0% found this document useful (0 votes)
69 views37 pages

Column Reinforcement

This document provides design details for column reinforcement in a building. It summarizes load combinations and calculations for column sections 1C1, 1C2, 2C1 and 2C2 of Storeys 1 and 2. Minimum steel reinforcement requirements and shear capacities are calculated according to design code BS8110 considering the specified concrete grade and rebar type. Load combinations include gravity and lateral loads. Critical load combinations and resulting axial force, bending moments and required versus provided steel ratios are reported for each column section.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
69 views37 pages

Column Reinforcement

This document provides design details for column reinforcement in a building. It summarizes load combinations and calculations for column sections 1C1, 1C2, 2C1 and 2C2 of Storeys 1 and 2. Minimum steel reinforcement requirements and shear capacities are calculated according to design code BS8110 considering the specified concrete grade and rebar type. Load combinations include gravity and lateral loads. Critical load combinations and resulting axial force, bending moments and required versus provided steel ratios are reported for each column section.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 37

OkeBen (*1LX-CWX8-822F-L6MU)

COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-1

1C1 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 54.9 -0.3 0.9 49.8 0.7 -1.8
2 60.1 -0.5 0.9 55.0 1.0 -1.9
3 44.0 -0.3 0.6 38.9 0.6 -1.2
4 45.8 -0.1 0.9 40.7 0.2 -1.9
5 55.7 -0.3 0.8 50.6 0.6 -1.7
6 54.2 -0.2 0.9 49.1 0.5 -1.8
7 55.0 -0.3 0.9 49.9 0.7 -1.8
8 46.5 -0.2 0.9 41.4 0.3 -1.9
9 55.7 -0.3 0.8 50.6 0.7 -1.8
10 60.1 -0.5 0.9 55.0 1.0 -1.9
11 43.9 -0.3 0.6 38.8 0.6 -1.1
12 44.7 2.0 0.7 40.4 -1.6 -1.5
13 48.9 -2.6 0.8 44.5 2.8 -1.6
14 48.4 -0.5 2.8 44.1 0.8 -3.5
15 45.2 -0.1 -1.3 40.8 0.4 0.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 54.9 - 54.9
M1 (kN.m) 0.7 0.6 0.0
M2 (kN.m) -1.8 -0.6 -2.5 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.043 Le1/b1 = 8.6 < 15.0 225
Beta = 0.95 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.8 / 2.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.82 / 0.82 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.05 N/mm2
Links = Y8-175

2C1 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 10.7 -0.3 1.6 5.0 0.4 -1.0
2 10.5 -0.6 1.5 4.9 0.3 -1.0
3 9.8 -0.4 1.0 4.2 0.4 -0.7
4 9.9 0.2 1.7 4.3 0.1 -1.1
5 10.6 -0.4 1.5 5.0 0.5 -0.9
6 10.8 -0.3 1.6 5.2 0.4 -1.0
7 10.7 -0.4 1.6 5.1 0.4 -1.0
8 9.8 0.2 1.6 4.2 0.0 -1.0
9 10.6 -0.5 1.5 5.0 0.5 -0.9
10 10.5 -0.6 1.5 4.9 0.3 -1.0
11 9.8 -0.3 1.0 4.1 0.4 -0.7
12 8.9 0.0 1.3 4.1 0.0 -0.9
13 9.3 -0.6 1.3 4.5 0.6 -0.9
14 9.3 -0.3 1.5 4.5 0.3 -1.1
15 8.9 -0.3 1.1 4.1 0.3 -0.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 10.7 - 10.7
M1 (kN.m) 0.4 0.1 0.0
M2 (kN.m) 1.6 0.1 2.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.008 Le1/b1 = 9.6 < 15.0 225
Beta = 0.99 Le2/b2 = 9.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 0.8 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.02 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-2

1C2 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 154.4 -1.5 1.1 149.3 3.0 -2.2
2 124.8 -0.6 1.2 119.7 1.3 -2.5
3 139.5 -1.5 0.5 134.4 3.0 -1.0
4 147.6 -1.8 1.1 142.5 3.6 -2.2
5 155.6 -1.4 1.0 150.5 3.0 -2.1
6 157.3 -1.5 1.0 152.2 3.2 -2.1
7 154.2 -1.5 1.1 149.1 3.0 -2.2
8 144.8 -1.7 1.1 139.7 3.4 -2.3
9 155.7 -1.5 1.0 150.6 3.0 -2.1
10 124.8 -0.6 1.2 119.7 1.3 -2.5
11 139.5 -1.4 0.5 134.4 2.9 -0.9
12 132.4 1.1 0.8 128.0 0.2 -1.8
13 129.4 -3.6 0.9 125.0 4.8 -1.9
14 132.1 -1.5 3.0 127.7 2.7 -3.8
15 129.7 -1.0 -1.2 125.3 2.3 0.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 154.4 - 154.4
M1 (kN.m) 3.0 1.7 4.8
M2 (kN.m) -2.2 -1.7 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.122 Le1/b1 = 8.6 < 15.0 225
Beta = 0.86 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 0.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.84 / 0.87 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.01 N/mm2
Links = Y8-175

2C2 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 14.5 -2.6 1.1 8.9 1.7 0.0
2 13.3 -1.0 1.3 7.7 0.8 0.0
3 14.5 -2.6 0.4 8.9 1.8 0.0
4 13.7 -3.0 1.2 8.1 1.9 0.0
5 14.3 -2.7 1.2 8.7 1.8 0.0
6 14.4 -2.8 1.1 8.8 1.8 0.0
7 14.3 -2.6 1.1 8.7 1.7 0.0
8 13.9 -2.8 1.2 8.3 1.8 0.0
9 14.5 -2.7 1.2 8.9 1.9 0.0
10 13.3 -1.0 1.3 7.7 0.8 0.0
11 14.5 -2.6 0.4 8.9 1.7 0.0
12 12.6 -1.8 1.0 7.8 1.0 0.0
13 12.3 -2.6 0.9 7.5 1.9 0.0
14 12.5 -2.2 1.1 7.7 1.5 0.0
15 12.5 -2.2 0.7 7.7 1.4 0.0
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 13.7 - 13.7
M1 (kN.m) -3.0 -0.2 -4.2
M2 (kN.m) 1.2 0.2 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.011 Le1/b1 = 9.5 < 15.0 225
Beta = 0.99 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.5 / 0.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-3

1C3 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 108.9 -0.2 -0.1 103.8 0.5 0.1
2 109.4 -0.2 0.0 104.3 0.5 0.0
3 92.7 -0.2 0.3 87.6 0.5 -0.5
4 99.7 -0.2 -0.2 94.6 0.5 0.4
5 91.9 -0.2 -0.4 86.8 0.4 0.7
6 108.8 -0.2 -0.1 103.7 0.4 0.1
7 108.9 -0.2 -0.1 103.8 0.5 0.1
8 99.7 -0.3 -0.2 94.6 0.5 0.4
9 91.9 -0.2 -0.4 86.8 0.4 0.7
10 109.4 -0.2 0.0 104.3 0.5 0.0
11 92.7 -0.2 0.2 87.6 0.5 -0.4
12 92.3 1.4 -0.1 87.9 -0.4 0.1
13 92.7 -1.8 0.0 88.4 1.2 0.0
14 92.8 -0.3 2.1 88.5 0.5 -2.0
15 92.2 -0.1 -2.2 87.8 0.4 2.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 108.9 - 108.9
M1 (kN.m) 0.5 1.2 0.0
M2 (kN.m) 0.1 1.2 2.3 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.086 Le1/b1 = 10.3 < 15.0 225
Beta = 0.90 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.6 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.84 / 0.79 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.00 N/mm2
Links = Y8-175

2C3 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 9.8 0.4 -0.6 4.2 0.0 0.6
2 10.0 0.4 -0.5 4.3 0.0 0.6
3 9.3 0.4 0.1 3.6 0.0 0.2
4 9.8 0.4 -0.8 4.2 0.0 0.7
5 9.4 0.4 -1.0 3.8 0.0 0.9
6 9.8 0.4 -0.5 4.2 0.0 0.6
7 9.8 0.4 -0.6 4.2 0.0 0.6
8 9.8 0.5 -0.8 4.2 0.0 0.7
9 9.4 0.4 -1.0 3.8 0.0 0.9
10 10.0 0.4 -0.5 4.3 0.0 0.6
11 9.3 0.4 0.1 3.6 0.0 0.2
12 8.4 -0.4 -0.5 3.6 0.0 0.5
13 8.5 1.1 -0.5 3.7 0.0 0.5
14 8.5 0.4 -0.1 3.7 0.0 0.2
15 8.4 0.3 -0.9 3.6 0.0 0.9
Critical Combination:1 - (G+Q *F)
MinDesign
N (kN) 9.8 - 9.8
M1 (kN.m) 0.4 0.1 0.0
M2 (kN.m) 0.6 0.1 1.0 225
N-max (kN) 0.0
Concrete Cover 25.0
= mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.008 Le1/b1 = 10.8 < 15.0 225
Beta = 0.99 Le2/b2 = 9.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 0.6 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-4

1C4 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 158.6 0.0 -0.1 153.5 0.0 0.3
2 156.7 0.0 -0.1 151.6 0.0 0.2
3 129.5 0.0 0.4 124.4 0.0 -0.8
4 149.5 0.0 -0.3 144.4 0.0 0.6
5 133.2 0.0 -0.6 128.1 0.0 1.1
6 158.7 0.1 -0.1 153.6 0.0 0.3
7 158.6 0.0 -0.1 153.5 0.0 0.2
8 149.4 0.0 -0.3 144.3 0.0 0.5
9 133.2 0.0 -0.6 128.1 0.0 1.0
10 156.7 0.0 -0.1 151.6 0.0 0.2
11 129.5 0.1 0.3 124.4 0.0 -0.7
12 133.8 1.1 -0.1 129.5 0.2 0.2
13 133.7 -1.1 -0.1 129.3 -0.3 0.2
14 134.0 -0.1 2.1 129.6 0.0 -2.0
15 133.5 0.1 -2.3 129.1 0.0 2.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 158.6 - 158.6
M1 (kN.m) 0.0 1.8 0.0
M2 (kN.m) 0.3 1.8 3.3 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.125 Le1/b1 = 10.3 < 15.0 225
Beta = 0.85 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 0.3 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.83 / 0.90 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.01 N/mm2
Links = Y8-175

