NEWEST Canadian Building Wire Catalogue - WEB PDF
NEWEST Canadian Building Wire Catalogue - WEB PDF
This catalogue has been prepared for the convenience of those using electrical conductors in buildings of
all classes. The information included in the many tabulations will be of particular value to the architect,
engineer, electrician, and layperson alike. For your convenience, we have referenced applicable Articles
and Tables from the NEC.
All the cables in this catalogue are LEAD FREE. This indicates that the Nexans cable components have less
than 300 ppm of lead, which is well below the 1000 ppm level indicated in RoHS (restriction of
hazardous substances) regulations and below the level requiring labeling by California Proposition #65.
1
Table of Contents
Introduction ..................................................................................................................... 1
Bare Copper
Soft Bare Copper .............................................................................................................. 33
Armoured Cables
AC90 ............................................................................................................................... 34
AC90 ISO-BX ................................................................................................................... 39
ACWU90 ......................................................................................................................... 40
CORFLEX® II Cables
CORFLEX® II RA90 .......................................................................................................... 44
SECUREX® Cables
Unshielded SECUREX® II FAS105/LVT ........................................................................... 49
Armoured Unshielded SECUREX® II FAS105 .................................................................. 52
2
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Application
For open or concealed wiring in dry or damp locations where not exposed to
mechanical injury.
Standards
National CSA C22.2 N° 48
Minimum recommended handling temperature minus 25°C for 2 conductor cables
and minus 10°C for 3 conductor cables (with suitable handling procedures).
Maximum conductor temperature 90°C.
Approved for use with ceiling fixtures.
Characteristics
Construction characteristics
Conductor material Copper
Electrical characteristics
Maximum operating voltage 300 V
Usage characteristics
Maximum operating temperature 90 °C
Selling information
Jacket Colours: Insulation Colours:
#14 AWG - White 2 & 3C #14 for General Application 2 Conductors - Black, White
- Blue 2C#14 for Bedroom Outlets terminating at Arc Fault Circuit Interrupters (AFCI) 3 Conductors - Black, Red, White
#12 AWG - Yellow
#10 AWG - Orange
#8 AWG and larger - White 3
NMD90 CANADEX® 300 Volts 90ºC
NMD90 CANADEX® Al 300 Volts 90ºC
Nexans ref.: Aluminum/Aluminium
Description
CSA File #LL23462 Class 5821 02
Three ACM aluminum conductors, with 90°C PVC Nylon T90 Nylon insulation.
Bare bonding wire an overall jacket of moisture resistant and flame retardant
PVC, with FT1 rating.
Standards
Rated 300 volts. RoHS compliant.
National CSA C22.2 N° 48
Application
For open or concealed wiring in dry or damp locations where not exposed to
mechanical injury.
Minimum recommended handling temperature minus 10°C for 3 conductor cables
(with suitable handling procedures).
Maximum conductor temperature 90°C.
Characteristics
Construction characteristics
Conductor material Aluminum
Electrical characteristics
Maximum operating voltage 300 V
Usage characteristics
Maximum operating temperature 90 °C
Approximate
Bonding Insulation Nylon Jacket Overall Approximate Net Ampacity
Number Wire Size Thickness Thickness Thickness Dimensions Cable Weight 30°C Ambient
Size of AWG
AWG Conductors (Aluminum) mm in mm in mm in mm in kg/km lbs/kft A
8 (7) 3 10 (1) 0.89 0.035 0.12 0.005 1.14 0.045 13.7 0.54 192 129 30
6 (7) 3 8 (7) 1.14 0.045 0.15 0.006 1.14 0.045 16.6 0.65 285 192 55
4 (7) 3 6 (7) 1.14 0.045 0.15 0.006 1.52 0.060 19.8 0.78 418 281 65
2 (7) 3 6 (7) 1.14 0.045 0.15 0.006 2.03 0.080 23.5 0.93 606 407 95
Selling information
Jacket Colours: Grey
4
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Description
CSA File #LL23462 Class 5821 02
NMD90 (Red) HEATEX® is a variant of copper conductor NMD90 CANADEX ®,
with NO WHITE WIRE in the 2 conductor cable. This cable is designed for use on
240-volt systems where there is no NEUTRAL, therefore the cable has a black
and a red conductor in addition to the bare bonding wire. To make identification
easier it is usually supplied with a RED overall jacket. It should NOT be used on
120 volt systems as there is no neutral, and it is dangerous to use either the red Standards
or the black as a neutral. Large sizes are available for use with electric furnaces. National CSA C22.2 N° 48
Application
For open or concealed wiring in dry or damp locations where not exposed to
mechanical injury.
Minimum recommended handling temperature minus 25°C (with suitable handling
procedures).
Maximum conductor temperature 90°C.
Specifically designed for 240 V heating circuits.
Characteristics
Construction characteristics
Conductor material Copper
Electrical characteristics
Maximum operating voltage 300 V
Usage characteristics
Maximum operating temperature 90 °C
Approximate Approximate
Bonding Wire Insulation Nylon Jacket Overall Net Cable Ampacity
Number Size Thickness Thickness Thickness Dimensions Weight 30°C Ambient
Size of AWG
AWG Conductors (Copper) mm in mm in mm in mm in kg/km lbs/kft A
14 (1) 2 14 (1) 0.76 0.030 0.10 0.004 0.76 0.030 4.9 x 9.9 0.19 x 0.39 99 67 15
12 (1) 2 14 (1) 0.76 0.030 0.10 0.004 0.76 0.030 5.3 x 10.7 0.21 x 0.42 127 85 20
10 (1) 2 12 (1) 0.76 0.030 0.10 0.004 0.76 0.030 5.9 x 12.2 0.23 x 0.48 181 122 30
8 (7) 2 10 (1) 0.89 0.035 0.12 0.005 1.14 0.045 7.7 x 15.9 0.3 x 0.63 299 201 45
6 (7) 2 8 (7) 1.14 0.045 0.15 0.006 1.14 0.045 9.0 x 19.5 0.35 x 0.77 453 304 65
4 (7) 2 8 (7) 1.14 0.045 0.15 0.006 1.52 0.060 19.0 0.75 638 429 85
3 (7) 2 6 (7) 1.14 0.045 0.15 0.006 2.03 0.080 21.3 0.84 839 564 105
2 (7) 2 6 (7) 1.14 0.045 0.15 0.006 2.03 0.080 22.8 0.90 986 663 120
Selling information
Note: Sizes 4 AWG and larger are twisted.
Jacket Colour: Red
Insulation Colours: Black, Red
5
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Two or three copper conductors with extra thickness of 60°C PVC insulation. Bare
bonding wire and an overall sunlight resistant PVC jacket. Rated 300 volts.
Application
For direct earth burial (with protection as required by the inspection authority).
For wiring exposed to the weather. For Category 1 and 2 locations see Section 22 Standards
of the Canadian Electrical Code including barns, stables, etc.
National CSA C22.2 N° 48
For open and concealed wiring in wet or dry locations where not exposed to
mechanical injury.
Minimum recommended handling temperature minus 25°C (except for 3 conductor cables at minus 10°C) with
suitable handling procedures.
Maximum conductor temperature 60°C.
Characteristics
Construction characteristics
Conductor material Copper
Electrical characteristics
Maximum operating voltage 300 V
Usage characteristics
Maximum operating temperature 60 °C
Approx.
Bonding
Net Ampacity
Number Wire Approx.
