LR-G200 Rebar Scanner PDF
LR-G200 Rebar Scanner PDF
Operating Instructions
1 Overview ......................................................................................................................1
1.1 Introduction ...............................................................................................................1
1.2 Functions and characteristics..................................................................................1
1.3 Technical indicators..................................................................................................2
1.4 Performance Indicators............................................................................................4
1.5 Precaution ..................................................................................................................4
1.6 Responsibility.............................................................................................................6
2 Instrument Description.............................................................................................7
2.1 Instrument Composition..........................................................................................7
2.2 Testing Principle .......................................................................................................9
3 Operation Descriptio .................................................................................................9
3.1 System Overview .......................................................................................................9
3.2 Function description ..............................................................................................10
3.3 Firmware upgrading ...............................................................................................44
4 Maintenance and repair ..........................................................................................45
4.1 Pre-operation inspection .......................................................................................45
4.2 Cleaning ....................................................................................................................45
4.3 Battery.......................................................................................................................45
5 Precautions on field detection...............................................................................46
6 Metering and calibration.........................................................................................47
7 Data analysis software description.......................................................................49
7.1 Introduction..............................................................................................................49
7.2 Software installation...............................................................................................50
7.3 System setting ..........................................................................................................51
7.4 Receiving component data ....................................................................................52
7.5 Data processing .......................................................................................................54
7.6 Upgrading .................................................................................................................58
1 Overview
1.1 Introduction
LR-G200 integrated rebar scanner is a portable intelligent NDT device, which is
mainly used for structural testing of reinforced concrete, and able to carry out
accurate testing on depth of rebar cover and diameter of rebar on the surface of
reinforced concrete, and analyze distribution of rebar.
1.2 Functions and characteristics
1. The instrument sensor is of integrated structure in small size, thus permitting
easy operation.
2. Carry out testing with combination of high-power transmitting coil and
multiple small coil to ensure higher accuracy and resolution.
3. Perform displacement scanning and rebar distance measurement at a higher
accuracy level with use of high-accuracy grating sensor.
4. Provide different types of scanning to suit the different measurement cases.
5. Permit large and small-range testing, with the scanning distance up to 65m
max. Perform data testing in a flexible way. The instrument itself allows storage
of max. 4000 components.
6. Permit correction of multiple stirrup so as to obtain more accurate testing
results.
7. Furthermore, the USB wire data transmission and Bluetooth wireless data
1
transmission are allowed so that the quick data uploading is possible.
8. Use 3.2"65K color LCD screen to yield the higher resolution and better display,
plus the capacitive touch screen, thus facilitating the man-machine interaction.
9. Perform power supply with use of 8.4v 3200mah high capacity lithium-ion
battery to ensure that the instrument can continuously operate around-the-clock.
1.3 Technical indicators
2
Detailed specification on testing of concrete cover depth
Range Small Large
Dia.
6 2~70 2~97
8 2~70 2~97
10 2~75 3~100
12 2~75 3~107
14 2~75 3~117
16 3~85 3~120
18 3~85 3~125
20 3~85 3~137
22 3~85 3~140
25 3~90 3~145
28 3~90 3~145
32 4~95 4~155
36 4~95 4~155
40 4~95 5~185
50 6~100 6~200
3
1.4 Performance Indicators
Performance indicators on LR-G200 integrated rebar scanner
Quick scanning Fine scanning Profile scanning Grid scanning
Yes Yes Yes Yes
Data correction Way of power Instrument
supply weight Screen size
Yes Lithium battery 1KG 3.2"
Image Range of Mode of data
scanning 3-D imaging
scanning transmission
Yes Yes Unbounded Bluetooth or US
Laser positioning Touch screen Screen lattice Instrument size
operation
3-wire Yes 320x240 235x120x130
1.5 Precaution
1. Please carefully read the instructions prior to use.
2. Expected operating environment:
Ambient temp.: -10℃~40℃
Relative humidity: <90%RH
Electromagnetic interference: no strong alternating electromagnetic field
4
Exposure to direct sunshine for an extended period prohibited
Corrosion control: take necessary measures to ensure proper operation at the
humid, dust and corrosive gas environment.
