4ltill: Irlll
4ltill: Irlll
l| $ I
$
D
fr I
I
i 5
4.o
4ltill l,I.
irLll UrJro
Lt f) a )
af .l
cJrt" t
Lecture (2)
Power systems 3'd Year
':.-o=fiVlcos9
Foreconomicreasons,transmissionsystemsisdesignedtotransferthemaximumamountof
system is directly proportional to the
power, from the above expression the power in fiansmission
following operational parameters:
P^o, c( V-r, l^tn
l_,
In such that :a.
It is desire dtoincreasethevoltagelevelaspossible(lz1)(limitedbythecapitalcostof
- i'-"
insulators, towers, transformers and switchge
ars)' ,
t
Lecture (2)
?ower Systems 3'd Year
transmission voltage
emP irical formula can be used to find the economical
The following
level in a 3-Phase ac system: .- '
N 3P
V=5.5 0.62i + Go
Where
2,2 Conductors:
in overhead line must have:
The conductor material used
(low resistance)
a) High electrical conductiviry
strongJ
bJ High tensile srrength [mechanically
aJ Low cost
ThetwomostcommonmaterialsusedinoverheadlineconstructionareCopper(Cu)and
explains the main differences berween the two
comparison
Aluminum (AI) , the following
materials attrfuutes are better)
ftiotaea
Melting FlexibilitY
Tensile Weight Cost
ConductivitY Tempe rature
Strength
High Higher Higher
Higher Higher Higher
Lower Lower
Lower Lower Cheaper
37.570 Lower
2
Power Systems 34year Lecure (2) I
.t For the same resistance, Al has a larger diameter than Cu (reduced corona effectJ
. Cu has higher current carrying capacity.
Al conductors used in T.L. are always strandertlaf€-asier handling, easier trarsportation l(on
drums]i and to avoid mechanical vibration which may lead to conductor breaking. LG
&
@
Stranded conductors are easier in manufacturing, instillation, have better flexibility and
mechanical properfies, large cross-section conductors can be obtained by simply adding
The number of strands depends on the number of layers ana on[glg$g1all the strands
are the same diameter. (all strands are equal in diameter) ,total number of strands can be
obtained by the following expression:
r_fl
N"=1+3n(n+t)
1+'
Where n - is the number of layers around the central strand.
No. of layers (n J 1 2 3 4
t4tt*tld
Sranded conductors usually have cenffal wire
(corel rounded by several layers of ( 6 , t2 , tB , 24 )
wires as shown in the following figure. i,. t -i t
',- ",.'
D=(t+zn)d
Where d - is the diameter of the sffand'
Al-Mamon College / DeDartment ofElectrical Power Technioues Engineerina - h Azhat M' Al'Rawi 3
#+,+, Lecture (2)
Power Systems 3'd Year
of conductor'
mm Calculate the equivaient diameter
Example: Stranded conductor 79 l2'9
(dJ = 2 9 mm
Solution: The diameter of one strand
Ns=1+3n(n+1)
;. 19 = 1+ 3n(a+ 1)
\8 -- 3n2 +3n
nz +n-6=o
(n+3)(n-z)=0 "'n=2
Therefore,thenumberoflayersis(2J'distributedas:
=t 1 + 6 + 12 I
core 1st laYer 2nd laYer
D=(1.+Zn)d
(1 + 2x2)xZ'9 = 74'5 mm
-
2.2.1 TWes of Conductors:
SeveralconstructionrypesofAlconductorareavailableininternationalmarkets,theseare:
shorter
All Aluminum Conductor purity 99'9% 'which are usually used for
1) AAC :- '
' spans'pecause ofthe low tensile strength'
of Al Mg and Si thermally feated
2) AAAC r- All Aluminum AIIoy Conductor ' made '
resisdve'
Alloy , better tensile strength and corro^sion
tr-,e inner strands are made of
steel
3) ACSR :- Aluminum Conduc"tor Steet n?'#tt;q
and distribution
(71i18o/o of conductor weightJ this type B-u,1ed :'iransmission
tow,Fd! tire cost is rerativery row.
lines because of the high tensite strengrhiid
Reinforced ' same alloy of AAAC '
for
4J AACSR :- Aluminum Alloy Conductor Steel
resistance'
befter mechanical properties and corrosion
Reinforced ' outer strands made of
AAC
5J ACAR :- Aluminum Conductor Al' Alloy
properties are between ACSR
alloy while the inner is made by AAAC conducto$'
and AACSR
Same as ACSR
,. 6) ACSR\AS :'Aluminum Conductor etuminun(@lSteel Reinforced '
steel to improve corrosion
but the inner strands are made of aluminum-plated
resistance and to lower the conductor weight'
2,3 Resistance:
I
Rpc = P
Whichisdirectlyproportionaltotheresistivitypandlengthofconductorl,andinversely
proportional to the cross section area A'
Theresistivityofconductorsisafun*ionoftemperature,hencewhentheconductor
temperature changed and resistance isE y9r9d,
': -5?
\-
Rz = Rr[1 + a1(tz + t1)]
J'"
"-
Where a1 is the temperature coefficient at t1
('C)' this coefficient is associated with the
material used
is expresses as the resistance of one
ln three-phase AC transmission' the resistance
conductor(resistanceperphase)'ItisslightlydifferentthanDCresistanceandcanbefoundby:
>\ Rnr=T
2.3.1 Skin Effectr
current
In high volage power transmission' the +
is :
distribution inside the cross section of conductors +
+ +
' Uniformly distributed >> ln HVDC
Lecture (2)
?ower Systems 3'd Year
2,4 Inductance:
The induced voltage in any conductor is :
d!)
"dt
dtb di
- di" dt
di
= Lx--
clt
Whererpisthemagneticfluxlinkageoftheconductorinweber-turn,/-istheinductanceofthe
conductorinhenry,Theinductanceinnon.linearmagneticcircuitsmaybedefinedastherateof
e
dil)
I:-:-
dL
Whileinlinearmagneticcircuit(constantpermeabilityp),theinductancemayexpressedby
l, =!I
two types of flux linkage, internal and
Each conductor in the transmission system undertakes
external,theinternalfluxisproducedbytheinternalcurrentinsidetheconductor,whilethe
adiacent conductors'
external flux is produced by the current flowing inside
ltotat .7 thte,not * Terternot
Where
I T
7',., x!0-7 Wb.-
2 m
- Dr Ador M AI-Rowi 6
Al-Momon College / Dt)r,artment o.f Elecl.:ical Power Technioues Engineefing
Power Systems 3'd year Lecture (2)
Therefore ,
Ttrt
7D
I (-*ln-
= 2x70-7
4r
D
= 2xl0-7 / In (------,-;
t4 re
-D
\r*,-lli J* .. L = zxt0-, ln (T)
The term r' is thei fictitious conductor assumed to have no internat flux but with the same
inductance as the actual conductor of radius r ,
The e:qtression (r' = 0. 7788 r ) is applicable only for solid round conductors
Gron-strandedl.