2C4 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 5.6 0.0 0.0 0.0 0.0 0.0
2 5.6 0.0 0.0 0.0 0.0 0.0
3 5.6 0.0 0.0 0.0 0.0 0.0
4 5.6 0.0 0.0 0.0 0.0 0.0
5 5.6 0.0 0.0 0.0 0.0 0.0
6 5.6 0.0 0.0 0.0 0.0 0.0
7 5.6 0.0 0.0 0.0 0.0 0.0
8 5.6 0.0 0.0 0.0 0.0 0.0
9 5.6 0.0 0.0 0.0 0.0 0.0
10 5.6 0.0 0.0 0.0 0.0 0.0
11 5.6 0.0 0.0 0.0 0.0 0.0
12 4.8 0.3 0.0 0.0 0.0 0.0
13 4.8 -0.3 0.0 0.0 0.0 0.0
14 4.8 0.0 0.3 0.0 0.0 0.0
15 4.8 0.0 -0.3 0.0 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 5.6 - 5.6
M1 (kN.m) 0.0 -0.1 0.0
M2 (kN.m) 0.0 -0.1 -0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.004 Le1/b1 = 10.8 < 15.0 225
Beta = 0.99 Le2/b2 = 10.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 0.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.76 / 0.76 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-5

1C5 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 44.6 0.0 -0.9 39.5 0.1 1.7
2 50.7 -0.3 -0.8 45.6 0.6 1.6
3 46.0 0.0 -0.8 40.9 0.1 1.6
4 33.5 0.2 -0.8 28.4 -0.3 1.5
5 34.6 0.0 -0.7 29.5 0.1 1.2
6 44.8 0.0 -0.9 39.7 0.0 1.7
7 44.8 0.0 -0.8 39.7 0.1 1.7
8 33.2 0.1 -0.8 28.1 -0.2 1.5
9 34.5 0.0 -0.7 29.4 0.1 1.2
10 50.7 -0.3 -0.8 45.6 0.6 1.6
11 45.9 0.0 -0.8 40.8 0.1 1.7
12 36.3 2.3 -0.8 31.9 -2.1 1.5
13 40.1 -2.4 -0.7 35.7 2.3 1.4
14 36.5 -0.1 1.3 32.1 0.2 -0.5
15 39.9 0.1 -2.8 35.5 0.0 3.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 44.6 - 44.6
M1 (kN.m) 0.1 0.5 0.0
M2 (kN.m) 1.7 0.5 2.2 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.035 Le1/b1 = 8.6 < 15.0 225
Beta = 0.96 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 2.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.76 / 0.81 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.05 N/mm2
Links = Y8-175

2C5 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 9.9 1.6 -2.1 4.3 -1.0 1.6
2 9.8 1.3 -2.1 4.2 -1.0 1.5
3 9.7 1.5 -2.0 4.1 -0.9 1.4
4 9.2 1.9 -1.9 3.6 -1.1 1.5
5 9.2 1.4 -1.6 3.6 -0.8 1.3
6 10.0 1.4 -2.1 4.4 -0.8 1.5
7 9.9 1.6 -2.1 4.3 -1.0 1.6
8 9.1 2.1 -1.9 3.5 -1.3 1.5
9 9.2 1.4 -1.6 3.6 -0.8 1.3
10 9.8 1.3 -2.1 4.2 -1.0 1.5
11 9.7 1.5 -2.0 4.1 -0.9 1.4
12 8.2 1.7 -1.8 3.4 -1.3 1.4
13 8.7 1.0 -1.8 3.9 -0.5 1.3
14 8.2 1.4 -1.6 3.4 -0.9 1.1
15 8.6 1.4 -2.0 3.8 -0.9 1.6
Critical Combination:8 - ((G+Q)P41 *F)
MinDesign
N (kN) 9.1 - 9.1
M1 (kN.m) 2.1 0.1 4.0
M2 (kN.m) -1.9 -0.1 0.0 225
N-max (kN) 0.0
Concrete Cover 25.0
= mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.007 Le1/b1 = 9.6 < 15.0 225
Beta = 0.99 Le2/b2 = 9.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.0 / 1.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.03 / 0.03 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-6

1C6 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 171.3 -2.5 -0.6 166.2 5.1 1.2
2 138.8 -1.6 -0.7 133.7 3.2 1.4
3 173.3 -2.4 -0.5 168.2 5.0 1.1
4 158.1 -2.6 -0.5 153.0 5.4 1.0
5 157.6 -2.4 -0.3 152.5 5.0 0.4
6 171.2 -2.4 -0.6 166.1 5.0 1.2
7 171.0 -2.5 -0.6 165.9 5.1 1.2
8 158.2 -2.7 -0.5 153.1 5.5 1.0
9 157.7 -2.4 -0.3 152.6 5.0 0.4
10 138.8 -1.6 -0.7 133.7 3.2 1.4
11 173.5 -2.4 -0.6 168.4 5.0 1.2
12 146.4 0.3 -0.5 142.0 1.9 1.0
13 144.5 -4.5 -0.5 140.1 6.7 1.0
14 143.8 -2.2 1.6 139.4 4.4 -1.0
15 147.1 -2.0 -2.6 142.7 4.2 3.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 171.3 - 171.3
M1 (kN.m) 5.1 1.9 6.7
M2 (kN.m) 1.2 1.9 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.135 Le1/b1 = 8.6 < 15.0 225
Beta = 0.84 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.5 / 0.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.85 / 0.90 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.02 N/mm2
Links = Y8-175

2C6 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 13.9 -2.8 -1.2 8.3 1.0 0.0
2 12.6 -0.9 -1.3 7.0 -0.1 0.0
3 13.8 -2.8 -1.1 8.2 1.0 0.0
4 13.2 -3.2 -1.0 7.6 1.4 0.0
5 13.8 -3.0 -0.6 8.2 1.2 0.0
6 13.8 -3.0 -1.2 8.2 1.3 0.0
7 13.8 -2.8 -1.2 8.2 1.0 0.0
8 13.2 -3.0 -1.0 7.6 1.1 0.0
9 13.8 -3.0 -0.6 8.2 1.2 0.0
10 12.6 -0.9 -1.3 7.0 -0.1 0.0
11 13.9 -2.9 -1.1 8.2 1.1 0.0
12 12.0 -1.8 -1.0 7.2 0.3 0.0
13 11.9 -2.9 -1.0 7.1 1.4 0.0
14 11.9 -2.4 -0.8 7.1 0.9 0.0
15 11.9 -2.3 -1.2 7.1 0.8 0.0
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 13.2 - 13.2
M1 (kN.m) -3.2 -0.1 -4.2
M2 (kN.m) -1.0 -0.1 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.010 Le1/b1 = 9.5 < 15.0 225
Beta = 0.99 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.4 / 0.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.03 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-7

1C7 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 194.0 0.3 1.2 188.9 -0.7 -2.4
2 167.7 -0.7 1.3 162.6 1.3 -2.6
3 179.5 0.3 0.7 174.4 -0.6 -1.3
4 170.3 1.1 1.1 165.2 -2.3 -2.3
5 194.0 0.4 1.1 188.9 -0.8 -2.3
6 170.9 1.2 1.2 165.8 -2.4 -2.5
7 193.1 0.3 1.2 188.0 -0.7 -2.4
8 193.5 0.3 1.1 188.4 -0.6 -2.2
9 195.1 0.4 1.1 190.0 -0.7 -2.3
10 167.7 -0.7 1.3 162.6 1.3 -2.6
11 179.4 0.4 0.6 174.3 -0.7 -1.2
12 163.8 2.6 1.0 159.5 -2.9 -2.0
13 165.1 -2.1 1.0 160.7 1.7 -2.0
14 166.0 0.1 3.2 161.6 -0.3 -4.0
15 162.9 0.5 -1.2 158.5 -0.8 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 194.0 - 194.0
M1 (kN.m) -0.7 -2.2 0.0
M2 (kN.m) -2.4 -2.2 -4.2 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.153 Le1/b1 = 8.6 < 15.0 225
Beta = 0.82 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 0.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.90 / 0.88 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.01 N/mm2
Links = Y8-175

2C7 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 21.5 1.7 1.2 15.9 -1.9 -0.1
2 19.9 -0.2 1.4 14.3 -0.9 -0.1
3 21.4 1.6 0.5 15.8 -1.8 -0.1
4 20.1 3.4 1.2 14.5 -2.8 -0.1
5 20.6 1.6 1.2 15.0 -1.8 -0.1
6 20.4 3.2 1.3 14.8 -2.7 -0.1
7 20.5 1.7 1.2 14.9 -1.8 -0.1
8 21.2 1.9 1.1 15.6 -2.0 -0.1
9 21.6 1.6 1.3 16.0 -1.9 -0.1
10 19.9 -0.2 1.4 14.3 -0.9 -0.1
11 21.4 1.7 0.5 15.8 -1.8 -0.1
12 18.4 1.8 1.0 13.6 -2.1 -0.1
13 18.5 1.1 1.0 13.7 -1.2 -0.1
14 18.5 1.4 1.4 13.7 -1.6 -0.1
15 18.4 1.5 0.6 13.6 -1.7 -0.1
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 20.1 - 20.1
M1 (kN.m) 3.4 0.2 4.6
M2 (kN.m) 1.2 0.2 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.016 Le1/b1 = 9.6 < 15.0 225
Beta = 0.98 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.9 / 0.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.78 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-8

1C8 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 186.8 -5.0 -0.4 181.7 10.2 0.9
2 184.5 -5.1 -0.5 179.4 10.3 1.0
3 161.2 -5.1 0.1 156.1 10.4 0.0
4 162.4 -2.8 -0.4 157.3 5.7 0.8
5 168.5 -5.0 -0.8 163.4 10.2 1.6
6 186.2 -5.0 -0.4 181.1 10.2 0.9
7 187.5 -5.1 -0.4 182.4 10.2 0.9
8 163.0 -2.9 -0.4 157.9 5.8 0.9
9 168.4 -5.0 -0.8 163.3 10.2 1.5
10 184.5 -5.1 -0.5 179.4 10.3 1.0
11 160.5 -5.0 0.0 155.4 10.3 0.1
12 156.5 -1.9 -0.4 152.2 6.4 0.8
13 158.0 -6.5 -0.4 153.6 10.7 0.8
14 156.8 -4.4 1.9 152.4 8.7 -1.5
15 157.8 -4.1 -2.7 153.4 8.4 3.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 186.8 - 186.8
M1 (kN.m) 10.2 2.1 11.9
M2 (kN.m) 0.9 2.1 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.148 Le1/b1 = 8.6 < 15.0 225
Beta = 0.83 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 5.7 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.94 / 0.89 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.14 / 0.00 N/mm2
Links = Y8-175