Size Insulation Jacket Cable (amps)
of Size Overall
AWG Thickness Thickness Weight 30°C
Conductors AWG Dimensions
Copper Ambient
(Copper)
Conductors
mm in mm in mm in kg/km lbs/kft
14 (1) 2 14 (1) 1.52 0.060 0.76 0.030 6.3x12.7 0.25x0.50 142 95 15
12 (1) 2 14 (1) 1.52 0.060 0.76 0.030 6.8x13.6 0.27x0.53 173 117 20
10 (1) 2 12 (1) 1.52 0.060 0.76 0.030 7.3x15.1 0.29x0.59 234 157 30
8 (7) 2 10 (1) 1.91 0.075 1.14 0.045 9.9x20.0 0.39x0.79 402 270 40
6 (7) 2 10 (1) 2.29 0.090 1.14 0.045 11.6x23.5 0.46x0.92 565 379 55**
4 (7) 2 8 (7) 2.29 0.090 1.52 0.060 23.9 0.94 804 541 70
3 (7) 2 8 (7) 2.29 0.090 2.03 0.080 26.3 1.04 995 669 80
2 (7) 2 8 (7) 2.29 0.090 2.03 0.080 27.9 1.10 1157 778 100
NOTE: 2/C cables sizes 4 AWG and larger and all 3/C cables are twisted
14 (1) 3 14 (1) 1.52 0.060 0.76 0.030 11.9 0.47 181 122 15
12 (1) 3 14 (1) 1.52 0.060 0.76 0.030 12.8 0.50 227 152 20
10 (1) 3 12 (1) 1.52 0.060 0.76 0.030 13.9 0.55 306 205 30
8 (7) 3 10 (1) 1.91 0.075 1.14 0.045 18.6 0.73 523 351 40
6 (7) 3 10 (1) 2.29 0.090 1.14 0.045 22.3 0.88 752 505 55**
4 (7) 3 8 (7) 2.29 0.090 1.52 0.060 25.6 1.01 1098 738 70
3 (7) 3 8 (7) 2.29 0.090 2.03 0.080 28.1 1.11 1354 910 80
2 (7) 3 8 (7) 2.29 0.090 2.03 0.080 29.8 1.17 1591 1069 100
6
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Selling information
Jacket Colours: Black is standard and is sunlight resistant.
White jackets are available on request. These can be sunlight resistant, if required.
** For 3 wire 120/240 and 120/208 volt residential services or sub-services, the allowable ampacity for size 6 AWG shall be
60 amperes. In this case, the 5% adjustment per Rule 8-106(1) cannot be applied.
7
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Description
Solid Bare Copper Conductor(s), with a flame retardant, heat and moisture
resisting PVC insulation with FT1 rating. Two or three insulated conductors are
twisted. LEAD FREE.
Application
Standards
For connecting electric call bells, buzzer systems, door chimes, etc., on low
voltage battery or transformer circuits. Multiconductors suitable for oil burner International Nexans specification
control, inter-communications, etc.
Characteristics
Construction characteristics
Conductor material Copper
Usage characteristics
Maximum operating temperature 60 °C
Selling information
*Insulated conductors are laid parallel.
8
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
TEW
Description
CSA Spec: C22.2 No. 127
Size Range: 24 AWG to 4/0 AWG
UL Listed: Appliance Wiring-Material, AWM
Style 1015, 24 AWG to 9 AWG
File No. E-34548
Solid or Stranded Soft Bare Copper Conductor, Thermoplastic Insulation with extruded nylon jacket.
Application Standards
Internal Wiring of Electrical Equipment and Lighting Fixtures.
National CSA C22.2 N° 127
Note: 105ºC rating in dry locations and 60ºC where exposed to oil.
Characteristics
Construction characteristics
Conductor material Copper
Electrical characteristics
Maximum operating voltage 600 V
Usage characteristics
Maximum operating temperature 105 °C
Size No. of Insulation Thickness Overall Diameter Conductor Net Cable Weight
AWG Strands mm in mm in Ampacity kg/km lb/kft
24 1 0.8 0.03 2.1 0.082 2 6 4
24 7 0.8 0.03 2.2 0.085 2 6 4
22 1 0.8 0.03 2.2 0.087 3 8 5
22 7 0.8 0.03 2.3 0.091 3 8 5
20 1 0.8 0.03 2.4 0.094 4 10 7
20 10 0.8 0.03 2.6 0.101 4 10 7
18 1 0.8 0.03 2.6 0.102 6 13 9
18 7 0.8 0.03 2.7 0.108 6 13 9
18 16 0.8 0.03 2.8 0.109 6 13 9
16 1 0.8 0.03 2.9 0.113 8 18 12
16 7 0.8 0.03 3.0 0.120 8 20 13
16 26 0.8 0.03 3.1 0.122 8 20 13
14 1 0.8 0.03 3.2 0.126 17 27 18
14 7 0.8 0.03 3.4 0.133 17 28 19
14 19 0.8 0.03 3.4 0.133 17 27 18
14 41 0.8 0.03 3.5 0.136 17 28 19
12 1 0.8 0.03 3.6 0.143 23 39 26
12 7 0.8 0.03 3.8 0.151 23 40 27
12 19 0.8 0.03 3.8 0.151 23 40 27
12 65 0.8 0.03 3.9 0.155 23 40 27
10 1 0.8 0.03 4.2 0.165 28 58 39
10 7 0.8 0.03 4.5 0.176 28 61 41
10 19 0.8 0.03 4.5 0.176 28 61 41
10 105 0.8 0.03 4.6 0.180 28 63 42 9
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Description
CSA File #LL23462 Class 5832 02
Standards
Application National CSA C22.2 N° 75
For exposed wiring, and in raceways (except cable trays and ventilated flexible
cableways) in dry or wet locations.
For exposed wiring exposed to the weather.
Minimum recommended installation temperature minus 40°C (with suitable
handling procedures).
Maximum conductor temperature 60°C.
Characteristics
Construction characteristics
Conductor material Copper
Electrical characteristics
Maximum operating voltage 600 V
Usage characteristics
Maximum operating temperature 60 °C
10
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
1/0 (19) 2.03 0.080 13.1 0.52 584 392 195 125
2/0 (19) 2.03 0.080 14.2 0.56 730 490 225 145
3/0 (19) 2.03 0.080 15.4 0.61 894 601 260 165
4/0 (19) 2.03 0.080 16.8 0.66 1117 751 300 195
250 (37) 2.41 0.095 18.7 0.73 1318 885 340 215
300 (37) 2.41 0.095 20.5 0.81 1572 1056 375 240
350 (37) 2.41 0.095 21.6 0.85 1773 1191 420 260
400 (37) 2.41 0.095 22.9 0.90 2060 1384 455 280
500 (37) 2.41 0.950 25.0 0.99 2545 1710 515 320
600 (61) 2.79 0.110 27.8 1.09 3063 2058 575 355
750 (61) 2.79 0.110 30.4 1.20 3785 2544 655 400
1000 (61) 2.79 0.110 34.2 1.35 4983 3348 780 455
Selling information
Colours: Standard colours are available.
*For 3-wire 120/240 and 120/208 volt residential services or sub-services, the allowable ampacity for size 6 AWG shall be
60 amperes. In this case, the 5% adjustment per Rule 8-106(1) cannot be applied.
# Based on not more than 3 copper conductors in raceway or cable.
11
TW75 PVC 600 Volts 75ºC
TW75 PVC 600 Volts Al
Nexans ref.: TW75 Al
Description
CSA File #LL23462 Class 5832 02
Single ACM aluminum conductor with a flame retardant, heat and moisture
resisting PVC insulation with FT1 rating. Rated 600 volts. Sunlight Resistant.
LEAD FREE.
Application
For exposed wiring and in raceways (except cable trays and ventilated flexible
cableways) in dry or wet locations.
Standards
For exposed wiring where exposed to weather.
National CSA C22.2 N° 75
Minimum recommended installation temperature minus 10°C.
Maximum conductor temperature 75°C.