I. Therefore, the inductance per conductor in single-phase transmission line is:
ii-iirt${ie *jdiu
II. Sometimes it is required to estimate the inductance per-loop length. in this case it is
double the per-phase inductance i.e :
.D
L
=*xtu-? tu{ cun)
III. In three phase transmission. finding the inductance per-phase for the line can by classified
into lwo scenarios: r '- \ " '
aJ Three phasci ln-Syumetrjeslspacing lines
J i*t D=GMD= 3
drxdrxd,
---a A
A T d.t
AB
?'i,'3-a; t
C
ts q---.._d, C
ds a B
..-
dj
t dz :
J --l c 1- di S,
GMDA+GMDB*GMDc
// \
w
The acronym GMD is the Geometric Mean Distance.
balance the
lnthiscase,theinductanceofeachconductorisdifferent:technicallythiswillun
inductances'
voltages due to different voltage drops cause by different
receiving
to
The solution of this Problem is ,1
.
,ulj, tu"LLF:
-' @thelinesattf) tntrin' D.,
Drz Posltron
Position
1
2 2
Io'
lort
D., Position 3 3
Iength as shown in the following D;l
figure.
3
J
This procedure is well know as
:
e n
t
clrer
lines'
b) Three phase S-vnrmetrical spacing
drdz=ds
d
i ,d
o d
a
:.D -- GMD -fi =a
.!.Thelineimpedanceisbothcases(un.symmetricaltransposedandsymmetrical}ines)can
be found by the following expression:
G'lolD\
L = zxLg-? ln{f*n, fllm
Forallstrandedconductors,manufacturersillustrateGMRintab)es,electricalengineers
is calculated
by knowing condudor type and size, while GMD
values
can easily locate the right
from the line configuration'
C4J'
- o'On' o'*o*' 8
rr^on r"'r"0" n"non^"" ''
n ''""'"o' 'on"""'nn''""'"n'no"'o "
nf
Power Systems 3'd year reaure (z) f
GMR= (dud12di3.... dr" ).(d2r . d ,-..0r" )......(0"r.d.2.....d*)
1
J
drr=GMRr
dzz=GMRz
?
n
dnn=GMRn
same v-,-
)sJ
v"p
o
b
o a c b
o
c
o o,n
om CC
Where D"a,is the distance between conductors (a) and (a') etc.
1,'"
I
'
Examole: Find the loop inductance and reactance per km for a single-phase overhead line consists
of two solid conductors, e ach 1.213cm diameter. The spacing between conductors i s 1.25m.
h?" ' 'c" 'l
Sotutionl:
i'r ' '' \" r-.,,rr-. : ..?*,
' / ':\c-^
D=1.25 m
1.25 m
r_
lP l-)e \r ) .Yl,
r = d/2 = 7.213/2 =0.5065 cm 1 273 cm L__ ;OD
Since both conductors are solid and identical ." GMR = r' = rx} '7788 = 0'4723 cm '
D 1.25 uH
L = 4x70-7 ln (
GMR
)= 4x10-'l"(OEfu) =2.23 m or 2.23mH /km
'/r!\;vrvr $-:'J. "'
Xl = \trf L = 2xnx50x2.23x10-3 = 7 O/ km
-bt'',
d\)-/-v
EuFz\\
9
Lecture (2)
Power systems 3'd Year
Example:ifwereplacetheconductor(bJoftheaboveexampleintol.Scmdiameterconductor'
Lz =2x70-7
L.25
ln( 0.5841x 10-2 - 1.07 'uHor 7.07 mH
1-
mKm
f"11lS"S^LS = 1. tt1 + 7.07 = 2.185 mH
/km
1u ,^\ Xl = Zttf L = 6'86 A/km
= 2xtrx50x2.185, -\
t/D -
d=1.2m t.
4,i '.d
l=150 km c d
b
Solution:
1 4 cn)
Solution
GMD =
3
d.o6xd.6rxdo, = 5x5x10 = 6.3 m
con)'<to' ii"^*i
q,t;d ;v',,'ti i. 1.4
| xfi-l x0J7 88 =
<*-J,i g yp= 5.4516x10-3 m
t rr, 4j'a
i,!.,;,','" Al-Mamon Colleoe / Depofiment of Electrical Power Technioues Engineering - Dr Azhat M AI'Rowi 10
Power Systems 3'd year Lecture (2)
Example: Find GMD, GMR for each circuit, inductance for each circuit, and total inductance and
reactance per meter for the following two circuits tlat are run in parallel. One circuit consists of
three 0.25 cm radius conductors. The second circuit consists of two 0.5 cm radius conductor.
9m
a
a
a
6m ,"[
rT
, i' b
{. b
b
m 6
c
\ r_.c
Circuit A Circuit B
Solution
m=3,n'=2,.'. m.n' = 6
6
GMD = (D oo, D o6,)(Dyo, D 66,)(D ro, D
"6,)
/l k4)( tSrto'gl)
-r,l 0 * p.lt ) ( tt-C
where
D,'o'=fiou'=9* 19-/43n
Do6,=Do;=Dcb,= 62 +92 =ffim : tb-81
. . GMD = 70.743 m
Inductance of circuit A :
.f-p \V, Al.Mamon College/ Deoartment ofElectrtcol Power Techniques Enolneering - Dr Azhar M. Al'Rawi 7t
"v o-??il
-Yu
e I
Lecture (2)
er systems 3'd year
lnductance of circuit B:
Islal-Be3carl!e!
Xl = zttf Lr - 0.+622 A/km
{ )+&
:L " l.
o
,t l.l"/., ) the electrical current of eac h phase using multiPle
Most transmission lines curry
e;
u4rY conductors ( 2,3 or 4 ), this configuration is used to:
dt
1)\ azit ,t)
,4., -
efficiency by reducing Corona Loss fty enlarging the
lncrease the transmission
t. o-----t
3-----O
\ a . O. -a
L ''''^-'?
l^ (6#-r-o*n gr''.
L:z' ti7 Two Bundle conductors [1ip!gBund)e conductors
\Quad Bundle conductors
. GMD
L = Zxlj-/ l" (EtqRo) H/m
Al-Momon Colleoe / Depdrtment ofElectrical Pon er Technioues Enoineerino - Dr Azhor M' Al'Rowi t2
Power Systems 3'd year Lecture (2) I
$aCIBE: 3-phase , 50Hz , 400 KV overhead transmission line the conductors are arranged in a
horizontal plane , each phase has two strand bundle conductors , the diameter of each strand is
25mm , as shown in the figure below. Find the inductance per km per phase .
0.3m 25nun
*--->r
+i
a
I
r_>
ta, aa F-
a a I
I
6m 6m
Phase A Phase B Phase C
Solution :
-\
+ A\
L"7 le th
J45
2 ,y' e'/
/'
{'cnt ),r/o '^
orT l.r t
>;tu-
'")u t -
r^7v ',fu,P,,g,.Z
JI - \)-'Y r\
q \-, ,''rt Jry''w
\-t-/-'
d $
$
D
t.
$ t
I
4-o
t
4!r$t lt
i$^ll LtJr"
J*4 -P) o )
.,. .i
cJrt, t
\
Power Systems 3'd year
Lecture (2)
2-s-C3paqta!ee! d--:Ir? ,( f
for long cylindrical isolated conductors, the
flux is radially distributed and the equipotential surfice
is also cylindricai surrounding the conductor,
The potential difference between two points in volt
is
equal to the work done (in joule/coulombl
to move a unit charge b-etween the points in different
equipotential levels.
