Generator-Transformer Unit Protection (RCS-985BT) PDF
Generator-Transformer Unit Protection (RCS-985BT) PDF
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
The information in this chapter of the equipment documentation is intended to ensure that
equipment is properly installed and handled in order to maintain it in a safe condition.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason, only qualified personnel may work on or operate the equipment.
z Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
z Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
z Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
DANGER!
It means that death, severe personal injury, or considerable equipment damage will occur if safety
precautions are disregarded.
WARNING!
It means that death, severe personal, or considerable equipment damage could occur if safety
precautions are disregarded.
CAUTION!
It means that light personal injury or equipment damage may occur if safety precautions are
disregarded. This particularly applies to damage to the device and to resulting damage of the
protected equipment.
WARNING!
The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.
WARNING!
During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.
In particular, the general facility and safety regulations for work with high-voltage equipment must
be observed. Noncompliance may result in death, injury, or significant equipment damage.
DANGER!
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING!
z Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous
z Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.
CAUTION!
z Earth
z Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
z Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.
Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.
z External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
z Connection cable
Copyright
Manual: R1.00 NANJING NARI-RELAYS ELECTRIC CO., LTD.
P/N: EN_YJBH2051.0086.0001 69 SuYuan. Avenue, Nanjing 211102,China
Copyright © NR 2009. All rights reserved
Tel: 86-25-87178185, Fax: 86-25-87178208
We reserve all rights to this document and to the information Website: www.nari-relays.com
contained herein. Improper use in particular reproduction and Email: [email protected]
dissemination to third parties is strictly forbidden except where
expressly authorized.
Table of Contents
Preface ........................................................................................................................................... i
Introduction ............................................................................................................................ i
3.3.9 Restricted Earth Fault Protection for Main Transformer .................................. 47
Chapter 1 Introduction
1.1 Application
For a large scale generator-transformer unit, two sets of RCS-985BT can be used and then main
protection, abnormal operation condition protection and backup protection can be duplicated.
Operating circuits and mechanical protection equipment (RCS-974 series) are installed on a
separated panel. Independent CT groups are used by two RCS-985BT while main and backup
protection in a RCS-985BT share one CT group. Outputs of the protection correspond to
independent trip coils. Therefore, the following features can be achieved:
2. Convenient, reliable and secure for operation of equipment and requirements of accident
prevention
1.2 Function
RCS-985BT suits connection of generator-transformer unit with generator with capacity 100MW or
above, one 220kV or 500kV main transformer (two windings) and two step-down transformers
(three windings or one split winding). RCS-985BT can provide completed main and backup
protection functions for generator-transformer unit of large-scale thermal power unit with circuit
breaker in the generator terminal, nuclear power unit and gas turbine unit, main transformer and
step-down transformer.
2 zones/2
7 Impedance protection at HV side 21P
time delays
2 stages/2
8 Voltage controlled overcurrent protection 51/27, 67P
time delays
2 stages/4
9 Zero-sequence overcurrent protection at HV side 50N, 51N
time delays
Directional zero-sequence overcurrent protection at HV 2 stages/4
10 67N
side time delays
11 Gap zero-sequence overvoltage protection at HV side
12 Gap zero-sequence overcurrent protection at HV side
13 Zero-sequence overvoltage alarm at LV side
inverse-time/
14 Over-excitation protection 24
definite-time
15 Breaker flashover protection
16 Breaker failure protection 50BF
17 Overload alarm 49
18 Initiating cooling 49
19 Overcurrent alarm output
20 VT circuit supervision 47,60G
21 CT circuit supervision 50/74
Other functions
Automatic
relay hardware supervision and secondary circuit supervision
self-supervision
Metering 24 samples per cycle
CPU module 32 latest fault reports, 8 latest fault waveforms
Fault recorder 4 or 8 seconds continuous oscillogram function for latest
MON module
fault
Self-supervision
32 latest abnormality reports
report
Event recorder
Binary input
32 latest binary status input change reports
change report
Present recording One normal operating waveform triggered manually
Local HMI LCD and keypad
RCSPC software or substation automation system
Remote HMI
software
Front communication port
for software RCSPC with local protocol
(RS232)
Rear Ports type 4 RS-485 ports (two can be configured as fiber port)
communication
Protocol type IEC 60870-5-103/Modbus
ports to host
Rear communication port to
one RS-485 or RS-232
printer
Time synchronization port IRIG-B (optional)
Voltage and current drift auto-adjustment
Connection shown in the figure is that of panel A. However, connection of panel B including
polarity mark of CT is the same as panel A. Although exciter or excitation transformer is drawn in
these figures, either of them is applicable for any scheme.
