0% found this document useful (0 votes)
250 views2 pages

Detail of Connected Load & Max Demand

This document provides details of the connected load and maximum demand for a 4 bedroom + garden + 15 townhouse residential and commercial building project in Al Mamzar, Dubai. It lists the rating, cable size, connected load and proposed meter details for the main distribution board (MDB), 10 sub-main distribution boards (SMDBs), and notes the total connected 3-phase load is 1315.3 kW at a 0.9 diversity factor, resulting in a maximum demand of 1183.7 kW. The MDB receives power from DEWA and connects to the SMDBs.

Uploaded by

haseebamer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
250 views2 pages

Detail of Connected Load & Max Demand

This document provides details of the connected load and maximum demand for a 4 bedroom + garden + 15 townhouse residential and commercial building project in Al Mamzar, Dubai. It lists the rating, cable size, connected load and proposed meter details for the main distribution board (MDB), 10 sub-main distribution boards (SMDBs), and notes the total connected 3-phase load is 1315.3 kW at a 0.9 diversity factor, resulting in a maximum demand of 1183.7 kW. The MDB receives power from DEWA and connects to the SMDBs.

Uploaded by

haseebamer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

DETAIL OF CONNECTED LOAD & MAX DEMAND

PROJECT: 4B+G+15 TYP.+ROOF OWNER: MR. ABDULLA ALI HAMAD AREA: AL MAMZAR , DUBAI, U.A.E
(COMMERCIAL & RESIDENTIAL BUILDING) SAEED BUHALEEBA

PLANNED COMPLETION DATE: CONSULTANT: ENGINEERING ASSOCIATES PLOT NO: 134-1040

MDB-01 LOCATION OF MDB: LV ROOM (GROUND FLOOR)

Rating AMPS CABLE SIZE PROPOSED TYPE & No. OF


PVC/ XLPE CONNECTED LOAD - kW
CIRCUIT/ FAULT kWh METERS
ECC SIZE-
SP/TP DUTY REMARKS
FEEDER F/S MCCB MCB 2/4x1C mm2 2/3/4C mm2 1C mm2 TOTAL 1-PH 3-PH 3-PH LV/HV
kA R-PH Y-PH B-PH
SWA/ PVC
DB NO. ISO ACB kW kW kW kW CT

(1) (2) (3) (4)

2500 BY DEWA
INCOMER-1 4P 50 2x1C-150 439.01 438.31 437.94 1315.26 1 2400/5A CT
SET @ 0.85

2500 BY GENERATOR SUPPLIER PROVISION FOR MOBILE GENERATOR WITH ELECTRICAL AND MECHANICAL INTERLOCK
INCOMER-2 4P 50
Set @ 0.85

OUTGOING

2500
BB1-MDB-01 TP 50 2500A TPN+E COPPER BUSBAR RISER 439.0 438.3 437.9 1315.3 100
Set @ 0.8
CAPACITOR BANK TP 1000 50 XLPE/SWA/LSZH 3x4C-240 3x1C-120 400 kVAR CAPACITOR BANK

MDB-01 CONNECTED TO: DEWA

Transf-01

TOTAL CONNECTED LOAD PER PHASE 439.0 438.3 437.9 1315.3 0 100 0 1 TOTAL

SMDB CONNECTED TO:

MDB

MAX DEMAND (3 PH) _______ 1183.7 kW @ 0.9 DIVERSITY TOTAL CONNECTED LOAD (3PH) 1315.3 kW

CONTRACTOR:

Type of Meter (Rating of Incomer): (1) Up to 60A (2) Up to 100A (3) Up to 125-160A (4) LV CT …../5A

( 1 PHASE ) ( 3 PHASE )
DETAIL OF CONNECTED LOAD & MAX DEMAND

PROJECT: 4B+G+15 TYP.+ROOF OWNER: MR. ABDULLA ALI HAMAD AREA: AL MAMZAR, DUBAI, U.A.E
COMMERCIAL & RESIDENTIAL BUILDING SAEED BUHALEEBA

PLANNED COMPLETION DATE: CONSULTANT: ENGINEERING ASSOCIATES PLOT NO: 134-1040

BB1-MDB-01 LOCATION OF LV: LV ROOM (GROUND FLOOR)

Rating AMPS CABLE SIZE PROPOSED TYPE & No. OF


FAULT PVC/ XLPE CONNECTED LOAD - kW
CIRCUIT/ ECC SIZE- kWh METERS
SP/TP DUTY 2/4x1C REMARKS
FEEDER F/S MCCB MCB 2/3/4C mm2 1C mm2 R-PH Y-PH B-PH TOTAL 1-PH 3-PH 3-PH LV/HV
kA SWA/ PVC mm2
DB NO. ISO ACB kW kW kW kW CT
(1) (2) (3) (4)

INCOMER TP 2500 50 2500A TPN+E COPPER BUSBAR RISER 439.01 438.31 437.94 1315.26

OUTGOING

SMDB-1F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10


SMDB-2F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-3F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-4F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-5F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-6F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-7F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-8F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-9F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 43.9 43.8 43.8 131.5 10
SMDB-10F TP 300 50 XLPE/SWA/LSZH 4C-185 1x1C-95 44.1 43.8 43.6 131.5 10

MDB CONNECTED TO: DEWA


Transf-01
TOTAL CONNECTED LOAD PER PHASE 439.0 438.3 437.9 1315.3 0 100 0 0 TOTAL
SMDB CONNECTED TO:
BB1-MDB-01

MAX DEMAND (3 PH) _______ 1183.7 kW @ 0.9 DIVERSITY TOTAL CONNECTED LOAD (3PH) 1315.3 kW

CONTRACTOR:

Type of Meter (Rating of Incomer): (1) Up to 60A (2) Up to 100A (3) Up to 125-160A (4) LV CT …../5A