P1
,u = o* =
Ioi,', [oo,' #na. = frm(f,)
D1
where e is the permittivity of the material.
a b
fo rh
on conductor a is equal to :
vot(q) = lum!
zIf€ ra
The potential difference due to the charge
on conductor b is equal to :
vba(q) = !t-n!
tfte Tb
ifbothconductorscurriesthesamecurrentvaluesbutinoppositedirection:.Qo=_eb
+ vot(qt) =:qo hD
zE€ f6
@vrerTechniques Enoineering_ Dr Azhar M. Al-Rawi ,14
'Power Systdms 3'd year Lecture (2)
Qa 1T€
Cat
llnh D D
7r€
ffi ln
tlroro
ifro=76=1'
Tre F
Caa
P-* T
or
r --
eaa
-
1
n pF /km
36xln!'!'
This represents t}te capacitance beEween two conductors (Line-Line Capacitance)
a B
Con = pF /km
,,=
#rynF/kmlphqse
Charging Current Per Phase:
Ir=jaCoVun
Examole : Find the capacitanqe between conductors and the capacitance of each conductor to
neutral for a single phase transmission line, 10km long the diameter of each conductor is 1.213cm ,
Solution:
GMD:D
ft€ nx8.85x10-12 F
Caa
. GMD . r.2S - 5.27x10-12
m GMD ;Jv
a ln- T ''' 1^-2l3x1^0-2
jJt
2 t.L .-/
1 tu- t'/h
- or S.ZlpF/m L a f/n
(:rL- t or 5.2Lx10-31tF/km 3 ^
,ri nlf. _
t-Lfi
"o Cqn = 2Ca6 = L0.45x70-3 ttF /km
for L0km
y'L
,o
.4.'
(t
v6t 4 V
()u (
Al-Mqmon Colleoe / Deportmeft of tlecticol Power Technioues Engineering - Dr Azhar M AI'Rdwi 1r,
Power Systems 3'd year Lecture (2)
*?- r\
. Exanrple.: a 220kV,200km ,3-phase rransmission line, the conductors are aligned on the corner ofa
t iliffi rvf tit 6m, 5m and 12m sides. The radius of conductor is 1.81 cm. Find the Spacitance per
phase per km, capacitive reactance per phase, the charging current and the total charging MVA.
Solution:
,J"ag-o
Capacitance Per Phase :
7
cn pF/km/ptnse
].BxlnGMD
r
GMD =
3
6x6x12 = 7.56 m t.8lzm
l-
A ,.Cn
7.56 -e.2x!0-1 \prrcn\
l9xln 1.81x 10-2
\-
'a,spt lt tit*
1
L't- ur/**
ta*@
for two bundle conductors rb = .'lVxd
for three bundle conductors rb = 'r/lW
for four bundle conductors rD = l.O9x\lrxa3
Example; a 400 kv, 3-phase transmission line, the T.L use two bundle conductors per phase
horizontally aliSnment, radius ofconductor is 1.6 cm ,the bundle space is 45cm, distances between
the center to center of conductors are 12, LZ and 24 m.
Solution :
7
ctL 1tF /km
lBxLn -vr
GMD
1
cn- L5.L2 = 0.0107L ttF/km
18xlnOTB45
H,W:
rt
r
,Pt .1
g.ltlt 'o'-*llJ eJttll #lrill 6-,11.,19
ir.t+ll ar.Ltt 4,tIS
'
t)
d $ I
$
D
----4.4
ra t
t
4.0
lijrlt lt
iJl.oll U,Jr"
Lt -P) a )
.l ra
cJ$" a
_-- /1,
-Jar^---f\\-'-->
& ,t4l'
o
Power Syslems 3'd year
,y'r')
Lecture (3) I
1) i Performan4of Trans Z
:
Transmission lines are usually classified as :-
F xr
I
lEl
v6 vB t8]
ul
a
{* 1
6=V,+i,z Q)
For any two-port (four-terminal network) the relationship between iBPut and output
quantities could be described as:
Is=CV,*Dl, (4)
In equations 3 & 4, the coefficients A, B, C and D are called tu)o'port parametcrs (or two-port
coefficients). Those parameters are :
-DrA I
AI
Ledure {3)
Power sysiems 3'd Year
(7)
AD-BC=7
below
(% is taken as a reference ) as shown in
:
3.1,1 The phasor diagram : for a short T'L
VS
>e' *,
.lr,
'ry 4 I Xr-
\ n\0
r J) f
6 A
t
F 1 I
(nri r6l \,7 I
B
0/
L'
6-iscalledthepoweranglefortheloadangle]anditrepresents$eanglebetween%and%,6is
usually small ( 1' to 7' ) for short T'L
0.iscalledthepowerfactorangleanditrepresentstheanglebetweenthevoltageandcurrent,
cos 0 is the pow er factor (normally equal
to 0'B to 0'91
Whenthepowerfactorisleadingthereceivingvoltagewillbeslightlygreaterthanthe
sending voltage, i.e
I
?0
+ IRcosQ, - lX6in0, = 0
7
R
:. tanb, =
V
* As it could be seen from equations 10 & 14, the voltage drop in the line depends on the
the
power transmitted (proportional to Iine current). As t]re power transmitted is increased,
voltage drop in the line (A[) is also in*eased,
.1. Also the load power factor affect the voltage drop ( as cos@ increases, Q. shall be reduced )
* In many practical calculations and at the initial design stages when the voltages at the
for finding t.}]e
sending and receiving ends are not known, we can use the rated line voltage
approximate value of AV'
p- p_ .t -_.Ju
,/"q =';=4f,;xLooo/o . ' ".;,i,,-
5tot| 1''''!')2 'u t'"'>')tt
Example; a 3-ph overhead ?ransmission line deliver 5MW at 1ikv (RMS line voltage) with 0'8
Rowerfactorlag.g]tt.thelineresistanceisl.36o.Lineinductanceisl6.5mH$lerphase).Calculate
obtain zero regulation'
(a) Sending voitage and voltage regulation. (b) Power factor ofthe load to
(a)
/,!'*f{h '
,sl
Y',Q7 A*'
, ,
+ lj3l+rz<7tL
A 2 ? 'l s"r,
^(
.,,? stn0 = sin (cos-1 0'8) = 9'6
cosO = 0.8
Xr = 2trx50x76.5x10-3 = 5.784 oltm
. r.5[a1 zO /to /
*Dl cut -/ r/ -t, ,i]
Q/ t); / 4
"//-t
r.6/+,'f-tlt1
h./ * to ,n;l ttL,;,!'It\,4t
t '< :Jt y<sut n
Lecture (31
Power SYstems 3d year N // JV rrr
)(L"1,$',\ &-, 1
J'1-
a t- " o
4)"'Q'vt'')\? X 5.184
r.d")
voitage droP o n this
the power factor from 0'B to 0.941 result fi ZERO 4*ry'-
eans that improving
,o{{rn6 ec e ivi n g e n d'
achieved by adding capaci
rransmission line. This can be ^rr
is lc' the new line
(in each phase)' the capacitor current
receiving end
c) if we add capacitors at the
I
the phasor diagram we can see
thatt '' ,):' dtl,n.i+i
.urrent is the sum ofboth lc+[r, from
I
-t
1. cos 36'87 = I cos 1-9'7-5
cos36'87
l;:s'[yyr,,
r , ,. rl . , -328cos L9'75 = 278.85 arnpere lc
\Jt .D \l t-ZI J .P
-sr'/
c= L45.e
,.
