Instrument Identification Notes & Instructions
Instrument Identification Notes & Instructions
Equipment Installation Instrument TAG BH Purchase Code Instrument Type Notes for mechanical completion team/commissioning team
Check:
1)"HA1C", "00800" are present in the product code
Other notes:
- 0% (LRV) elev. = internal bottom of the vessel; 100% (URV) = top of the internal vessel
- probe TIP shall not contact the bottom of the pipe/chamber: 5mm clearance min. required
- ensure with actual installation that probe tip extends at least 150mm below
0% (LRV)
- set for DC=1.4
V-0401
vertical vessel GWR 5301 Level Indicator &
(inside cold box Z- top mounted on 3" Transmitter, C, 3B probe coaxial
0401) chamber, cold insulated 104-0xA(B)-LIT-04102 RT-96942 perforated, remote head
Check: 1)"HA1S", "01002" are present in the product code
Other notes:
- 0% (LRV) elev. = vessel BTL; 100% (URV) = upper chamber flange CL
- probe TIP shall not contact the bottom of the pipe/chamber: 5mm clearance min. required
- ensure with actual installation that probe tip extends at least 150mm below
0% (LRV)
- set for DC=1.2