Characteristics
Construction characteristics
Conductor material Aluminum
Electrical characteristics
Maximum operating voltage 600 V
Usage characteristics
Maximum operating temperature 75 °C
1/0 (18) 2.03 0.080 12.7 0.50 246 165 150 180 100 120
2/0 (18) 2.03 0.080 13.7 0.54 295 198 175 210 115 135
3/0 (18) 2.03 0.080 14.7 0.58 356 239 200 240 130 155
4/0 (18) 2.03 0.080 16.3 0.64 431 287 235 280 150 180
250 (35) 2.41 0.095 18.0 0.71 520 349 265 315 170 205
300 (35) 2.41 0.095 19.3 0.76 604 406 295 350 195 230
350 (35) 2.41 0.095 20.6 0.81 687 462 330 395 210 250
400 (35) 2.41 0.095 21.6 0.85 769 517 355 425 225 270
500 (35) 2.41 0.095 23.6 0.93 929 624 405 485 260 310
12
TW75 PVC 600 Volts 75ºC
TW75 PVC 600 Volts Al
Nexans ref.: TW75 Al
Selling information
Colours: Standard colours are available.
Description
CSA File #LL23462 Class 5832 02
Single copper conductor with a flame retardant, heat and moisture resisting PVC
insulation with FT1 rating. Rated 600 volts. Sunlight Resistant 6 AWG and larger.
LEAD FREE.
Standards
Application
National CSA C22.2 N° 75
For exposed wiring and in raceways (except cable trays and ventilated flexible
cableways) in dry or wet locations.
For exposed wiring where exposed to weather.
Minimum recommended installation temperature minus 10°C.
Maximum conductor temperature 75°C.
Characteristics
Construction characteristics
Conductor material Copper
Electrical characteristics
Maximum operating voltage 600 V
Usage characteristics
Maximum operating temperature 75 °C
13
TW75 PVC 600 Volts 75ºC
TW75 PVC 600 Volts Cu
Nexans ref.: TW75 Cu
1/0 (19) 2.03 0.080 13.1 0.52 584 392 230 150
2/0 (19) 2.03 0.080 14.2 0.56 730 490 265 175
3/0 (19) 2.03 0.080 15.4 0.61 894 601 310 200
4/0 (19) 2.03 0.080 16.8 0.66 1117 751 360 230
250 (37) 2.41 0.095 18.7 0.73 1318 885 405 255
300 (37) 2.41 0.095 20.5 0.81 1574 1057 445 285
350 (37) 2.41 0.095 21.6 0.85 1773 1191 505 310
400 (37) 2.41 0.095 22.9 0.91 2061 1385 545 335
500 (37) 2.41 0.095 25.0 0.99 2547 1711 620 380
Selling information
Colours: Standard colours are available.
#See Table 1 in the Canadian Electrical Code.
##Based on not more than 3 copper conductors in raceway or cable. See Table 2 in the Canadian Electric Code.
14
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Buried Circuits
Description
CSA File #LL23462 Class 5832-02 Standards
Single solid or compressed stranded (Class B) copper conductor with extra National CSA C22.2 N° 75
thickness of FT1 rated flame retardant, low temperature, moisture resisting PVC
insulation. Rated 600 volts. LEAD FREE
Application
For direct earth burial (with protection as required by the Local Inspection
Authority). Direct buried installations must comply with 2012 CEC Rules 12-012
and 4-004. For exposed wiring exposed to the weather. Cables are marked "SR"
for sunlight resistant (all colours). For service entrance above or below ground.
Minimum recommended installation temperature minus 40°C (with suitable
handling procedures).
Characteristics
Construction characteristics
Conductor material Copper
Electrical characteristics
Maximum operating voltage 600 V
Usage characteristics
Maximum operating temperature 60 °C
15
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
1/0 (19) 2.41 0.095 13.9 0.55 606 407 195 125
2/0 (19) 2.41 0.095 15.0 0.59 753 506 225 145
3/0 (19) 2.41 0.095 16.3 0.64 919 618 260 165
4/0 (19) 2.41 0.095 17.6 0.70 1137 764 300 195
250 (37) 2.79 0.110 19.4 0.76 1348 906 340 215
300 (37) 2.79 0.110 21.3 0.84 1606 1079 375 240
350 (37) 2.79 0.110 22.3 0.88 1852 1245 420 260
400 (37) 2.79 0.110 23.7 0.93 2097 1409 455 280
500 (37) 2.79 0.110 25.8 1.02 2586 1737 515 320
600 (61) 3.18 0.125 28.6 1.13 3108 2089 575 355
750 (61) 3.18 0.125 31.2 1.23 3835 2577 655 400
1000 (61) 3.18 0.125 35.0 1.38 5039 3386 780 455
Selling information
Colours: Standard colours are available.
*Direct buried installations must comply with C.E. Code Rules 12-012 and 4-004.
**For 3-wire 120/240 and 120/208 volt residential services or sub-services, the allowable ampacity for size #6 AWG shall be
60 amperes.
In this case, the 5% adjustment per Rule 8-106(1) cannot be applied.
# Based on not more than 3 copper conductors in raceway or cable.
16
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Description
CSA File #LL23462 Class 5832 02
U.L. Standard #83 - U.L. Approval # E70347
Standards
Single copper conductor with thin wall PVC insulation and nylon covering with
FT1 rating. Rated 600 volts. LEAD FREE. National CSA C22.2 N° 75
Application
General purpose building wire for installation as exposed or concealed wiring and
in raceways (except cable trays) in dry or damp locations.
Minimum recommended installation temperature minus 10°C (with suitable
handling procedures).
Maximum conductor temperature 90°C dry, 75°C in wet locations, and 60°C when
exposed to oil.
Approved for use with ceiling fixtures.
Nexans INSTAGLIDE® reduced friction construction in sizes 6 AWG and larger.
Characteristics
Construction characteristics
Conductor material Copper
Electrical characteristics
Maximum operating voltage 600 V
Usage characteristics
Maximum operating temperature 90 °C
17
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Ampacity
Insulation Nylon Approximate Approx. Net (amps at 30°C Ambient) Where
Size AWG Thickness Thickness Diameter Cable Weight exposed
or Damp & Dry Wet to oil
kcmil Conduit
Free Conduit Free Conduit #
mm in mm in mm in kg/km lbs/kft Air # Air #
14 (1) 0.38 0.015 0.10 0.004 2.7 0.11 25 15 20 15 20 15 15
12 (1) 0.38 0.015 0.10 0.004 3.1 0.12 35 23 25 20 25 20 20
10 (1) 0.51 0.020 0.10 0.004 3.9 0.15 55 37 40 30 40 30 30
3 (19) 1.02 0.040 0.15 0.006 9.0 0.36 288 193 155 105 145 100 80
2 (19) 1.02 0.040 0.15 0.006 9.8 0.39 357 240 180 120 170 115 100
1 (19) 1.27 0.050 0.18 0.007 10.9 0.43 446 300 210 140 195 130 110
1/0 (19) 1.27 0.050 0.18 0.007 11.8 0.47 555 373 245 155 230 150 125
2/0 (19) 1.27 0.050 0.18 0.007 12.9 0.51 698 470 285 185** 265 175 145
3/0 (19) 1.27 0.050 0.18 0.007 14.2 0.56 862 579 330 210 310 200 165
4/0 (19) 1.27 0.050 0.18 0.007 15.5 0.61 1077 724 385 235 360 230 195
250 (37) 1.52 0.060 0.20 0.008 17.2 0.68 1272 855 425 265 405 255 215
300 (37) 1.52 0.060 0.20 0.008 18.5 0.73 1521 1022 480 295 445 285 240
350 (37) 1.52 0.060 0.20 0.008 19.7 0.78 1762 1184 530 325 505 310 260
400 (37) 1.52 0.060 0.20 0.008 20.8 0.82 2002 1345 575 345 545 335 280
500 (37) 1.52 0.060 0.20 0.008 22.9 0.90 2482 1668 660 395 620 380 320
**For 3-wire 120/240 and 120/208V residential services or sub-services, the allowable ampacity
for #2/0 AWG copper shall be 200 amperes. In these cases, the 5% adjustment per C.E. Code Rule 8-106(1) cannot be applied.
