The document provides an overview and specifications for Morris Line Engineering's range of drop-out fuse switches for voltages up to 36kV. The switches are available with expulsion or cartridge fuses and can be operated from the ground using fibreglass poles for reliable protection and isolation of distribution lines and transformers.

Uploaded by

Suresh Kota
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
933 views86 pages

MLE Complete Product Range 2015

The document provides an overview and specifications for Morris Line Engineering's range of drop-out fuse switches for voltages up to 36kV. The switches are available with expulsion or cartridge fuses and can be operated from the ground using fibreglass poles for reliable protection and isolation of distribution lines and transformers.

Uploaded by

Suresh Kota
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 86

Morris Line Engineering

Manufacturers of High Voltage Disconnectors & Switches

Complete Product Range Catalogue

Overview
Equipment manufactured by MLE is used by
electricity companies, oil and gas companies
and rail electrification schemes throughout
the UK and Ireland in addition to extensive
exports to the Middle and Far East and Africa.
The voltage range of the equipment is 750V
to 145kV with current ratings up to 4,000A,
short time fault currents up to 120kA and
fault make currents up to 25kA.
Our disconnectors and switches are available
with porcelain or composite insulators.
The high quality of the products
manufactured is ensured by :
• In house design and development of new
products.
• All products designed to comply with
the relevant British and International
standards.
• The entire manufacturing process from
initial product design to final test, and if
necessary, installation is carried out by fully
trained MLE personnel.
• All manufacturing and assembly tasks are
controlled by a purpose designed computer
system.
• All finished products undergo inspection
and testing procedures in accordance with
relevant international standards.
• Fully documented quality control system
accredited to ISO 9001:2008.
• Fully documented environmental system
accredited to ISO 14001:2004.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Contents
Drop-Out Fuse Switches ....................................................................................... Section 1
Drop-Out Fuse Switches (Cat. No. DOF/15)

Fault Throwing Switches ...................................................................................... Section 2


Fault Throwing Switches (Cat. No. FTS/15)

Interrupter Heads ................................................................................................. Section 3


Loadmaster Interrupter Heads (Cat. No. IH/15)

Isolating Links ....................................................................................................... Section 4


Pole Operated Isolating Links (Cat. No. IL/15)

Pusher Disconnectors ........................................................................................... Section 5


‘M’ Range (Cat. No. M/15)

Rocking Disconnectors ......................................................................................... Section 6


‘R’ Range (Cat. No. R/15)
‘RX’ Range (Cat. No. RX/15)
‘RX2’ Range (Cat. No. RX2/15)

Rotating Disconnectors ........................................................................................ Section 7


‘RDB’ & ‘RSB’ Range (Cat. No. RB/15)
‘RDB’ Major Pattern 155kV (Cat. No. RDBM/15)

Railway Equipment............................................................................................... Section 8


1250A Track Switch Range (Cat. No. TS/15)
Fixed Earthing Devices (Cat. No. FED/15)

Operating Mechanisms ........................................................................................ Section 9


Manual and Power Mechanisms (Cat. No. OM/15)

Operating Poles Sets........................................................................................... Section 10


Glass Fibre Operating Pole Sets (Cat. No. OP/15)

Installation .......................................................................................................... Section 11


Installation Services (Cat. No. IS/15)

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Drop-Out
Fuse
Switches
Section
1
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. DOF/15

DOEF & DOPF


DROP-OUT FUSE SWITCHES
UP TO 36kV
Switch Overview
The type DOEF fuse switch uses a rewirable dropout expulsion fuse. The type DOPF fused
switch uses a cartridge based current limiting fuse.
This range of equipment provides reliable and cost-effective protection of distribution
lines and transformers, while also offering a visual indicator as to the status of operation
and disconnection from supply.
Each single pole fuse switch unit can be operated from the ground using an optional
multi-section, portable fibreglass operating pole. Available in 1.2m sections, the poles are
available to suit a wide range of applications (full details available in catalogue OP/15).

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. DOF/15


DOEF & DOPF DROP-OUT FUSE SWITCHES
UP TO 36kV
THE MLE RANGE: INSULATORS
• With expulsion fuseholders for button head Our disconnectors and switches are available with porcelain or
composite insulators. M.L.E. standard insulators for a given service
pattern links manufacturers of high voltage
voltage generally have higher electrical values than those contained
disconnectors & switches in both IEC 60694 (expulsion fuses) and IEC 60282 (powder fuses),
based on practice in most European and several other countries.
Ratings
Service Fuse Interrupting Fuse Link ORDERING INFORMATION
Voltage Capacity Ratings
Please provide the maximum possible information at the time
12kV 8kA 1-100A of placing your order. In particular we need to know the service
24kV 8kA 1-100A voltage, insulation level, interrupting capacity, fuse link rating, and
insulator creepage distance required.
36kV 8kA 1-100A
Receipt of this information with the order will save time-consuming
correspondence and avoid unnecessary delays in submitting
• With non-fusible tubular links in place of drawings for approval.
fuseholders
• With current limiting fuse links (for backup SPECIAL REQUIREMENTS
protection) We are always ready to consider any special requirements
regarding the specifications or arrangement of our equipment.
• Mount only to accommodate Cooper
Bussmann or Brush sectionalisers
Ratings
Service Fuse Interrupting Fuse Link Transformer
Voltage Capacity Ratings Rating
12kV 40kA 5-100A 1000kVA

24kV 25kA 5-40A 1000kVA


36kV 16kA 5-31.5A 1000kVA

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. DOF/15


DOEF & DOPF DROP-OUT FUSE SWITCHES
UP TO 36kV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT FOR ANGLE BRACKET
PATTERN TYPE DOEF FUSE-SWITCH (AVAILABLE UP TO 24KV)

AVAILABILITY
Morris Line Engineering has established a global distribution
network which operates in over 25 countries. Agents and trading
partners represent the Company across Europe, the Middle East,
the Far East and Africa.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. DOF/15


DOEF & DOPF DROP-OUT FUSE SWITCHES
UP TO 36kV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT
FOR CHANNEL BASE PATTERN TYPE DOEF FUSE-SWITCH

Product Technical Specification DOEF DOPF

Rated Voltage Up to 36kV Up to 36kV


Rated Continuous Current Up to 100A Up to 100A
Frequency 50/60Hz 50/60Hz
Interrupting Capacity Up to 8kA Up to 40kA

Morris Line Engineering reserves the right to amend specifications and designs
without notice. All information contained in this catalogue is for guidance only.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Fault Throwing
Switches

Section
2
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. FTS/15

TYPE FTS
FAULT THROWING SWITCHES
Up to 40kApk 16kA/1 sec.
Switch Overview The switch portion is basically a single pole MLE type RDB
disconnector to which has been added a closing spring toggle,
The purpose of the MLE Fault Throwing Switch is to create a which in the closed ‘straight-line’ position locks the switch closed
deliberate fault on an overhead line, responding from a signal given to prevent bounce and throw open by the short-circuit forces
by the protective relays of a malfunctioning transformer. Tripping of encountered on closing. At near ground level is positioned the
the source circuit breaker which senses the fault will automatically spring close mechanism in a weatherproof galvanised housing. This
cut off all of the system being supplied. It is, therefore, customary also contains two powerful closing springs which in the service
to isolate the faulty transformer quickly, in the ‘dead period’ before position are restrained by a lever released by a trip solenoid. An
the circuit breaker recloses, by means of an MLE type RLS spring adjustable length of galvanised pipe couples the mechanism to a
opening switch, initiated to open by a late closing auxiliary switch clevis on the switch.
on the FTS. The MLE type FTS will make without welding closed on to a 40kA
peak, and withstand 16kA for 1 second.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. FTS/15


TYPE FTS FAULT THROWING SWITCHES
UP TO 72.5kV
SPRING CLOSING MECHANISM
(With cover removed)

MOUNTING
Either vertical or horizontal base mounting on MLE designed
structure, or single wood, concrete or steel pole.
Preferable to limit mounting height to 4800mm from ground to
base so as to keep the moving parts, i.e. coupling pipe between
mechanism and FTS as short as possible, and also to have easy
access to main contacts after a fault closure.

STANDARD FITMENTS
• Terminal pads with one hole and slot per pad to
receive Customer’s connection.
• 110V trip coil, 100W
• One normally open and one normally closed
auxiliary switches for Customer’s indicative circuits.
(Additional switches to order.)
• One heater with fuse and link. (Usually 250V a.c.,
100VA.)
• Permali insert to order. (This is recommended when
FTS is mounted on wood or concrete pole.)

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. FTS/15


TYPE FTS FAULT THROWING SWITCHES
UP TO 72.5kV
OPERATION Raising the handle, now unlocked, will open the switch. Downward
movement will re-charge the mechanism closing springs, latch the
The service position is with the FTS open and the operating handle mechanism, and finally at the extreme end of the downward stroke
down in an inherent locked position. A supply to the trip coil on lock the handle.
terminals 3 and 4 (see wiring diagram), will release the spring
Mechanical tripping for trial and maintenance is possible by
retaining catch, releasing the springs which will, via the operating
removing the housing cover and pulling downwards on the red
pipe, close the switch at high speed. The toggle on the base of the
coated trip lever.
switch will form a straight line at the end of the closing stroke and
prevent any reaction to open.

