Transformer Pile Calculations PDF

This document provides calculations to determine the pile capacity for a pile cap foundation for a 230 kV transformer. It includes calculations for skin friction and end bearing of a 0.5m diameter concrete pile that is 12m long. The skin friction is calculated to be 23.94 tons based on soil properties like SPT values and unit weights at different depths. The end bearing is calculated to be 27.29 tons based on effective overburden pressure and bearing capacity factors at the pile tip. The total pile capacity is determined to be 48.39 tons or 474.7 kN.

Uploaded by

MaienAhasan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
440 views

Transformer Pile Calculations PDF

This document provides calculations to determine the pile capacity for a pile cap foundation for a 230 kV transformer. It includes calculations for skin friction and end bearing of a 0.5m diameter concrete pile that is 12m long. The skin friction is calculated to be 23.94 tons based on soil properties like SPT values and unit weights at different depths. The end bearing is calculated to be 27.29 tons based on effective overburden pressure and bearing capacity factors at the pile tip. The total pile capacity is determined to be 48.39 tons or 474.7 kN.

Uploaded by

MaienAhasan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Foundation Design For 230 KV Transformer

Project: Design, Supply, Installation, Testing and Commissioning of 230 KV Indoor GIS Substation with 132 kV AIS at
Faridpur and GIS Bay Ex-tension of existing 230/132 kV Barisal (North) AIS Substation on turnkey basis
Determination of pile capacity for pile cap 2 : (Bore Hole-8)
General Data:
Pile cap bottom level from FSL = 1.5 m
Diameter of pile = 0.5 m
Unit weight of concrete = 2.45 t/m3
3
Unit weight of concrete in submerged condition = 1.35 t/m
3
Unit weight of soil = 1.8 t/m
3
Unit weight of soil in submerged condition = 0.7 t/m
Distance from FSL to FGL = 0.3 m
Skin friction calculation:
Layer-1
Start depth of layer = 1.5 m
End depth of layer = 12 m
Layer thickness = 10.5 m
Soil parameter:
For clay/silty clay layer
Thickness of silty clay layer = 0m
Average SPT = 0
2
Cohesion value = 0 Kg/m
Cohesion reduction factor, α = 0.7
For sand/silt/silty sand layer
Start depth = 1.5 m
End depth = 12 m
Average SPT = 15.30
Angle of internal friction = 31.67 degree
= 0.553 radian
2
Effective overburden pressure, Pd = 8.4 t/m
Lateral earth pressure coefficient, K0 = 0.7
Skin friction from clay = 0 ton
skin friction from sand = 59.86 ton
Total skin friction in this layer considering FS=2.5 = 23.94 ton
Overall skin friction = 23.94 ton
End bearing calculation:
End depth of pile from GL = 12 m
2
Effective overburden pressure = 10 ton/m

Average SPT at bottom of pile = 21


Type of soil = sand
Cohesion value = 0 Kg/m2
Angle of internal friction = 33.4337 degree
= 0.584 radian
Bearing capacity factors
Nc = 50.12
Nq = 34.12
Nγ = 35.33
End bearing at tip of pile (F.S=2.5) = 27.29 ton

Pile length below cut-off level = 10.7 m


Weight of pile in dry condition = 5.15 ton
Weight of pile in submerged condition = 2.84 ton

Net capacity in compression = 48.39 ton


= 474.7 KN