Selling information
18
INSTAGLIDE® RW90 (–40°C) XLPE Insulated Wire 90°C
1 kV Aluminum
Nexans ref.: RW90
INSTAGLIDE® RW90 (–40°C) EXELENE® XLPE 1 kV Aluminum Service Entrance and Branch Circuit Wire
Description
CSA File #L23462 Class 5832 03.
Compact stranded AA-8000 series aluminum conductor material (ACM) per ASTM
B801 Class B or ASTM B836 (Single Input Wire) with low temperature moisture
resisting EXELENE ® cross-linked polyethylene (XLPE) insulation. RoHS
compliant.
Standards
Application
National CSA C22.2 N° 38
For open wiring and raceways (except cabletroughs and ventilated flexible
cableway) in dry or wet locations.
For exposed wiring where exposed to weather with sunlight resistant insulation.
Standard Black 6 AWG and larger is sunlight resistant and marked "SR"; coloured
insulation is NOT.
Minimum recommended installation temperature minus 40°C (with suitable
handling procedures).
Maximum conductor temperature 90°C.
Approved for use with ceiling fixtures. Nexans INSTAGLIDE® reduced friction
construction in sizes 6 AWG and larger, black and colours.
Characteristics
Construction characteristics
Conductor material Aluminum
Usage characteristics
Maximum operating temperature 90 °C
19
INSTAGLIDE® RW90 (–40°C) XLPE Insulated Wire 90°C
1 kV Aluminum
Nexans ref.: RW90
RW90 1 kV Aluminum
Ampacity (Note 5) (A) 30°C Ambient
Insulation Nominal Approximate Net
Size
Thickness Diameter Cable Weight Free Air (Note 2) Conduit (Note 3)
AWG or
kcmil mm in mm in kg/km lbs/kft 60ºC 75ºC 90ºC 60ºC 75ºC 90ºC
55
6 (7) 1.52 0.060 7.4 0.29 64 43 65 75 85 40 50 (Note 4)
4 (7) 1.52 0.060 8.6 0.34 91 61 85 100 115 55 65 75
3 (7) 1.52 0.060 9.1 0.36 108 73 95 115 130 65 75 85
2 (6) 1.52 0.060 9.9 0.39 131 88 115 135 150 75 90 100
1 (8) 2.03 0.080 11.7 0.46 177 119 130 155 175 85 100 115
1/0 (10) 2.03 0.080 12.7 0.50 213 143 150 180 205 100 120 135
2/0 (12) 2.03 0.080 13.7 0.54 257 173 175 210 235 115 135 150
3/0 (16) 2.03 0.080 15.0 0.59 312 210 200 240 270 130 155 175
4/0 (18) 2.03 0.080 16.2 0.64 384 258 235 280 315 150 180 205
250 (35) 2.28 0.090 17.8 0.70 475 307 265 315 355 170 205 230
300 (35) 2.28 0.090 19.1 0.75 536 360 295 350 395 195 230 260
350 (35) 2.28 0.090 20.3 0.80 614 413 330 395 445 210 250 280
400 (35) 2.28 0.090 21.3 0.84 692 465 355 425 480 225 270 305
500 (35) 2.28 0.090 23.4 0.92 844 567 405 485 545 260 310 350
600 (58) 2.28 0.090 25.1 0.99 997 670 455 545 615 285 340 385
750 (58) 2.28 0.090 27.7 1.09 1223 822 520 620 700 320 385 435
1000 (58) 2.28 0.090 31.5 1.24 1600 1075 630 750 845 375 445 500
Notes:
1) Where stated, “nominal” and “approximate” values are provided for information purposes only
and are subject to standard manufacturing tolerances.
2) Based on CE Code Table 3, for single conductors in free air.
3) Based on CE Code Table 4, for not more than 3 current carrying conductors in a cable or
raceway.
4) For 3-wire 120/240 V and 120/208 V residential services or sub-services the allowable
ampacity for 6 AWG shall be 60 amperes. In this case, the 5% adjustment
Rule (CE Code Rule 8-106(1)) cannot be applied.
5) The maximum conductor temperature (used to determine the maximum conductor
ampacity) shall be based on the lowest temperature rating of the electrical equipment,
any wire connector, or cable (CE Code Rule 4-006).
Selling information
Colours: Standard colours are available.
Non-jacketed RW-90 (XLPE) cables are not suitable for installation in vaults and switchrooms under the conditions of C.E.
Code Part 1 Rule 12-2202(3). Suitable flame retardant jacketed cables are available on request.
20
INSTAGLIDE® RW90 (–40°C) XLPE Insulated Wire 90°C
1 kV Copper
Nexans ref.: RW90
INSTAGLIDE® RW90 (–40°C) EXELENE® XLPE 1 kV Copper Service Entrance and Branch Circuit Wire
Description
CSA File #LL23462 Class 5832 03
Application Standards
For open wiring and raceways (except cabletroughs and ventilated flexible National CSA C22.2 N° 38
cableway) in dry or wet locations.
For exposed wiring where exposed to weather with sunlight resistant insulation.
Standard Black 6 AWG and larger is sunlight resistant and marked "SR"; coloured
insulation is NOT.
Minimum recommended installation temperature minus 40°C (with suitable
handling procedures).
Maximum conductor temperature 90°C.
Approved for use with ceiling fixtures. Nexans INSTAGLIDE® reduced friction
construction in sizes 6 AWG and larger, black and colours.
Characteristics
Construction characteristics
Conductor material Copper
Usage characteristics
Maximum operating temperature 90 °C
21
INSTAGLIDE® RW90 (–40°C) XLPE Insulated Wire 90°C
1 kV Copper
Selling information
Colours: Standard colours are available.
Non-jacketed RW90 (XLPE) cables are not suitable for installation in vaults and switchrooms under the conditions of C.E.
Code Part 1 Rule 12-2202(3). Suitable flame retardant jacketed cables are available on request.
22
INSTAGLIDE® RW90 (–40°C) XLPE Insulated Wire 90°C
600 V Aluminum
Nexans ref.: RW90
INSTAGLIDE® RW90 (–40°C) EXELENE® XLPE 600 V Aluminum Service Entrance and Branch Circuit Wire
Description
CSA File #LL23462 Class 5832 03
Compact stranded AA-8000 series aluminum conductor material (ACM) per ASTM
B801 Class B or ASTM B836 (Single Input Wire) with low temperature moisture
resisting EXELENE® cross-linked polyethylene insulation. RoHS compliant.
Application Standards
For open wiring and raceways (except cabletroughs and ventilated flexible National CSA C22.2 N° 38
cableway) in dry or wet locations.
For exposed wiring where exposed to weather with sunlight resistant insulation.
Standard Black 6 AWG and larger is sunlight resistant and marked "SR"; coloured
insulation is NOT.
Minimum recommended installation temperature minus 40°C (with suitable
handling procedures).
Maximum conductor temperature 90°C.
Approved for use with ceiling fixtures. Nexans INSTAGLIDE® reduced friction
construction in sizes 6 AWG and larger, black and colours.
Characteristics
Construction characteristics
Conductor material Aluminum
Usage characteristics
Maximum operating temperature 90 °C
23
INSTAGLIDE® RW90 (–40°C) XLPE Insulated Wire 90°C
600 V Aluminum
Nexans ref.: RW90
Notes:
1) Where stated, “nominal” and “approximate” values are provided for information purposes only and are
subject to standard manufacturing tolerances.
2) Based on CE Code Table 3, for single conductors in free air.
3) Based on CE Code Table 4, for not more than 3 current carrying conductors in a cable or raceway.
4) For 3-wire 120/240 V and 120/208 V residential services or sub-services the allowable ampacity for 6 AWG
shall be 60 amperes. In this case, the 5% adjustment Rule (CE Code Rule 8-106(1)) cannot be applied.