WIRING DIAGRAM
TERMINALS:
1 & 2 ..................... Heater circuit.
3 & 4 ..................... Trip circuit.
5, 6, 7 & 8 ............. Auxiliary switches for Customer’s use
5 & 6 ..................... Closed with FTS closed.
7 & 8 ..................... Open with FTS closed.

AUXILIARY SWITCH OPERATION:


As the FTS closes ‘a’ opens to isolate the trip circuit. To reset
FTS the handle is raised. This opens and latches FTS, closes ‘a’
and opens ‘b’. Handle must then be lowered, which charges
mechanism opening springs and closes ‘b’. Auxiliary switch ‘a’
remains closed.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. FTS/15


TYPE FTS FAULT THROWING SWITCHES
UP TO 72.5kV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT
FOR TYPE FTS FAULT THROWING SWITCH

INSULATORS
Our disconnectors and switches are available with porcelain or
composite insulators.

Morris Line Engineering reserves the right to amend specifications and designs
without notice. All information contained in this catalogue is for guidance only.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Interrupter
Heads

Section
3
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. IH/15

LOADMASTER
INTERRUPTER HEADS
UP TO 36kV
Equipment Overview
All types of disconnector manufactured by MLE can be converted to switch disconnectors
by the addition of MLE Loadmaster interrupter heads.
Interrupter heads are available in two sizes; 12kV and 24/36kV.
Arc interruption within the Loadmaster is achieved by a hard gas generated at high
pressure in the space occupied by the arc column. The hydrogen and carbon dioxide
gases which are generated by thermal action on the acrylic liner acts to de-ionise the gas
produced by the arc and improve its electric strength.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. IH/15


LOADMASTER INTERRUPTER HEADS
UP TO 36kV
LOAD BREAK SWITCHES
The fitting of MLE interrupter heads converts the basic MLE disconnector into a load break switch. The principle of
operation is shown diagrammatically and explained below. Please note that the maximum service voltage is 36kV.

OPERATION
A B (Refer to diagrams)

A. Switch closed.
Blue line indicates current flow through main
contacts. Interrupter does not carry current.

B. Start of opening sequence.


Main contacts have parted. All current now
flows through the interrupter. Transfer
contact maintains a continuous circuit
between main contacts parting and the
blade probe engaging with the operatingarm.
During the movement from ‘A’ to ‘B’ opening
and resetting springs are charged.

C. Further movement of the blade from that


shown by position ‘B’ causes retaining catch
to be released. The interrupter moving
contact including trailer, due to the action

C D of the opening spring, shoots upwards at


high speed to create a separation from the
interrupter fixed contacts.
The separation of the interrupter contacts is
maintained through to ‘C’ when subsequent
movement of the blade causes blade probe
to part company with the operating arm,
which falls back, by the action of the resetting
spring, to a closed position of the interrupter.

D. Shows the position taken by the interrupter


with a switch in the open position.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. IH/15


LOADMASTER INTERRUPTER HEADS
UP TO 36kV

PRINCIPLE OF INTERRUPTION CLOSING OF SWITCH


The duration of separation of the interrupter contacts is sufficient The circuit is energised by the blade probe first touching the
to interrupt all currents within the specified range, before the transfer contact, which also acts as a making contact. Further
contacts reclose to position ‘D’. Arcing times of currents up to 400A movement of the blade causes the blade probe to get behind the
are about 1/50th of a second. operating arm and main contact to be established.
Interruption is caused by a self-generated gas at high pressure in
the space occupied by the arc column. As the interrupter contacts
part an arc is drawn in the plastic-lined bore of the interrupter
body. The arc is squeezed into the annular space between the
clearance of the trailer and the bore. During arcing, energy in the
form of gas is released from the trailer which is moulded from a
compound of acrylic and cellulose powders which, under arcing
conditions, release sufficient proportion of gases and have a low
carbonisation rate since carbon atoms in the molecular structure
are protected by hydrogen atoms, the build-up of the dielectric
strength of the gas is greater than the breakdown strength of the
rate of rise of the recovery voltage and an interruption occurs.

FIELD APPLICATION OF MLE LOAD BREAK SWITCHES


Breaking Capacities
Service Voltage Transformer Transformer
Line Charging
Off Load Full Load
12kV 25A 400A 30A
24kV 20A 400A 25A
36kV 10A 400A 16A

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. IH/15


LOADMASTER INTERRUPTER HEADS
UP TO 36kV
LIFE CURVES OF MLE LOADMASTER INTERRUPTER HEADS

TYPICAL TYPE RXL LOAD BREAK SWITCH COMPLETE


WITH LOADMASTER INTERRUPTER HEADS
ORDERING INFORMATION
Loadmaster interrupter heads can be installed during switch
production or added later as a field retrofit or
upgrade. Please provide the maximum possible information at the
time of placing your order.

Morris Line Engineering reserves the right to amend specifications and designs
without notice. All information contained in this catalogue is for guidance only.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Isolating
Links

Section
4
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. IL/15

TYPE I/L
POLE OPERATED ISOLATING LINKS
Up to 52kV 2000A 25kA/3 secs.

Switch Overview
The type I/L range of equipment provides reliable and cost-effective isolation of
distribution lines and transformers, while also offering a visual indicator as to the status
of operation and disconnection from supply.
Each single pole switch unit can be operated from the ground using an optional multi-
section, portable fibreglass operating pole. Available in 1.2m sections, the poles are
available to suit a wide range of applications (full details available in catalogue OP/15).

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. IL/15


TYPE I/L POLE OPERATED ISOLATING LINKS
UP TO 52kV
TYPICAL OUTLINE FOR TYPE TYPICAL OUTLINE FOR REMOVABLE
I/L ISOLATING LINK ISOLATING LINK

MATERIALS: Base:
Current Carrying Parts:
Galvanised Channel.
H.D.H.C. Copper, Nickel Plated.
Connector Pads: H.D.H.C. Copper, Tinned.
Insulators: Porcelain or Composite
Fasteners: Either Stainless Steel or Hot Dipped
Spun Galvanised Steel.

MOUNTING: Vertical (as shown) or underhung.

OPERATION: By insulated pole with projecting pin (supplied as optional extra).

CURRENT RATINGS: 400A, 630A, 800A, 1250A, and 2000A continuous.

SHORT TIME RATING: Up to 25kA for 3 seconds.

SPECIAL REQUIREMENTS: We are always ready to consider any special requirements


regarding the specifications or arrangement of our equipment.

Morris Line Engineering reserves the right to amend specifications and designs
without notice. All information contained in this catalogue is for guidance only.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Pusher
Disconnectors

Section
5
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. M/15

M RANGE
PUSHER DISCONNECTORS
UP TO 52kV
1250A 25kA/3 secs.
Switch Overview
The MLE range of M type disconnectors is a cost effective, reliable,
and low maintenance design. The use of nickel plated solid copper
switching blades dispenses with the need for flexible cables and
pantographs that historically have been proved to be a source of
trouble. The hinge end contacts are of the self cleaning design with
independent pressure springs on each side. The whole assembly makes
for a very robust and reliable design.

Principal features: • Correct operating rod movement in all mounting positions


• Cost effective design • Self cleaning hinge contacts
• Compact size and low mass • Open slotted base for versatile mounting
• Low operating toque required • No flexible cables of pantographs used
• High fault-making capacity • Long life, low maintenance design

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. M/15


M RANGE PUSHER DISCONNECTORS
UP TO 52kV

CURRENT RATINGS POLE GUIDES AND BEARINGS


Current ratings of up to 1250A, with short time currents of up to Pole guides of the pivoting type are available which offer virtually
25kA for 3 seconds, can be achieved in line with IEC 62271-102. frictionless support. They are designed to be attached to wooden,
The M range can be supplied with fault make capability, meaning steel, or concrete poles. All pivots and bearings are made from
the switches are able to withstand fault making currents up to 25kA corrosion resistant stainless steel running in brass bearings. No
peak. maintenance is required.

INSULATORS CONNECTOR PADS


All insulators used meet the requirements of IEC 60694. Either All connector pads are manufactured from HDHC copper and have
porcelain or composite insulators can be fitted. Composite a hard nickel plated finish as standard.
insulators show a significant weight saving over porcelain,
A 14mm diameter hole and a 14mm x 20mm slot at 41.5mm
particularly where higher creepages are required.
centres are provided for connections.

