Reverse Current
Reverse Current
Reverse Current
Advice on generator configuration for PV systems
using Sunny Mini Central
Contents
In contrast to the Sunny Boy string inverters, or the Sunny Boy Multi-String inverters, in the PV generator of a
system using the Sunny Mini Central, three and more strings are usually connected in parallel. This does not
sound particularly spectacular but it has practical consequences because, in such large generators, certain
faults which are totally uncritical in string systems must be allowed for: short circuits can cause wrongly directed
module current, leading to a PV module being subjected to so-called reverse current, which may be several
times more than the normal maximum current (short circuit current) of the PV module.
Reverse current into the faulty string = total current of the remaining strings
Short circuit!
+ L
- N
2.1 String Technology
All components in a string (modules, cable cross-section, plug connectors) must be designed as reverse current
for the remaining generator short-circuit current. In the case of a parallel connection of a maximum of two
strings, this is always so, since the resulting reverse current of a (defective) string can reach no higher value
than that of the short circuit current of the (intact) string.
2.2 String Diodes
The so-called string diodes connected in series with the individual strings prevent any reverse current in the
corresponding string. Disadvantage: The diode is always connected in series to the corresponding generator
string, the string current flows through it and leads to correspondingly high continuous losses. Moreover, the
failure of the diode may cause the loss of the safety function or lead to the failure of the entire string.
2.3 String Fuses
String fuses connected in series to the individual strings can limit the reverse current in the corresponding string
to the permitted maximum. The losses at the string fuses are significantly lower than those of string diodes.
Failure of a string fuse can be detected by monitoring the fuse or by intelligent fault monitoring of the PV
generator. The Sunny Mini Central 9000TL / 10000TL / 11000TL inverters are already equipped with an
integrated, monitored string fuse unit.
Detailed information on the choice of fuses and approved fuse types can be found in the technical information
"Application of string fuses of Sunny Mini Central 9000TL/10000TL/11000TL" in the download area at
www.SMA.de.