Multiple lines of text or graphic display
3 3 • Icons for quick identification of system status
Air Density =1.20 𝑘𝑔/𝑚 (0.075 𝑙𝑏/𝑓𝑡 )
• 6 language: Chinese, English, French, German,
Portuguese and Spanish
Fuel Consumption Communication Features
• Engine communication via CANbus
Diesel , L/h load% Standby
• Modus communication via RS485 or Ethernet
100% 586.1 • PC and flash drive connection via USB
Diesel , L/h load% Prime Function
100% 527.6 • View and adjust system operation parameters
• View system faults
75% 428.8
Viewable/Selectable Parameters (may require
50% 288.7 optional module)
25% 154.4 • Voltage/Current/Frequency
• Power (active/reactive/apparent)/Power factor
• Engine speed/Oil pressure/Coolant temperature/Battery
Voltage/Fuel level (%)/Time delays
Viewable Faults (over 60 individual faults are
monitored) including:
• Alternator protection
• Circuit breaker and grounding fault protection
• Communication and engine EMC monitor
• Cooling air monitoring
• Electrical charging system
• Engine cooling system
• Engine lube system
• Fuel system
• Generator set status
KOHLER CO., Kohler Power Systems
Kohler, Wisconsin 53044 USA 400 1808 900
Phone +1 (920)-565-3381 [email protected]
Kohler Power.com

Standard Configuration Dimension and weight


• Diesel engine
• Mechanical cooling system
• IP23 alternator:
- Space heater
- DVR2000E+
- PMG
- Winding PT100
- Rotor PT100
⚫ DEC4000 Controller (with battery charger)
L x W x H (mm): 7062 x 2859 x 3072
Option Dry weight (kg): 17550
• Coolant Heater Wet weight (kg): 18475
• Coolant and oil
• Spring isolator
• Battery kits