CONTACTS EARTH BLADES


The main and hinge end moving contacts are of the female type
All equipment can be supplied with mechanically interlocked earth
and are designed to exert additional pressure on the fixed contacts
blades on ‘Live Side’ or ‘Dead Side’ if required. By fitting spring
during short-circuit conditions. All contacts are manufactured from
closing mechanisms fault-making capability of 25kApk can be
hard drawn high conductivity (H.D.H.C.) copper and have a hard
achieved.
nickel plated finish.
Contact pressure is maintained by stainless steel conical springs.
Pressures are set during final assembly at works and require no
further adjustment or maintenance.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. M/15


M RANGE PUSHER DISCONNECTORS
UP TO 52kV

MOUNTING ARRANGEMENTS SPECIAL REQUIREMENTS


The disconnectors are available in single, double, or triple pole We are always ready to consider any special requirements
form as standard. Multiple arrangements are available at special regarding the specifications or arrangement of our equipment.
request.
They are suitable for horizontal or vertical mounting on wooden, AVAILIBILITY
steel or concrete poles. When vertically mounted the operating Morris Line Engineering has established a global distribution
rods maintains its correct orientation, i.e. in tension when opening. network which operates in over 25 countries.
This last point is an important safety consideration.
Agents and trading partners represent the Company across Europe,
All types of disconnectors are fitted with open type slotted bases the Middle East, the Far East and Africa.
and clamping plates. This arrangement together with one piece
phase coupling tube (which can be fitted separately) greatly
simplifies the erection process. All ferrous metal parts and
mounting steelwork have hot-dipped galvanised finish.

ORDERING INFORMATION
Please provide the maximum possible information at the time
of placing your order. In particular we need to know the service
voltage, insulation level, interrupting capacity, and insulator
creepage distance required.
Receipt of this information with the order will save time-consuming
correspondence and avoid unnecessary delays in submitting
drawings for approval.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. M/15


M RANGE PUSHER DISCONNECTORS
UP TO 52kV
LOAD BREAK SWITCHES
The fitting of MLE interrupter heads converts the basic type M disconnector into a
type ML load break switch. The principle of operation is shown diagrammatically and
explained below. Please note that the maximum service voltage is 36kV.

OPERATION
A B (Refer to diagrams)

A. Switch closed.
Blue line indicates current flow through main
contacts. Interrupter does not carry current.

B. Start of opening sequence.


Main contacts have parted. All current now
flows through the interrupter. Transfer
contact maintains a continuous circuit
between main contacts parting and the blade
probe engaging with the operating arm.
During the movement from ‘A’ to ‘B’ opening
and resetting springs are charged.

C. Further movement of the blade from that


shown by position ‘B’ causes retaining catch
to be released. The interrupter moving
contact including trailer, due to the action

C D of the opening spring, shoots upwards at


high speed to create a separation from the
interrupter fixed contacts.

The separation of the interrupter contacts is


maintained through to ‘C’ when subsequent
movement of the blade causes blade probe
to part company with the operating arm,
which falls back, by the action of the resetting
spring, to a closed position of the interrupter.

D. Shows the position taken by the interrupter


with a switch in the open position

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. M/15


M RANGE PUSHER DISCONNECTORS
UP TO 52kV

PRINCIPLE OF INTERRUPTION CLOSING OF SWITCH


The duration of separation of the interrupter contacts is sufficient The circuit is energised by the blade probe first touching the
to interrupt all currents within the specified range, before the transfer contact, which also acts as a making contact. Further
contacts reclose to position ‘D’. Arcing times of currents up to 400A movement of the blade causes the blade probe to get behind the
are about 1/50th of a second. operating arm and main contact to be established.
Interruption is caused by a self-generated gas at high pressure in
the space occupied by the arc column. As the interrupter contacts
part an arc is drawn in the plastic-lined bore of the interrupter
body. The arc is squeezed into the annular space between the
clearance of the trailer and the bore. During arcing, energy in the
form of gas is released from the trailer which is moulded from a
compound of acrylic and cellulose powders which, under arcing
conditions, release sufficient proportion of gases and have a low
carbonisation rate since carbon atoms in the molecular structure
are protected by hydrogen atoms, the build-up of the dielectric
strength of the gas is greater than the breakdown strength of the
rate of rise of the recovery voltage and an interruption occurs.

FIELD APPLICATION OF MLE LOAD BREAK SWITCHES


Breaking Capacities
Service Voltage Transformer Transformer
Line Charging
Off Load Full Load
12kV 25A 400A 30A
24kV 20A 400A 25A
36kV 10A 400A 16A

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. M/15


M RANGE PUSHER DISCONNECTORS
UP TO 52kV

The basic M range disconnector can be supplied as a load break


switch or can be combined with drop out fuses. The equipment
shown below has both these features. The insulators are made of
silicone rubber which allows ease of handling and operation.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. M/15


M RANGE PUSHER DISCONNECTORS
UP TO 52kV
DISCONNECTOR-FUSES AND SWITCH-FUSES
The basis of this equipment is either the type M disconnector, or the type ML load break switch. Either type of equipment can be combined with
a variety of fuse arrangements to meet the requirements of most distribution systems.

The following combinations are currently available:

Types M/EF & ML/EF A three phase gang operated disconnector or load break switch
fitted with a single pole drop out expulsion fuse on each phase.
Ratings
Service Fuse Interrupting Fuse Link
Voltage Capacity Ratings
12kV 8kA 1-100A
24kV 8kA 1-100A
36kV 8kA 1-100A

A three phase gang operated disconnector or load break switch


fitted with a single pole drop out current limiting fuse on each
phase.

Types M/CLF & ML/CLF Ratings


Service Fuse Interrupting Fuse Link Transformer
Voltage Capacity Ratings Rating
12kV 40kA 5-100A 1000kVA

24kV 25kA 5-40A 1000kVA


36kV 16kA 5-31.5A 1000kVA

Higher fuse link ratings can be supplied by replacing the drop out
arrangement with fixed fuse mounts and two, three or four current
limiting fuses in parallel on each phase.

TRIP-ALL PHASE UNIT (T.A.P.)


To overcome the problems associated with ‘single phasing’ caused mechanism which in turn will open the switch and isolate all three
when only one fuse in a supply blows, MLE have developed a phases. The switch can also be operated manually for normal
unique system. The design is designated a ‘Trip-All Phase Unit’ switching operations.
(T.A.P.).
On 12kV switches, the tripping mechanism is an integral part of
The principle of operation is that in the event that one or more of the switch. On 36kV switches, the tripping mechanism is housed
the T.A.P. fuses blow, the fuse (or fuses) will swing downwards and in a separate unit which forms part of the operating mechanism.
strike a tripping bar. The tripping bar will release a spring-charged

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. M/15


M RANGE PUSHER DISCONNECTORS
UP TO 52kV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT FOR TYPE M
DISCONNECTORS & TYPE ML LOAD BREAK SWITCHES

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. M/15


M RANGE PUSHER DISCONNECTORS
UP TO 52kV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT FOR 12KV TYPE M
DISCONNECTORS & TYPE ML LOAD BREAK SWITCHES WITH HOOKSTICK
OPERATING MECHANISM

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. M/15


M RANGE PUSHER DISCONNECTORS
UP TO 52kV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT
FOR TYPES M/EF, M/CLF, ML/EF & ML/CLF

TECHNICAL SPECIFICATION
Product M Range
Rated Voltage Up to 52kV
Rated Continuous Current Up to 1250A
Frequency 50/60Hz
Short Time Current Up to 25kA/3secs.
Load Breaking Capacity Up to 400A
Fault Making Capacity Up to 25kApk

Morris Line Engineering reserves the right to amend specifications and


designs without notice. All information contained in this catalogue is for
guidance only.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Rocking
Disconnectors
Section
6
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. R/15

R RANGE
ROCKING DISCONNECTORS
UP TO 52kV
1600A 25kA/3 secs.
Switch Overview
Morris Line Engineering has over 35 years experience in the design and manufacture
of high voltage disconnectors and switches. The Company is widely regarded as one
of the market leaders, providing equipment tailored to meet individual customers’
requirements. The MLE range of R type switches and disconnectors is a reliable, robust,
and long-standing design. They are particularly suited to substation applications, but due
to their flexible design, can be installed throughout the distribution network, fitted with
load break interrupter heads, and equipped with motorised operating mechanisms to
suit each customer’s individual requirements.
The type R can be rated up to 1600A, 25kA/3secs, in accordance with IEC 62271:2008.
Each disconnector can be factory fitted with a range of optional extras, including earth
blades. Supporting steelwork can be provided to suit almost any application. A wide
range of porcelain and composite insulators are available, providing a solution to almost
any specification.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. R/15


R RANGE ROCKING DISCONNECTORS
UP TO 52kV

CURRENT RATINGS Receipt of this information with the order will save time-consuming
correspondence and avoid unnecessary delays in submitting
Current ratings of up to 1600A, with short time currents of up to drawings for approval.
25kA for 3 seconds, can be achieved in line with IEC 62271-102.
SPECIAL REQUIREMENTS
INSULATORS We are always ready to consider any special requirements
All insulators used meet the requirements of IEC 60694. Either regarding the specifications or arrangement of our equipment.
porcelain or composite insulators can be fitted. Composite
insulators show a significant weight saving over porcelain,
particularly where higher creepages are required.
AVAILIBILITY
Morris Line Engineering has established a global distribution
Current ratings of up to 1600A, with short time currents of up to network which operates in over 25 countries.
25kA for 3 seconds, can be achieved in line with IEC 62271-102.
Agents and trading partners represent the Company across Europe,
EARTH BLADES the Middle East, the Far East and Africa.

All equipment can be supplied with mechanically interlocked earth


blades on ‘Live Side’ or ‘Dead Side’ if required.