3. Expected storage environment:
Ambient temp.: -20℃~50℃
Relative humidity: <90%RH
In case of out of use for an extended period, please regularly switch on the instru-
ment and recharge it. The instrument shall be placed at a well ventilated, cool
and dry location without repeated exposure to direct sunshine.
4. Prevent moisture impact, and operation at the intense magnetic fields, such as
in the vicinity of large electrical magnet, transformer, VFD, etc.
5. Vibration control: take measures to prevent violent vibration and impact during
operation and handling.
6. Charge management: the instrument is recharged with the rechargeable
lithium battery. In case of low battery, recharge the instrument without delay to
avoid battery damage. Perform recharge with the recharger specific to the instru-
ment rather than other types of adapter or recharger, which may otherwise lead
to battery damage.
7. Maintenance: conduct proper cleaning at the end of operation every time to
prevent declined performance or property damage due to dust presence in the
5
instrument or plug connector.
1.6 Responsibility
The instrument is a precision detector. We will bear no responsibility in case of
the following user operations being identified.
1. Incompliance with the above working environment requirements or storage
environment requirements.
2. Non-standard operation.
3. Unauthorized removal of the casing and parts.
4. Serious instrument damage by operator or accident.
6
2 Instrument Description
2.1 Instrument Composition
The instrument consists of main machine, specific charger and attachment.
2.1.1 Main Machine
LR-G200 integrated rebar scanner is illustrated below.
7
2.1.3 Key Description
Note: Refer to the related chapters for details on function of each key.
8
2.2 Testing Principle
The instrument will generate the pulsed magnet field via high-current excitation
transmitting coil. In case of rebar being detected underneath the magnetic field,
the rebar will produce the turbulence at the excitation of pulsed magnet field, and
then make an induced magnetic field. The receiving coil will convert the induced
magnetic field to an electrical signal. The main machine performs real-time analysis
of the electrical signal, and then identify the location of rebar, concrete cover
depth and diameter. The receiving coil is configured in a multiple set of coil
combination, thus yielding the higher testing accuracy against the traditional coil
testing in a single way.
3 Operation Description
3.1 System Overview
LR-G200 Integrated rebar scanner system is designed to assure indication of each
function menu, instrument status, measurement data and result. The man-machine
interaction for the entire system is achieved through the key and touch units,
which is easier to operate than the traditional simple key operation.
3.1.1 Interface Description
The system interface mainly contains the menu selection and data result display,
in which there are title display zone and content display zone. In the title display
zone, the current interface title, Bluetooth device and USB interface readiness
9
and instrument battery status appear. In the content display zone, the main
content in the current interface appears.
3.1.2 Operation Method Description
The user can work via key or touch screen. Use of touch screen is more convenient
so we recommend to run the instrument with touch screen.
Key operation: the user can select the desired menu via Up or Down key in each
interface, and confirm with【OK】key. Exit or cancel with【C】key.
Touch screen operation: the user can work with the icon in the touch screen.
3.2 Function description
The instrument is designed for rebar detection, data view, data uploading, data
deleting, system setting, instrument information, etc. The main interface of the
system is illustrated in Fig.3.1
Key:
【 】key: view the measurement data in the previous page during detection
【 】key: view the measurement data in the next page during detection
【�】key: keep pressing the key to estimate the diameter of rebar being
scanned, and instantaneously press for instrument self-calibration.
【C】key: exit the profile scanning
Touch operation: complete appropriate operation in the field corresponding to
the touch status bar.
18
3.2.1.4 Fine scanning
The mode of fine scanning provides the real-time indication of waveform of the
rebar being detected, rebar location, concrete cover depth, center-to-center
distance of neighboring rebars, estimated diameter, etc. in the waveform
diagram. The user may also manually add or delete the measuring point of rebar
according to the waveform distribution pattern.
It is required to determine the location of rebar in a real-time manner under the
quick scanning. Thus, the quick scanning is not suitable for scanning of heavi-
ly-distributed rebar. The fine scanning is specifically designed for heavily-distrib-
uted rebar. The fine scanning interface is illustrated in Fig.3.6.