1C9 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 160.1 6.0 -0.3 155.0 -12.0 0.6
2 142.8 4.1 -0.3 137.7 -8.3 0.6
3 146.0 6.0 -0.4 140.9 -12.0 0.9
4 157.1 5.9 -0.3 152.0 -11.9 0.6
5 140.6 5.9 -0.2 135.5 -11.9 0.3
6 160.4 6.0 -0.3 155.3 -12.1 0.7
7 144.7 6.0 -0.4 139.6 -12.0 0.9
8 156.9 5.9 -0.3 151.8 -11.9 0.5
9 139.4 5.9 -0.2 134.3 -11.9 0.2
10 142.8 4.1 -0.3 137.7 -8.3 0.6
11 162.5 5.9 -0.3 157.4 -11.9 0.7
12 136.0 7.3 -0.3 131.7 -12.3 0.6
13 134.7 2.8 -0.2 130.4 -8.1 0.5
14 135.6 4.9 2.0 131.2 -10.1 -1.7
15 135.2 5.2 -2.5 130.8 -10.3 2.8
Critical Combination:12 - (G+Q+Nx)
Min Design
N (kN) 136.0 - 136.0
M1 (kN.m) -12.3 -1.5 -13.6
M2 (kN.m) 0.6 1.5 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.107 Le1/b1 = 8.6 < 15.0 225
Beta = 0.87 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 6.5 / 0.3 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.91 / 0.90 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.16 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-9

1C10 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 92.6 2.4 1.4 87.4 -4.9 -2.8
2 95.0 2.7 1.4 89.9 -5.5 -2.7
3 92.8 2.4 1.5 87.7 -4.9 -2.9
4 73.8 1.2 1.3 68.7 -2.5 -2.6
5 80.9 2.5 0.9 75.8 -5.0 -1.9
6 74.4 1.4 1.5 69.3 -2.7 -2.9
7 92.5 2.4 1.5 87.4 -4.9 -2.9
8 92.0 2.3 1.3 86.9 -4.8 -2.5
9 81.1 2.5 1.0 76.0 -5.0 -2.0
10 95.0 2.7 1.4 89.9 -5.5 -2.7
11 92.6 2.5 1.4 87.5 -4.9 -2.8
12 79.8 4.3 1.2 75.4 -6.3 -2.4
13 77.6 -0.2 1.2 73.2 -2.1 -2.4
14 81.0 1.9 3.5 76.6 -4.0 -4.5
15 76.4 2.3 -1.1 72.0 -4.4 -0.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 92.6 - 92.6
M1 (kN.m) -4.9 -1.0 -7.5
M2 (kN.m) -2.8 -1.0 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.073 Le1/b1 = 8.7 < 15.0 225
Beta = 0.91 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.5 / 2.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.85 / 0.86 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.09 / 0.06 N/mm2
Links = Y8-175

2C10 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 12.7 5.1 2.1 7.1 -3.0 -1.0
2 12.7 5.6 2.0 7.1 -3.0 -1.0
3 12.8 5.0 2.3 7.2 -2.9 -1.2
4 11.4 3.1 2.0 5.7 -2.0 -0.9
5 11.9 5.1 1.2 6.3 -3.0 -0.6
6 11.4 3.0 2.2 5.8 -1.9 -1.1
7 12.7 5.2 2.0 7.1 -3.0 -1.0
8 12.6 5.3 1.9 7.0 -3.1 -0.8
9 11.9 5.1 1.4 6.3 -2.9 -0.7
10 12.7 5.6 2.0 7.1 -3.0 -1.0
11 12.7 5.1 2.1 7.1 -2.9 -1.1
12 11.0 4.6 1.7 6.2 -2.8 -0.9
13 10.8 4.2 1.8 6.0 -2.2 -0.9
14 11.3 4.4 2.2 6.5 -2.5 -1.4
15 10.5 4.4 1.3 5.7 -2.5 -0.4
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 12.7 - 12.7
M1 (kN.m) 5.6 0.1 7.6
M2 (kN.m) 2.0 0.1 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.010 Le1/b1 = 9.9 < 15.0 225
Beta = 0.99 Le2/b2 = 9.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.6 / 1.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.06 / 0.03 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-10

1C11 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 183.4 2.4 -0.8 178.3 -4.8 1.6
2 172.0 2.4 -0.8 166.9 -5.0 1.7
3 181.0 2.4 -0.7 175.9 -4.9 1.5
4 133.5 1.1 -0.8 128.4 -2.3 1.8
5 176.1 2.4 -0.5 171.0 -4.8 1.0
6 187.6 2.5 -0.7 182.5 -4.9 1.5
7 181.6 2.4 -0.7 176.5 -4.9 1.6
8 129.2 1.1 -0.9 124.1 -2.2 1.9
9 175.6 2.4 -0.5 170.4 -4.8 0.9
10 172.0 2.4 -0.8 166.9 -5.0 1.7
11 183.3 2.4 -0.8 178.2 -4.8 1.6
12 153.4 4.4 -0.7 149.0 -6.3 1.4
13 155.2 -0.4 -0.7 150.9 -1.6 1.4
14 152.3 1.8 1.6 147.9 -3.8 -0.8
15 156.3 2.2 -2.9 151.9 -4.2 3.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 183.4 - 183.4
M1 (kN.m) -4.8 -2.1 -6.5
M2 (kN.m) 1.6 2.1 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.145 Le1/b1 = 8.6 < 15.0 225
Beta = 0.83 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 0.9 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.84 / 0.89 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.02 N/mm2
Links = Y8-175

2C11 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 -16.2 8.7 -2.1 -21.8 -9.2 1.2
2 -17.0 8.9 -2.1 -22.6 -9.2 1.2
3 -16.6 8.8 -1.9 -22.3 -9.3 1.0
4 -15.0 6.3 -2.2 -20.6 -7.6 1.3
5 -12.8 8.2 -1.5 -18.4 -8.5 0.9
6 -14.1 8.4 -2.0 -19.7 -8.9 1.1
7 -16.6 8.9 -2.2 -22.2 -9.3 1.2
8 -17.2 6.6 -2.3 -22.8 -8.0 1.4
9 -13.2 8.3 -1.3 -18.8 -8.6 0.8
10 -17.0 8.9 -2.1 -22.6 -9.2 1.2
11 -15.8 8.6 -2.0 -21.5 -9.1 1.1
12 -14.3 7.9 -1.8 -19.1 -8.4 1.0
13 -13.4 6.9 -1.8 -18.2 -7.4 1.0
14 -14.1 7.3 -1.3 -18.9 -7.8 0.5
15 -13.6 7.5 -2.2 -18.4 -7.9 1.5
Critical Combination:7 - ((G+Q)P32 *F)
Min Design
N (kN) -22.2 - -22.2
M1 (kN.m) -9.3 0.2 -11.5
M2 (kN.m) -2.2 0.2 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.018 Le1/b1 = 9.5 < 15.0 225
Beta = 1.00 Le2/b2 = 9.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 5.5 / 1.1 kN As (Required): %0.86 433.96 mm2 4Y16
vc'(1/2)= 0.73 / 0.72 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.13 / 0.03 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-11

1C12 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 170.7 -0.9 3.6 165.6 1.8 -7.2
2 163.0 -1.0 3.6 157.9 2.0 -7.3
3 147.3 -0.8 2.2 142.2 1.7 -4.2
4 158.7 -0.5 3.6 153.6 0.9 -7.2
5 165.5 -0.9 3.6 160.3 1.8 -7.3
6 149.1 -0.4 3.7 144.0 1.0 -7.4
7 147.2 -0.8 2.2 142.1 1.7 -4.2
8 180.5 -0.9 3.6 175.4 1.7 -7.1
9 165.0 -0.9 3.5 159.9 1.8 -7.1
10 163.0 -1.0 3.6 157.9 2.0 -7.3
11 171.2 -0.8 3.7 166.1 1.7 -7.4
12 146.0 1.7 3.0 141.6 -0.8 -6.1
13 144.7 -3.1 3.0 140.3 3.9 -6.1
14 146.3 -0.9 5.3 141.9 1.7 -8.1
15 144.4 -0.6 0.8 140.0 1.3 -4.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 170.7 - 170.7
M1 (kN.m) 1.8 1.9 0.0
M2 (kN.m) -7.2 -1.9 -8.9 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.135 Le1/b1 = 8.6 < 15.0 225
Beta = 0.84 Le2/b2 = 8.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.3 / 4.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.94 / 0.93 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.06 / 0.11 N/mm2
Links = Y8-175

2C12 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 66.5 -8.2 6.3 60.9 15.8 -2.9
2 66.0 -8.4 6.3 60.4 16.0 -2.9
3 65.5 -8.1 3.8 59.9 15.7 -2.0
4 61.0 -6.8 6.2 55.3 14.3 -3.0
5 60.4 -7.5 6.1 54.8 14.2 -2.7
6 61.9 -7.1 6.4 56.3 14.4 -3.1
7 65.3 -8.0 3.4 59.7 15.6 -1.6
8 65.7 -7.8 6.1 60.1 15.7 -2.8
9 61.1 -7.6 6.3 55.4 14.4 -3.1
10 66.0 -8.4 6.3 60.4 16.0 -2.9
11 66.0 -8.1 6.4 60.4 15.7 -3.0
12 57.4 -6.5 5.2 52.6 13.1 -2.5
13 56.5 -7.5 5.3 51.7 14.0 -2.5
14 57.0 -7.1 5.7 52.2 13.7 -3.0
15 56.8 -6.9 4.8 52.0 13.5 -2.0
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 66.0 - 66.0
M1 (kN.m) 16.0 0.7 21.9
M2 (kN.m) 6.3 0.7 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.052 Le1/b1 = 9.5 < 15.0 225
Beta = 0.94 Le2/b2 = 9.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 7.4 / 2.8 kN As (Required): %1.18 594.88 mm2 4Y16
vc'(1/2)= 0.82 / 0.82 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.18 / 0.07 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-12

1C13 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 83.1 1.9 3.0 78.0 -3.9 -6.0
2 83.4 1.9 3.0 78.3 -3.9 -6.0
3 67.2 1.9 2.1 62.1 -3.8 -3.9
4 71.1 1.3 3.0 65.9 -2.6 -6.0
5 83.8 2.0 3.0 78.7 -3.9 -6.1
6 71.5 1.4 3.1 66.4 -2.7 -6.1
7 67.5 1.9 2.0 62.3 -3.8 -3.9
8 82.6 1.9 3.0 77.5 -3.8 -6.0
9 82.9 2.0 2.9 77.8 -3.9 -5.9
10 83.4 1.9 3.0 78.3 -3.9 -6.0
11 83.8 2.0 3.1 78.7 -3.9 -6.2
12 71.8 4.0 2.6 67.4 -5.5 -5.1
13 69.3 -0.7 2.5 64.9 -1.1 -5.1
14 71.5 1.5 4.9 67.1 -3.2 -7.3
15 69.6 1.8 0.2 65.2 -3.5 -2.9
Critical Combination:12 - (G+Q+Nx)
Min Design
N (kN) 71.8 - 71.8
M1 (kN.m) -5.5 -0.8 -10.3
M2 (kN.m) -5.1 -0.8 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.057 Le1/b1 = 8.6 < 15.0 225
Beta = 0.93 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.2 / 4.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.84 / 0.84 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.08 / 0.10 N/mm2
Links = Y8-175