ORDERING INFORMATION
Please provide the maximum possible information at the time
of placing your order. In particular we need to know the service
voltage, insulation level, interrupting capacity, and insulator
creepage distance required.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. R/15


R RANGE ROCKING DISCONNECTORS
UP TO 52kV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT FOR TYPE R
DISCONNECTOR

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. R/15


R RANGE ROCKING DISCONNECTORS
UP TO 52kV
LOAD BREAK SWITCHES
The fitting of MLE interrupter heads converts the basic MLE disconnector into a load break switch. The principle of
operation is shown diagrammatically and explained below. Please note that the maximum service voltage is 36kV.

OPERATION
A B (Refer to diagrams)

A. Switch closed.
Blue line indicates current flow through main
contacts. Interrupter does not carry current.

B. Start of opening sequence.


Main contacts have parted. All current now
flows through the interrupter. Transfer
contact maintains a continuous circuit
between main contacts parting and the blade
probe engaging with the operating arm.
During the movement from ‘A’ to ‘B’ opening
and resetting springs are charged.

C. Further movement of the blade from that


shown by position ‘B’ causes retaining catch
to be released. The interrupter moving
contact including trailer, due to the action

C D of the opening spring, shoots upwards at


high speed to create a separation from the
interrupter fixed contacts. The separation
of the interrupter contacts is maintained
through to ‘C’ when subsequent movement
of the blade causes blade probe to part
company with the operating arm, which falls
back, by the action of the resetting spring, to
a closed position of the interrupter.

D. Shows the position taken by the interrupter


with a switch in the open position.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. R/15


R RANGE ROCKING DISCONNECTORS
UP TO 52kV

PRINCIPLE OF INTERRUPTION CLOSING OF SWITCH


The duration of separation of the interrupter contacts is sufficient The circuit is energised by the blade probe first touching the
to interrupt all currents within the specified range, before the transfer contact, which also acts as a making contact. Further
contacts reclose to position ‘D’. Arcing times of currents up to 400A movement of the blade causes the blade probe to get behind the
are about 1/50th of a second. operating arm and main contact to be established.
Interruption is caused by a self-generated gas at high pressure in
the space occupied by the arc column. As the interrupter contacts
part an arc is drawn in the plastic-lined bore of the interrupter
body. The arc is squeezed into the annular space between the
clearance of the trailer and the bore. During arcing, energy in the
form of gas is released from the trailer which is moulded from a
compound of acrylic and cellulose powders which, under arcing
conditions, release sufficient proportion of gases and have a low
carbonisation rate since carbon atoms in the molecular structure
are protected by hydrogen atoms, the build-up of the dielectric
strength of the gas is greater than the breakdown strength of the
rate of rise of the recovery voltage and an interruption occurs.

FIELD APPLICATION OF MLE LOAD BREAK SWITCHES


Breaking Capacities
Service Voltage Transformer Transformer
Line Charging
Off Load Full Load
12kV 25A 400A 30A
24kV 20A 400A 25A
36kV 10A 400A 16A

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. R/15


R RANGE ROCKING DISCONNECTORS
UP TO 52kV
The basic R range disconnector can be supplied as a load break switch or can be combined
with drop out fuses. The equipment shown below has both these features.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. R/15

R RANGE ROCKING DISCONNECTORS


UP TO 52kV
DISCONNECTOR-FUSES AND SWITCH-FUSES
The basis of this equipment is either the type R disconnector, or the type RL load
break switch. Either type of equipment can be combined with a variety of fuse
arrangements to meet the requirements of most distribution systems.

The following combinations are currently available:

Types R/EF & RL/EF A three phase gang operated disconnector or load break switch
fitted with a single pole drop out expulsion fuse on each phase.

Ratings
Service Fuse Interrupting Fuse Link
Voltage Capacity Ratings
12kV 8kA 1-100A
24kV 8kA 1-100A
36kV 8kA 1-100A

A three phase gang operated disconnector or load break switch


Types R/CLF & RL/CLF fitted with a single pole drop out current limiting fuse on each phase.

Ratings
Service Fuse Interrupting Fuse Link Transformer
Voltage Capacity Ratings Rating
12kV 40kA 5-100A 1000kVA

24kV 25kA 5-40A 1000kVA


36kV 16kA 5-31.5A 1000kVA

Higher fuse link ratings can be supplied by replacing the drop out
arrangement with fixed fuse mounts and two, three or four current
limiting fuses in parallel on each phase.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. R/15


R RANGE ROCKING DISCONNECTORS
UP TO 52kV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT
FOR TYPES R/EF, R/CLF, RL/EF & RL/CLF

TECHNICAL SPECIFICATION
Product R Range
Rated Voltage Up to 52kV

Morris Line Engineering reserves the right to amend specifications and Rated Continuous Current Up to 1600A
designs without notice. All information contained in this catalogue is for
guidance only.
Frequency 50/60Hz
Short Time Current Up to 25kA/3secs.
Load Breaking Capacity Up to 400A

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX/15

RX RANGE
ROCKING DISCONNECTORS
UP TO 52kV
1250A 25kA/3 secs.
Switch Overview
Morris Line Engineering has over 35 years experience in the design and manufacture
of high voltage disconnectors and switches. The Company is widely regarded as one
of the market leaders, providing equipment tailored to meet individual customers’
requirements.
The MLE range of type RX switches is a cost effective, reliable, and innovative design.
They can be installed throughout the distribution network, fitted with load break
interrupter heads, and fully automated to suit each customer’s individual requirements.
The RX can be rated up to 1250A, 25kA/3secs, in accordance with IEC 62271:2008. Each
disconnector can be factory fitted with a range of optional extras, including earth blades.
Supporting steelwork can be provided to suit almost any application. A wide range of
porcelain and composite insulators are available, providing a solution to almost any
specification.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX/15


RX RANGE ROCKING DISCONNECTORS
UP TO 52kV

CURRENT RATINGS Receipt of this information with the order will save time-consuming
correspondence and avoid unnecessary delays in submitting
Current ratings of up to 1250A, with short time currents of up to drawings for approval.
25kA for 3 seconds, can be achieved in line with IEC 62271-102. The
RX range can be supplied with fault make capability, meaning the
switches are able to withstand fault making currents up to 7.5kA
SPECIAL REQUIREMENTS
peak. We are always ready to consider any special requirements
regarding the specifications or arrangement of our equipment.
INSULATORS
All insulators used meet the requirements of IEC 60694. Either
AVAILIBILITY
porcelain or composite insulators can be fitted. Composite Morris Line Engineering has established a global distribution
insulators show a significant weight saving over porcelain, network which operates in over 25 countries.
particularly where higher creepages are required. Agents and trading partners represent the Company across Europe,
the Middle East, the Far East and Africa.
EARTH BLADES
All equipment can be supplied with mechanically interlocked earth
blades on ‘Live Side’ or ‘Dead Side’ if required.

ORDERING INFORMATION
Please provide the maximum possible information at the time
of placing your order. In particular we need to know the service
voltage, insulation level, interrupting capacity, and insulator
creepage distance required.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX/15


RX RANGE ROCKING DISCONNECTORS
UP TO 52kV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT FOR TYPE RX
DISCONNECTOR & TYPE RXL LOAD BREAK SWITCHES

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX/15

RX RANGE ROCKING DISCONNECTORS


UP TO 52kV
LOAD BREAK SWITCHES
The fitting of MLE interrupter heads converts the basic RX disconnector into a type RXL load break switch. The principle
of operation is shown diagrammatically and explained below. Please note that the maximum service voltage is 36kV.

OPERATION
A B (Refer to diagrams)

A. Switch closed.
Blue line indicates current flow through main
contacts. Interrupter does not carry current.

B. Start of opening sequence.


Main contacts have parted. All current now
flows through the interrupter. Transfer
contact maintains a continuous circuit
between main contacts parting and the blade
probe engaging with the operating arm.
During the movement from ‘A’ to ‘B’ opening
and resetting springs are charged.

C. Further movement of the blade from that


shown by position ‘B’ causes retaining catch
to be released. The interrupter moving
contact including trailer, due to the action

C D of the opening spring, shoots upwards at


high speed to create a separation from the
interrupter fixed contacts. The separation
of the interrupter contacts is maintained
through to ‘C’ when subsequent movement
of the blade causes blade probe to part
company with the operating arm, which falls
back, by the action of the resetting spring, to
a closed position of the interrupter.

D. Shows the position taken by the interrupter


with a switch in the open position.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX/15


RX RANGE ROCKING DISCONNECTORS
UP TO 52kV

PRINCIPLE OF INTERRUPTION CLOSING OF SWITCH


The duration of separation of the interrupter contacts is sufficient The circuit is energised by the blade probe first touching the
to interrupt all currents within the specified range, before the transfer contact, which also acts as a making contact. Further
contacts reclose to position ‘D’. Arcing times of currents up to 400A movement of the blade causes the blade probe to get behind the
are about 1/50th of a second. operating arm and main contact to be established.
Interruption is caused by a self-generated gas at high pressure in
the space occupied by the arc column. As the interrupter contacts
part an arc is drawn in the plastic-lined bore of the interrupter
body. The arc is squeezed into the annular space between the
clearance of the trailer and the bore. During arcing, energy in the
form of gas is released from the trailer which is moulded from a
compound of acrylic and cellulose powders which, under arcing
conditions, release sufficient proportion of gases and have a low
carbonisation rate since carbon atoms in the molecular structure
are protected by hydrogen atoms, the build-up of the dielectric
strength of the gas is greater than the breakdown strength of the
rate of rise of the recovery voltage and an interruption occurs.