Different groups of CT are used for them. Panel C comprises mechanical protection.
It can be used either for generator-transformer unit with capacity 100MW or above or similar
connection diagram.
500kV
RCS-974A
RCS-985BT RCS-985BT
RCS-974A
Main Transformer
Step-down Step-down
transformer A transformer B
Generator
As shown in Figure 1.3-2, this typical protection configuration scheme consists of three protection
panels, in which panels A and B comprises separately one set of electric quantity protection.
Different groups of CT are used for them. Panel C comprises mechanical protection and control
circuit of 220kV circuit breaker.
It can be used either for generator-transformer unit with capacity 100MW or above or similar
connection diagram.
220kV
Busbar VT
CJX
RCS-985BT RCS-985BT
Main RCS-974A
transformer
Step-down Step-down
transformer A transformer B
Generator
Exciter
Panel A and B are equipped with complete set of backup protection and different CTs are used for
them.
For zero-sequence current protection, if there is only one group of zero sequence current CT, it
can be connected to panel A. While panel B can adopt calculated zero sequence current from
bushing CT. Protective ranges of these two kinds of zero sequence current protection are different
to each other. Their setting shall be calculated separately.
2. Main protection and backup protection share the same group of CT.
2. For zero-sequence voltage, there are two windings adopted by two sets of RCS-985BT
simultaneously in general.
Breaker failure initiation is very important to power plant. In general, generator-transformer unit
protection tripping contact is an essential to breaker failure initiation. Considering importance of
such protection, it is recommended to realize it as follows:
2. In order to make it more reliable, circuit breaker failure initiation should be independent device
with electric quantity protection device.
1.4 Features
RCS-985BT adopts high-performance digital signal processor DSP chip as its core calculating unit.
It is indeed digital protection device.
RCS-985BT comprises two independent CPU systems where low-pass filter, A/D converter, fault
calculation and logic output are all independent. CPU1 is used for tripping matrix while CPU2 for
fault detector. The equipment will be blocked and issue alarm if any one of CPU fails. Hence,
An independent general fault detector is equipped in management module (MON module). Power
source of output relay can be connected only when the fault detector operates. Besides, various
other fault detectors are provided for various protection functions. Tripping outputs of protective
elements on CPU module can be validated only when corresponding fault detector on MON
module picks up. Any component failures during normal condition will not cause unwanted
operation.
The equipment adopts high-speed sampling and parallel calculation. Sampling rate is 24 points
per cycle. Calculation of all protection elements can be performed during one sampling period.
High security, reliability and speed can be reached then.
Variable slope percentage characteristic is adopted for differential protection (refer to Figure 3.3-1).
Slopes Kb11 and Kb12 can be so set that high sensitivity can be got during internal fault and
transient unbalance current can be avoided during external fault. In order to prevent unwanted
operation of differential protection due to CT saturation, measures to discriminate CT saturation
are provided for phase current on each side.
DPEC percentage differential protection reflects only deviation components of differential current
and unrestraint current and is not effected by load current. It can detect small fault within
transformer and generator. Besides, it is insensitive to CT saturation since its restraint coefficient is
set comparatively high.
Inrush current blocking is used for the equipment. Second harmonic and waveform of current can
be used for discrimination of inrush current by option.
According to relation between DPFC of restraint current and differential current of differential
protection, external or internal fault can be discriminated correctly. For external fault, criterion of
waveform of current is adopted. Unwanted operation will not occur if the correct transfer time from
primary to secondary side of CT is not less than 5ms. As to internal fault, the equipment will
operate quickly.
Two groups of VT inputs are equipped for generator end. If one group fails the equipment will issue
alarm and switch to the healthy group automatically. It is not needed to block protective function
relevant to voltage of generator.
This function adopts percentage differential principle. Detection ability of CT circuit failure can
enhanced significantly and unwanted operation can be avoided then.
1.4.3 Intellectuality
The HMI interface with a LCD and a 9-button keypad on the front panel is very friendly to the user.
Real time, connection diagram, phase current, differential current and voltage can be displayed on
LCD during normal condition.
1.4.3.2 Transparency
More than 500 sampled data including differential current and phase angle etc. can be displayed
on LCD and more than 1500 internal data of the equipment can be supervised through dedicated
auxiliary software RCSPC that provides user with great convenience to know about the operation
situation of RCS-985.
