Open Delta Transformer Connection
Open Delta Transformer Connection
electricalpereview.com/open-delta-transformer-connection/
How much power can an open delta deliver compared to a standard three phase delta
transformer?
Where does the power formula for the open delta transformer connection come from?
1/23
What about the current and voltages for an open delta transformer?
If you’ve ever tried finding this information on the open delta transformer connection in
a book, or on the internet, you’ve no doubt come across over simplified diagrams and
empty explanations that left you grasping for more information and still feeling
uncertain.
To fix that, we made a complete step by step break down analysis on the open delta
transformer connection starting with a standard three phase delta connection and
finishing with a two-winding open delta connection.
This is by far the most complete and in-depth information you will find on the internet
or elsewhere on the subject of open delta transformer connections.
2/23
Below is a diagram of three single phase transformers connected in delta to form a three
phase delta transformer. For the sake of this article let’s assume we are working with a
balanced, positive ABC sequence system.
With the chosen reference angle and a balanced, positive sequence system we can
determine the delta phase voltages:
3/23
Here is the resulting phasor diagram for the delta
phase voltages:
Maximum power conditions for a transformer exist when the power factor is unity.
When this is true, the delta phase current will be exactly in phase with the delta phase
voltage, and the active power output in watts (P) will be equal to the apparent power
volt-amp rating (S) of the transformer:
4/23
Since we know that each delta phase current is now in phase with each delta phase
voltage, the phase currents will have the same angle as their respective phase voltage.
This lets us determine the complex value of each delta phase current.
From there, we can determine each system line current since by definition they are
larger by a factor of √3 and lag by 30º compared to their respective delta phase current:
Notice each phase current has the same angle as the previously determined delta phase
voltage since power factor is equal to unity.
Here is the resulting delta phase current and system line current phasor diagram:
5/23
(Go back to top)
Recall that this is the correct relationship that will result in maximum power output for
the delta transformer:
6/23
Now, let’s solve for the total three phase power of the delta transformer during these
conditions by adding up the power delivered by each of the three windings.
Theta is equal to the difference between the phase voltage angle and the phase current
angle. Since these angles are equal, theta is equal to zero for each pair:
The maximum power delivered by a three phase delta transformer is equal to three
times the delta phase voltage magnitude times the delta phase current magnitude.
7/23
Example – Determine the maximum power of a three phase transformer if
three individual single-phase transformers rated for 150kVA and
4,160V/480V are connected in delta.
Let’s use the previous formula we derived to solve for maximum power.
Note that we can use either the secondary phase voltage with the secondary phase
current, or the primary phase voltage with the primary phase current and still get the
same answer.
8/23
So far so good, this is the easy stuff.
Now that we are familiar with the maximum power relationships for the three phase
delta transformer, let’s look at what happens when one winding is removed and we are
left with the open delta transformer connection.
This results in an open delta transformer configuration that looks like this:
9/23
(Go back to top)
So far, nothing has changed for the delta A-phase and C-phase voltage, but we are not so
sure about the delta B phase voltage just yet:
Let’s use a delta phase voltage magnitude of 1 so that we can plug these values into our
calculator and see if the magnitude and angle increases or decrease in value:
The surprising finding is that the connected three phase system sees no
difference in the supply voltage with the missing winding!
The open delta phase voltages are identical to the three phase delta voltages prior to the
winding being removed:
11/23
(Go back to top)
First, recognize that there is no change in the system line voltage since the open delta
phase voltage is identical to the three phase delta phase voltages. The result of this is
that the angles of each system line current will be the same as before.
The magnitudes of the system line currents will still be balanced and equal, but will be
different in value since the previous KCL formulas for a three phase delta no longer
apply with the missing winding:
12/23
(Go back to top)
Recognize that when we look at each of the single-phase transformers individually, even
though the B phase transformer is no longer connected, it does not affect the full load
amps of each of the two remaining single phase transformers that make up the two
remaining windings of the open delta transformer.