FIELD APPLICATION OF MLE LOAD BREAK SWITCHES


Breaking Capacities
Service Voltage Transformer Transformer
Line Charging
Off Load Full Load
12kV 25A 400A 30A
24kV 20A 400A 25A
36kV 10A 400A 16A

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX/15


RX RANGE ROCKING DISCONNECTORS
UP TO 52kV
The basic RX range disconnector can be supplied as a load break switch or can be
combined with drop out fuses. The equipment shown below has both these features.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX/15

RX RANGE ROCKING DISCONNECTORS


UP TO 52kV
DISCONNECTOR-FUSES AND SWITCH-FUSES
The basis of this equipment is either the type RX disconnector, or the type RXL load break switch. Either type of equipment can be
combined with a variety of fuse arrangements to meet the requirements of most distribution systems.

The following combinations are currently available:

Types RX/EF & RXL/EF A three phase gang operated disconnector or load break switch
fitted with a single pole drop out expulsion fuse on each phase.

Ratings
Service Fuse Interrupting Fuse Link
Voltage Capacity Ratings
12kV 8kA 1-100A
24kV 8kA 1-100A
36kV 8kA 1-100A

Types RX/CLF & RXL/CLF A three phase gang operated disconnector or load break switch
fitted with a single pole drop out current limiting fuse on each phase.

Ratings
Service Fuse Interrupting Fuse Link Transformer
Voltage Capacity Ratings Rating
12kV 40kA 5-100A 1000kVA

24kV 25kA 5-40A 1000kVA


36kV 16kA 5-31.5A 1000kVA

Higher fuse link ratings can be supplied by replacing the drop out
arrangement with fixed fuse mounts and two, three or four current
limiting fuses in parallel on each phase.

TRIP-ALL PHASE UNIT (T.A.P.)


To overcome the problems associated with ‘single phasing’ caused when only one fuse in a supply blows, MLE
have developed a unique system. The design is designated a ‘Trip-All Phase Unit’ (T.A.P.).
The principle of operation is that in the event that one or more of the T.A.P. fuses blow, the fuse (or fuses) will
swing downwards and strike a tripping bar. The tripping bar will release a spring-charged mechanism which in turn
will open the switch and isolate all three phases. The switch can also be operated manually for normal switching
operations.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX/15


RX RANGE ROCKING DISCONNECTORS
UP TO 52kV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT
FOR TYPES RX/EF, RX/CLF, RXL/EF & RXL/CLF

TECHNICAL SPECIFICATION
Product RX
Rated Voltage Up to 52kV
Rated Continuous Current Up to 1250A
Morris Line Engineering reserves the right to amend specifications and Frequency 50/60Hz 50/60Hz
designs without notice. All information contained in this catalogue is
for guidance only. Short Time Current Up to 25kA/3secs.
Load Breaking Capacity Up to 400A
Fault Making Capacity Up to 7.5kApk

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX2/15

RX2 RANGE
ROCKING DISCONNECTORS
UP TO 15kV
800A 25kA/3 secs.
Switch Overview
Morris Line Engineering has over 35 years experience in the design and manufacture
of high voltage disconnectors and switches. The Company is widely regarded as one
of the market leaders, providing equipment tailored to meet individual customers’
requirements.
The MLE range of RX2 type switches is a cost effective, reliable, and innovative design.
They can be installed throughout the distribution network, fitted with load breaking
facilities and fully automated to suit our customers’ diverse needs.
The RX2 and its ancillaries have been tested up to 630A, 25kA/3secs, to IEC 62271:2008.
Each disconnector can be factory fitted with optional fault making capabilities, or earth
blades. Supporting steelwork can be provided to suit almost any application. A wide
range of porcelain and composite insulators are available, providing a solution to almost
any specification.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX2/15

RX2 RANGE ROCKING DISCONNECTORS


UP TO 15kV

QUALITY AND LONGEVITY ADAPTABILITY


All switch components are manufactured from corrosion resistant The RX2 range of air break switch disconnectors is available in a
materials. number of options. The fitting of MLE arc chutes makes the RX2
a load break switch. A wide variety of fuse arrangements can be
Contacts are designed to allow short time currents of up to 25kA
fitted to meet the requirements of most distribution systems.
for 3 seconds. The RX2 range can be supplied with fault make arc
horns, meaning the switches are able to withstand fault making
currents up to 25kA peak. OPERATION
All current carrying components are manufactured from hard Low level dependent manual operation can be achieved through
drawn high conductivity (H.D.H.C.) copper and have a hard nickel the use of our standard manual mechanism. Where required,
plated finish, giving a life expectancy of up to 40 years. Contact our low level motor mechanism may be used. High fault make
pressure is maintained by stainless steel conical springs. Pressures situations require the use of our low level independent manual
are set during final assembly at works and require no further spring assisted manual mechanism. Manually operated high level
adjustment or maintenance. hookstick mechanisms may be utilised where lack of earth mat
or vandalism may be a problem. In order to allow for remote
The MLE load break arc chute has been designed for quenching operation, these may be replaced with our high level motor
arcs formed when breaking loads of up to 630A. As an indication of operated hookstick mechanism which can be fitted with Remote
their reliability they are fully tested to IEC 60265:1998. Terminal Units (R.T.U.’s) in order to allow for remote operation.
All MLE disconnectors are suitable for use in the harshest of
environments, including areas with high pollution, salinity and
humidity.

COST EFFECTIVE
Significant cost reduction has been achieved through the design
and development of the load break arc chute.
Due to the reliability of our products, we do not normally
recommend spares for any of our equipment. However, should
spare contacts, insulators, or other components of any nature
be required, these can be provided in a short period of time, if
required.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX2/15


RX2 RANGE ROCKING DISCONNECTORS
UP TO 15kV

MOUNTING ARRANGEMENTS Receipt of this information with the order will save time-consuming
correspondence and avoid unnecessary delays in submitting
The disconnectors are available in single, double, or triple pole drawings for approval.
form as standard. Multiple arrangements are available at special
request. They are suitable for horizontal or vertical mounting on
wooden, steel or concrete poles. When vertically All ferrous metal
SPECIAL REQUIREMENTS
parts and mounting steelwork have hot-dipped galvanised finish. We are always ready to consider any special requirements
regarding the specifications or arrangement of our equipment.
EARTH BLADES
All equipment can be supplied with mechanically interlocked
AVAILIBILITY
earth blades on ‘Live Side’ or ‘Dead Side’ if required. By fitting Morris Line Engineering has established a global distribution
spring closing mechanisms fault-making capability of 25kApk can be network which operates in over 25 countries.
achieved. Agents and trading partners represent the Company across Europe,
the Middle East, the Far East and Africa.
ORDERING INFORMATION
Please provide the maximum possible information at the time
of placing your order. In particular we need to know the service
voltage, insulation level, interrupting capacity, and insulator
creepage distance required.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX2/15


RX2 RANGE ROCKING DISCONNECTORS
UP TO 15kV
The basic RX2 disconnector is supplied as a load break switch and can also be combined
with drop out fuses, as shown below.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX2/15


RX2 RANGE ROCKING DISCONNECTORS
UP TO 15kV
DISCONNECTOR-FUSES AND SWITCH-FUSES
The basis of this equipment is the type RX2 load break switch. This equipment can
be combined with a variety of fuse arrangements to meet the requirements of
most distribution systems.

The following combinations are currently available:

Type RX2/EF A three phase gang operated disconnector or load break switch
fitted with a single pole drop out expulsion fuse on each phase.

Ratings
Service Fuse Interrupting Fuse Link
Voltage Capacity Ratings
12kV 8kA 1-100A

Types RX2/CLF A three phase gang operated disconnector or load break switch
fitted with a single pole drop out current limiting fuse on each phase.

Ratings
Service Fuse Interrupting Fuse Link Transformer
Voltage Capacity Ratings Rating
12kV 40kA 5-100A 1000kVA

Higher fuse link ratings can be supplied by replacing the drop


out arrangement with fixed fuse mounts and two, three or four
current limiting fuses in parallel on each phase.

TRIP-ALL PHASE UNIT (T.A.P.)