19
In the fine scanning interface, locate the instrument on the surface of object to
be measured, and slowly move to the right to start measurement. The signal
waveform will appear in the screen, and the real-time displacement value will
appear in the bottom left of screen. The signal value starts to increase with the
instrument approaching the rebar, and the waveform curve slowly rises. When
the instrument moves far from the rebar, the waveform curve slowly lowers
down. Now, a peak may appear. The location of peak is just the location of rebar.
A white line appears at the peak, indicating that there is a rebar here. The
concrete cover depth for the rebar will appear above the peak. When a number
of rebar is detected, the instrument will automatically calculate the rebar
distance, to be displayed below the waveform.
In case of intensive distribution of rebar distance occurring during detection, the
waveform signal will get gentle, wider than the waveform signal in the single
rebar waveform diagram. Now, the instrument has to make judgment on rebar
location in combination with variation in the neighboring waveforms. Thus, the
delayed determination of rebar location may occur.
It is required to switch to the pretty heavily-distributed rebar mode in case of
need to measure the heavily-distributed rebar. In the detection interface, press
the Down key to switch to the pretty intensive rebar mode. Under the pretty
intensive rebar mode, slowly move the trolley at constant speed to assure detection
20
accuracy. Press the Down key again to return to the intensive rebar mode.
When the scanning distance is beyond the range of screen display, the instrument
will automatically conduct screen scrolling for display, and permit max. 10m
range of scanning.
The following operations are allowed in the fine scanning:
Key:
【 】key: view the measurement data in the previous page during detection
【 】key: view the measurement data in the next page during change on mode of
detection or during detection
【�】key: keep pressing the key to estimate the diameter of rebar being scanned,
and instantaneously press for instrument self-calibration.
【FN】key: keep pressing the key to go to the manual addition and deletion of
measuring point interface
【C】key: exit the fine scanning
Touch operation: keep pressing the waveform display field in the touch screen to
go to the manual addition and deletion of measuring point interface to complete
appropriate operation in the field corresponding to the touch status bar.
In case of unacceptable waveform signal or deviation in rebar determination
occurring during detection, you may withdraw to the left to erase the waveform
with determination deviation, and restart scanning. Alternatively, you may keep
21
pressing【FN】key at the end of scanning or keep pressing the waveform display
field in the touch screen to go to the manual addition and deletion of measuring
point interface, as illustrated in Fig.3.7. Now, the user is allowed to manually add
or delete the rebar measuring point in the interface.
The following operations are allowed in the manual addition and deletion of
measuring point interface.
Key:
【 】key: instantaneously press the key to move the cursor to the location of last
signal. Keep pressing for quick move
【 】key: instantaneously press the key to move the cursor to the location of next
signal. Keep pressing for quick move
【FN】key: add or delete a rebar at current position
【C】key: exit the fine scanning
Touch:
Touch the waveform data display field to move the cursor to the location where
the rebar needs to be added or deleted. In case that rebar addition at the current
position is allowed, the rebar button in the top of screen is highlighted. Now, you
can touch the button for rebar addition. Similarly, when the button for rebar
deletion is On, touch the button for rebar deletion.
22
Fig.3.7 Manual rebar addition/deletion
measuring point interface for fine scanning
Note:
Max. 10m scanning is permitted under fine scanning.
With access to the manual addition/deletion measuring point function under fine
scanning, the instrument is not able to return to continue measurement of this
component.
Set to the intensive rebar mode in default under the fine scanning. Measurement
of most intensive rebars can be accomplished under the fine scanning. For the
pretty intensive rebar measurement, press the Down key to switch to the pretty
intensive rebar mode, in which the rebar diameter has to be correctly set.
Conduct scanning slowly at constant speed to assure accuracy of sampling data.
23
3.2.1.5 Grid scanning
31
Fig.3.13 Fine scanning
32
Fig.3.15 Image scanning
Note:
1. The title bar of component data graphic display interface mainly provides
information on the scanning type of the component, no. of component and
design diameter; the graphic display field provides information on location,
depth and distance of measuring point in the measurement data in graphics.
