4.2. Design Calculation of Isolated Footing at Point 18: D.L 42.78k, L.L 6.9k

1) The document summarizes the design calculation of an isolated square footing to support a 12"x12" column. 2) The 4'x4' footing is designed to support 42.78 kips of dead load and 6.9 kips of live load. 3) Reinforcement of 3 #16mm bars spaced at 3" centers is determined to be required based on the moment and bearing capacity calculations.

Uploaded by

Kendrick
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
90 views

4.2. Design Calculation of Isolated Footing at Point 18: D.L 42.78k, L.L 6.9k

1) The document summarizes the design calculation of an isolated square footing to support a 12"x12" column. 2) The 4'x4' footing is designed to support 42.78 kips of dead load and 6.9 kips of live load. 3) Reinforcement of 3 #16mm bars spaced at 3" centers is determined to be required based on the moment and bearing capacity calculations.

Uploaded by

Kendrick
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 4

33

4.2. Design Calculation of Isolated Footing At Point 18


Design calculation of isolated footing with required area footing size is as follow.

D.L=42.78k, L.L=6.9k

(1) Design information,


fcʹ = 3000 psi
fy = 60000 psi
column size = 12ʹʹ x 12ʹʹ
foundation depth = 4ʹ
By soil test result, ɤ = 123.51 lb/ft3
Allowable soil bearing pressure, qu = 1.7 t/ft2
= 3808 psf
= 3.808 ksf
(2) Design procedure
(a) Depth of fill = 4 -1 = 3ʹ
weight of fill = 3 x 123.51 = 370.53 psf
weight of footing = 12/12 x 150 = 150 psf
520.53 psf
Effective bearing pressure, qe = qa – 520.53 psf
= 3808 – 520.53
= 3287.5 psf = 3.288 ksf
(b) Compute required footing area and choose footing
P (unfactored)
Required area =
qe
DL+¿
=
qe
42.78+6.9
= = 15.11 ft2
3.288
A = B x B (square)
15.11 = B x B
B = 3.89 ≈ 4ʹ
34

Take 4ʹ x 4ʹ
(3) To find upward soil pressure,
footing size = 4ʹ x 4ʹ
Pu 1.4 D. L+1.7 L . L
qu = =
A act BxB
1.4 x 42.78+ 1.7 x 6.9
= = 4.48 ksf
4x4
(4) (a) Punching shear,
Vu = Bearing capacity x (Footing area – Punching area)
( 12+ d )2
= 4.48( 42 – )
144
Nominal punching shear length,
∅Vc = ∅ 4 √ fc' bo d
d
= 0.85 x 4 x√ 3000 x 4(12 + d) x
1000
∅Vc = Vu
d ( 12+ d )2
0.85 x 4 x√ 3000 x 4(12 + d) x = 4.48 (42 - )
1000 144
d = 4.96ʹʹ
(b) Check one-way shear,
L−c
Vu = qu x B x ( −d )
2
12
4−
= 4.48 x 4 x 12 4.96
( − )
2 12
= 19.47 k
Nominal one-way shear length,
1
∅ Vc=∅ 2 √ fc ' B d = 0.85 x 2 x √ 3000 x 4 x 12 x 4.96 x
1000
= 22.17k ¿ Vc (OK!)
(5) To find moment and reinforcement,
1
Mu = q (B-c)2 x B
8 u
1 12 2
= x 4.48 x (4 - ) x 4 x12
8 12
= 241.92 k-in
35

2 Mu
2
a=d- d −
√ 0.765 f c ' b
2 x 241.92

= 4.96 – 4.96 2−
0.765 x 3 x 4 x 12
= 0.465ʹʹ
Mu
Required As = a
∅ fy(d− )
2
241.92
= 0.465 = 0.95 in2 (Control)
0.9 x 60( 4.96− )
2
200
Minimum As = bd
60000
200
= x 4 x 4.96 x 12 = 0.79 in2
60000
Use 5#4 bars (As = 0.98 in2)
π d2
Area of one bar = = π ¿ ¿ = 0.395 in2
4
required area
No of bar =
Area of one ¯¿ ¿
0.95
= = 2.4 ≈ 3Nos
0.395
Use 3-16mm
0.312 x 12
Spacing = =4
0.95

(6) Check bearing capacity,


( 1.4 x 42.78 )+(1.7 x 6.9)
Actual bearing strength = = 0.497 ksi
12 x 12
A2
Design bearing strength = 0.85 ∅ fc’
√ A1
≤ 0.85 ∅ f c ' x 2

4 x 4 x 144
= 0.85 x 0.7 x 3 x
√ 12 x 12
≤ 0.85 x 0.7 x 3 x 2

= 7.14 ksi ≤ 3.57 ksi


Design strength = 3.57 ksi ¿ Actural strength = 0.497ksi (OK!)
DL=42.78kip,LL=6.9k
ip
36

12”x12”colum
n

1’-6” 1’-6”

16mm@3”C/C 16mm@3”C/C

Fig 4.1. Isolated Footing