1C14 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 146.4 3.2 -1.3 141.2 -6.3 2.7
2 146.4 3.0 -1.3 141.3 -6.1 2.7
3 126.6 3.1 -0.3 121.5 -6.3 1.0
4 127.9 2.1 -1.2 122.8 -4.1 2.6
5 134.3 3.2 -1.7 129.2 -6.3 3.4
6 145.6 3.2 -1.3 140.5 -6.4 2.7
7 122.7 3.1 -0.5 117.6 -6.2 1.3
8 128.6 2.0 -1.2 123.5 -4.1 2.6
9 149.9 3.2 -1.2 144.8 -6.3 2.5
10 146.4 3.0 -1.3 141.3 -6.1 2.7
11 134.7 3.2 -1.5 129.6 -6.3 3.2
12 125.5 5.0 -1.0 121.1 -7.6 2.2
13 122.4 0.3 -1.1 118.1 -3.1 2.3
14 123.8 2.6 1.4 119.5 -5.2 -0.2
15 124.1 2.7 -3.5 119.7 -5.4 4.7
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 146.4 - 146.4
M1 (kN.m) -6.3 -1.6 -8.6
M2 (kN.m) 2.7 1.6 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.116 Le1/b1 = 8.6 < 15.0 225
Beta = 0.86 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.2 / 2.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.91 / 0.91 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.10 / 0.07 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-13

1C15 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 259.1 -2.4 -1.2 254.0 4.9 2.4
2 236.7 -2.5 -1.5 231.6 5.1 3.0
3 225.9 -2.4 0.1 220.8 4.9 0.0
4 238.7 -1.4 -1.1 233.6 2.9 2.4
5 242.2 -2.4 -1.6 237.1 4.9 3.2
6 257.6 -2.3 -1.2 252.5 4.8 2.5
7 221.0 -2.4 -0.1 215.9 5.0 0.4
8 240.4 -1.5 -1.1 235.3 3.0 2.4
9 262.7 -2.4 -1.1 257.6 4.9 2.2
10 236.7 -2.5 -1.5 231.6 5.1 3.0
11 243.5 -2.4 -1.4 238.4 4.9 3.0
12 217.7 0.3 -0.9 213.3 1.9 2.0
13 220.1 -4.4 -1.0 215.7 6.4 2.0
14 219.9 -2.1 1.4 215.6 4.2 -0.4
15 217.9 -1.9 -3.4 213.5 4.1 4.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 259.1 - 259.1
M1 (kN.m) 4.9 2.9 7.1
M2 (kN.m) 2.4 2.9 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.205 Le1/b1 = 8.6 < 15.0 225
Beta = 0.76 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.5 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.89 / 0.87 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.00 N/mm2
Links = Y8-175

2C15 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 22.0 -0.9 -2.0 16.4 0.1 0.4
2 21.1 -1.1 -2.5 15.4 0.1 0.7
3 21.1 -1.0 0.3 15.5 0.1 -0.9
4 20.8 0.2 -2.1 15.2 0.0 0.5
5 19.6 -1.2 -3.0 14.0 0.0 1.2
6 21.5 -1.1 -2.1 15.9 0.1 0.5
7 21.5 -0.9 -0.3 15.9 0.1 -0.4
8 21.4 0.5 -2.0 15.8 0.0 0.4
9 21.1 -1.1 -1.8 15.5 0.1 0.4
10 21.1 -1.1 -2.5 15.4 0.1 0.7
11 20.2 -1.0 -2.5 14.5 0.1 0.7
12 19.0 -0.5 -1.7 14.2 0.0 0.3
13 18.8 -1.0 -1.7 14.0 0.1 0.4
14 19.1 -0.7 -0.9 14.2 0.0 -0.4
15 18.7 -0.7 -2.5 13.9 0.1 1.1
Critical Combination:5 - ((G+Q)P22 *F)
Min Design
N (kN) 19.6 - 19.6
M1 (kN.m) -1.2 -0.2 0.0
M2 (kN.m) -3.0 -0.2 -4.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.016 Le1/b1 = 10.6 < 15.0 225
Beta = 0.98 Le2/b2 = 9.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 1.3 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.03 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-14

1C16 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 212.7 -3.1 0.6 207.6 6.4 -1.2
2 158.0 -1.9 0.7 152.8 3.9 -1.3
3 212.9 -3.1 0.7 207.8 6.4 -1.3
4 201.5 -3.2 0.6 196.4 6.5 -1.3
5 203.5 -3.1 0.3 198.4 6.3 -0.6
6 212.7 -3.0 0.6 207.6 6.3 -1.2
7 212.3 -3.2 0.7 207.2 6.5 -1.3
8 201.6 -3.2 0.6 196.5 6.6 -1.2
9 204.5 -3.0 0.3 199.4 6.2 -0.7
10 158.0 -1.9 0.7 152.8 3.9 -1.3
11 212.3 -3.1 0.6 207.2 6.4 -1.2
12 182.4 -0.2 0.5 178.0 3.1 -1.0
13 177.1 -5.0 0.5 172.7 7.7 -1.1
14 181.7 -2.7 2.8 177.3 5.5 -3.2
15 177.7 -2.5 -1.7 173.4 5.3 1.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 212.7 - 212.7
M1 (kN.m) 6.4 2.4 8.3
M2 (kN.m) -1.2 -2.4 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.168 Le1/b1 = 8.6 < 15.0 225
Beta = 0.81 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.2 / 0.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.97 / 0.93 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.10 / 0.02 N/mm2
Links = Y8-175

2C16 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 19.2 1.0 1.0 13.6 -5.5 -0.1
2 17.1 2.9 1.0 11.4 -6.2 -0.1
3 19.2 0.9 1.1 13.6 -5.6 -0.1
4 17.9 0.1 1.0 12.3 -4.6 -0.1
5 18.8 0.3 0.6 13.2 -4.6 -0.1
6 19.2 0.7 1.0 13.6 -5.2 -0.1
7 19.3 1.0 1.0 13.6 -5.6 -0.1
8 17.8 0.6 1.0 12.2 -5.0 -0.1
9 18.5 0.4 0.7 12.9 -4.6 -0.1
10 17.1 2.9 1.0 11.4 -6.2 -0.1
11 19.5 0.8 1.1 13.8 -5.4 -0.1
12 16.4 1.4 0.9 11.6 -5.2 -0.1
13 16.5 0.4 0.9 11.7 -4.3 -0.1
14 16.3 0.9 1.3 11.5 -4.7 -0.1
15 16.5 1.0 0.5 11.7 -4.8 -0.1
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 17.1 - 17.1
M1 (kN.m) -6.2 -0.2 -7.2
M2 (kN.m) 1.0 0.2 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.013 Le1/b1 = 9.5 < 15.0 225
Beta = 0.98 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.8 / 0.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.07 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-15

1C17 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 32.6 -0.2 -0.6 27.5 0.4 1.2
2 43.1 -0.2 -0.5 38.0 0.5 1.0
3 27.8 -0.2 -0.2 22.7 0.4 0.5
4 27.3 0.0 -0.6 22.2 0.2 1.2
5 24.9 -0.1 -0.8 19.8 0.4 1.6
6 32.6 -0.1 -0.6 27.5 0.4 1.2
7 20.7 -0.2 -0.4 15.6 0.5 0.8
8 27.3 -0.1 -0.6 22.2 0.2 1.2
9 40.7 -0.1 -0.5 35.6 0.2 1.0
10 43.1 -0.2 -0.5 38.0 0.5 1.0
11 24.0 -0.2 -0.7 18.9 0.5 1.4
12 25.5 2.2 -0.5 21.1 -1.9 1.0
13 30.6 -2.5 -0.5 26.2 2.6 1.0
14 28.1 -0.2 1.8 23.7 0.4 -1.2
15 28.0 -0.1 -2.7 23.6 0.2 3.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 32.6 - 32.6
M1 (kN.m) 0.4 0.4 0.0
M2 (kN.m) 1.2 0.4 1.6 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.026 Le1/b1 = 8.5 < 15.0 225
Beta = 0.97 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.7 / 2.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.80 / 0.79 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.05 N/mm2
Links = Y8-175

1C18 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 89.3 0.2 1.9 84.2 -0.3 -3.9
2 100.5 0.1 1.9 95.4 -0.2 -3.8
3 61.3 0.1 1.2 56.2 0.0 -2.2
4 82.7 0.3 1.9 77.6 -0.5 -3.9
5 83.0 0.2 1.9 77.9 -0.3 -4.0
6 88.7 0.2 1.9 83.6 -0.3 -3.8
7 90.5 0.2 2.0 85.4 -0.3 -3.9
8 83.1 0.2 1.9 78.0 -0.5 -3.9
9 61.5 0.1 1.0 56.4 0.0 -2.0
10 100.5 0.1 1.9 95.4 -0.2 -3.8
11 81.6 0.2 2.1 76.4 -0.2 -4.2
12 73.1 2.5 1.6 68.7 -2.5 -3.2
13 78.4 -2.2 1.6 74.1 2.0 -3.3
14 75.0 0.1 3.9 70.6 -0.2 -5.4
15 76.5 0.2 -0.6 72.1 -0.2 -1.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 89.3 - 89.3
M1 (kN.m) -0.3 -1.0 0.0
M2 (kN.m) -3.9 -1.0 -4.8 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.071 Le1/b1 = 8.5 < 15.0 225
Beta = 0.92 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 3.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.79 / 0.85 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.07 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-16

1C19 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 192.2 -2.5 -0.7 187.1 5.2 1.5
2 145.9 -1.6 -0.7 140.8 3.3 1.4
3 190.3 -2.6 -0.6 185.1 5.4 1.4
4 183.6 -2.6 -0.7 178.5 5.4 1.4
5 183.0 -2.4 -0.6 177.9 5.0 1.1
6 195.3 -2.5 -0.7 190.2 5.3 1.4
7 192.4 -2.5 -0.7 187.3 5.2 1.4
8 180.3 -2.6 -0.7 175.2 5.4 1.5
9 181.1 -2.5 -0.6 176.0 5.2 1.1
10 145.9 -1.6 -0.7 140.8 3.3 1.4
11 191.9 -2.5 -0.7 186.8 5.2 1.4
12 164.2 0.3 -0.6 159.8 2.1 1.2
13 160.8 -4.6 -0.6 156.4 6.8 1.2
14 160.2 -2.2 1.6 155.9 4.4 -0.9
15 164.7 -2.1 -2.8 160.3 4.4 3.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 192.2 - 192.2
M1 (kN.m) 5.2 2.2 7.0
M2 (kN.m) 1.5 2.2 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.152 Le1/b1 = 8.6 < 15.0 225
Beta = 0.82 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.6 / 0.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.86 / 0.91 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.02 N/mm2
Links = Y8-175