CPU module: latest 32 groups of fault data and event sequence, 8 groups of fault oscillogram, 32
status changes of binary inputs and 32 self-supervision reports can be recorded.
MON module: when the equipment picks up, oscillogram of all analog sampling quantity,
differential current and operation of the protection equipment can be recorded with duration up to 4
seconds or 8 seconds (depend on sample rate configured).
The format of event or fault report is compatible with international COMTRADE format.
Two rear RS-485 ports with IEC 60870-5-103 protocol or MODBUS protocol which can be
re-configured as optical fiber ports
Various GPS clock synchronizations: second/minute pulse via binary input or RS-485, message
via communication ports and IRIG-B synchronization.
Enclosure dimensions
482.6mm×532.6mm×285mm, 12U
(W×H×D)
Trepanning dimensions
450mm×534mm, M6 screw
(W×H)
Mounting Way Flush mounted
Weight per device Approx. 30kg
2.7 Certifications
1. ISO9001:2000
2. ISO14001:2004
3. OHSAS18001:1999
4. ISO10012:2003
5. CMMI L3
Range: 0.1Ie~1.5Ie
Range: 2Ie~14Ie
Accuracy: ±2.5%
Range: 0.10~0.50
Range: 0.50~0.80
Range: 0.10~0.35
≤30ms (Id≥2×[I_Pkp_PcntDiff_Tr])
≤25ms (Id≥1.5×[I_InstDiff_Tr])
Where:
Range: 0.1Ie~1.5Ie
Range: 2Ie~14Ie
Accuracy: ±2.5%
Range: 0.10~0.50
Range: 0.50~0.80
Range: 0.10~0.35
≤35ms (Id≥2×[I_Pkp_PcntDiff_Tr])
≤25ms (Id≥1.5×[I_InstDiff_Tr])
Range: 0.1In~1.5In
Scope: 2In~14In
Scope: 0.00~0.80
≤30ms (I0d≥2×[I_Pkp_PcntREF_Tr])
≤25ms (I0d≥1.5×[I_InstREF_Tr])
Where:
Range: 0.1In~1.5In
Scope: 2In~14In
Scope: 0.00~0.80
≤30ms (Id≥2×[I_Pkp_PcntWdgDiff_Tr])
≤25ms (Id≥1.5×[I_InstWdgDiff_Tr])
Dual protection schemes are necessary for a large-scale generator-transformer unit to be safe in
operation. There are three principles for duplicating the complete set of protection schemes.
2. Main protection, backup protection and fail condition protection share the data sampled from
the same CT
With the fast development of electronic technology, especially the extensive application of DSP
(Digital Signal Processor), CPLD (Complex Programmable Logic Device) and FPGA (Field
Programmable Gate Array), it is possible to integrate main and backup protection of a
generator-transformer unit into one set of protection equipment.
For important 220kV or above voltage level substation and large-scale generator-transformer
group, duplicate independent groups of DC storage batteries for protection are provided. For
some substations and generator-transformer not quite important, although only one group of DC
storage batteries is provided considering economic factor, duplicate DC source for protection
equipments can be obtained by dividing the DC source into different DC bus bar by DC breaker. In
the same way, duplicate protection for transformer can share the same output circuit and get
voltage from different AC voltage bus bar whose voltages origin are same VT distributed by AC
breaker. Of course, it is better that independent sets of CTs are provided for the duplicated
protection, one for each. Duplicate protection configuration principle for transformer doesn’t
enlarge the investment of secondary circuit. In fact, on the contrary, the investment in protection
equipment is reduced. At least one protection will clear transformer’s inner fault, which eliminates
the possibility of delay clearance that exists before if only backup protection left when differential
protection fails to operate due to any causes.
The additional output blocking circuit controlled by general fault detectors calculated in MON
module makes the output circuit more secure, because not only the relationship between tripping
command sending and additional output blocking circuit is logic “AND” in software, but also they
keeps the logic “AND” relationship in hardware. It is displayed in below figure.
+24V FD
+24V
Trip
Relay
R
G1
Tripping Transistor
The general fault detectors calculated in MON module and operation elements calculated in CPU
module use their independent data sampled by themselves, so the equipment will not operate by
mistake due to any of module’s data channel’s failure.
When the maximal value of three-phase differential currents of main transformer is greater than
the pickup setting of percentage differential protection of main transformer ([I_Pkp_PcntDiff_Tr]),
the percentage differential protection of main transformer will be released.
