Operating Manual Autozero Option TPFAS

This document provides information on the autozero function for Gefran's TPFAS series industrial pressure transmitters. The transmitters have an option for either magnetic (Option M) or external (Option E) activation of autozero. Autozero can zero out pressure readings and can be fine-tuned in small increments. The document describes the application, limits, and results of using autozero, fine-autozero, calibration (Option M only), and reset functions.

Uploaded by

Gopal Hegde
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
44 views

Operating Manual Autozero Option TPFAS

This document provides information on the autozero function for Gefran's TPFAS series industrial pressure transmitters. The transmitters have an option for either magnetic (Option M) or external (Option E) activation of autozero. Autozero can zero out pressure readings and can be fine-tuned in small increments. The document describes the application, limits, and results of using autozero, fine-autozero, calibration (Option M only), and reset functions.

Uploaded by

Gopal Hegde
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

INDUSTRIAL PRESSURE TRANSMITTER

TPFAS series

Operating manual
Autozero Option

code 85305 ed. 01 - 10/2014

This section contains information and warnings of a gene-


ral nature which should be read before proceeding with any
function activation
The flush diaphragm pressure transmitter series TPFAS is available The available functions are as follows:
with Autozero function that can be activated in two different ways:
1) Autozero
• Option M: Magnetic autozero 2) Fine-Autozero
• Option E: External autozero 3) Calibration (option M only)
4) Reset
The above functions can be activated via the following devices:
CAL pin:
• CAL Pin The CAL function activation (Calibration or Autozero) is achieved by
• Magnetic pen closing the contact between the following pins or cables:

Option E involves the activation of all functions exclusively through • 6 pole connector version (V) pin E-F
the CAL pin. • 7 pole connector version (P) pin 5-6
• Cable version (F) wires blue-orange
Option M involves the activation of all features using the magnetic
pen and CAL pin. The following pages present the methods of application, the applica-
bility limits, and the results of such functionality.

1) Autozero
Application mode Limits Results
The Autozero function is activated by: The whole Zero unbalancement in The Autozero effect will be visible after
addition to the zero done by the waiting 2 sec from the release of the
1) positioning the magnet near the manufacturer, has to be within ± magnetic pen.
Autozero label on the shell of the sensor. 10% FS.
The precision of the zero value will be
2) Short-circuiting the CAL pin or cable within the accuracy class or setting tole-
wires (option E) rance of the transducer.

The contact has to be maintained on the The Autozero function doesn’t work out-
Autozero position for a time within 1 to side the defined limits.
10 sec.
NOTE:
During the Autozero phase, the output for current transmitter series, will increase around 7mA.
That’s a short variation only visible during the Autozero phase; it won’t have any effects on the final result.

Figure 1 : represents the “magnetic pen”

Figure 2 : represent the Autozero function label


on the sensor housing

Figure 3 : shows the position of the pen on the


shell while activating the autozero

Figure 1 Figure 2 Figure 3 function

85305_MAN_Autozero_TPFAS_10-2014_ENG 1
2) Fine-Autozero Function
Application mode Limits Results
The Fine-Autozero function is activated The whole Zero unbalancement in The output signal will change within a ±
by: addition to the zero done by the 100mV value (± 0.16mA for 4 to 20mA
1) positioning the magnet near the manufacturer, has to be within ± output) in steps of 6mV ( 12mA for 4 to
Autozero label on the shell of the sensor. 10%FS 20mA output).
The contact has to be maintained on the Eg:
Autozero position for a time within 10 to 0..-6..-12..//-100..+100..+94..+88..0
30 sec. After removing the contact the
signal will start changing the value step When the desired zero value is reached
by step. stop the adjustment cycle by touching
the Autozero area with the magnet.
2) Short-circuiting the CAL pin or cable
wires (option E) The Fine-Autozero function doesn’t work
outside the defined limits.
Stop adjustment:
Touch the Autozero area with the magnet
to stop the signal scrolling or close con-
tact on CAL pin (option E).
NOTE:
The step duration time is 5 sec
- During the Autozero phase, the output for current transmitter series, will increase to around 7mA. Furthermore between
the step variations it will be possible to have short overcurrent up to 7mA.
- That’s an immediate variation only visible during the Autozero phase; it won’t have any effects on the final result.
- The new zero value setted with the “Fine-Autozero” function, will be the zero reference for future “Autozero” procedures.

3) Calibration (with option M only, Magnetic Autozero)


Application mode Limits Results
Start calibration The whole Zero unbalancement in During the Calibration phase the signal
The Calibration function is activated by addition to the zero done by the will be unbalanced at 80% FS.
short-circuiting the CAL pin for a mini- manufacturer, has to be within ± The calibration effect is visible 2 sec after
mum time of 1 sec 20%FS. short-circuiting CAL pin.

Stop calibration The Calibration function doesn’t work


Release the CAL pin short-circuit outside the defined limits.
NOTE:
- Switching off the supply while the calibration function is activated, could be cause of calibration problems; the transmitter
can be restored to the initial value by activating the “reset function”.
- To locate the CAL pin contacts, please refer to item “CAL pin” at the beginning of this manual.

4) Total reset of the calibration values


Application mode Limits Results
1) The total reset function is activa- The Zero of the transmitter will be resto-
ted by positioning the magnet near the red to the factory settings.
Autozero label on the shell of the sensor

2) by short-circuiting the CAL pin (or


cable wires) on option E.

The contact has to be maintained on the


Autozero position for a time over 60 sec.
NOTE:
- During the total reset phase, the output for current transmitter series, will increase around 7mA
- An internal timer will trigger the function as soon as the elapsed time will exceed 60 sec.

GEFRAN spa
via Sebina, 74 - 25050 PROVAGLIO D’ISEO (BS) - ITALIA
tel. 0309888.1 - fax. 0309839063 Internet: http://www.gefran.com
2 85305_MAN_Autozero_TPFAS_10-2014_ENG