2C19 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 13.4 13.3 -1.0 7.8 -27.6 -0.1
2 12.2 14.9 -1.0 6.6 -28.2 -0.1
3 13.3 13.3 -0.9 7.7 -27.6 -0.1
4 12.7 11.4 -1.0 7.1 -24.7 -0.1
5 13.6 11.0 -0.8 8.0 -23.4 -0.1
6 14.2 12.6 -1.0 8.6 -26.7 -0.1
7 13.4 13.3 -1.1 7.8 -27.5 -0.1
8 11.4 12.4 -1.0 5.8 -25.9 -0.1
9 12.9 11.4 -0.7 7.3 -24.0 -0.1
10 12.2 14.9 -1.0 6.6 -28.2 -0.1
11 14.1 12.9 -1.0 8.5 -27.0 -0.1
12 11.2 12.1 -0.9 6.4 -24.2 -0.1
13 11.7 10.9 -0.9 6.9 -23.1 -0.1
14 11.4 11.5 -0.5 6.6 -23.7 -0.1
15 11.5 11.4 -1.3 6.7 -23.6 -0.1
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 12.2 - 12.2
M1 (kN.m) -28.2 -0.1 -29.2
M2 (kN.m) -1.0 -0.1 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.010 Le1/b1 = 9.5 < 15.0 225
Beta = 0.99 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 13.1 / 0.4 kN As (Required): %2.06 1044.26 mm2 8Y16
vc'(1/2)= 0.96 / 0.96 N/mm2 As (Provided): %3.18 1608.50 mm2
v (1/2)= 0.32 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-17

1C20 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 340.2 2.9 2.7 333.4 -5.7 -5.4
2 303.4 1.3 3.0 296.6 -2.7 -6.0
3 311.6 3.0 0.9 304.8 -5.8 -1.3
4 311.2 3.6 2.8 304.4 -7.1 -5.5
5 317.6 2.7 3.2 310.8 -5.4 -6.7
6 315.9 3.7 2.7 309.1 -7.3 -5.4
7 347.0 2.9 2.7 340.2 -5.7 -5.2
8 336.8 2.8 2.8 330.0 -5.5 -5.5
9 300.8 2.8 0.8 294.0 -5.5 -1.6
10 303.4 1.3 3.0 296.6 -2.7 -6.0
11 321.5 2.9 3.3 314.7 -5.7 -6.7
12 287.3 5.6 2.3 281.4 -7.9 -4.6
13 288.5 -0.7 2.3 282.7 -1.8 -4.5
14 287.0 2.4 7.6 281.2 -4.8 -9.4
15 288.8 2.5 -3.0 282.9 -4.9 0.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 340.2 - 340.2
M1 (kN.m) -5.7 -3.8 -8.7
M2 (kN.m) -5.4 -5.1 0.0 300
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.202 Le1/b1 = 8.6 < 15.0 225
Beta = 0.77 Le2/b2 = 6.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 1.1 kN As (Required): %0.40 (min) 270.00 mm2 4Y16
vc'(1/2)= 0.78 / 0.87 N/mm2 As (Provided): %1.19 804.25 mm2
v (1/2)= 0.01 / 0.02 N/mm2
Links = Y8-175

2C20 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 72.8 -16.8 3.5 65.3 51.0 -0.3
2 71.3 -19.7 4.1 63.8 52.4 -0.6
3 71.2 -16.7 0.5 63.7 50.9 0.5
4 66.4 -13.8 3.7 58.9 45.6 -0.6
5 64.2 -13.7 4.4 56.8 42.9 -0.6
6 70.0 -15.1 3.4 62.5 48.8 -0.2
7 72.2 -16.9 3.1 64.7 51.0 -0.3
8 70.6 -16.0 3.8 63.2 48.9 -0.7
9 66.4 -14.2 0.3 58.9 44.5 1.1
10 71.3 -19.7 4.1 63.8 52.4 -0.6
11 69.7 -16.2 5.0 62.2 49.3 -1.3
12 62.7 -13.8 3.0 56.2 43.1 -0.3
13 62.1 -15.1 2.9 55.7 44.3 -0.3
14 62.3 -14.4 3.9 55.9 43.7 -1.4
15 62.5 -14.6 2.0 56.1 43.8 0.8
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 71.3 - 71.3
M1 (kN.m) 52.4 0.8 55.2
M2 (kN.m) 4.1 1.1 0.0 300
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.042 Le1/b1 = 9.7 < 15.0 225
Beta = 0.95 Le2/b2 = 7.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 21.9 / 0.0 kN As (Required): %2.87 1940.61 mm2 10Y16
vc'(1/2)= 0.98 / 0.85 N/mm2 As (Provided): %2.98 2010.62 mm2
v (1/2)= 0.40 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-18

1C21 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 116.8 1.3 1.1 111.6 -2.6 -2.2
2 120.7 1.6 1.1 115.6 -3.2 -2.2
3 99.2 1.3 0.6 94.1 -2.6 -0.9
4 100.4 0.5 1.2 95.3 -0.9 -2.3
5 106.8 1.4 1.3 101.7 -2.7 -2.7
6 101.3 0.5 1.1 96.2 -0.9 -2.2
7 122.0 1.3 1.2 116.9 -2.6 -2.2
8 115.8 1.3 1.2 110.7 -2.6 -2.3
9 95.8 1.4 0.5 90.7 -2.6 -0.9
10 120.7 1.6 1.1 115.6 -3.2 -2.2
11 104.9 1.3 1.4 99.8 -2.6 -2.7
12 100.4 3.5 1.0 96.0 -4.4 -1.9
13 97.4 -1.2 0.9 93.1 0.1 -1.8
14 98.6 1.1 3.4 94.2 -2.2 -4.3
15 99.2 1.1 -1.5 94.9 -2.2 0.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 116.8 - 116.8
M1 (kN.m) -2.6 -1.3 -4.6
M2 (kN.m) -2.2 -1.3 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.092 Le1/b1 = 8.6 < 15.0 225
Beta = 0.89 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.6 / 2.6 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.88 / 0.88 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.06 / 0.06 N/mm2
Links = Y8-175

1C22 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 150.0 3.1 -0.6 144.9 -6.2 1.2
2 150.0 2.9 -0.6 144.9 -6.0 1.3
3 129.3 3.1 0.2 124.2 -6.2 -0.2
4 131.6 2.1 -0.5 126.5 -4.1 1.2
5 137.4 3.1 -1.1 132.2 -6.2 2.1
6 149.0 3.2 -0.6 143.9 -6.2 1.3
7 137.0 3.1 -0.8 131.9 -6.2 1.7
8 132.7 2.0 -0.5 127.6 -4.0 1.2
9 127.7 3.1 -0.1 122.6 -6.1 0.2
10 150.0 2.9 -0.6 144.9 -6.0 1.3
11 152.0 3.1 -0.6 146.9 -6.2 1.3
12 128.6 5.0 -0.4 124.2 -7.5 1.0
13 125.5 0.2 -0.5 121.1 -2.9 1.1
14 127.5 2.7 2.0 123.1 -5.3 -1.4
15 126.6 2.6 -2.9 122.2 -5.2 3.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 150.0 - 150.0
M1 (kN.m) -6.2 -1.7 -7.6
M2 (kN.m) 1.2 1.7 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.119 Le1/b1 = 8.6 < 15.0 225
Beta = 0.86 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.2 / 2.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.91 / 0.92 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.10 / 0.05 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-19

1C23 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 254.3 -2.2 -0.5 249.2 4.7 1.1
2 233.1 -2.4 -0.8 228.0 4.9 1.7
3 219.0 -2.2 0.6 213.9 4.7 -1.1
4 234.8 -1.2 -0.5 229.7 2.6 1.1
5 237.8 -2.2 -1.0 232.7 4.7 2.0
6 252.6 -2.2 -0.5 247.5 4.6 1.1
7 236.9 -2.2 -0.7 231.8 4.7 1.7
8 236.5 -1.3 -0.5 231.4 2.7 1.0
9 217.6 -2.2 0.3 212.5 4.7 -0.7
10 233.1 -2.4 -0.8 228.0 4.9 1.7
11 256.6 -2.2 -0.5 251.5 4.7 1.1
12 213.4 0.5 -0.4 209.0 1.7 0.9
13 215.9 -4.3 -0.4 211.6 6.2 0.9
14 214.5 -1.8 2.0 210.1 3.9 -1.5
15 214.8 -1.9 -2.8 210.5 4.0 3.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 254.3 - 254.3
M1 (kN.m) 4.7 2.9 6.9
M2 (kN.m) 1.1 2.9 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.201 Le1/b1 = 8.6 < 15.0 225
Beta = 0.77 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 0.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.87 / 0.98 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.01 N/mm2
Links = Y8-175

2C23 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 14.0 -2.0 -1.3 8.4 0.1 0.8
2 12.7 -2.4 -1.9 7.1 0.2 1.1
3 13.5 -2.0 0.9 7.9 0.1 -0.4
4 13.7 -0.8 -1.3 8.1 0.1 0.8
5 13.2 -2.0 -2.4 7.6 0.1 1.5
6 13.6 -2.1 -1.4 8.0 0.1 0.9
7 12.8 -2.0 -2.1 7.1 0.1 1.4
8 14.1 -0.7 -1.2 8.5 0.1 0.8
9 14.0 -2.1 0.5 8.4 0.1 -0.3
10 12.7 -2.4 -1.9 7.1 0.2 1.1
11 13.9 -2.0 -1.2 8.3 0.1 0.7
12 12.1 -1.5 -1.1 7.3 0.1 0.7
13 12.0 -1.9 -1.1 7.1 0.1 0.7
14 12.0 -1.7 -0.4 7.2 0.1 0.0
15 12.0 -1.7 -1.8 7.2 0.1 1.4
Critical Combination:5 - ((G+Q)P22 *F)
Min Design
N (kN) 13.2 - 13.2
M1 (kN.m) -2.0 -0.1 0.0
M2 (kN.m) -2.4 -0.1 -4.4 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.010 Le1/b1 = 10.6 < 15.0 225
Beta = 0.99 Le2/b2 = 9.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.8 / 1.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.03 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-20

1C24 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 94.2 0.2 -1.7 89.1 -0.4 3.4
2 107.5 0.1 -1.7 102.4 -0.2 3.4
3 65.6 0.2 -0.7 60.5 -0.2 1.5
4 87.7 0.4 -1.7 82.6 -0.6 3.4
5 85.9 0.2 -2.0 80.8 -0.3 3.9
6 94.2 0.3 -1.7 89.1 -0.4 3.4
7 86.3 0.2 -1.8 81.2 -0.3 3.7
8 87.7 0.3 -1.7 82.6 -0.6 3.4
9 64.2 0.1 -0.9 59.1 -0.1 1.8
10 107.5 0.1 -1.7 102.4 -0.2 3.4
11 95.1 0.3 -1.7 90.0 -0.5 3.4
12 77.1 2.6 -1.4 72.8 -2.6 2.9
13 82.9 -2.2 -1.4 78.6 2.0 2.9
14 80.9 0.3 0.8 76.5 -0.4 0.7
15 79.2 0.1 -3.7 74.8 -0.2 5.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 94.2 - 94.2
M1 (kN.m) -0.4 -1.1 0.0
M2 (kN.m) 3.4 1.1 4.4 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.074 Le1/b1 = 8.5 < 15.0 225
Beta = 0.91 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.7 / 0.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.87 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.00 N/mm2
Links = Y8-175