Where:
ΔI dt is the floating threshold value which will rise automatically and gradually according to
increasing of the output of deviation component. In order to ensure that the threshold value of
current is slightly higher than the unbalance output, multiple 1.25 of the deviation component is
reasonable.
• •
Δ I 1 …. Δ I m are the DPFC current of each side of transformer respectively
This fault detector is not influenced by the direction of power flow and so it is very sensitive. The
setting is fixed and need not to be set. When the above condition is met, DPFC differential
protection will be released.
When the maximum value of three-phase current is greater than its setting value [I_OCx_Tr], the
overcurrent protection at relevant side will be released. (x can be 1 or 2)
Where:
ΔI t is the floating threshold which will rise automatically and gradually according to increasing of
the output of deviation component. In order to ensure that the threshold current is slightly higher
than the imbalance value, multiple 1.25 of the deviation component is reasonable.
I th is the fixed threshold of 0.2In and need not to be set case to case.
When the above condition is met, impedance protection at relevant side will be released.
When the zero-sequence current is greater than its setting value [I_ROCx_Tr], the stage 1 or 2 of
zero-sequence overcurrent protection at relevant side will be released. (x can be 1 or 2)
When the gap zero-sequence current is greater than its setting value [I_ROC_Gap_HVS_Tr], the
gap zero-sequence overcurrent protection will be released.
When the gap zero-sequence voltage is greater than its setting value [V_ROV_Gap_HVS_Tr], the
gap zero-sequence overvoltage protection will be released.
When the maximal value of three-phase differential currents of step-down transformer is greater
than the pickup setting of percentage differential protection of step-down transformer, the
percentage differential protection of step-down transformer will be released.
When the maximal value of three-phase current is greater than its setting value, the overcurrent
protection at HV side of step-down transformer will be released.
When the maximal value of three-phase current is greater than its setting value, the overcurrent
protection at branch 1 of LV side of step-down transformer will be released.
When the maximal value of three-phase current is greater than its setting value, the overcurrent
protection at branch 2 of LV side of step-down transformer will be released.
When the zero-sequence current is greater than its setting value, the zero-sequence overcurrent
protection at branch 1 of LV side of step-down transformer will be released.
When the zero-sequence current is greater than its setting value, the zero-sequence overcurrent
protection at branch 2 of LV side of step-down transformer will be released.
The fault detector operates when measured U/F is greater than definite time setting.
The fault detector operates when over excitation inverse time accumulated value is greater than
inverse time setting.
In following logic diagrams, all logic inputs starting with “En_xx” represent enabling logic settings
which will be explained in later section, all logic inputs starting with “EBI_xx” represent enabling
binary inputs from panel, those starting with “Flg_xx” represent internally generated flags
indicating whether or not a certain element is met, those words begin with “Alm_xx” and “Op_xx”
represent output for alarming and operation of protective element respectively.
During the normal operation, the magnitude and angle of secondary currents at each side of
transformer are different due to different CT ratios, different voltage levels and different
transformer connection groups. This kind of current differentiations shall be eliminated under
normal operation and compensated in fact by a built-in compensation method.
Sn
I b1n = (Equation 3.3-1)
3U b1n
Where:
U b1n is the rated phase-to-phase voltage at the calculated side of the transformer (i.e.
[U1n_HVS_Tr] or [U1n_LVS_Tr])
I b1n
Ib2n = (Equation 3.3-2)
nbLH
Where:
I b 2 n −b
K ph = (Equation 3.3-3)
I b 2n
Where:
The currents used in the following analysis have been corrected, that means the currents are the
products of the original secondary current of each side multiplying its own correction coefficient
( K ph ).
By defining which particular connection group the protected transformer belongs to, the proper
calculation routine will be applied.
3. The positive polarity of CT at HV and MV side is at busbar side and that at LV side is at
branch side or generator side.
4. Polarity of each secondary winding of CT is as same as shown in Figure 1.3-1 and Figure
1.3-2.
The secondary current phase shift compensation for all CTs are achieved by software, Y→Δ
transform method is used for this purpose. For connection Y/Δ-11, the correction equations are as
follows:
At side Y0:
⎧ •' • •
⎪I A = (I A − I B ) / 3
⎪ •' • •
⎨ I B = ( I B − I C)/ 3 (Equation 3.3-4)
⎪ '
• • •
⎪I C = ( I C − I A ) / 3
⎩
At side Δ:
⎧•' •
⎪ I• a = I a
⎪' •
⎨I• b = I b (Equation 3.3-5)
⎪ ' •
I c = Ic
⎪
⎩
Where:
• • •
I A , I B , I C are the secondary currents of CT at side Y
• • •
I A , I B , I ' C are the corrected current of each phase at side Y
' '
• • •
I a , I b , I c are the secondary currents of CT at side Δ
• • •
I ' a , I ' b , I ' c are the corrected currents of each phase at side Δ
For other connection type,the current can be calculated according to the equations listed above.