To overcome the problems associated with ‘single phasing’ caused when only one fuse in a supply blows, MLE
have developed a unique system. The design is designated a ‘Trip-All Phase Unit’ (T.A.P.).
The principle of operation is that in the event that one or more of the T.A.P. fuses blow, the fuse (or fuses) will
swing downwards and strike a tripping bar. The tripping bar will release a spring-charged mechanism which in turn
will open the switch and isolate all three phases. The switch can also be operated manually for normal switching
operations.
On the RX2 range, the tripping mechanism is an integral part of the switch.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX2/15


RX2 RANGE ROCKING DISCONNECTORS
UP TO 15kV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT
FOR TYPE RX2 LOAD BREAK SWITCHES

Standard on the RX2 range, the manual reciprocating mechanism In cases where an auxiliary supply is available, the optional
has padlocking facilities in the open and closed position. Key motorised mechanism allows for local and remote operation
interlocks may be fitted as optional extras, and through the use of driven by hard wired reliable relay logic. Wiring can accommodate
an optional auxiliary mechanism, up to ten normally open and ten specific electrical interlocking arrangements, and optional
normally closed auxiliary switches, anti-condensation heater, and auxiliary contacts, anti-condensation heater, and an E.B.I. may be
an electrical bolt interlock (E.B.I.) may be included. included. In areas where an auxiliary supply is not available but
remote operation is required, our self contained battery operated
Independent manual operation can be achieved either through
mechanism is available.
the use of spring assisted operating rods or our spring mechanism,
which has been adapted for high fault-make currents. Powerful
closing springs and position locking devices prevent bounce and
throw open by short-circuit forces encountered on closing.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX2/15


RX2 RANGE ROCKING DISCONNECTORS
UP TO 15kV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT FOR TYPE RX2 LOAD
BREAK SWITCHES WITH HOOKSTICK OPERATING MECHANISM

Pole-mounted hookstick mechanisms offer a very reliable, vandal-


resistant and relatively maintenance free form of operation. The
low-level manual variant is self-latching, can be fitted with an
optional safety lock and may be supplied as a retrofit item to
replace other types of operating mechanism.
The high-level motorised variant is designed for installation above
climbing guards and can be fitted with an R.T.U., extended life
batteries and an intelligent charger/monitor.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RX2/15


RX2 RANGE ROCKING DISCONNECTORS
UP TO 15kV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT FOR TYPE RX2 LOAD
BREAK SWITCHES WITH HOOKSTICK OPERATING MECHANISM

TECHNICAL SPECIFICATION
Morris Line Engineering reserves the right to amend specifications and
designs without notice. All information contained in this catalogue is Product RX2
for guidance only.
Rated Voltage Up to 15kV
Rated Continuous Current Up to 800A
Frequency 50/60Hz
Short Time Current Up to 25kA/3secs.
Load Breaking Capacity Up to 630A
Fault Making Capacity Up to 25kApk

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Rotating
Diconnectors

Section
7
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RB/15


RDB & RSB
ROTATING DISCONNECTORS
UP TO 72.5kV
2500A 31.5kA/3 secs.

Switch Overview
The MLE Rotating Single Break (RSB) disconnector, and the Rotating Double Break (RDB)
disconnector illustrated above are of the same basic design.
The contacts are similar to those used on our RX range of disconnectors. The electro-
mechanical forces are kept ’in-line’ to achieve high short time current ratings.
The swivel contacts on the RDB and RSB types are made of high conductivity material
and are designed to withstand the short time current without welding.
The bearing for the rotating insulator is common to both types. The shaft is
manufactured from high grade stainless steel, and is fitted with ‘sealed for life’ ballraces.
No maintenance is required.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RB/15

RDB & RSB ROTATING DISCONNECTORS


UP TO 72.5kV

CURRENT RATINGS ORDERING INFORMATION


Current ratings of up to 2500A, with short time currents of up to Please provide the maximum possible information at the time
31.5kA for 3 seconds, can be achieved in line with IEC 62271-102. of placing your order. In particular we need to know the service
voltage, insulation level, interrupting capacity, and insulator
INSULATORS creepage distance required.

All insulators used meet the requirements of IEC 60694. Either Receipt of this information with the order will save time-consuming
porcelain or composite insulators can be fitted. Composite correspondence and avoid unnecessary delays in submitting
insulators show a significant weight saving over porcelain, drawings for approval.
particularly where higher creepages are required.
SPECIAL REQUIREMENTS
EARTH BLADES We are always ready to consider any special requirements
All equipment can be supplied with mechanically interlocked earth regarding the specifications or arrangement of our equipment.
blades on ‘Live Side’ or ‘Dead Side’ if required.
AVAILIBILITY
Morris Line Engineering has established a global distribution
network which operates in over 25 countries. Agents and trading
partners represent the Company across Europe, the Middle East,
the Far East and Africa.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RB/15


RDB & RSB ROTATING DISCONNECTORS
UP TO 72.5kV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT FOR
TYPE RSB DISCONNECTOR

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RB/15


RDB & RSB ROTATING DISCONNECTORS
UP TO 72.5kV
LOAD BREAK SWITCHES
The fitting of MLE interrupter heads converts the basic RDB or RSB disconnector into a RDBL or RSBL load break switch. The
principle of operation is shown diagrammatically and explained below. Please note that the maximum service voltage is 36kV.

OPERATION
A B (Refer to diagrams)

A. Switch closed.
Blue line indicates current flow through main
contacts. Interrupter does not carry current.

B. Start of opening sequence.


Main contacts have parted. All current now
flows through the interrupter. Transfer
contact maintains a continuous circuit
between main contacts parting and the blade
probe engaging with the operating arm.
During the movement from ‘A’ to ‘B’ opening
and resetting springs are charged.

C. Further movement of the blade from that


shown by position ‘B’ causes retaining catch
to be released. The interrupter moving
contact including trailer, due to the action

C D of the opening spring, shoots upwards at


high speed to create a separation from the
interrupter fixed contacts. The separation
of the interrupter contacts is maintained
through to ‘C’ when subsequent movement
of the blade causes blade probe to part
company with the operating arm, which falls
back, by the action of the resetting spring, to
a closed position of the interrupter.

D. Shows the position taken by the interrupter


with a switch in the open position.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RB/15


RDB & RSB ROTATING DISCONNECTORS
UP TO 72.5kV

PRINCIPLE OF INTERRUPTION
The duration of separation of the interrupter contacts is sufficient
to interrupt all currents within the specified range, before the
contacts reclose to position ‘D’. Arcing times of currents up to 400A
are about 1/50th of a second.
Interruption is caused by a self-generated gas at high pressure in
the space occupied by the arc column. As the interrupter contacts
part an arc is drawn in the plastic-lined bore of the interrupter
body. The arc is squeezed into the annular space between the
clearance of the trailer and the bore. During arcing, energy in the
form of gas is released from the trailer which is moulded from a
compound of acrylic and cellulose powders which, under arcing
conditions, release sufficient proportion of gases and have a low
carbonisation rate since carbon atoms in the molecular structure
are protected by hydrogen atoms, the build-up of the dielectric
strength of the gas is greater than the breakdown strength of the
rate of rise of the recovery voltage and an interruption occurs.

FIELD APPLICATION OF MLE LOAD BREAK SWITCHES


Breaking Capacities
Service Voltage Transformer Transformer
Line Charging
Off Load Full Load
12kV 25A 400A 30A
24kV 20A 400A 25A
36kV 10A 400A 16A

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RB/15


RDB & RSB ROTATING DISCONNECTORS
UP TO 72.5kV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT FOR
TYPE RDB DISCONNECTOR

TECHNICAL SPECIFICATION
Product RDB RSB
Morris Line Engineering reserves the right to Rated Voltage Up to 72.5kV Up to 72.5kV
amend specifications and designs without
notice. All information contained in this Rated Continuous Current Up to 2500A Up to 1250A
catalogue is for guidance only.
Frequency 50/60Hz 50/60Hz
Short Time Current Up to 31.5kA/3 secs. Up to 25kA/3secs.
Load Breaking Capacity Up to 400A Up to 400A

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RDBM/15

RDB DOUBLE BREAK


DISCONNECTORS
MAJOR PATTERN 145KV
Switch Overview
Morris Line Engineering has developed and fully type tested their range of 145kV
Disconnectors using Silicone Rubber or Porcelain Insulators.
The basic design has been developed using the concept of the 72.5kV rotating range,
which has proved very reliable and successful over the previous 20 years.
Our design team has used the concept of a locking/guide arrangement on all the contacts
that acts when the Disconnector is in the closed position preventing contact separation
and contact pressure variation when using silicone insulators under fault conditions.
All the contact spring pressure are accurately achieved by using adjustable contact
fingers which are set up once the forces of any bus bar or conductors are connected to
the connector pads, this concept maintains the correct pressure as was originally type
tested.
The 145kV RDB can be operated either manually or motorised.
Earth blades can be fitted on either or both sides of the Disconnector.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RDBM/15


RDB DOUBLE BREAK DISCONNECTORS
MAJOR PATTERN 145KV
DESIGN FEATURES
CONTACTS BASES
Higher kA rating from in-line blade tip and fingers. Balanced forces Usually double steel channel in box section or in some cases,
reduce finger movement on short circuit and increase contact hollow steel section depending on the size of the disconnector.
pressure. Finish is hot-dip galvanised to ISO 1461. Fixings are arranged to suit
individual requirements.
• Copper fingers and tips
• Nickel plated contact points for high currents. OPERATING MECHANISMS
• Stainless steel springs and fastenings including fixings to Reciprocating mechanism either manual or motor operated, are
terminal pads. supplied to suit the requirements of individual customers. Auxiliary
• High pressure point contact. contacts etc can be fitted as reasonably required.