1C25 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 213.6 -2.9 0.2 208.5 5.9 -0.4
2 158.9 -1.7 0.3 153.8 3.5 -0.7
3 205.0 -2.9 0.1 199.9 6.1 -0.1
4 202.4 -2.9 0.2 197.3 6.0 -0.4
5 212.8 -2.8 0.1 207.7 5.9 -0.3
6 213.6 -2.8 0.2 208.5 5.9 -0.4
7 212.8 -2.8 0.2 207.7 5.9 -0.4
8 202.4 -3.0 0.2 197.3 6.1 -0.4
9 212.7 -2.9 0.1 207.6 6.1 -0.3
10 158.9 -1.7 0.3 153.8 3.5 -0.7
11 205.9 -2.8 0.0 200.8 5.9 0.0
12 183.1 0.0 0.2 178.8 2.7 -0.3
13 177.7 -4.8 0.2 173.4 7.3 -0.3
14 182.4 -2.3 2.4 178.0 4.9 -2.4
15 178.5 -2.5 -2.0 174.1 5.1 1.8
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 213.6 - 213.6
M1 (kN.m) 5.9 2.4 7.9
M2 (kN.m) -0.4 -2.4 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.169 Le1/b1 = 8.6 < 15.0 225
Beta = 0.80 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.89 / 0.86 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-21

2C25 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 21.1 -0.7 0.0 15.5 -4.7 0.1
2 19.7 1.2 0.2 14.1 -5.6 0.1
3 20.6 -1.0 -0.1 14.9 -4.5 0.1
4 19.6 -1.3 0.1 14.0 -4.0 0.1
5 20.6 -1.0 0.0 15.0 -4.1 0.1
6 21.1 -0.8 0.0 15.5 -4.6 0.1
7 21.1 -0.6 0.0 15.4 -4.8 0.1
8 19.6 -1.1 0.0 14.0 -4.1 0.1
9 20.7 -1.1 0.1 15.1 -4.1 0.1
10 19.7 1.2 0.2 14.1 -5.6 0.1
11 20.5 -0.8 -0.2 14.9 -4.4 0.1
12 18.1 0.0 0.0 13.3 -4.5 0.1
13 18.1 -1.0 0.0 13.3 -3.6 0.1
14 18.3 -0.5 0.4 13.5 -4.2 0.1
15 17.9 -0.6 -0.3 13.1 -4.0 0.1
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 19.7 - 19.7
M1 (kN.m) -5.6 -0.2 -5.9
M2 (kN.m) 0.2 0.2 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.016 Le1/b1 = 9.5 < 15.0 225
Beta = 0.98 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.1 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.76 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.00 N/mm2
Links = Y8-175

1C26 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 51.0 -0.3 0.0 45.9 0.8 0.1
2 57.4 -0.4 0.0 52.3 0.9 0.1
3 47.6 -0.2 -0.2 42.5 0.7 0.5
4 41.5 -0.2 0.0 36.4 0.6 0.1
5 47.7 -0.3 0.1 42.6 0.8 -0.3
6 50.6 -0.2 -0.1 45.5 0.7 0.1
7 42.6 -0.3 0.1 37.5 0.9 -0.2
8 41.8 -0.3 0.0 36.7 0.7 0.1
9 62.8 -0.2 -0.1 57.7 0.6 0.1
10 57.4 -0.4 0.0 52.3 0.9 0.1
11 40.8 -0.3 -0.2 35.7 0.8 0.4
12 40.4 2.1 0.0 36.1 -1.6 0.1
13 47.4 -2.7 0.0 43.1 3.0 0.1
14 43.6 -0.2 2.2 39.2 0.6 -2.1
15 44.3 -0.4 -2.3 39.9 0.8 2.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 51.0 - 51.0
M1 (kN.m) 0.8 0.6 1.4
M2 (kN.m) 0.1 0.6 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.040 Le1/b1 = 8.6 < 15.0 225
Beta = 0.95 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.9 / 1.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.82 / 0.82 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.04 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-22

2C26 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 31.8 0.2 -0.4 26.2 -0.2 0.3
2 31.9 -0.2 -0.4 26.3 0.0 0.3
3 30.6 0.3 -0.5 25.0 -0.3 0.0
4 28.7 0.1 -0.4 23.0 -0.1 0.3
5 28.7 0.3 -0.1 23.1 -0.3 0.4
6 32.2 0.1 -0.3 26.6 -0.1 0.3
7 32.1 0.1 -0.2 26.5 -0.1 0.2
8 28.2 0.3 -0.4 22.6 -0.3 0.3
9 28.2 0.5 -0.4 22.6 -0.5 0.5
10 31.9 -0.2 -0.4 26.3 0.0 0.3
11 30.8 0.2 -0.4 25.2 -0.2 0.0
12 26.6 0.6 -0.3 21.8 -0.6 0.2
13 27.9 -0.3 -0.3 23.1 0.3 0.2
14 27.2 0.2 0.5 22.4 -0.2 -0.5
15 27.3 0.1 -1.1 22.5 -0.2 1.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 31.8 - 31.8
M1 (kN.m) -0.2 -0.4 0.0
M2 (kN.m) -0.4 -0.4 -0.7 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.025 Le1/b1 = 9.5 < 15.0 225
Beta = 0.97 Le2/b2 = 9.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

1C27 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 157.8 -1.0 0.0 152.7 2.2 0.0
2 134.3 -0.7 0.0 129.2 1.4 0.0
3 148.6 -0.9 0.3 143.5 2.1 -0.4
4 152.0 -1.1 0.0 146.9 2.5 0.0
5 148.5 -1.0 -0.3 143.4 2.2 0.4
6 159.8 -1.0 0.0 154.7 2.3 0.0
7 156.8 -1.0 0.1 151.7 2.2 -0.1
8 150.0 -1.1 0.0 144.9 2.4 0.0
9 150.2 -0.9 -0.2 145.1 2.1 0.4
10 134.3 -0.7 0.0 129.2 1.4 0.0
11 147.9 -1.0 0.2 142.8 2.2 -0.3
12 137.1 1.6 0.0 132.7 -0.5 0.0
13 131.7 -3.3 0.0 127.4 4.3 0.0
14 134.5 -0.8 2.3 130.1 1.8 -2.3
15 134.3 -1.0 -2.3 129.9 2.0 2.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 157.8 - 157.8
M1 (kN.m) 2.2 1.8 3.8
M2 (kN.m) 0.0 1.8 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.125 Le1/b1 = 8.6 < 15.0 225
Beta = 0.85 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.5 / 1.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.92 / 0.95 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.06 / 0.04 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-23

2C27 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 13.5 -1.2 -0.2 7.9 0.7 0.0
2 12.0 -0.8 -0.2 6.4 0.5 0.0
3 13.6 -1.2 0.2 8.0 0.7 0.0
4 12.4 -1.7 -0.2 6.8 1.1 0.0
5 13.6 -1.2 -0.4 7.9 0.7 0.0
6 13.0 -1.5 -0.2 7.4 0.9 0.0
7 13.2 -1.3 -0.2 7.6 0.8 0.0
8 12.9 -1.4 -0.2 7.3 0.9 0.0
9 14.0 -1.1 -0.3 8.4 0.6 0.0
10 12.0 -0.8 -0.2 6.4 0.5 0.0
11 13.4 -1.2 0.1 7.8 0.7 0.0
12 11.8 -0.5 -0.1 7.0 0.1 0.0
13 11.3 -1.6 -0.1 6.5 1.2 0.0
14 11.5 -1.1 0.4 6.7 0.6 0.0
15 11.5 -1.1 -0.6 6.7 0.7 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 13.5 - 13.5
M1 (kN.m) -1.2 -0.2 -1.4
M2 (kN.m) -0.2 -0.2 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.011 Le1/b1 = 9.5 < 15.0 225
Beta = 0.99 Le2/b2 = 10.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 0.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.00 N/mm2
Links = Y8-175

1C28 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 226.7 0.5 -0.2 221.6 -0.8 0.6
2 193.9 -0.3 -0.2 188.8 0.7 0.5
3 214.9 0.5 -0.5 209.8 -0.8 1.3
4 203.9 1.1 -0.2 198.8 -2.0 0.6
5 215.8 0.5 0.1 210.7 -0.8 -0.4
6 206.7 1.1 -0.2 201.6 -2.1 0.6
7 208.6 0.5 0.2 203.5 -0.8 -0.2
8 223.9 0.4 -0.2 218.7 -0.8 0.6
9 239.1 0.5 -0.3 234.0 -0.8 0.5
10 193.9 -0.3 -0.2 188.8 0.7 0.5
11 209.7 0.5 -0.5 204.6 -0.8 1.1
12 191.4 2.9 -0.2 187.0 -3.1 0.5
13 192.7 -2.0 -0.2 188.3 1.7 0.5
14 192.1 0.5 2.2 187.7 -0.8 -1.8
15 191.9 0.3 -2.6 187.6 -0.6 2.8
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 226.7 - 226.7
M1 (kN.m) -0.8 -2.5 0.0
M2 (kN.m) 0.6 2.5 4.6 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.179 Le1/b1 = 8.6 < 15.0 225
Beta = 0.79 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 0.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.96 / 0.95 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-24

2C28 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 18.4 2.4 -0.7 12.8 -2.5 0.3
2 16.8 0.6 -0.6 11.2 -1.3 0.2
3 16.7 2.4 -1.1 11.1 -2.5 0.3
4 17.7 3.3 -0.7 12.1 -2.7 0.3
5 16.8 2.4 -0.1 11.2 -2.5 0.2
6 19.1 3.3 -0.7 13.4 -2.8 0.3
7 17.2 2.5 -0.1 11.6 -2.6 -0.1
8 17.0 2.4 -0.6 11.4 -2.5 0.2
9 17.4 2.4 -0.6 11.8 -2.4 0.3
10 16.8 0.6 -0.6 11.2 -1.3 0.2
11 17.4 2.4 -1.2 11.7 -2.5 0.6
12 15.9 2.6 -0.6 11.1 -2.6 0.2
13 15.5 1.5 -0.6 10.7 -1.6 0.2
14 15.7 2.1 0.1 10.9 -2.1 -0.5
15 15.7 2.0 -1.3 10.9 -2.1 0.9
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 17.7 - 17.7
M1 (kN.m) 3.3 0.2 4.0
M2 (kN.m) -0.7 -0.2 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.014 Le1/b1 = 9.8 < 15.0 225
Beta = 0.98 Le2/b2 = 9.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.8 / 0.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.02 N/mm2
Links = Y8-175