5) The maximum conductor temperature (used to determine the maximum conductor ampacity) shall be based
on the lowest temperature rating of the electrical equipment, any wire connector, or cable
(CE Code Rule 4-006).
Selling information
Colours: Standard colours are available.
Non-jacketed RW-90 (XLPE) cables are not suitable for installation in vaults and switchrooms under the conditions of C.E.
Code Part 1 Rule 12-2202(3). Suitable flame retardant jacketed cables are available on request.
24
INSTAGLIDE® RW90 (–40°C) XLPE Insulated Wire 90°C
600 V Copper
Nexans ref.: RW90
INSTAGLIDE® RW90 (–40°C) EXELENE® XLPE 600 V Copper Service Entrance and Branch Circuit Wire
Description
CSA File #LL23462 Class 5832 03
Application Standards
For open wiring and raceways (except cabletroughs and ventilated flexible National CSA C22.2 N° 38
cableway) in dry or wet locations.
For exposed wiring where exposed to weather with sunlight resistant insulation.
Standard Black 6 AWG and larger is sunlight resistant and marked "SR"; coloured
insulation is NOT.
Minimum recommended installation temperature minus 40°C (with suitable
handling procedures).
Maximum conductor temperature 90°C.
Approved for use with ceiling fixtures. Nexans INSTAGLIDE ® reduced friction
construction in sizes 6 AWG and larger, black and colours.
Characteristics
Construction characteristics
Conductor material Copper
Usage characteristics
Maximum operating temperature 90 °C
25
INSTAGLIDE® RW90 (–40°C) XLPE Insulated Wire 90°C
600 V Copper
Selling information
Colours: Standard colours are available.
Non-jacketed RW-90 (XLPE) cables are not suitable for installation in vaults and switchrooms under the conditions of C.E.
Code Part 1 Rule 12-2202(3). Suitable flame retardant jacketed cables are available on request.
26
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Construction
Conductor:
Bare, annealed copper conforming to ASTM B3 and Class B compressed stranded copper in accordance to
ASTM B8, from 8 AWG to 3/0 AWG.
Insulation:
Coloured cross-linked polyethylene meeting the requirements for RW90 per CSA C22.2 No. 38.
Assembly:
Cabled without a ground wire.
Conductor Identification:
3 Conductors: Black, Red, Blue
4 Conductors: Black, Red, Blue, White
Characteristics
Construction characteristics
Conductor material Copper
Electrical characteristics
Maximum operating voltage 600 V
Usage characteristics
Maximum operating temperature 90 °C
27
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Approximate Approximate
Insulation
Part Size No. of Overall Net Cable
Thickness
Number (AWG) Conductors Diameter Weight
mm inches mm inches kg/km lbs/kft
604750 8 (7) 3 1.14 0.045 12.7 0.50 280 188
604752 8 (7) 4 1.14 0.045 14.2 0.56 373 251
604720 6 (7) 3 1.14 0.045 14.7 0.58 427 287
604719 6 (7) 4 1.14 0.045 16.5 0.65 569 383
604748 3 (7) 3 1.14 0.045 18.8 0.74 817 549
604749 3 (7) 4 1.14 0.045 21.1 0.83 1091 733
604754 3/0 (19) 3 1.40 0.055 30.2 1.20 2496 1677
604755 3/0 (19) 4 1.40 0.055 34.0 1.34 3331 2238
Selling information
Colours:
3 Conductors: Black, Red, Blue.
4 Conductors: Black, Red, Blue, White.
28
INSTAGLIDE® RWU90 (–40°C) XLPE Insulated Wire 1 kV 90°C
1 kV Aluminum
Nexans ref.: RWU90
INSTAGLIDE® RWU90 (–40°C) EXELENE® XLPE Underground Service Entrance and Branch Circuit Wire
Description
CSA File #LL23462 Class 5832 03
Compact stranded AA-8000 series aluminum conductor material (ACM) per ASTM
B801 Class B or ASTM B836 (Single Input Wire) with low temperature moisture
resisting EXELENE® cross-linked polyethylene (XLPE) insulation. Rated 1000
volts. RoHS Compliant.
Standards
National CSA C22.2 N° 38
Application
For direct earth burial (with protection as required by inspecting authority -
direct buried installations must comply with CE Code Rules 12-012 and 4-004).
For exposed wiring where exposed to weather with sunlight resistant insulation.
Standard Black 8 AWG and larger is sunlight resistant and marked "SR", coloured
insulation is NOT.
For service entrance above or below ground.
Minimum recommended installation temperature minus 40°C (with suitable
handling procedures).
Maximum conductor temperature 90°C. Nexans INSTAGLIDE® reduced friction
construction sizes 6 AWG and larger, black and colours.
Characteristics
Construction characteristics
Conductor material Aluminum
Electrical characteristics
Operating voltage 1 kV
Usage characteristics
Maximum operating temperature 90 °C
29
INSTAGLIDE® RWU90 (–40°C) XLPE Insulated Wire 1 kV 90°C
1 kV Aluminum
Nexans ref.: RWU90
RWU 1 kV Aluminum
Ampacity (Note 5) (A)
30°C Ambient
Insulation Approximate Approximate Net Free Air Conduit
Size Thickness Diameter Cable Weight (Note 2) (Note 3)
AWG or
kcmil mm in mm in kg/km lbs/kft 60ºC 75ºC 90ºC 60ºC 75ºC 90ºC
55
6 (7) 2.03 0.080 8.4 0.33 77 52 65 75 85 40 50 (Note 4)
4 (7) 2.03 0.080 9.6 0.38 106 71 85 100 115 55 65 75
3 (7) 2.03 0.080 10.2 0.40 126 85 95 115 130 65 75 85
2 (6) 2.03 0.080 11.1 0.44 150 101 115 135 150 75 90 100
1 (8) 2.41 0.095 12.4 0.49 193 130 130 155 175 85 100 115
1/0 (10) 2.41 0.095 13.5 0.53 232 156 150 180 205 100 120 135
2/0 (12) 2.41 0.095 14.5 0.57 278 187 175 210 235 115 135 150
3/0 (16) 2.41 0.095 15.7 0.62 335 225 200 240 270 130 155 175
4/0 (18) 2.41 0.095 17.3 0.68 408 274 235 280 315 150 180 205
250 (35) 2.79 0.110 19.0 0.75 494 332 265 315 355 170 205 230
300 (35) 2.79 0.110 20.3 0.80 576 387 295 350 395 195 230 260
350 (35) 2.79 0.110 21.6 0.85 668 442 330 395 445 210 250 280
400 (35) 2.79 0.110 22.6 0.89 737 495 355 425 480 225 270 305
500 (35) 2.79 0.110 24.6 0.97 896 602 405 485 545 260 310 350
600 (58) 3.17 0.125 27.2 1.07 1193 802 455 545 615 285 340 385
750 (58) 3.17 0.125 29.7 1.17 1332 895 520 620 700 320 385 435
1000 (58) 3.17 0.125 33.5 1.32 1720 1156 630 750 845 375 445 500
Notes:
1) Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing
tolerances.
2) Based on CE Code Table 3, for single conductors in free air.
3) Based on CE Code Table 4, for not more than 3 current carrying conductors in a cable or raceway.
4) For 3-wire 120/240 V and 120/208 V residential services or sub-services the allowable ampacity for 6 AWG shall be 60 amperes. In this case,
the 5% adjustment Rule (CE Code Rule 8-106(1)) cannot be applied.
5) The maximum conductor temperature (used to determine the maximum conductor ampacity) shall be based on the lowest temperature
rating of the electrical equipment, any wire connector, or cable (CE Code Rule 4-006).
Selling information
Colours: Standard colours are available.