#i= 1tF
97= -C,t jqpll
(d)
t\h\/\ cti:.t,
. v)it,7,tt,tt
AD-Bc-- 1
/' l" ,{
,I
kW T -tro.1
,4'2i ;'w'4.',
Zz"t'^
Prors = 312 R = 3x(328)2 x1'86 = 600
$'
,1U\
;i=s..
*-oC.9
' .:::
'i '9<)t9)dt )
v"rt =
#x1oo96 = 35ffi = 8e'3o/o
-P,""*4
)' '"
l'l)
"n*o,, Homeworlc
?r' \Lot!.,
. y\ytvitt; &+*<S*-,L)t'tr\iu"* L *'; tvl"g
and Design
.3^1r.9,<1Ll pSB & Ex3 7 p5 I in Power System Analysis
Ex.3.4 P57 & Ex 3.5 & Ex 3.6
I r-tr+; I
B.R GuPta
Splucion;
Since the receiving end quantities are given, for lagging p,f we shall use equation 12:
o/oLV
Pa..R. + AX x 100o/o
=
Pr = S,cos@ = 20x0.8 = L6 MW
?ufhilo R = 5n f J 7-*.t
IL: ILfu
Vl7 = alkv
Pl ' o't,,
y1): /"0 lltlA
d d $ I
0
Il
-...-._
$ t
4-(
eilll ll"
ilLll #Jr"
J*+ -P) a )
ll tr
cJrL, a
Lecture (3)
Power syrtems 3'd year
.2El
importance
the length of T.L. increases, line capacitance becomes of gradually increasing
As
solutions can be
and should be included in the line representations and calcul ations. Satisfactory
obtained from what are called the nominal T ond n methods
1s N2 &2 ts wxLEh
i
+ lc
EI
ladI
vs tol
I
=c I
Hr
I
i
I I tI
Naukal
Therelationshipbetweenthesendingandreceivingendsquantitiesandthevoltagedrop
canbefoundfromthephasordiagram,thephasorbecomesmorecomplicatedinmediumT'Land
used
the theory of four terminal newvorks is usually
_-l>-f t3'""*
---'ir ---"-: ls TF D
--/-- ,Z
-q" 'R2,
lF
x,
2
h Ic B
V, = V,
zz
+ 1,2+ I"Z= Vr
ZZYZZ2Y
* l, i+U.T+ Ir2+ lr n
ZY ZY
L--'- = Ur( 1*T + tfL 1*z- (16)
',
The four-ports network presentation of nominal T T.L regarding equations 3 & 4 result in :
ZY
A=D _L+T dlmentionless ; o= z(t.'*) n; c= Y 3 orlJ (stemens or mho)
In matrix form: f b
1*z
ZY
Z 1+-ZY
4 ) (17)
ffir= ZY l',)
Y r*-u
C D
Example: A 3-phase, 50-Hz overhead transmission line 100 km long has the following constants
:
Solution:
'(,
at t;f
/
:
c loi ls n, '*#
IlJ lB
B
t -a
l
Neutral
t I^
( +z]) = oo + izo) [, .
q,4@] = s.sb +,1's.s7 9 ;f,+
B =z
-).?-&'
{e
q+ = | = j4x70-a U';'\t'? ?o.'; 7'';;i @
'4"7.'a:\
tr l[: Air4t';'b
tA"')j' a'j;it;' at a/ Z"z-t 1^:
,rv.
I
ryt?) s;r
(l) l'= QY, + Dl, = j4x7l-4x38105 + (0.996 + iO.OO2)x(87'28 -155'3)"'c+
-- jL5.24 + 87.06 - i64.86 = 87.06 - i49.62 = \0o'24 - 29'680
omp ;,.t$y>:
y's
;4;.x r cc\
(O.gs6+i0'002)x38105 + (9'95 + i19'97)x(87'28 -16s 3)
.Q)V; = AV, + Blr =
= 37952.58 + j7 6.21 + i1092.59 = 40725'93 + il76B'8
+ 2173.35
AV Z'zir G,
Li.,z 2'*?
IS R lL {L IB
\Q'tr I
r#J y_' \
, r I i
a+
o"//
*,rr, I
* A 1
,/u''ry
The phasor diagram is as shown in figure below:
o Ir-xr-
ts
lc2
B
1L
Ict
Is'.
T
The following matrix form of rr circuit illustrated by the four port parameters as in the following
equation: -_ O 'bYv)\s(; A G
6
)iY
t+-; z
rfl= Dzv (18)
Y (,.+) t*T ]rrr
Example: Solve the above example using nominal pi m':thod
A=D=r-T=0.996+lo.ooz , B=.2--70+j20
(10 + j20)xj(4x10-4)
c=v (t *L) =l+xro-*x + 4
= -4oox1o-e +l4oox10-6
[r
(t) t, = CVr + Dlr = (-400x10-e +i400x10-6)x38105 + (0.996 +i0'002)x(87'28 -165'3)
D Pi1 000
n = 95.450/o
Ps Pr + PLoss 1 475
(sl
69.53 - 66
Voltage Regulatton = AV =";,"'
vf = 66 = 5.34o/o
If the transmission line length is more t}lan 250km, the line parameters ( & L, C, G ) must b-e
distributed uniformly over the entire length. ln long tlansmissjon lines,Llumped representation as
in short and medium lines fails to provide correct cu+rent, voltage and power values. Due to this
fact, all line parameters is distributed uniformly over small incremenqlengths (AxJ until / reached'
(1e)
7
4
i; /
t'c s.clrll '''-ftlJ sJtdt dh3ll i;1.16
ir.t+ll ,13.LJl4$
l)
t 4
4#L.J+sll 6-;.$Jt et4jti L.:l #
$ l| $ I
D
t.l
r| t
44
lilrjjl lt
i$^ll UnJr"
Lt -P) a )
.l t
drtt a
-Power systems 3'd year Lecture (4)
L.A
l, =Ev'-EV,
A 1
"B o-Ur,
. Iet V. = lV,lz\ ,V = lvslz| ,A _ lAlza ,B = lBlzp
\=ff.{o+6-n-ffi.-s
The conjugates of both currents are:
+--E.rp-D-AJislz$-a)
,;=W.o-a-6)-#.u
The complex power (per phase) at both ends are :
s, =.
p, * je, = v,E = lv)zo x[H.* _ q _VM.* _ a]
s, = p, +/Q" = %6 = tu"tza x
IW.*- d - d) -#*)
Note:
The total three phase power is Three Times the per phase power, this is because each
term of
equations t1l & (2) use a product of two per phase voltages so J5xy': = 3
1' A
-- ll., -
t-,B -t/
8,,
AL
I,=EV,-AV"
Let V. = l\lz\,V = lvslz|, A = lAlLq, B = lBlzp
\=ffza+6-p)-ff.-o
The conjugates of both currents are:
,;=H.a-D-WLG-a)
,; =tor|jYl .$- a - 6) -ffi.p
The complex power (per phase) at both ends are :
Note:
The total three phase power is Three Times the per phase power, this is because each term of
equations t1l & (2) use a product of Ewo per phase voltages so V3x V3 3
=
From equation (1J&(2) the active and reactive power of both transmission ends can be expressed
as
r. = I'lyil' cos(p - a)
$fl.,"(, - u, - 13)
Q, =
t|fl ",,,
o - a -tAlVrit' sin(B - a) (4)
Note: To achieve maximum receiving active power in eq (7J, the load must consume the reactive
power in eq(8J.