1C29 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 116.1 0.4 2.3 111.0 -0.6 -4.6
2 129.1 0.2 2.3 124.0 -0.4 -4.7
3 107.4 0.4 2.6 102.3 -0.6 -5.1
4 109.6 0.5 2.3 104.5 -0.9 -4.6
5 78.4 0.2 1.0 73.3 -0.3 -2.2
6 116.1 0.5 2.3 111.0 -0.7 -4.6
7 116.8 0.4 2.3 111.7 -0.7 -4.7
8 109.6 0.5 2.3 104.5 -0.8 -4.6
9 76.9 0.3 1.1 71.8 -0.3 -2.3
10 129.1 0.2 2.3 124.0 -0.4 -4.7
11 108.2 0.3 2.5 103.1 -0.5 -5.0
12 95.4 2.8 1.9 91.0 -2.8 -3.9
13 101.2 -2.1 1.9 96.8 1.8 -3.9
14 97.7 0.5 4.2 93.3 -0.7 -6.1
15 98.9 0.2 -0.4 94.5 -0.3 -1.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 116.1 - 116.1
M1 (kN.m) -0.6 -1.3 0.0
M2 (kN.m) -4.6 -1.3 -5.8 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.092 Le1/b1 = 8.5 < 15.0 225
Beta = 0.89 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.9 / 3.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.89 / 0.87 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.08 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-25

1C30 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 211.0 -2.6 -0.1 205.9 5.5 0.3
2 157.9 -1.6 -0.3 152.8 3.2 0.6
3 211.1 -2.6 0.0 206.0 5.5 0.2
4 199.8 -2.6 -0.2 194.7 5.6 0.4
5 201.2 -2.7 -0.1 196.1 5.7 0.0
6 211.0 -2.6 -0.1 205.9 5.4 0.3
7 211.0 -2.6 -0.1 205.9 5.5 0.2
8 199.7 -2.7 -0.1 194.6 5.7 0.3
9 201.1 -2.7 0.0 196.0 5.7 0.0
10 157.9 -1.6 -0.3 152.8 3.2 0.6
11 211.1 -2.7 -0.1 206.0 5.6 0.3
12 181.0 0.2 -0.1 176.6 2.3 0.3
13 175.5 -4.7 -0.1 171.2 7.0 0.3
14 176.6 -2.0 2.1 172.2 4.5 -1.8
15 179.9 -2.4 -2.3 175.6 4.8 2.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 211.0 - 211.0
M1 (kN.m) 5.5 2.4 7.4
M2 (kN.m) 0.3 2.4 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.167 Le1/b1 = 8.6 < 15.0 225
Beta = 0.81 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.7 / 0.3 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.88 / 0.92 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.01 N/mm2
Links = Y8-175

2C30 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 21.2 -1.1 -0.3 15.6 -4.2 -0.1
2 19.8 0.7 -0.5 14.2 -5.1 -0.1
3 21.3 -1.0 -0.2 15.7 -4.4 -0.1
4 19.7 -1.6 -0.3 14.0 -3.5 -0.1
5 20.0 -1.7 -0.1 14.4 -3.3 -0.1
6 21.2 -1.3 -0.3 15.5 -4.1 -0.1
7 21.1 -1.2 -0.4 15.5 -4.1 -0.1
8 19.7 -1.5 -0.3 14.1 -3.6 -0.1
9 20.1 -1.6 0.0 14.5 -3.4 -0.1
10 19.8 0.7 -0.5 14.2 -5.1 -0.1
11 21.3 -1.0 -0.3 15.7 -4.3 -0.1
12 18.2 -0.4 -0.3 13.4 -4.1 -0.1
13 18.2 -1.4 -0.3 13.4 -3.1 -0.1
14 18.0 -0.9 0.1 13.2 -3.6 -0.1
15 18.4 -0.9 -0.6 13.6 -3.7 -0.1
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 19.8 - 19.8
M1 (kN.m) -5.1 -0.2 -5.6
M2 (kN.m) -0.5 -0.2 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.016 Le1/b1 = 9.5 < 15.0 225
Beta = 0.98 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.8 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.76 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-26

1C31 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 290.7 -2.9 1.8 285.6 6.0 -3.6
2 269.2 -3.1 2.0 264.1 6.3 -4.1
3 274.5 -2.8 2.3 269.4 6.0 -4.4
4 265.4 -1.5 1.8 260.3 3.3 -3.6
5 244.7 -2.9 0.3 239.6 6.1 -0.8
6 289.1 -2.8 1.8 284.0 5.9 -3.7
7 292.4 -2.8 1.9 287.3 6.0 -3.6
8 267.0 -1.6 1.8 261.9 3.4 -3.6
9 242.4 -2.9 0.5 237.3 6.0 -1.0
10 269.2 -3.1 2.0 264.1 6.3 -4.1
11 275.1 -2.9 2.1 270.0 6.0 -4.2
12 243.7 0.0 1.5 239.3 2.8 -3.0
13 246.2 -4.8 1.5 241.9 7.3 -3.0
14 244.9 -2.2 3.9 240.5 4.9 -5.4
15 245.0 -2.6 -0.9 240.7 5.2 -0.7
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 290.7 - 290.7
M1 (kN.m) 6.0 3.3 8.7
M2 (kN.m) -3.6 -3.3 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.230 Le1/b1 = 8.6 < 15.0 225
Beta = 0.73 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 0.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.93 / 0.80 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.00 N/mm2
Links = Y8-175

2C31 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 12.8 -3.6 3.0 7.2 0.1 -1.3
2 11.6 -4.0 3.5 5.9 0.2 -1.6
3 11.6 -3.6 4.0 6.0 0.1 -2.0
4 12.5 -1.8 3.0 6.9 0.1 -1.4
5 13.1 -3.6 0.2 7.5 0.1 0.2
6 12.4 -3.7 3.0 6.8 0.1 -1.3
7 12.8 -3.6 2.8 7.2 0.1 -1.2
8 12.9 -1.7 3.0 7.3 0.1 -1.4
9 13.4 -3.6 0.6 7.8 0.1 -0.1
10 11.6 -4.0 3.5 5.9 0.2 -1.6
11 11.3 -3.6 3.7 5.7 0.1 -1.8
12 11.1 -2.8 2.5 6.3 0.1 -1.1
13 11.0 -3.2 2.5 6.2 0.1 -1.1
14 11.1 -3.0 3.2 6.2 0.1 -1.8
15 11.1 -3.0 1.8 6.2 0.1 -0.4
Critical Combination:3 - ((G+Q)P12 *F)
Min Design
N (kN) 11.6 - 11.6
M1 (kN.m) -3.6 -0.1 0.0
M2 (kN.m) 4.0 0.1 7.5 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.009 Le1/b1 = 10.6 < 15.0 225
Beta = 0.99 Le2/b2 = 9.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.3 / 1.8 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.03 / 0.04 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-27

1C32 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 188.7 3.9 1.9 183.6 -7.7 -3.7
2 188.6 3.7 1.8 183.5 -7.5 -3.7
3 176.8 4.0 2.3 171.7 -7.8 -4.4
4 164.8 2.5 1.9 159.7 -4.9 -3.8
5 155.3 3.9 0.7 150.1 -7.7 -1.5
6 187.9 4.0 1.9 182.8 -7.8 -3.8
7 189.9 4.0 1.9 184.8 -7.8 -3.8
8 165.7 2.5 1.9 160.6 -4.9 -3.7
9 153.5 3.9 0.8 148.4 -7.7 -1.7
10 188.6 3.7 1.8 183.5 -7.5 -3.7
11 177.4 3.9 2.1 172.3 -7.7 -4.2
12 160.8 5.7 1.6 156.4 -8.8 -3.2
13 157.6 0.9 1.6 153.3 -4.2 -3.1
14 159.3 3.5 4.1 155.0 -6.7 -5.6
15 159.1 3.1 -0.9 154.7 -6.3 -0.7
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 188.7 - 188.7
M1 (kN.m) -7.7 -2.1 -10.8
M2 (kN.m) -3.7 -2.1 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.149 Le1/b1 = 8.6 < 15.0 225
Beta = 0.83 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.9 / 0.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.92 / 0.79 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.09 / 0.00 N/mm2
Links = Y8-175

1C33 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 143.7 1.8 -0.2 138.6 -3.5 0.4
2 145.8 1.8 -0.2 140.7 -3.7 0.5
3 132.9 1.8 -0.3 127.8 -3.5 0.9
4 121.3 1.0 -0.1 116.2 -1.8 0.4
5 130.5 1.8 0.1 125.4 -3.5 -0.3
6 127.7 1.0 -0.2 122.6 -1.9 0.4
7 128.7 1.8 0.2 123.6 -3.5 -0.1
8 137.3 1.8 -0.1 132.2 -3.4 0.4
9 149.5 1.9 -0.2 144.4 -3.6 0.4
10 145.8 1.8 -0.2 140.7 -3.7 0.5
11 128.9 1.8 -0.4 123.8 -3.4 0.8
12 123.8 3.9 -0.1 119.4 -5.1 0.3
13 121.0 -0.9 -0.2 116.6 -0.7 0.4
14 122.4 1.6 2.3 118.0 -3.0 -2.0
15 122.4 1.4 -2.6 118.0 -2.8 2.7
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 143.7 - 143.7
M1 (kN.m) -3.5 -1.6 -4.9
M2 (kN.m) 0.4 1.6 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.114 Le1/b1 = 8.6 < 15.0 225
Beta = 0.87 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 0.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.78 / 0.87 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-28

2C33 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 51.3 3.0 0.7 45.7 0.1 -2.1
2 51.3 2.9 0.7 45.7 0.1 -2.1
3 48.7 3.0 -0.2 43.1 0.1 -0.5
4 46.2 1.8 0.5 40.6 0.1 -1.8
5 44.9 3.1 1.5 39.3 0.0 -3.4
6 51.3 1.8 0.6 45.7 0.1 -2.1
7 49.7 3.0 1.8 44.1 0.1 -4.3
8 46.3 3.0 0.6 40.6 0.1 -1.9
9 46.4 3.1 0.4 40.7 0.0 -1.3
10 51.3 2.9 0.7 45.7 0.1 -2.1
11 48.9 3.0 -0.3 43.3 0.1 -0.3
12 44.0 2.8 0.6 39.2 0.0 -1.8
13 44.0 2.4 0.6 39.2 0.1 -1.8
14 44.0 2.6 1.1 39.2 0.1 -1.9
15 44.0 2.5 0.0 39.2 0.1 -1.7
Critical Combination:7 - ((G+Q)P32 *F)
Min Design
N (kN) 49.7 - 49.7
M1 (kN.m) 3.0 0.6 0.0
M2 (kN.m) -4.3 -0.6 -7.2 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.039 Le1/b1 = 10.6 < 15.0 225
Beta = 0.95 Le2/b2 = 9.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 1.9 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.79 / 0.80 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.04 N/mm2
Links = Y8-175