30
INSTAGLIDE® RWU90 (–40°C) XLPE Insulated Wire 1 kV 90°C
1 kV Copper
Nexans ref.: RWU90
INSTAGLIDE® RWU90 (–40°C) EXELENE® XLPE Underground Service Entrance and Branch Circuit Wire
Description
CSA File #LL23462 Class 5832 03
Application
For direct earth burial (with protection as required by inspecting authority - direct
buried installations must comply with CE Code Rules 12-012 and 4-004).
For exposed wiring where exposed to weather with sunlight resistant insulation.
Standard Black 8 AWG and larger is sunlight resistant and marked "SR", coloured
insulation is NOT.
For service entrance above or below ground.
Minimum recommended installation temperature minus 40°C (with suitable
handling procedures).
Maximum conductor temperature 90°C. Nexans INSTAGLIDE® reduced friction
construction in sizes 6 AWG and larger, black and colours.
Characteristics
Construction characteristics
Conductor material Copper
Electrical characteristics
Operating voltage 1 kV
Usage characteristics
Maximum operating temperature 90 °C
31
INSTAGLIDE® RWU90 (–40°C) XLPE Insulated Wire 1 kV 90°C
1 kV Copper
Nexans ref.: RWU90
RWU 1 kV Copper
Ampacity (Note 6) (A)
30°C Ambient
Insulation Approximate Approximate Net Free Air Conduit
Size Thickness Diameter Cable Weight (Note 2) (Note 3)
AWG or
kcmil mm in mm in kg/km lbs/kft 60ºC 75ºC 90ºC 60ºC 75ºC 90ºC
14 (1)
(Note 5) 1.52 0.060 4.7 0.19 33 22 25 30 35 20 20 25
12 (1)
(Note 5) 1.52 0.060 5.2 0.20 46 31 30 35 40 25 25 30
10 (1)
(Note 5) 1.52 0.060 5.7 0.22 66 44 40 50 55 30 35 40
14 (7)
(Note 5) 1.52 0.060 4.9 0.19 34 23 25 30 35 20 20 25
12 (7)
(Note 5) 1.52 0.060 5.4 0.21 48 32 30 35 40 25 25 30
10 (7)
(Note 5) 1.52 0.060 6.0 0.24 69 46 40 50 55 30 35 40
8 (7) 2.03 0.080 7.8 0.31 112 76 60 70 80 40 50 55
55
6 (7) 2.03 0.080 8.8 0.35 164 110 80 95 105 (Note 4) 65 75
4 (7) 2.03 0.080 10.0 0.39 243 164 105 125 140 70 85 95
3 (7) 2.03 0.080 10.6 0.42 298 201 120 145 165 85 100 115
2 (7) 2.03 0.080 11.4 0.45 367 247 140 170 190 95 115 130
1 (19) 2.41 0.095 13.0 0.51 464 312 165 195 220 110 130 145
1/0 (19) 2.41 0.095 13.9 0.55 572 384 195 230 260 125 150 170
195
2/0 (19) 2.41 0.095 15.0 0.59 715 480 220 265 300 145 175 (Note 4)
3/0 (19) 2.41 0.095 16.2 0.64 878 590 260 310 350 165 200 225
4/0 (19) 2.41 0.095 17.6 0.69 1089 732 300 360 405 195 230 260
250 (37) 2.79 0.110 19.5 0.77 1300 874 340 405 455 215 255 290
300 (37) 2.79 0.110 21.4 0.84 1544 1038 370 445 500 240 285 320
350 (37) 2.79 0.110 21.9 0.86 1775 1193 425 505 570 260 310 350
400 (37) 2.79 0.110 23.9 0.94 2027 1362 455 545 615 280 335 380
500 (37) 2.79 0.110 26.0 1.02 2507 1685 520 620 700 320 380 430
600 (61) 3.17 0.125 28.7 1.13 3012 2024 580 690 780 350 420 475
750 (61) 3.17 0.125 31.3 1.23 3728 2505 655 785 885 400 475 535
1000 (61) 3.17 0.125 35.1 1.38 4917 3304 785 935 1055 455 545 615
Notes:
1) Where stated, “nominal” and “approximate” values are provided for information purposes only and are subject to standard manufacturing
tolerances.
2) Based on CE Code Table 1, for single conductors in free air.
3) Based on CE Code Table 2, for not more than 3 current carrying conductors in a cable or raceway.
4) For 3-wire 120/240 V and 120/208 V residential services or sub-services the allowable ampacity for 6 AWG shall be 60 amperes, and 2/0 AWG
shall be 200 amperes. In this case, the 5% adjustment Rule (CE Code Rule 8-106(1)) cannot be applied.
5) The overcurrent protection shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG after any
corrections factors for ambient temperature and number of conductors have been applied (CE Code Rule 14-104(2)), or as provided for
by other Rules of the CE Code.
6) The maximum conductor temperature (used to determine the maximum conductor ampacity) shall be based on the lowest temperature
rating of the electrical equipment, any wire connector, or cable (CE Code Rule 4-006).
Selling information
Colours: Standard colours are available.
32
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Characteristics
Construction characteristics
Conductor material Annealed copper
33
AC90 (–40°C) XLPE 600 Volts 90°C Zero Halogen
2 Conductors
Nexans ref.: AC90
Description
CSA File #LL23462 Class 5811 01
Application
For open and concealed wiring in dry locations only.
For use in cabletroughs and ventilated flexible cableways in dry locations only.
Minimum recommended installation temperature minus 40°C (with suitable
handling procedures).
Maximum conductor temperature 90°C. Approved for use with ceiling fixtures.
Characteristics
Construction characteristics
Conductor material Copper or Aluminum
Electrical characteristics
Maximum operating voltage 600 V
Usage characteristics
Maximum operating temperature 90 °C
Selling information
Insulation Colour Code: 2 Conductors - Black, White
**Copper bonding wire supplied with copper conductors. Aluminum bonding wire supplied with aluminum conductors.
34
AC90 (–40°C) XLPE 600 Volts 90°C Zero Halogen
3 Conductors
Nexans ref.: AC90
Description
CSA File #LL23462 Class 5811 01
Application
For open and concealed wiring in dry locations only.
For use in cabletroughs and ventilated flexible cableways in dry locations only.
Minimum recommended installation temperature minus 40°C (with suitable
handling procedures).
Maximum conductor temperature 90°C. Approved for use with ceiling fixtures.
Characteristics
Construction characteristics
Conductor material Copper or Aluminum
Electrical characteristics
Maximum operating voltage 600 V
Usage characteristics
Maximum operating temperature 90 °C
35
AC90 (–40°C) XLPE 600 Volts 90°C Zero Halogen
3 Conductors
Nexans ref.: AC90
Selling information
Insulation Colour Code: 3 Conductors - Black, Red, White
***Copper bonding wire supplied with copper conductors. Aluminum bonding wire supplied with aluminum conductors.
#For 3-wire 120/240 V and 120/208 V service conductors for single dwellings, or for feeder conductors supplying single
dwelling units of row housing, of apartments and similar buildings, and sized in accordance with Rules 8-200(1), 8-200(2)
and 8-202(1), the allowable ampacity for sizes No. 6, No. 2 and No. 4/0 AWG aluminum shall be 60 A, 100 A and 200 A
respectively. For No. 2/0 AWG copper it shall be 200 A. In these cases the 5% adjustment Rule 8-106(1) cannot be applied.
36
AC90 (–40°C) XLPE 600 Volts 90°C Zero Halogen
4 Conductors
Nexans ref.: AC90
Description
CSA File #LL23462 Class 5811 01
Application
For open and concealed wiring in dry locations only.
For use in cabletroughs and ventilated flexible cableways in dry locations only.
Minimum recommended installation temperature minus 40°C (with suitable
handling procedures).
Maximum conductor temperature 90°C. Approved for use with ceiling fixtures.