Special Case
As an approximation. the transmission line is represented in the simplest way, i,e short
transmission line in such that:
A_D=7zo,B=Z=lZlL9
Substituting these parameters in equations (3)&(4J result in :
r.=ff*r1e'-al-ff,,,6 (e)
o,=ff,inre-a>-ff,i,3 (10)
Practically, the transmission line resistance is verv small as compared with the line inductive
reactance, i.e R << X andlZl x Xand0 = 90".Dueto this fac! the above equations (9J&(10J canbe
simplified into the following forms:
I
Fower Systems 3'd year tecture (4)
D
= l5ily'_l
x
cos(90 - 6)
sin(ci)' (11)
q. -Wy! ,in(eo - 6) -g
-q"=ff,os(d)-ry . (.12),,
Another practical fact, generally d is keot very small due to system stability restrictions'
in other
words cos(d) ^, 1. This may simplify equation [12J into the following final form:
Npls:
.i. Examining equation (11), the maximum active power transferred ( also known as Steady
State Stabitiry Limit SSstJ occurs at 6 = 90", technically the power angle
is kept lower than
g0o to obtain stable system, practical power angle values is beween 30oto 45o
t Examining equation [13J, the voltage drop along the line is independent ofpower angle
5" it
is directly pioportional to the reactive power transferred'
Al-Mamot colleoe / Deoor'/nent ofElectrtcal Poti4r ?echnlques Enoineeting - Dr Azhar M' Al'Rowi 3
Power Systems 3'd year Lecture (4)
Example: a 3-ph l.32kV transmission line deliver 50MVA at 0.8 power factor lagging. The line
parameters are ,4 = 0.9823" , B = 11,0275" A/phase.
Find: d ?
L. Sending end voltage and power angle
2. Power factor at sending end
3. Sending end active and reactive power
4. Line loss
5. Transmission Line Maximum Capecity ti.e Maximum Power that could be transferred)
6. Transmisslon line efficienry
7. Voltage regulation
SoJulipn:
732
V, = ,15-
-76.2120- kV
0.98xL65.22 t3?xt65.2
= 110-.os(75 - 3) - 110 cos(75 + 11.35) = 62.S.LMW
since X xB
i6s:2I132
Pu"' - lu'.]-u'l = - D8.24 MW
since the transmission line maximum capacity is 19g.24 Mw and the actual active power
delivered is 50*0.8=40 MW. ,h" lin" ir .unnirg ra 20olo of SSSL. ,o po-.. flo*i, ,..nr.i..ion
Iine is in safe values
(61
Pr 40
4 x 640/o
Ps 62.51
(7)
AV =
165.2 - L32
= ZSo/o
-x710o/o
Al-M"^""kn"r"/D .]grSIU 5
.:.r' ,
.,'l
:
,g.
.l' ,/ s.hll '''-JrlJ sldl fttl3ll i;15
,N ,P.z 4
irri.lliills
Ar.l+ll
b
4#b.J#Jl 6;rul crllfi 4*.il pJ
$ $ t
I lr 0
D
I
ti a
I
4.o
liltll ll'
[rt^ll J^
I
-J =.rL 'rt
a
.l t
cJrL, I
Electrical Power Dept. Of Electrical Power Techniques Engineering 3'd year
f---'
-)-\i),/)
1-
2-
Pin insulators. (conductor at top, used up to 33 KV).
Post insulators. (used for bus bars, switches, etc. in substatiors) --, ; lt!,t i
B!! 80..
r '!4.
,
g-t
84,/
(
power voltage at which the insulator
material or air surrounding the iffiulator surface electrically breakdown or become conductivity
causing FLASH OVER.
4' conductor
insrro tor
e0r-'l n
The actual working voitage (line voltage) is less than flashover voltage by a factor of safetv
t'actor of safety
flashover voltage under srandard conditions +o 1),( /b cfd,s
working of lroltage (line to eotth)across irts../'lator "f,\nl. l*1., -4 t:)
suspension tx)e insulators consist of nu.mber of disks each having some standard voltages 4 s/rt
ratings.
prlr
1
4r* L;n.. t3L -2 L,'A-' -' d L /"''')
a/r7
IT v \t
-1
uz
T
\'3
)
Calculatious of voltase distribution
P-+"!g Find the voltage distribution across each unit of string of 4 disks aod the strhg efEciency
for 66 KV traasmission line. The capacita[ce of the lbk pirs joint to tower metal is t-0% of disk
capacrtance.
Solution:
Ir
<- .{f L1
toal voltage across 4 di-sks stri"S
<*L tsorr.\- F + = 3B.l KV 0.1 cc
F
iz=\*ir
jafiv2: ja(o.L)cv7+ jocvT t/'tu i {Lut+r,o16-t /,t,
*:
l1
c
a
_)
t t1
Vz = l.LVt ........(l )
1
'0-l C v-
R-
It\
c
At poiot Q
Tt liu
\=121-i2
j aCV, j o:(0.7)C (h + V) * j otCV2
-
2
_\F-JL
_rF{ {g'
--.-\ \ : I
t3
tt-a .{ rtJ
I
I
R
s
'J-
/ --a"u
Electrical Power Dept. Of Electrical power Techniques Engineering year
ir= Is* i3
jacva - j a(o.r)C(\ + V2 * ft) + jaCV, C La Urr*
V+ = \.L V3 + o.LVz I 0.7\
= t.gg y, ........(3)
Wehave VL+V2+V3+V4=#=3B.7KV .......(4)
A large metal ring is placed around the lowest insulator disk is electrically comected to the
conductor. This introd uces additional capacitance and together with the shunt capacitance
makes
the voltage distributi on more uniform.
) \ o". ( ):,\t .i":--'J:2\
Example: a 3 tmits string insulator is fitred with guard ring around the button insulator. The
capacitance of the link pins joint to tower metal and to guard rurg are t5%
and 5% respecrively of disk
capacitance. Find the voltage distribution across each unit of string and the string
efficiency
Solution: ./
I Nlal
\il *'u )
I
J/
t
,Dr
,rq
tt- '.- Nf)
Electrical Power Dept. Of Electrical power Techniques Engineering 3d year
{- t--
1.05v2-- 1.1s t/1- o.os (iH vr+ffvr) = l- l5vt -.0.05, vt - t.l|a v
\r\ ;\r),
slt ar V2 = (7.0345)V1 .(3)
Substitute 3 in 2
7r = 30.3 o/o
,V, -- 31.24 o7o,Vz = 38.54 Vo
V + t-oiL.l5tt-t?/)=loo
10t) . ,_ . )/-
(r''ogUS+\.L4/\
4
.a--4, a/\)
el 84 --+ 3-rz
171-------z w
Electrical Power Dept. Of Electrical Power Techniques Engineering 3'd year
-/) /3\ a ./o
Cables for Porver Transntission
l? *,
The overhead lines for powertralstiission have advanrages of lower cost and ease of connecdon
for,apping,isince conducioiis,b6ie,all along tength) compared with overhead line. The cosr of
c?rble due to the cost of insulation which has to be provided all along the leng& ofconductor.
J.
How the cable has jts own adl'antages over the overhead liles in respect of:
- cS^S t ti-'
r) etc., it's not possible to put overhead lines.
cost.
2) lightning, thunderstorms, rain...etc.
