BMS-Concept IO Schedule For MEP
BMS-Concept IO Schedule For MEP
Building management system will be included to monitor, control and collect data
of MEP services as listed below:
1) Mechanical
IO from/to
HOA status – pump
pumps
trip status , pumps Monitor
Transfer control
15 run status pump and
pumps panel, and
start/stop command control
pressure
Discharge Pressure
sensor
HOA status – pump
Monitor IO from/to
Booster trip status , pumps
16 an d pumps
pumps run status pump
control control panel
start/stop command
HOA status – pump Monitor IO from
Recirculation
17 trip status , pumps an d pumps
pumps
run status control control panel
HOA status – pump IO from/to
Monitor
trip status , pumps pumps
18 Lifting station an d
run status pump control
control
start/stop command panel
Pre-
chlorination
19 dosing
system
2) HVAC
Sl. No. Type Remark Status Device
1 Fire pump Start/ stop command Monitor
ventilation fresh air / exhaust an d
fan , motorised control
damper , damper
status, fan trip, run
status, air flow
status
2 Smoke extract Start/ stop command Monitor
fan fresh air / exhaust an d
fan , motorised control
damper , damper
status, fan trip, run
status, air flow
status
3 Car park Start/ stop command Monitor
ventilation fresh air / exhaust an d
fan , motorised control
damper , damper
status, fan trip, run
status, air flow
status
4 Staircase Start/ stop command Monitor
pressurization fresh air / exhaust an d
fan , motorised control
damper , damper
status, fan trip, run
status, air flow
status
5 Fan coil unit Monitor Only
an d common are
control FCU shall be
controlled
through BMS