1C34 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 95.9 -1.0 -4.8 90.8 2.4 9.7
2 97.6 -1.3 -4.8 92.5 2.7 9.8
3 96.2 -1.0 -4.7 91.1 2.3 9.7
4 83.3 -0.3 -4.8 78.2 1.0 9.8
5 72.6 -1.2 -3.0 67.5 2.6 5.9
6 95.8 -1.0 -4.8 90.7 2.3 9.8
7 95.9 -1.0 -4.8 90.8 2.3 9.7
8 83.5 -0.4 -4.8 78.4 1.0 9.8
9 72.6 -1.1 -2.9 67.5 2.5 5.8
10 97.6 -1.3 -4.8 92.5 2.7 9.8
11 96.3 -1.1 -4.8 91.2 2.4 9.8
12 79.7 1.5 -4.1 75.3 -0.3 8.2
13 82.4 -3.3 -4.0 78.1 4.3 8.2
14 80.1 -0.6 -1.9 75.8 1.7 6.2
15 82.0 -1.1 -6.2 77.6 2.2 10.2
Critical Combination:15 - (G+Q-Ny)
Min Design
N (kN) 82.0 - 82.0
M1 (kN.m) 2.2 0.9 0.0
M2 (kN.m) 10.2 0.9 12.2 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.065 Le1/b1 = 8.6 < 15.0 225
Beta = 0.92 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.5 / 5.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.86 / 0.85 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.06 / 0.13 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-29

1C35 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 148.6 0.0 0.0 143.5 0.2 0.0
2 125.7 0.2 0.0 120.6 -0.3 0.0
3 148.6 0.1 0.1 143.5 0.2 0.0
4 125.1 -0.4 0.0 120.0 1.2 0.0
5 146.2 0.1 0.0 141.1 0.1 0.0
6 153.0 0.0 0.0 147.9 0.3 0.0
7 148.7 0.0 0.1 143.6 0.2 0.0
8 120.7 -0.5 0.0 115.6 1.1 0.0
9 146.1 0.1 0.0 141.0 0.1 0.0
10 125.7 0.2 0.0 120.6 -0.3 0.0
11 148.6 0.0 0.0 143.5 0.3 0.0
12 125.8 2.5 0.0 121.4 -2.2 0.0
13 125.6 -2.5 0.0 121.3 2.7 0.0
14 125.7 0.2 1.5 121.3 0.0 -0.6
15 125.8 -0.3 -1.5 121.4 0.5 0.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 148.6 - 148.6
M1 (kN.m) 0.2 1.7 0.0
M2 (kN.m) 0.0 1.7 3.1 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.117 Le1/b1 = 8.6 < 15.0 225
Beta = 0.86 Le2/b2 = 10.3 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.79 / 0.76 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

2C35 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 24.4 11.5 -0.1 18.8 -22.4 -0.1
2 23.6 12.0 -0.1 18.0 -22.6 -0.1
3 24.3 11.6 -0.1 18.7 -22.5 -0.1
4 22.3 9.6 -0.1 16.7 -20.2 -0.1
5 23.4 10.4 -0.1 17.8 -20.3 -0.1
6 25.9 10.6 -0.1 20.3 -21.5 -0.1
7 24.4 11.4 -0.1 18.8 -22.3 -0.1
8 20.8 10.5 -0.1 15.2 -21.1 -0.1
9 23.4 10.5 0.0 17.8 -20.4 -0.1
10 23.6 12.0 -0.1 18.0 -22.6 -0.1
11 24.4 11.5 -0.1 18.7 -22.4 -0.1
12 20.5 10.4 -0.1 15.7 -19.8 -0.1
13 21.3 9.2 -0.1 16.5 -18.6 -0.1
14 20.9 9.9 -0.7 16.0 -19.2 -0.1
15 20.9 9.8 0.5 16.1 -19.1 -0.1
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 23.6 - 23.6
M1 (kN.m) -22.6 -0.3 -22.8
M2 (kN.m) -0.1 -0.3 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.019 Le1/b1 = 9.5 < 15.0 225
Beta = 0.98 Le2/b2 = 10.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 10.5 / 0.0 kN As (Required): %1.48 748.21 mm2 4Y16
vc'(1/2)= 0.78 / 0.76 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.25 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-30

1C36 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 215.4 0.0 -4.4 210.3 0.3 9.0
2 199.6 -0.6 -4.5 194.5 1.3 9.2
3 216.0 0.0 -4.4 210.9 0.3 9.1
4 190.6 0.6 -4.4 185.5 -0.9 9.0
5 182.1 0.0 -2.5 177.0 0.3 5.0
6 187.9 0.6 -4.5 182.8 -0.9 9.1
7 215.3 0.0 -4.3 210.2 0.3 8.9
8 218.1 0.0 -4.3 213.0 0.3 8.8
9 182.0 0.0 -2.5 176.9 0.3 5.0
10 199.6 -0.6 -4.5 194.5 1.3 9.2
11 216.2 -0.1 -4.5 211.1 0.4 9.1
12 182.1 2.5 -3.7 177.7 -2.2 7.5
13 182.2 -2.5 -3.7 177.8 2.7 7.6
14 180.8 0.2 -1.4 176.4 0.0 5.4
15 183.5 -0.3 -5.9 179.1 0.5 9.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 215.4 - 215.4
M1 (kN.m) 0.3 2.4 0.0
M2 (kN.m) 9.0 2.4 10.9 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.170 Le1/b1 = 8.6 < 15.0 225
Beta = 0.80 Le2/b2 = 8.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 5.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.89 / 0.97 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.13 N/mm2
Links = Y8-175

2C36 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 36.1 -10.9 -8.2 30.5 22.8 3.8
2 35.1 -11.8 -8.3 29.5 23.4 3.9
3 36.0 -10.8 -8.0 30.4 22.7 3.6
4 33.3 -9.1 -8.2 27.7 20.6 3.8
5 32.8 -9.9 -4.9 27.2 20.5 2.6
6 32.2 -9.8 -8.4 26.6 21.3 4.0
7 36.2 -11.0 -8.3 30.5 22.9 4.0
8 37.2 -10.2 -8.0 31.6 22.1 3.6
9 32.7 -9.8 -4.6 27.1 20.4 2.2
10 35.1 -11.8 -8.3 29.5 23.4 3.9
11 36.1 -10.8 -8.2 30.5 22.7 3.8
12 31.3 -8.7 -6.9 26.5 18.9 3.2
13 30.5 -9.9 -6.9 25.7 20.1 3.2
14 30.7 -9.3 -6.5 25.9 19.4 2.7
15 31.1 -9.4 -7.3 26.3 19.6 3.7
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 35.1 - 35.1
M1 (kN.m) 23.4 0.4 31.4
M2 (kN.m) -8.3 -0.4 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.028 Le1/b1 = 9.6 < 15.0 225
Beta = 0.97 Le2/b2 = 9.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 10.6 / 3.8 kN As (Required): %2.13 1076.41 mm2 8Y16
vc'(1/2)= 0.99 / 0.99 N/mm2 As (Provided): %3.18 1608.50 mm2
v (1/2)= 0.26 / 0.09 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-31

1C37 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 103.3 2.4 -4.0 98.2 -4.6 8.1
2 104.5 2.3 -4.0 99.4 -4.6 8.2
3 104.0 2.5 -3.9 98.9 -4.7 8.1
4 86.4 1.5 -3.9 81.3 -2.8 8.1
5 80.8 2.3 -2.5 75.7 -4.5 4.9
6 86.7 1.5 -4.0 81.6 -2.8 8.2
7 103.2 2.4 -3.9 98.1 -4.6 8.0
8 102.9 2.4 -3.9 97.8 -4.6 7.9
9 80.9 2.4 -2.4 75.8 -4.6 4.9
10 104.5 2.3 -4.0 99.4 -4.6 8.2
11 104.0 2.4 -4.0 98.9 -4.6 8.3
12 88.5 4.4 -3.3 84.1 -6.2 6.8
13 85.8 -0.4 -3.4 81.5 -1.6 6.9
14 86.3 2.3 -1.0 81.9 -4.1 4.6
15 88.0 1.8 -5.7 83.6 -3.6 9.0
Critical Combination:12 - (G+Q+Nx)
Min Design
N (kN) 88.5 - 88.5
M1 (kN.m) -6.2 -1.0 0.0
M2 (kN.m) 6.8 1.0 12.4 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.070 Le1/b1 = 8.6 < 15.0 225
Beta = 0.92 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.5 / 4.9 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.87 / 0.86 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.09 / 0.12 N/mm2
Links = Y8-175

2C38 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 -0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.8 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-32

2C39 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 -0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.8 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

2C40 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 -0.1 0.0
M2 (kN.m) 0.0 -0.1 -0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.8 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-33

2C42 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.8 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

2C43 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.8 < 15.0 225
Beta = 1.00 Le2/b2 = 9.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-34

2C44 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.7 < 15.0 225
Beta = 1.00 Le2/b2 = 9.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

2C45 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 0.1 0.0
M2 (kN.m) 0.0 -0.1 -0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.7 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-35

2C46 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.7 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

2C47 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 -0.1 0.0
M2 (kN.m) 0.0 -0.1 -0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.8 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-36

2C48 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.7 < 15.0 225
Beta = 1.00 Le2/b2 = 9.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

2C49 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 32.6 10.0 0.0 27.0 -3.7 0.4
2 32.2 7.3 0.0 26.6 -2.9 0.4
3 31.5 10.0 0.0 25.9 -3.7 0.1
4 30.8 9.8 0.0 25.2 -3.6 0.5
5 30.5 9.7 0.0 24.8 -3.5 0.7
6 32.6 9.8 0.0 27.0 -3.5 0.4
7 32.1 10.0 -0.1 26.5 -3.8 0.2
8 30.9 10.1 0.0 25.3 -3.8 0.6
9 31.1 9.7 0.0 25.5 -3.5 0.9
10 32.2 7.3 0.0 26.6 -2.9 0.4
11 31.4 9.9 0.0 25.8 -3.6 0.1
12 28.1 8.9 0.0 23.3 -3.6 0.4
13 27.9 8.1 0.0 23.1 -2.7 0.3
14 28.0 8.4 0.0 23.2 -3.1 0.0
15 28.0 8.5 -0.1 23.2 -3.2 0.8
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 30.9 - 30.9
M1 (kN.m) 10.1 0.3 10.6
M2 (kN.m) 0.6 0.3 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.024 Le1/b1 = 9.8 < 15.0 225
Beta = 0.97 Le2/b2 = 9.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.2 / 0.3 kN As (Required): %0.49 250.14 mm2 4Y16
vc'(1/2)= 0.79 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.10 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-37

2C50 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 -0.1 0.0
M2 (kN.m) 0.0 -0.1 -0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.9 < 15.0 225
Beta = 1.00 Le2/b2 = 9.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

2C51 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 -0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.8 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175