3) The cables can be buried under ground and space above ground can still be used safely
The main disadvantage of cables apart from its high cost is the difficulty of making joint,
tapping and the problems o fdigging for repair and maintenance.
w
U
\_ __,
Constnrctio n of cables F
Basically cable consists of a conductor insulated al1 along length from other similar
conductors and protected from molsture, chemical, mechanical handling and storage. Thus
Lh e main components ofa cable are:
,7 .
b) The mechanical damage by providing rmor consisting of steel tapes or rouud wtes.
Protection provided against damage due to pulling, bending, mlling and storage.
c) Protection against attack chemical. abrasion...etc.
r----/
--*\.;i-^*'--'."-.'' ('-:t'
In between sheath and armor ,ul wcll as outsidg complete covering is provided using PVC or
other fibrous material.
i) e ')J lP-a
*
1 4) XLPE(cross linked polythene) much superior to polythene, lower weight, 1ow dielectric
strengt[ good mechanical str€,lgth, working temp€rature up to 90 e continuous or 250 c
for shon time during fault an short circuit, v€ry suitable W to 33 KV.
5) Paper insulation: work up to high temp€rature, high dielectric strei:gth when
impregnated with oil, low cost.
lhe
most important ffi of cable laying is tt t u not be bent less than 6-g tirues
the dimeter of cable. "aUfl.no"rd
Capacitance of cables:
In cables the capacitance betv/een condustors as well as between conductor and ground is much
more than in overhead lines when cable is energized the current flowing in this qapacltance ig
called charging current and this can bq quite, high for loug high voltage cables.
.1
Over the soall elem€,nt of insulatioo of thickness dx
3 v- A single core cable 2.4 km long rated for 6.6 kv, 50 Hz, has a conductor diameter of 1.77
crn and
\. irsulation thickuess of 2.032 cm, the relarive permittivity of insulation is 3. Determine
the
,,
oo
.t,,,-. cbargjng KVA in thc insulation:
.l "
.
,\--)-..----:: -
b''L/' solution'-'o1 ") D l-17
ffi*o,**,,7o.uJ?
V -rsi, kne59
R = 0.887 * 2.032 = Z.92lcnt R 1
'/^"rrr=ff=Lu x 10- 10 F
h# ht tkn e!
-/A X
VL
1- r i'ipt, J' A
7 I h{'l
x airY\;-t- (K
zv'v-=,"
k
Ct \ t.t
.'.V-1.r'
),'
t- / //) 2./
2rT 6
t.-
J
y.
,/ x //o
\,,. 3
C\
3/ {/o
Z
7
2
I
J"\+a44_o
sJtarw JJ\
C.
-.-'--'>
3c"
-l,h cr1
4hDu
Ce
T. C
t/
C
+v!'";,
'q@"
8
I
EJJEII IL
)
6rUl uur^
I
-,rf\ s\:;\" , ar
drte I
7
r
6
/1
?/
'd r
Electrical power Dept. Of Electrical power Techniques
Engineerint 3rd yea r
)f'\,,* oFL,
lntroducflon
Faul tA na lvs is
'4p4v
ov 5 hoyl
t)t?'/w!v/v
e
The first type of faults is balanced
(or three phase) fault i s the
one when all three Imes are
*W'i,).-
shoned to ground. It is usually
They are the most common
rare, but can happen. Second
type is un balanced faults ,Lu+',Ld;
g r;-i'l
$,pes of fault and they are thre€ types: s lineto- und
faul linelo- line and doub le-l me-to- ult
When a fault occurs t ls lmportant
properly set the breakers,
to iso late it by openi ng protective
the magnitudes of the fault c breakers. To
the major p oint ofstudy Fault urents need to be known. This is
Analysis.
The life of a fault can be divided
;;a1.4i L The sub-traasient period which
into the follo wlng times which
lasts for only a few cycles
occur in sequeDce:
O
\, ?r Loads are converted to constant
assume iqual to I pu.
impedanc€s to ground using
The faulted network is reduced the bus vo.ltages.
into a Theven in equivalent circuit
faulted bus. Appl ylng Thev vi ewed from the
enin's theorem, changes in bus
a Bus voltages voltages are obtained.
d unng the fault are obtained
by sup erpo sition of the prefault
and the chan ges ln the bus bus voltsges
vol tages computed in the previous
a The currents step
during the laul t may now be
obta ined in all branches of
system. the faulted
y,i .:/? Exa,mole
linqLU 'w'
zt /
The one-line diagram of a three bus system
represented by an emf behind tr,. is shown below. Each generator is
t unri.nt
base and for simplicity,,
i...i;;;. iiih;drces are in per unit on a
lrJ#J.l resir,.r.., *. iigr..rcilil. io,orring assumptions
d"
J
24
Z-\,*t d. @4 /.ulL . v -,it
6)-o'(,(,,,,""',, t1:! ;y' ;t2--ns'
Electrical power Dept, Of Electrlcal power Techniques
Engineering 3d year
jo.I -->
t
to.2
e X { Kb ?o
K
3
7. to.1 J0.2
r\ ?"
j0. s
I 2
\R.
K
I RbR4
i0.4 j04 ko t(trRc RoRb
R --_.-__-
Ra. IiL r R C
Solution: (a):-
3
r2 Ro R"
Find Thevenin impedance seen at the
RatRLr
faulted bus.ltccording to Thevenin
change due to the short 's theorern, the
sircuit is equlvalent to that caused by
Vl=Vl (0) with all orher sources shorted, where V:(0) the added source
t+7-t3 J-' 6\ (where the fault will occur). i s the pre-fault vohage at bus 3
1 o
i0.t ,0-}{
i0..1 r(0)
\-r-F -\ J
\"U? f a"1r 3
r
trr]
7
t - j0.16 4-i0.t6 -i ,",l
-l
A lo"tb &-jo16 zf j0.t6 q-)0.t6
TT
0
6. L\
cgrqnt );o,ApL
Y^, t/'!b;*l
, O\r#f O -.t,(O-tl
o -.1 + o .q +o-g
o.l
\
Ay l^;u t:
,"J
( 0)
-[u' /(
,.].,,-t\
t
<'
iwrr 7
j
'J-----'Y
.),r''-.\r't -* \ ) '"rt/
Electrical Power Dept. Of Techniques eering
E 3d year
ILI(F)
v1(F) V2(F) 0.76 0.68
-
-
zrz =
lF.
- .\
= -io.tpu \
\
)-,
--o-/ r
v{F) -h(F) -
,V
0.76 0,32
[3(F) = =- = _j!.!pu I
Zts j0,4
r",rrr =@- %(F) 0.68 0.32 - q
Zzz =- j0.4 = _j0.9pu
J
J0.4 Jo-{
,0.a
-r
Zr. i0. tS
0
E) Zt- ,i'*l Zr-.,0-ld
2,rj016
,J.'? t
fov
g"1r o, 're
I d3y it
,,,1 The Thevenin impedance Zoat the.faurt point is givenby jo.24.The
fault current is given
by:
2,olv.',
5^*+Jfu
I.@=m=ffi;-iz,spu
I This cunent divided bctwcen the two gencrators as follows:
Ia, =
i0.4 6^," J
j6;;;5*ir(F) = -i7.0 pu
i0.6 bt ULr'
t ez = jdiTj16t2(F) = -i7.5 pu )O'
L4
26
4.