2. In the graphic display interface of image scanning component data, you will
see the summary of all measurements first, as illustrated in Fig.3.16. The user
shall press the down direction key to select the scanning location to be viewed,
and then press【OK】key to go to the graphic data view interface for selection of
scanning location.
33
Fig.3.16 Scanning location view interface with image scanning
34
Fig.3.17 Quick scanning
35
Fig.3.19 Fine scanning
36
Fig.3.21 Grid scanning at the vertical direction
39
Fig.3.24 Data deletion process interface
Note:
1. Figure out if the data are uploaded to the computer prior to data deletion since
the data are not retrieved after deletion.
2. The instrument is not configured to cancel with key or touch during data
deletion.
3.2.4 Data uploading
It is advisable to upload the data to the computer on completion of data detec-
tion or with the memory nearly fully loaded. The user can upload the data via
USB or Bluetooth interface. For Bluetooth transmission, which is an extended
function, the specific mobile phone software is required to complete uploading.
The user may make choice as required. Only USB transmission is outlined below.
40
USB transmission is carried out in steps below:
1. Conduct wiring to the instrument and computer via specific USB data cable;
2. Switch on the instrument;
3. Activate the Langrui rebar scanner management software already in the
computer;
4. Click the import component data menu in the menu bar;
5. Select the component data requiring uploading, and click the upload to start
uploading the data;
6. Wait until data transmission ends.
3.2.5 System setting
The system setting menu interface is designed to provide the user with the
system setting parameter information for his/her own adjustment, including the
power saving setting, sound setting, date setting, scan setting and system
management, as illustrated in Fig.3.25.
3.2.5.1 Power saving setting
In the power saving setting, the user can set the backlight brightness, standby
time, automatic shutdown time and horizontal laser light switch. At factory
delivery, the backlight brightness is set at 50% brightness, standby time at
10min., automatic shutdown time at 25min., and horizontal laser light On. The
user may make setting himself/herself whenever required, which can be accom-
41
plished via key and touch screen.
42
The scan setting menu covers the stirrup distance, range selection and rebar type.
Stirrup distance: during field detection, it is necessary to pre-scan the stirrup
distance. In case of less than 120mm, set the parameter at [100], [80], [60] and [40]
on a case-by-case basis. Now, the instrument will undergo the appropriate
compensation correction. In case of stirrup distance above 120mm, set the
parameter at [>120].
Range selection: select the small range for the small depth of rebar cover being
measured. Otherwise, switch to the large range mode. Make selection on a
case-by-case basis.
Rebar type: it includes the deformed bar and round steel.Make the appropriate
setting based on the type of rebar being detected. Ensure correct setting on rebar
type prior to detection, which may otherwise affect the measurement accuracy.
3.2.5.5 System management
Bluetooth-based uploading: instrument's extended function, to be used with the
specific mobile phone software.
Language selection: select the different operation language depending on the
user's need.
3.2.6 About device
The About device menu provides the information on the device, as illustrated in
Fig.3.26, including the following:
43
Instrument type and name
Firmware version no.
Device no.
Company contact tel.
Company website
48
7 Data analysis software description
7.1 Introduction
The rebar detection data analysis software is a multi-function analysis software
developed by Jinan Langrui Detection Technology Co., Ltd. for processing the
rebar detection data. The software can run in XP/win7/win10 OS, presenting
friendly interface and easy operation, which is specifically designed for project
detection staff.
1)Conduct management on all component information as well as the detection
data at each measuring point;
2)Conduct analysis and evaluation on detection data according to the construc-
tion quality acceptance criteria;
3)Display the component data in a graphic way;
4)Generate a detection data file through integration of several ones; it is easy to
add or remove the detection data;
5)Print the preview and export treatment results;
6)It is easy to import the rebar scanner data into the computer with use of the
software to facilitate further analysis and archive;
7)Automatically generate the detection report in word format.
The data files saved in the software has the file extension name in . xgjy format.
The detection report automatically generated has the file extension name in
49
.docx format.
7.2 Software installation
7.2.1 Installation of port driver
LR-G200 rebar scanner is furnished with the program U-disc. Please attach the
U-disc to the available USB port in the computer prior to operation. Activate the
U-disc and find out the port driver folder and open it. Double click the installation
program“setup”dialog box and then click“INSTALL”.
