Preliminary Heat Exchanger Sizing: These Calculations Are Provided For Educational Use Only - USE AT YOUR OWN RISK

This document provides a preliminary sizing calculation for a shell and tube heat exchanger. It calculates the heat transfer area and utility requirements based on input process and utility stream conditions. The results indicate a log mean temperature difference of 21°F, an overall heat transfer coefficient of 100 Btu/hr-ft2-°F, and a preliminary heat transfer area of 365 ft2 for a shell and tube exchanger with 70 tubes and a 13.25 inch shell inside diameter.

Uploaded by

Rajdeepsinh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
115 views

Preliminary Heat Exchanger Sizing: These Calculations Are Provided For Educational Use Only - USE AT YOUR OWN RISK

This document provides a preliminary sizing calculation for a shell and tube heat exchanger. It calculates the heat transfer area and utility requirements based on input process and utility stream conditions. The results indicate a log mean temperature difference of 21°F, an overall heat transfer coefficient of 100 Btu/hr-ft2-°F, and a preliminary heat transfer area of 365 ft2 for a shell and tube exchanger with 70 tubes and a 13.25 inch shell inside diameter.

Uploaded by

Rajdeepsinh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

www.hcheattransfer.

com
1-877-542-1214

Preliminary Heat Exchanger Sizing


This tool calculates the preliminary heat transfer area and utility requirements for shell and tube heat exchangers.

Process Side E-101


Process Description (choose from list) heating - liquid
Tin Process Inlet Temperature (oF) 147.94
Tout Process Outlet Temperature (oF) 226.67
Q Duty (BTU/hr) 7.68E+05
Utility Side
Type of Fluid (choose from list) Other
tin Utility Inlet Temperature (oF) 264.2
tout Utility Outlet Temperature (oF) 158.23

do Tube Outside Diameter (choose from list) (inches) 1.00


L Tube Length (ft) 20.00

RESULTS
DTlmtd Log Mean temperature Difference (oF) 21
2
U Overall Heat Transfer coefficient (Btu/hr-ft -°F) 100
A PRELIMINARY Heat Transfer Area (ft2) 365
Number of tubes 70
D Shell diameter (ID) (in) 13.250
Utility Flow Rate

Yellow fields are input


Red fields are results
* These calculations are provided for educational use only - USE AT YOUR OWN RISK.

Assumptions
1. 1 tube pass countercurrent flow arrangement
2. 1.25 triangular pitch layout
3. Glycol properties are based on 50% (wt) Ethylene Glycol at 0 oC
4. Refrigerant properties based on R-134a at -10oC
5. Steam properties based on steam at 100 psia
6. Hot oil properties based on Dowtherm Q at 200 C
heating - vapour
heating - liquid
cooling - vapour
cooling - liquid
condensing
boiling
Water 0.75
Glycol 1
Refrigerant 1.25
Steam
Hot Oil