A"u ll. 7* v:--
,4, grt I
Irz(F)
v1G) -vzF)
0,8 0.4 - jo.5pu
Zrz jo'8
vL(F)-h@)=W=
I13(F) =
ZB jo.4 -j0,5 pu
1(3G) -vzf) 0.6 - 0.4
/sz(F) -jo.5pu
zt, j0.4
*t7^// In the same way we find part (c) [currents equal -j0.3125
g)t
>p\ "\,
Fault Analysis Using lmpedance Matrix
Network reduction by ThCvenin's method is not efficient because it is difficult to apply to
large networks
Examplel
o
Resolve ve exam ple by the impedance matrix method:
.!v Z, ) o'?-
0-, I ;04
U f,s
@=
j1.2
4,7
2,s0 j2
t,25
j6.
j2.so
2.50
js. Q:r
\ ).r
@
-F.
I
e
t't-
(-)
<-l )0 c
@= I bus
0.16 j0.08 j0.12 J ,aN I i0 ,l >L Z
\tt |""\rt L btts - 0.08 j0.24 j0,16
0.L2 j0,16 j0.34 --2 >L'ta-
'lt, ls, \ts I/s (o) 1
\ t1v er't rrray'r*
r3(F) - 43 + Zf j0.34 + j0.16 -j2pu ' n o)o^ *)
I afdu.,
rl.. v1(F) - v\q- z$h$) 1 - (/0,12)(-j2.0) 0.76pu
ad zrala,-t<. ' J t)
4/
6,'h fr rtJ, ),"qton
(10.15)(-i2.0) - 0.68 pu
vt, v2(F) - v2@1
v3(F) - V3@)
- Zxlsr') = 1 -
- 43\61 = 1 - (10.34)(-i2'0) = s.32 o' . , l\\ J-D,,
.L-t
"'t \\__r
1t'"r i..J
\
-l-Lt _-L
I -u ') 2.5 \ 'i z's
.^r;z-"n';-rS
i nrJ
\
Electrical Power Dept. Of Electrlcal power Technlques Engineering 3d year
w
lB
y'3v,
B s base MVA and Vs is the line to line base vo Itage in KV. Thus the fault
ere ls
Ix(F) =l
, x 10
x Xxx y'3v,
. /t Thus we have for the SCC:
SCC
vK(o) sBvLK t/..
= Xxx Vr
If we the base voltage is equal to thc line voltage (i.e
= yr;6e1
as-sum^e
[s
Xxr
The prefault bus voltage is usuall y assumed 1.0 pu,
thus we have the foll owlng
xrmate tion for the short circuit c&paciiy or short circuit MVA.
SCC
I
Xrx
cV-*) G J\
J-u;, )
----<d!>^
k-R---
28
Electrical Power Oept. Of Electrical power Techniques Englneering 3'd year
Unbalanced Faults
the figure the fault occurs between line "a" and ground through a fault impedance
Zr".
V. = Z1l3 1
I,*
Z/rVL. )l bY It = Ic = 0........ 2
*at'f 1
But we have
[#] ,ti
a
a2 {rtll t L-0
,t-
4rtf ;,/r,r/ '- =l 3
lsf,ba
@ro 1o =
313 ......J F- '.-
Thus the three symmetrical somponents are equal and each is equal to one+hird phase ,a,'
current. )
Phase "a" voltage in terms of symmetricel components is:
Vo = Voo t v; + u; ..........................4
Substitute 1 and 3/ in 4
4lfrdl d,, Z + 1
+ o ttl
'oo'4rt'" ,.,,,41
-L
) t, Zrnl I = -
3 I a?a
/L 5
Ia
ltzor=0-ZrE)
Substitute 3 and 4 in 5
vo= Eo- (zo + zt + z2)tl 6
''l
Where Zo = Z, I 3Zn, Z L=22=Zs
Substitute I and 3' in 6
Szflg = Ea- (Zo + Zt + Zz) r3.
Rearrange
ro Ea
"- (Zo +ZL+22+3Zi 8
Fault cunent is
a- 3 Ia0
+ 9
29
Electrical Power Dept. Of Electrical power Techniques Engineering
3'd year
Equations 3&4/ are the conditions L-G fault and according to them the
sequence nerworks ma as which satisfies the two equations.
*ll
z2 I:
t zt
T Io
=l[ t
t::t
1
1 i:l[ii,]
Expanding the matrix equation we have:
+
v.
=Q Y.
4 -J--
11 1
*3- (a - a2)16 5
(a2 - a)16
.6
From 5&6 we have
tA = -ri 7
j aLb
a
V"L =4tl+Vi 8
1',ut\c11,,5k
Torn
tI"
Vo=V! a
equations for phase voltages
*
Z"
9c r) fL tS Xe ,/*H
Vot Voz
30
'-y' ,:c7tp
Electrical power Dept. Of Electrical power Techniques
Englneering 3'd year
Va=V!+azVoL+aV.2
uro + a vaL + azu]
Y: =
Hence
,' - 4 ==;:;- - va2)
a)(vo'
(u!=o-zot1\
Wehave J vt=E -ztrrl
li:=t-iiif
u]
tlre values of ani ir2 from 9 and fiom 7 we
e
!s;n8
[ffiPJ?,,-,fl+z21t1i=z,r, . have
-. .... .,.io
E"-(zr+22)4=zr 311
(a 11
(a2-a)(a-az)=3
solve for { we have
,"-V@
,1
-
Aa
.........12
The phase currents are:
jllri]
kh{,.***
la=-1"=(a2-a)l|
= -j'l3lA
u.ing ir,e'lymrn.t i"at compon"nt:.^1i
.,*..lits in- e4uarion 9, thd symmetrical
of voltage (hence phase *1,"g",
ff[il:11n- iy'il*rf"#.ii"",1 at the fault point are
Equations 4' 7 and g are the
terminar conditions for L-L
sequence networks may be faurt and according to them
connected * rh;;;i;;;i.#[,]
[e terminat conditions.
the
zt l1
21 J:
+
vI
Io
+
vo
31
Elecirical Power Dept. Of Electrical power Techniques Engineering
3'd year
Example:
The r;rie-line d_iagram of a simple powe;
system
sh /n in the figure. The neutril oi each gineratoris
is^drounded through a current-limiting
,Iu.ro, of )1- Tr
A
u.z) per unit on a 100-MVA base. The syslenl Cata
is tabulated, below, The generators are iunning
nl.louf their- ratqd voluge and rated frequincy
on
)1 -= Tr )1
1t t
wlth their emfs in' phase. Determine the fauit
cunent for the following faults:
(a) A.balanced three-phase fault
at bus3 through
fault impedance Zr =j0.1 per unit. 1
7- (/0.12s,{/0.15}
= j0.0357t43
J0.525
j0.125 ){J.0.!5
Zu' I
j0.525 -10.0595233
j0.2s j0.25 j0.2i p25
Zts - __F3ii-
U0.lr)( /0.2si
i0 0714286
j0. r35
?r (j0.2857t,t31I i0.3095238 r
l
+ /0,0?I4286
J0.50i2381 j0.15 3
jo?s j0.0lj?14 ( j0.059524
- J0.23
j0.071428
J J
33
Ele.trical Pcwer Dept. Of Electrical power Techniques EnBineerlnt
3'd year
S-Dt,@
fst!!)