The result is that each phase current in the two remaining open delta windings will have
the same magnitude as before.
However, since the KCL relationship has been changed by removing a connection
between the B an C phase, the angles will be different than before:
13/23
Let’s start with the C-line and C-phase current since they have the easiest
relationship:
Looking at the open delta digram, the C line current is now equal to the C phase current
for the open delta connection since the B winding is missing.
Since we know the magnitude of the C line current, and the angle of the C phase current,
we can determine the complex value for both:
Multiplying a vector by negative one does not change the magnitude, it only rotates the
vector by positive or negative 180 degrees.
Since the B-phase current equals the negative B-line current, we know that their
magnitudes are equal.
We already know the B-phase current magnitude and the B-line current angle.
We can find the missing B-phase angle by rotating it 180 degrees and solving for the
complex values for both:
15/23
The A-line current has a
magnitude equal to the phase
current magnitude with an angle
of 0º degrees.
Let’s draw all three line currents and both phase currents on the same phasor diagram.
Note that the C-line current and the C-phase current are equal and share the same
vector:
16/23
Last step, it’s time to finally understand where the formula for open delta power comes
from.
Let’s draw a phasor diagram that shows both pairs of the remaining phase values, the A-
phase voltage and current, and the C-phase voltage and current.
Note that we are not using line values because we want to find the complex sum of both
remaining individual single phase transformers that each make up the two remaining
phase windings of the open delta transformer:
17/23
Even though the open delta configured transformer is operating at maximum power
conditions the phase currents and phase voltages are no longer perfectly in phase and
have a displacement between them that is no longer equal to zero degrees.
Let’s take the complex sum of both remaining windings to determine the total
maximum power that the open delta transformer can deliver:
The maximum three phase power that the open delta configured transformer can
deliver is √3 times the phase voltage magnitude times the phase current magnitude.
18/23
13. Open Delta Max Power vs Standard 3ø Delta Max
Power
Intuitively we know that an open delta transformer cannot supply as much power as a
standard three phase delta since one of the windings is missing.
Since we already derived the formulas for both maximum open delta power and
maximum standard delta power, let’s see if we can determine the percent difference.
This only works we are comparing an open delta three phase transformer with the same
single phase transformer ratings. For example, if a three phase delta transformer loses
one of its windings, or, if the same rated single phase transformers are used to make
both a three phase delta transformer and an open delta transformer.
In both cases, the magnitudes of the phase voltage and phase current will be equal
between the two types of delta transfomers:
An open delta transformer can only supply 57.7% of the power that a three phase delta
transformer with equal single phase transformer ratings can deliver.
This is quite a large decrease in power when only losing a third of the
overall three phase transformer windings.
19/23
(Go back to top)
Time to use the max power formula for an open delta transformer:
20/23
Notice that the three phase open delta transformer with two windings will only deliver
17.3MW compared to the previous 30MW with three windings.
The trick here is that with open delta, we can’t just add the power ratings of both
windings (10MW + 10MW ≠ 17.3MW).
Again we used the secondary voltage and the secondary FLA for the phase voltage and
phase current magnitudes but we could have just as easily used the primary voltage and
primary FLA values instead to get the same results (try it and verify).
Since we already did the math in the previous two examples, let’s use the previous
values we calculated to find the percentage of power that the open delta can supply
compared to when all three windings were in service.
We can do this by dividing the max power we determined for the open delta transformer
by the max power we determined for the delta transformer.
21/23
The 17.3MW of power that the open delta can deliver is only 57.7% of the previous
30MW of power that the transformer was able to deliver before the winding failure.
The second way to calculate this is to compare the formulas for open delta maximum
power to standard delta maximum power.
Since the phase voltage magnitudes and phase current magnitudes are equal, they will
cancel.
22/23
Notice that we still get the same answer without having to know the actual values of the
phase voltage or phase current magnitudes!
Is this the first time you’ve seen a full-length explanation on the open delta
configuration?
Have any lingering questions after working your way to the bottom of this article?
23/23