Characteristics
Construction characteristics
Conductor material Copper or Aluminum
Electrical characteristics
Maximum operating voltage 600 V
Usage characteristics
Maximum operating temperature 90°C
37
AC90 (–40°C) XLPE 600 Volts 90°C Zero Halogen
4 Conductors
Nexans ref.: AC90
Selling information
Insulation Colour Code: 4 Conductors - Black, Red, Blue, White
***Copper bonding wire supplied with copper conductors. Aluminum bonding wire supplied with aluminum conductors.
#For 3-wire 120/240 V and 120/208 V service conductors for single dwellings, or for feeder conductors supplying single
dwelling units of row housing, of apartments and similar buildings, and sized in accordance with Rules 8-200(1), 8-200(2)
and 8-202(1), the allowable ampacity for sizes No. 6, No. 2 and No. 4/0 AWG aluminum shall be 60 A, 100 A and 200 A
respectively. For No. 2/0 AWG copper it shall be 200 A. In these cases the 5% adjustment Rule 8-106(1) cannot be applied.
38
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Characteristics
Construction characteristics
Conductor material Copper
Electrical characteristics
Maximum operating voltage 600 V
Usage characteristics
Maximum operating temperature 40°C
Selling information
#Two-conductor cable contains black and white circuit conductors, green isolated ground conductor, and a bare copper
bonding conductor.
Three-conductor cable contains red, black and white circuit conductors, green isolated ground conductor, and a bare copper
bonding conductor.
**Isolated Ground Conductor" covered with green (RW90) XLPE. Refer to the Canadian Electrical Code Part 1 2006 (Rules
10-906 and 24-100 to 24-114) for rules covering cables and systems containing isolated grounding conductors, etc.
39
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
One to four compact ACM aluminum conductors with low temperature, sunlight
resistant (black and colours) EXELENE ® cross-linked polyethylene insulation
(RW90 XLPE) and bare aluminum bonding wire in multi-conductor cables. Single
conductor cables have aluminum concentric bonding wires. Conductor assembly Standards
is wrapped and enclosed in an interlocked aluminum armour with an overall low
acid gas and low flame spread, sunlight resistant PVC jacket (LAG/LFS) with FT4 National CSA C22.2 N° 51
and AG14 rating. LEAD FREE and RoHS compliant.
8 and larger are HL rated for Class I Div 1 & 2 Groups A, B, C & D, Class II Div 1 & 2 Groups E, F & G and Class III
Hazardous Locations.
Application
For exposed and concealed wiring in dry or wet locations and where exposed to the weather. Nexans cables are marked
"SUN RES" for sunlight resistant.
For use in ventilated, non-ventilated and ladder type cable trays in wet and dry locations.
For direct earth burial (with protection as required by Inspection Authority).
For service entrance above or below ground.
For use in hazardous locations with approved connectors.
Minimum recommended installation temperature minus 40°C (with suitable handling procedures).
Maximum conductor temperature 90°C.
Rated 600 volts.
Characteristics
Construction characteristics
Conductor material Aluminum
Electrical characteristics
Maximum operating voltage 600 V
Usage characteristics
Maximum operating temperature 90 °C
40
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
41
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
42
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Insulation Colour Code: Black, Red, Blue, White (all sunlight resistant)
**Compact aluminum conductors are AA-8000 series aluminum alloy (ACM)
***Ampacity in accordance with Table 4 of the Canadian Electrical Code, assuming the fourth conductor is the neutral of a
balanced 3 phase, 4 wire system.
# For 3-wire 120/240 V and 120/208 V service conductors for single dwellings, or for feeder conductors supplying single
dwelling units of row housing, of apartments and similar buildings, and sized in accordance with Rules 8-200(1), 8-200(2)
and 8-202(1), the allowable ampacity for sizes 6 AWG, 2 AWG and 4/0 AWG shall be 60 A, 100 A and 200 A respectively.
In this case the 5% adjustment Rule 8-106(1) cannot be applied.
43
CORFLEX® II RA90
Aluminum Conductors
Nexans ref.: CORFLEX® II RA90
Description
Single or multi compact ACM aluminum conductors with EXELENE ® cross-linked
polyethylene insulation (RW90 XLPE) enclosed in a liquid- and vapour-tight solid
corrugated aluminum sheath. An overall sunlight resistant, low temperature, low
acid gas and low flame spread (LAG/LFS) PVC jacket with FT4 and AG14 rating.
Unjacketed CORFLEX® with FT4 and AG14 ratings is also available.
Rated 600 volts. LEAD FREE and RoHS compliant.
CSA File #LL19376 Class 5812 01 - Cable
CSA File #LL19376 Class 5818 01 - Hazardous Location Cable Application Standards
National CSA C22.2 N° 123
Application
For exposed and concealed wiring in dry or wet locations and where exposed to
the weather. Nexans cables are marked "SUN RES" for sunlight resistant.
For use in ventilated, non-ventilated, and ladder type cabletroughs and ventilated
flexible cableways in dry or wet locations.
For direct earth burial (with protection as required by Inspection Authority). For
direct embedding in concrete, masonry or plaster (with permission as required by
Local Inspection Authority).
For service entrance above or below ground.
CORFLEX ® cable is certified for use in hazardous locations with approved
connectors. Nexans Canada Type W connector are approved for Class II
Divisions 1 and 2 (Groups E, F and G) and Class III Divisions 1 and 2.
Characteristics
Construction characteristics
Conductor material Aluminum
Electrical characteristics
Maximum operating voltage 600 V
Usage characteristics
Maximum operating temperature 90°C
44
CORFLEX® II RA90
Aluminum Conductors
45
CORFLEX® II RA90
Aluminum Conductors
Selling information
Insulation Colour Code:
1 Conductor - Black
3 Conductors - Black, Red, White #14 - #2
4 Conductors - Black, Red, Blue, White #14 - #2
Black Insulation with white printed numbers #1 and larger
**Compact aluminum ACM conductors are aluminum alloy #8030.
****Assuming 4th conductor is the neutral of a balanced 3-phase 4 wire system.
#Conductor is compressed stranding not compact.
##For 3-wire 120/240 V and 120/208 V service conductors for single dwellings, or for feeder conductors supplying single
dwelling units of row housing, of apartments and similar buildings, and sized in accordance with Rules 8-200(1), 8-200(2)
and 8-202(1), the allowable ampacity for aluminum sizes No. 6, No. 2 and NO. 4/0 AWG shall be 60 A, 100 A and 200 A
respectively. In this case, the 5% adjustment of Rule 8-106(1) cannot be applied.
†C.E. Code Rule 12-712(3)
46
CORFLEX® II RA90
Copper Conductors
Nexans ref.: CORFLEX® II RA90
Description
Single or multi copper or compact ACM aluminum conductors with EXELENE ®
cross-linked polyethylene insulation (RW90 XLPE) enclosed in a liquid- and
vapour-tight solid corrugated aluminum sheath. An overall sunlight resistant, low
temperature, low acid gas and low flame spread (LAG/LFS) PVC jacket with FT4
and AG14 rating.
Unjacketed CORFLEX® with FT4 and AG14 ratings is also available.
Rated 600 volts. LEAD FREE and RoHS compliant.
CSA File #LL19376 Class 5812 01 - Cable Standards
CSA File #LL19376 Class 5818 01 - Hazardous Location Cable Application
National CSA C22.2 N° 123
Application
For exposed and concealed wiring in dry or wet locations and where exposed to
the weather. Nexans cables are marked "SUN RES" for sunlight resistant.
For use in ventilated, non-ventilated, and ladder type cabletroughs and ventilated
flexible cableways in dry or wet locations.
For direct earth burial (with protection as required by Inspection Authority). For
direct embedding in concrete, masonry or plaster (with permission as required by
Local Inspection Authority).
For service entrance above or below ground.
CORFLEX ® cable is certified for use in hazardous locations with approved
connectors. Nexans Canada Type W connector are approved for Class II
Divisions 1 and 2 (Groups E, F and G) and Class III Divisions 1 and 2.