The boundary conditions at the fault point are:
+
V1 = V" = Zr(lb + I) ....................1 I.'o
lo= 0 2
From equation 2
I0 +Q+E=o 3 t
/6&?. in terms of symmetrical components are +
t%=vf+a2vot+avo21 v.
lV, - Voo + aUat + arWJ '..........4
( uoo =o-zot1\ zo Jc
We have
I y; = fo - ilil! '.. , ..8
(lzo2=o-Z'E)
Subsritute 8 in 7
fi _ Ea-zttA
- zo+3zf 9
Using 8 in 5
_ Ea-zLtA
n*22
l0
Substiture 9&10 in 2&3
,a
11
-
Ed
...........11
-,.zz(ia+ii
"-,nZa;fr
The terminal conditions ofL-L-G fault are in the equations 3, 5 and 7. Hence the
impedance. seen b y E5 is; z! + *,a rrom this we note that the impendence
in series with the parallel combination oi Z, and
ffi 21
Zo + gZ,.
Thus the sequence networks .un b. .o*".t.J
.r ln *" i,l U" figure above.
Finally rhe fault current is found rrom:
I + =31 12
32
Electrical Power Dept. Of Electrlcal power Techniques Engineering 3'd year
t005
4
n"1
sequence circuit. The result is the simple cfucuit
shown below. ,0.1 io.l ,Ol j0.l
JO.l5
fi017064 s )0,151
,(,lt
tr_t ]t
i
2rro-:equrocr
34
t
=- j7.BS19 p.u
The fault current is:
11 r0
t3a 0
a2a ,1
t3a -3.2075 p.u
[[t]=[ aa2 Eo 3,2075
,1 7eo(0)
z'*$ * 1
1,
;o,zz+-ffiffiffi.
= -j2,6017 p.u
,z -ha(o) - ztq
-----vi--
,o -
1- U0.2?)(- j2.6017)
j0,22
- j7.9438
,s =W= 1 -
1.odl#!-/#01?) = jo.6s?e
t 30.
30.
It
0
4.0582165.93 p.u
4,0582r4.o7
lf=lt+lc=7.9732 290
35
Power Station Simulator Lab.(pST 22OO) i-.-eahJl o9--LrJl e-.S
Power System Engineering q..j LrrSJl i!;rriU I ol.,.i] 4.*rriD A...r9
Experi ment 5
Medi um Transmission Line Characteristics of
Nominal zr Connection
Theorv:
For medium length transmission lines (from g0 km
to 320 km), if the
total shunt admittance of the line, usualiy pure capacitance,
is iivided
into two equal parts at the sending and receiving ends
of the line, the
circuit is called the a nominal n. Referring to Figure
(23) to derive the
relating equations. To obtain an expressiJn for'Es
and ir, tt. g"nJ
expression can be given as below:
E, - AE,+BI" (t)
I, = CE, + DI, e)
Ist Rix {r
C1 z 2
Es Y/z Y/z IOAD
Figure (23)
Nominal z model transmission line
& n *
;.E--€- a
,T ,5
-A,- L3
fr
R
X,,E
Figure (26)
3.In cubicle (6), connect the front panels C6.J2l and C6.J25 as shown
in Figure (14). It is the necessary connections for the substation step
down transformer protection.
-
4.Connect one outgoing high voltage line from C3.K5 (choose bus A)
to the left side of OH REAL LINE MODEL 1 in C4.J2t,and further
one from the right side of the rine moder to one incoming HV line on
the substation C6K13, as shown in the Figure (15).
S.connectone ofthe outgoing feeder in cg (choose the right one) to the
3-phase load bus bar in crO and further one connect the load banks
by means of jumpers, as shown in Figure (16). The load (resistive,
capacitive or inductive) can now be applied by means of the
INCREASE LOAD / DECREASE LOAD butrons.
Procedure:
1. Set the turbine MAN/AIIT switch to AUT, and the generator
MAN/AUT switch to MAN.
2. Energize the system as explained in experiment (2). The generator
line voltage should be adjusted to approximately 400 V.
3. To supply the loads with power from the generator. Open the
corresponding circuit breakers and isolators from the generator to
the load. Remember that this must be done in a cirtain order
otherwise some isolators may be blocked by the logical blocking
unit.
4. Increase the resistive load by pressing the INCREASE button twice.
5. lncrease the capacitive and inductive loads by pressing the
INCREASE button once, respectively.
6. Readjust the generator line voltage to 400 V, using the Fine and
Coarse voltage potentiometers
3
/z
9€s0'0 -l 1966'0 8920'06 r r00-a699r,'8 Srst'rt r €99t'8 9t-c0'0- L966'0
6000'0i+ /966'0 ,00-e6S9r'81+ t00-a I SS6' €- ,s8'Ll+z'z 6000'0f+ 1966'0
zlLZ + I ( tnx+r A Z zlLZ +r
q f, s v
@yoo r) uapauuot td n{ aJh{
(o) atqel
'(st
py rO ]uexnc pue eEelloa aprs Burpues roJ sllnser pel€Jnclec eql prre
s8urpee: peJns€eur erp uee^qeq ecuereJJrp eql ssncsrp p* .*d*o3 .g
',(po Eurpear lsrg
(sI pw
eLIl roJ prrp sg) luernc pue e8ello.,\ Eurpues aq1 alulncpc o1 (7)
pu, (I) suorlsnbeJo pr' aqt qlr^\ (g) atqel ur piprocar-s8urpr"i .7
.a1e1d "q, "rii
aureu eurl uorssrusu€I
aql ur peprorer BtBp aql tuo{ ue{n (C prru .g .y) s.retaurered
auII uorssrusuer orp roJ
J
umoqs (6) elqeJ uI slep eql ua^ro.I
^\oJeq
:uo rssnrsrp ry po<Iag
ffir= evz
111z
:ffi rlltt
'du1r6 Lt ) tr ffi \iL
IJd syil 'dtuy 7s1 A/sf, peo'I
elqeJ,
, , ."",J;:[irjl?]
rorrcedec pue ecuslcnpur .acuelsrser eql procar
repun ewl uorssrusrru4 erp Jo elep epld eumu erp proceg.I
'{cllms ureru aql I
CCO qcttlr\s pue peads eurqrnl
aql ueql pue eEelyon rolerauaE eql ecnpeg .ro1e.,"ueE eql 01
peol aql tuo+ srolelosr pue sJaT€erq lrncrrc {cBq
.orez o! speol
IIE uedo
elrlsrser pue a,rrlrcedec .aaqcnpur aql asparcep .JSd eql Ools
o1.g1
"-
'(g) e1qe1 :og .qcee ecuo uounq
aSV1TJNI erp Bursserd ,({
speol e^IlJnpur puu elrtsrser eql Surseercur regu (g _ y) sdels
.(,I) eq teadeg .6
l11,n luexnc aql pue (,g) aq IIIa,r e8e11o,r
slqJ '(g) elqeJ eql ur s8urpear eqt proceg .€I).9C le pelecol
llun lueurulsur SuHnseeur eql le luernc puu a8e11o,r aseqd aqt peeu .g
a'err o rr ro, .
(s
jl'ilT;:il il,:: j'P
) q'r eqr,, !;H:
s e r
;:,j:,fr
uun lueurulstn EuFnseau eql tE tuoJrnc p.ue aEe11o,r eseqd at11 peag .t