• 1250 amp rating has a single contact assembly


INSULATORS
• 2000 amp rating has a double contact assembly
The disconnectors can be supplied with porcelain or composite
• Terminal pads to BEBS, NEMA, or to suit customer’s insulators to suit individual applications.
requirements.
Silicone rubber insulators with creepages up to 5,800mm and short
time current ratings up to 40kA/3 secs are available.
BEARING
Precision machined LM6 aluminium alloy housing with same PCD PHASE COUPLING
fixings as insulators contains a large diameter spindle running in
Bearings are fitted with a lever arm to which is attached a clamp
combined thrust and axial double taper roller bearings with grease
clevis. When the bolt is loosened, provision is made for inserting
nipple for long life. Adjustable stops for open and closed positions
a galvanised steel pipe which effectively couples the three phases
are provided in a galvanised steel bracket.
together. The pipe is usually installed with phases closed.

EARTH BLADES ARRANGEMENTS


Earth blades may be fitted at either end. Contacts are the same Alternative arrangements may be available to suit different site
pattern as for the main disconnect contacts. For ease of operation and requirements. Support Structures also available.
locking into the closed position, an‘ on-toggle’ linkage is incorporated
in the drive.

INTERLOCKS
Both manual and motor mechanisms can be fitted with electrical bolt
or mechanical key interlocks, the functions of which must be defined
at time of order. Mechanical key interlocking between main and earth
blade mechanisms are provided as standard.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches
Catalogue No. RDBM/15
RDB DOUBLE BREAK DISCONNECTORS
MAJOR PATTERN 145KV
CURRENT RATINGS
Continuous Current 3 Second Peak
IEC IEC 62271-102
1250A 40.0kA 100kA
2000A 40.0kA 100kA

INSULATION LEVELS
Station post, cap, pin or silicone rubber insulators can be fitted
to meet the requirements of IEC60694.

IEC 60694
Rated Impulse 1 Minute Power Frequency
Voltage Withstand Withstand
(kV rms) (kV Peak) (kV rms)
List 1 List 2 List 1 List 2
145 500 650 230 275

Catalogue No. RDBM/15


RDB DOUBLE BREAK DISCONNECTORS
MAJOR PATTERN 145KV
SPECIAL REQUIREMENTS
We are always ready to consider our Customer’s special requirements as regards current ratings and insulation levels.

ORDERING INFORMATION
Please provide the maximum information possible at the time of placing your order. In addition to voltage ratings, current ratings and
insulation levels, we need to know phase centres, mounting position and height, type of structure, functions of interlocks and auxiliary
switches together with details of auxiliary supply voltages. Receipt of this information with the purchase order will save time consuming
correspondence and avoid unnecessary delays in submitting drawings for approval.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. RDBM/15


RDB DOUBLE BREAK DISCONNECTORS
MAJOR PATTERN 145KV
TYPICAL OUTLINE AND MOUNTING ARRANGEMENT FOR
TYPE 145kV RDB DISCONNECTOR

Morris Line Engineering reserves the right to amend


specifications and designs without notice. All information
contained in this catalogue is for guidance only.

TECHNICAL SPECIFICATION Weight


in Kgs. 3
Phases,
Creepage BIL Withstand Dimensions in mm. mechanism
kV. Insulator and pipes.
in mm. kV. wet kV. V W X Y Z
145 Silicone Rubber 5800 650 605 610 900 950 1500 To suit 800

145 K47268 50 3350 650 275 610 900 950 1500 To suit 1052

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Railway
Equiptment

Section
8
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. TS/15


ROTATING TRACK SWITCHES
25kV 1250A 31.5kA / 3 secs.

Single Pole 3 Position (Closed/Open/Earth) Single Pole 2 Position (Closed/Open)

Product Features: Product Specifications:


• Improved Rating & Performance • Design based on Network Rail Specification NR/PS/
• Reduced Maintenance ELP/27184.
• Same application range as earlier MLE 800A units. • Rated Current 1250A
• Interchangeability with existing MLE 800A units* • Impulse Withstand 250kV
• Improved Direct Drive Motor Mechanism • Short Circuit 31.5kA for 3 secs.
• Making & Breaking of 6A Line Charging Current.
*Note: Single pole units can be mounted onto existing base
channels but twin units will require a new base channel. • Polymeric Insulators
• Available as 2 or 3 position.
• Available as single or twin format.
• Manual or Direct Drive Motorised Mechanism.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. TS/15


1250A Rotating Track Switch and BR Mk. 2
Motorised Operating Mechanism
Product Features:
• New direct drive motorised mechanism.
• Interchangeable with units complying with specification NR/
PS/ELP/27184.
• Remote or local operation
• Facility for remote or local confirmation of contact position.

Product Specifications:
• Design based on Network Rail specification NR/PS/ELP/27184
but using a proven direct drive motorised mechanism.
• The mechanism enclosure has the same dimensions & fixing
positions as earlier specification.
• The existing cables can be accommodated, in the same
position, in the new enclosure.
• Indication switches for remote confirmation of isolator
contact position.
• Mechanical flag to indicate earth contact is in closed
position.

Earth Contact Position Indicator Indication switches for isolator contact position

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. TS/15

About Morris Line Engineering (MLE)


Morris Line Engineering specialises in the production of isolators LV switchboards. Along with our experienced design & installation
for power systems. Supplying mainly power distribution utilities teams we are able to provide a complete turnkey package for
and railways, we have an extensive range from low voltage d.c. railway projects.
through to 132kV. We have supplied 25kV isolators to the British MLE is qualified as a registered supplier to Network Rail by Achilles
rail network for over 30 years. RISQS.
Although MLE is best known in the railway market as a supplier of Our quality system has been approved to ISO 9001:2008.
Our environmental system has been approved to ISO 14001:2004.
25kV isolators, we also manufacture high current DC switches and

Part Numbering Configurator


MLE 1250A 25kV Isolator Range
MLE D1250 - XXX / XXX / XXXX / XXXX - XX

A = Single Pole (2 Position)


B = Single Pole (3 Position)
C = Twin Isolator (3 Position)

G = Clockwise
H = Anti-Clockwise
I = Not Applicable (Twin)

M = Closed & Open


N = Closed, Open & Earth
O = Alternative Feed
P = Alternative Feed & Earth

S = Limit Switches & Supporting


Bracket
T = Flag Indicator Clockwise
U = Flag Indicator Anti-Clockwise
V = Operating Red Extension

AM = Motorised Unit

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. TS/15


1250A Rotating Track Switch Range
Description OLEMI Number PADS Number MLE Number = Insulator = Earth Connection

2-Position Closed/Open
(Clockwise)
With Base 199/588/101 0091/002850 30460
Without Base 199/588/111 0091/002651 30442

2-Position Closed/Open
(Anti-clockwise)
With Base 199/588/102 0091/002876 30462
Without Base 199/588/112 0091/002653 30444

3-Position Closed/Open/Earth
(Clockwise)
With Base 199/588/103 0091/002853 30459
Without Base 199/588/113 0091/002852 30437

3-Position Closed/Open/Earth
(Anti-clockwise)
With Base 199/588/104 0091/002854 30461
Without Base 199/588/114 0091/002652 30443

Twin 3-Position Closed/Open/Earth


(Common Earth)
With Base 199/588/105 0091/002654 30448
Without Base 199/588/113 0091/002855 30463
Twin 3-Position Closed/Open/Alternate Feed

With Base 199/588/106 0091/002857 30450


Without Base 199/588/116 0091/002856 30464
3-Position Closed/Open/Alternate Feed

With Base 199/588/107 0091/002859 30466


Without Base 199/588/117 0091/002858 30452
Twin 3-Position Closed/Open/Earth
(Common Contact)
With Base 199/588/108 0091/002656 30451
Without Base 199/588/118 0091/002860 30465
2-Position Earth/Open
(Clockwise)
With Base 199/588/109 0091/002864 30467
Without Base 199/588/119 0091/002863 30453
2-Position Earth/Open
(Anti-clockwise)
With Base 199/588/110 0091/002862 30643
Without Base 199/588/120 0091/002861 30644

Morris Line Engineering reserves the right to amend specifications and designs without notice. All information contained in this catalogue
is for guidance only.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. FED/15

TYPE FED FIXED EARTHING DEVICES


25kV
20kA/3 secs. (50kApk)
15kApk FAULT MAKE

Equipment Overview
Designed to be suitable for mounting on standard OLE support structures directly above the track, the type FED fixed
earthing device has been developed to cater for Network Rail’s latest requirements for fast and reliable section earthing
of overhead lines. It is the first of its kind to allow earthing from a control box, rather than portable earth leads, thereby
increasing safety while maximising productivity during trackside maintenance.
Available in a variety of single pole and ganged multi-pole configurations to suit all portal and gantry structures, the FED
can be operated either manually or by means of a purpose-designed motor mechanism which allows for remote operation
driven by hard wired reliable relay logic and can accommodate specific electrical interlocking arrangements.
Motor mechanisms are supplied with inputs and outputs suitable for use with Network Rail’s approved SCADA and RTU
communications equipment and a lockable access cover.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. FED/15