Characteristics
Construction characteristics
Conductor material Copper
Electrical characteristics
Maximum operating voltage 600 V
Usage characteristics
Maximum operating temperature 90°C
47
CORFLEX® II RA90
Copper Conductors
Three Copper Conductors
Approximate Diameter Approx Net Cable Weight Connectors Minimum†
(Nexans Bending Ampacity
Over PVC With PVC
Over Sheath Without Jacket Catalogue No) Radius 30°C
Size AWG Jacket jacket
Ambient
or
Wet (amps)
kcmil Dry
Hazardous (CE Code
mm in mm in kg/km lbs/kft kg/km lbs/kft Location mm in Table 2)***
Location
Type D
Type W
14 12.4 0.49 15.5 0.61 164 110 238 160 13D2 13W2 163 6.4 15
12 13.5 0.53 16.5 0.65 201 135 283 190 13D2 13W2 173 6.8 20
10 15.2 0.60 18.3 0.72 290 195 379 255 16D2 16W2 192 7.6 30
8 19.6 0.77 22.6 0.89 439 295 551 370 20D3 20W3 237 9.3 45
6 20.8 0.82 23.4 0.92 567 381 699 470 20D3 20W3 246 9.7 65
4 24.1 0.95 26.9 1.06 834 561 990 665 25D3 25W3 282 11.1 85
3 25.1 0.99 27.9 1.10 992 667 1153 775 25D3 25W3 293 11.5 105
2 29.2 1.15 31.8 1.25 1281 861 1466 985 30D4 30W4 334 13.1 120
1 30.7 1.21 33.4 1.31 1663 1117 1751 1177 30D4 30W4 351 13.8 140
1/0 34.3 1.35 37.1 1.46 1898 1275 2115 1421 35D5 35W5 390 15.3 155
2/0 38.9 1.43 42.0 1.53 2398 1611 2644 1777 40D5 40W5 441 17.4 185††
3/0 40.2 1.58 43.4 1.71 2873 1931 3128 2102 40D5 40W5 456 17.9 210
4/0 43.5 1.71 45.9 1.81 3569 2398 3845 2584 45D6 45W6 482 19.0 235
250 48.5 1.91 51.3 2.02 4394 2952 4703 3160 50D8 50W8 539 21.2 265
Selling information
Insulation Colour Code:
1 Conductor - Black 4 Conductors - Black, Red, Blue, White #14 - #2
2 Conductor - Black, White #14 - #2 Black Insulation with white printed numbers #1 and larger
3 Conductors - Black, Red, White #14 - #2
Fire Alarm and Signal. Security System and Extra Low Voltage Cable (FAS 105/LVT)
Description
20 to 12 AWG solid bare copper conductors (stranded conductors optional).
Multiconductors: 2 to 50 unarmoured. Conductor #3 of multiconductor cables is
coloured green, suitable for bonding purposes.
Outer jacket is 105°C flame retardant and sunlight resistant red PVC.
Optional aluminum/mylar shield with tinned copper drain wire. Rip cord under Standards
jacket for safe, easy jacket stripping.
National CSA C22.2 N° 208,
File No. LL23462
Application
Characteristics
Construction characteristics
Conductor material Copper
Electrical characteristics
Maximum operating voltage 300 V
Usage characteristics
Maximum operating temperature 105 °C
49
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Mutual Capacitance * ** * ** * ** * ** * **
(picofarads/m)
Unshielded Cables 108 -- 98 -- 89 -- 82 -- 79 --
(Pairs or Singles)
O/A Shielded Cables > 6/C 108 197 98 177 89 161 82 148 79 141
O/A Shielded Cables 6/C or less 223 400 203 361 177 318 157 279 154 272
*Capacitance between adjacent conductors.
**Capacitance between one conductor and other conductors connected to shield.
50
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Selling information
Notes
Unless otherwise permitted by local electrical inspection authorities, Section 32 (Canadian Electrical Code) requires that
non-metallic sheathed fire alarm cables used in non-combustible buildings be installed in conduit or metal armour (Rule
32-102), regardless of an FT4 designation. As a cost-effective alternative to metal conduit, SECUREX® II is available with
an interlock aluminum armour.
51
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Description
20 to 12 AWG solid bare copper conductors (stranded conductors optional).
Multiconductors: 3 to 50 armoured. Conductor #3 of multiconductor cables is
coloured green, suitable for bonding purposes. Armoured constructions must
have a minimum of 3 conductors, using the green conductor for bonding only.
Standards
Outer jacket is 105°C flame retardant red PVC. Optional aluminum/mylar shield
with tinned copper drain wire. Rip cord under jacket for safe, easy jacket National CSA C22.2 N° 208,
stripping. File No. LL23462
Application
SECUREX® II is a 300V 105°C cable specifically designed for the interconnection of security system elements:
including fire protective signaling devices such as smoke and fire detectors, fire alarms, and two-way emergency
communication systems.
Code Requirements
Although SECUREX® II cable is fire rated to CSA FT4 requirements, Section 32 of the Canadian Electrical Code requires
the use of mechanical protection for fire alarm cable installations in non-combustible buildings.
RULE 32-102
Subrule (1)
All conductors of a fire alarm system shall be:
installed in metal raceway of the totally enclosed type; or
incorporated in cable having a metal armour or sheath; or
installed in rigid non-metallic conduit where embedded in at least 50mm of masonry or poured concrete, or
or installed underground; or
installed in electrical non-metallic tubing where embedded in at least 50mm of masonry or poured concrete.
Subrule (2)
Notwithstanding Subrule (1), conductors installed in buildings of combustible construction in accordance with Rules
of Section 12 shall be permitted to be:
nonmetallic sheathed cable; or
fire alarm and signal cable; or
installed in a totally enclosed nonmetallic raceway.
As a cost-effective alternate to metal raceway, SECUREX® II is now available in popular sizes and conductor counts with
aluminum interlock armour.
Characteristics
Construction characteristics
Conductor material Copper
Electrical characteristics
Maximum operating voltage 300 V
Usage characteristics
Maximum operating temperature 105 °C
52
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Colour Codes
Multiconductor
Cond. Base Longitudinal Cond. Base Longitudinal
No. Colour Stripe No. Colour Stripe
1 Black 16 White Brown
2 Red 17 Green Brown
3 Green 18 Yellow Brown
4 Blue 19 White Orange
5 Brown 20 Black Orange
6 Orange 21 Red Orange
7 Black White 22 Green Orange
8 Red White 23 Brown Orange
9 Green White 24 White Blue
10 Yellow White 25 Red Blue
11 Red Black 26 Yellow Blue
12 Green Black 27 Brown Blue
13 Yellow Black 28 Black Red
14 Green Red 29 White Red
15 Yellow Red 30 Brown Red
Note: Cables over 30 Conductors will have Black or White insulation with number coding.
53
Contact
Residential/Commercial/Industrial
Phone: 905-944-4300
[email protected]
Mutual Capacitance * ** * ** * ** * ** * **
(picofarads/m)
Unshielded Cables 108 -- 98 -- 89 -- 82 -- 79 --
(Pairs or Singles)
O/A Shielded Cables > 6/C 108 197 98 177 89 161 82 148 79 141
O/A Shielded Cables 6/C or less 223 400 203 361 177 318 157 279 154 272
*Capacitance between adjacent conductors.
**Capacitance between one conductor and other conductors connected to shield.
Selling information
CAUTION
In case of fire, well-maintained early warning smoke detectors will give an alarm long before non-metallic coverings become
combustible.
However, in spite of the widespread and longstanding use of PVC in residential and commercial buildings, all purchasers of
PVC insulated/jacketed products should be aware of the following:
Non-metallic coverings of electrical cables can burn and may transmit fire when ignited.
Burning non-metallic coverings may emit gases which are toxic and may generate dense smoke.
Emission of acid gases may corrode metal in the vicinity; e.g., sensitive instruments and reinforcing rods in cement.