Start installation. Later, the“Driver pre-installation success”may appear in the
screen and click Ok. Next, attach the computer USB communication port to the
rebar scanner USB port via communication cable. Switch on the rebar scanner,
and the computer will show that the new hardware has been located. Several
minutes later, you may start operation on completion of hardware identification.
If you are asked to confirm the authorized selection, please select“Ok”and
confirm.
7.2.2 Software installation
The rebar scanner is furnished with the program U-disc. Please attach the U-disc
to the available USB port in the computer prior to operation. Activate the U-disc
and find out the“Rebar scanner online system”folder and open it. Double click
the installation program“setup-x.x”and open the installation wizard. Please
complete installation as instructed and operate it.
50
★ Please tick the option to generate a desktop shortcut. Then, you can run the
software by double clicking the desktop shortcut.
7.3 System setting
52
appears. The software provides the automatic port identification function. If the
rebar scanner host computer is correctly attached to the computer, and main-
tained online, the software can automatically identify the communication port
and Baud rate, and display it. If the software fails to identify the communication
port or the communication port is incorrect, please click the“Refresh”in the
dialog box.
54
When the data are uploaded, select the component no. in the left navigation bar,
and fill out and set the component information in the right item box. Further-
more, you can view the detection results on the component.
Grid scanning and image scanning can display 3D stereogram and plan in the
right graphic display box.
55
Display the waveform schematic via fine scanning
56
7.5.2 Report generation
Click the title bar“Data processing (D)”→ Generate report to generate a report. A
report no. (for example, Report 001) may appear in the“Detection report”bar in
the left navigation bar. Click the “Report 001” to display the report fillout
interface. In the right report composition option, select the report type and tick in
the square box before the data in the bottom the data requiring report generation.
After completing the report, you may select print preview to print the report.
★In the print pre-view, click“Export word”to save the pre-viewed report in word
format.
57
7.5.3 Data deletion
If you want to delete a component, click selection and press“Data processing (D)
”→“ Delete component”to delete the selected component.
★The deleted component goes to the list of deleted components, in which you
may select the component deleted by mistake and retrieve it.
7.5.4 Data save
The original data or completed report can be saved in the computer. Click the
title bar“File (F)”→“ Save”to save the file in a format of .xgjy.
7.6 Upgrading
The user can manually carry out software upgrading and firmware upgrading.
The computer shall be attached to the internet.
Software upgrading: click the title bar“Help”→“ Check new version”so that the
software will automatically check for latest version of software. If so, the comput-
er may ask the user if upgrading is required. Click“Upgrade”to start automatic
upgrading.
Firmware upgrading: attach the rebar scanner to the computer’s USB port via
data cable. Switch on the rebar scanner, and click the software title bar“Rebar
scanner”→“ Upgrade the rebar scanner”so that the software may automatically
check for latest version of firmware software. If so, the computer may ask the user
if upgrading is required. Click“Upgrade”to start automatic upgrading
58
Components
1.LR-G200 Integrated rebar scanner
2. U-disk memory
3.Charger
4.Communication data line
5.Instrument box
6.Instrument package
7.Operating instructions
8.Product certificate
59
1 2 3
4 5 6
7 8
60
Manufacturer warranty
LANGRY guarantees that the tool is free from defects in materials and manufac-
turing processes when it leaves the factory, and the warranty is valid only if the
user correctly installs, operates, maintains and cleans the tool in accordance with
Langry's operating instructions.
The warranty covers the free replacement or repair of damaged parts during the
whole service life of this tool. If the parts need to be repaired or protected due to
normal wear and tear, they are not covered by the warranty.
Other claims are not covered by the warranty unless there is a different provision
under the specific law of the customer's country. In particular, langry shall not be
liable for any direct, indirect, incidental or inevitable damage, financial loss or
additional expenses caused by or related to the improper use or abuse of this
tool. Expressly exclude implied warranties of merchantability and fitness for a
particular purpose.
In case of repair or replacement, the tool or relevant parts shall be sent to
Langry's market organization immediately after the failure is determined.
61