TYPE FED FIXED EARTHING DEVICES
25kV
Product Features

FED Motor Mechanism Indication Switch for Earth Status

Typical Outline and Mounting Arrangement for FED Fixed


Earthing Device

About Morris Line Engineering (MLE)


Morris Line Engineering specialises in the production of isolators LV switchboards. Along with our experienced design & installation
for power systems. Supplying mainly power distribution utilities teams we are able to provide a complete turnkey package for
and railways, we have an extensive range from low voltage d.c. railway projects.
through to 132kV. We have supplied 25kV isolators to the British MLE is qualified as a registered supplier to Network Rail by Achilles
rail network for over 30 years. RISQS.
Although MLE is best known in the railway market as a supplier of Our quality system has been approved to ISO 9001:2008.
Our environmental system has been approved to ISO 14001:2004.
25kV isolators, we also manufacture high current DC switches and

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Operating
Mechanisms

Section
9
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. OM/15


MANUAL AND POWER
MECHANISMS

Equipment Overview
The wide range of disconnectors and switches manufactured by Morris Line Engineering
lend themselves to applications throughout worldwide transmission and distribution
systems.
In order to meet individual end users’ requirements for operation of disconnectors
in varying settings, M.L.E. has designed and developed several types of operating
mechanism, each of which can be adapted to cater for almost any customer’s needs.
All types of operating mechanism manufactured by the Company have proved
themselves reliable and robust in locations throughout the world, and come with the
peace of mind that excellent aftersales support is on hand, should it be required.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. OM/15


MANUAL AND POWER MECHANISMS

MANUAL RECIPROCATING
MECHANISM
Standard on the MLE range of substation and line disconnectors,
the Manual Reciprocating Mechanism has padlocking facilities
in the open and closed position. Key interlocks may be fitted as
optional extras, and through the use of the standard optional
Auxiliary Mechanism, up to ten normally open and ten normally
closed auxiliary contacts, anti-condensation heater, electrical
socket outlet, fluorescent lamp and an electrical bolt interlock
(E.B.I.) may be included.

Manual Reciprocating Manual Reciprocating


Mechanism Auxiliary Mechanism with
mechanical key interlocks, and
weatherproof housing with EBI
and auxiliary switches.

OPERATING POLES MANUAL TORSION MECHANISM


For use with our range of drop-out fuse switches and isolating links, The Manual Torsion Mechanism is designed for operation of some
Operating Pole sets may be supplied including rain shield, operating of our rotating post Track Switches. The operating handle is of the
head and carrying bag. ‘lift-up, walk-around’ type and operates through 180°. Auxiliary
Mechanisms can be fitted as on the Reciprocating Mechanism.

Manual Torsion Auxiliary Mechanism


with mechanical key interlocks, and
Operating Pole Set
weatherproof housing with EBI and
auxiliary switches.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. OM/15


MANUAL AND POWER MECHANISMS

SPRING MECHANISM MOTOR MECHANISM


Designed for use with our Fault Throwing Switch range, the spring In cases where an auxiliary supply is available, the Motor
mechanism has been adapted for high fault-make currents. Two Mechanism allows for local and remote operation driven by
powerful closing springs and position locking devices prevent hard wired reliable relay logic. Wiring can accommodate specific
bounce and throw open by short-circuit forces encountered on electrical interlocking arrangements, and optional auxiliary
closing. contacts, anti-condensation heater, electrical socket outlet,
fluorescent lamp and an EBI may be included. Battery powered
operation is also available.

Spring Mechanism with Reciprocating Motor Mechanism for


cover removed substation disconnectors

HOOKSTICK MECHANISMS
Pole-mounted Hookstick Mechanisms offer a very reliable, vandal-
resistant and relatively maintenance free form of operation.
The high-level manual variant is self-latching, can be fitted with
an optional safety lock and may be supplied as a retrofit item
to replace other types of operating mechanism. The high-level
motorised variant is designed for installation above climbing guards
and can be fitted with an RTU, extended life batteries and an
intelligent charger/monitor.

Self-Latching Manual High Level Motor Operated


Hookstick Mechanism Hookstick Mechanism

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. OM/15


MANUAL AND POWER MECHANISMS
OPERATING MECHANISM COMPATIBILITY CHART
Mechanism Type

Manual Operation Motorised Operation


Reciprocating

Reciprocating
Operating

Hookstick

Hookstick
Torsion

Torsion
Spring
Rods

DOEF/DOPF 
FTS 
I/L 
Disconnector Type

M    
R   
RDB/RSB  
RX    
RX2    
TS  
ORDERING INFORMATION
Please provide the maximum possible information at the time of placing consuming correspondence and avoid unnecessary delays in submitting
your order. In particular we need to know the mechanism type, key drawings for approval.
interlock quantities and codings, EBI requirements, number of auxiliary Morris Line Engineering reserves the right to amend specifications and
contacts, and the number and type of any other optional extras. Receipt designs without notice. All information contained in this catalogue is
of this information with the order will save time- for guidance only.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Operating
Pole Sets

Section
10
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. OP/15


GLASS FIBRE OPERATING POLES
AND MEASURING RODS
• DIMENSIONAL STABILITY STANDARD OPTIONS
• RESISTANT TO CHEMICAL ACTION OPERATING HEAD ADDITIONAL 4 ft
SECTIONS CANVAS CARRYING BAG
• LIGHT WEIGHT Note: All sections are fitted with press
buttons.
• ALL SECTIONS READILY The top section has a spigot to
TRANSPORTABLE accommodate alternative adaptor
heads. The lower section is fitted
with a plastic rain shield and earthing
SPECIFICATION terminal.

Dry Withstand Per 4 ft 0 ins (1.2m) 380 kV


Dry Arc-Over Per 4 ft 0 ins (1.2m) 453 kV
Dry Withstand Per 8 ft 0 ins (2.4m) 500 kV
Wet Withstand Per 4 ft 0 ins (1.2m) 180 kV
Wet Arc-Over Per 4 ft 0 ins (1.2m) 240 kV
Wet Withstand Per 8 ft 0 ins (2.4m) 300 kV
Wet Arc-Over Per 8 ft 0 ins (2.4m) 405 kV

Impulse ( 1/50 + Wave )


Withstand Per 4 ft 0 ins (1.2m) 600 kV
Arc-Over Per 4 ft 0 ins (1.2m) 736 kV
Puncture Through Wall 33 kV
Tensile Strength 40,000 lb/in²
Ult. Compression 15.8 ton/in²
Spec. Grav. 1.8 Gr. Per C.C.
Co—Eff. Exp. 1.4 x 10-5 Per 1 in Per °C.
Standard Production Test:-
100kV for 1 Min. Per 12 in (305mm)

Morris Line Engineering reserves the right to amend specifications and


designs without notice. All information contained in this catalogue is for
guidance only.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Installation

Section
11
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. IS/15


INSTALLATION SERVICES

Service Overview
Morris Line Engineering can offer a worldwide, in-house installation service; the
equipment you purchase can be erected by the people who designed and manufactured
it.
Drawing on a wealth of experience, accumulated through decades of operating in the
High Voltage sector, we are pleased to offer a bespoke installation service for both
refurbishment and new build substations.
When our equipment is installed by our team of specialist site operatives, the warranty
period is automatically increased to five years at no additional cost.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering
Manufacturers of High Voltage Disconnectors & Switches

Catalogue No. IS/15

INSTALLATION SERVICES
BESPOKE SERVICE PREVIOUS CUSTOMERS
Supporting structures can be custom designed and made to Morris Line Engineering have completed installations for various
measure to meet the requirements of each individual customer’s Distribution Network Operators and other companies, including:
specifications, and can be tailored for use with both manually
operated or motorised line equipment. • AREVA Group

All projects, from the refurbishment and retrofitting of • CE Electric UK


disconnectors within existing DNO substations, through to new • Network Rail
build substations up to 145kV for off-shore wind farm projects, are
expertly carried out by our team of in-house site engineers. • Petroleum Development Oman
• RWE npower
EXPERT KNOWLEDGE • Scottish Power
All site operatives are extensively trained in the installation of
our complete range of products, and in accordance with specific • Western Power Distribution
Distribution Network Operator and client requirements.
Our site engineers are each in possession of a complete set of up
to date safety qualifications, and are fully qualified as Appointed
Personnel and Competent Personnel, as required.

Morris Line Engineering reserves the right to amend specifications and


designs without notice. All information contained in this catalogue is
for guidance only.

Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.


T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk
Morris Line Engineering is part of the Morris McLellan Group, which
offers a wide variety of other high quality engineering services
including:

• Electrical installation and maintenance services to industry


• Mechanical and electrical services to the built environment
• Manufacture of low voltage switchboards, control panels and motor control centres

• Worldwide, independent, multi-disciplinary, specialist consulting services

• Fire alarm system design, supply, installation, commissioning, maintenance and support
• Public address, voice alarm, loudspeaker, call, pager and disabled refuge systems
• Fire extinguisher servicing

• Electrical wholesaling and cable distribution services


Brackla Industrial Estate, Bridgend. CF31 2AG. United Kingdom.
T +44 (0) 1656 650680 F +44 (0) 1656 768209
www.morrisline.co.uk

You might also like