The connection type can be selected by following logic settings [Yd11_Conn] and [Yyd11_Conn]
(refer to system parameters in section 6.3).
Note!
If your actual transformer connection group is not included in above two groups, please let
us know before you make the order.
Id
Restraint area
Icdqd Kbl1
0
Ie nIe Ir
⎧ I1 + I 2 + I 3 + I 4 + I 5
⎪⎪ I r =
2
⎨ • • • • •
⎪I = I 1 + I 2 + I 3 + I 4 + I 5
⎪⎩ d
Where:
I d is differential current
I r is restraint current
I e is rated current
K bl1 is the first slope of percentage differential with setting range 0.05~0.15. 0.10 is applicable
usually
K bl 2 is the second slope of percentage differential with setting range 0.50~0.80. 0.70 is applicable
usually
Note!
For differential current of step-down transformer, I1, I2 and I3 are currents of HV side,
branches 1 or branch 2 at LV side of step-down transformer respectively. I4 has no
definition yet.
For differential current of excitation transformer, I1 and I2 are currents of HV side and LV
side respectively. I3 and I4 have no definition yet.
A percentage differential protection with high percentage and high setting is equipped with the
equipment to prevent delayed operation of percentage differential protection caused by CT
saturation and other factors during serious internal fault. This protection is blocked only by inrush
current criterion i.e. second harmonic of differential current or waveform discrimination. It can
prevent influence of steady state and transient CT saturation during external fault and can operate
correctly and quickly during internal fault even if CT is in saturation condition. Operation criterion
of this high setting percentage differential protection is:
⎧I d > 1.2 × I e
⎨ (Equation 3.3-7)
⎩I d > 1.0 × I r
Where:
When fault occurs, the operation criterion will be discriminated phase by phase and percentage
differential protection will operate if the criterion is met. For more detailed operation characteristic
please see Figure 3.3-3.
Note!
Parameters of this protection have been fixed in program and do not need to be
configured by user.
The aim of unrestrained instantaneous differential protection for transformer is to accelerate the
trip speed for transformer’s inner fault. So the element does not need any block element, but the
setting should be greater than maximum inrush current.
Where:
Note!
All the settings mentioned below are from main transformer for example. Figure 3.3-3
shows operation characteristic of unrestrained instantaneous differential protection.
1. Steady state percentage differential protection element (refer to section 3.3.2.1) will not send
tripping signal in case of CT saturation, CT circuit failure (optional), inrush current and
overexcitation condition. It can ensure sensitivity of protection and avoid unwanted operation
when CT is saturated during external fault. Its operation area is tint shadow area.
2. High setting percentage differential protection element (refer to section 3.3.2.2) will not send
tripping signal only due to CT circuit failure (optional) and inrush current. It eliminates
influence of transient and steady saturation of CT during external fault and ensures reliable
operation even if CT is in saturation condition during internal fault by means of its percentage
restraint characteristic. Its operation area is deep shadow area.
3. Unrestrained instantaneous differential protection element (refer to section 3.3.2.3) will send
tripping signal without any blocking if differential current of any phase reaches its setting. Its
operation area is over the above two areas with no shadow.
In the equipment, the second harmonic of differential current can be used to distinguish inrush
current. Its operation criterion is:
Where:
is recommended
During internal fault, differential currents of various sides transferred by CT are basically
fundamental sinusoidal wave. But when the transformer is energized, lots of harmonics occur.
The waveform is intermittent and unsymmetrical. A special algorithm can be used for
discrimination of the inrush current.
⎧S > kb*S +
⎨ (Equation 3.3-10)
⎩S > St
Where:
S + is full cycle integral of the sum of instantaneous value of differential current and that of half
cycle before
kb is a fixed constant
Where:
α is a proportional constant.
If any one of three phases can not meet above equation, the differential current can be considered
as inrush current and percentage differential relay will be blocked.
In this protection equipment, logic setting [Opt_Inrush_Ident_Tr] is provided for user to select the
restraint blocking principle. If the logic setting is set as “0”, discrimination by harmonics is enabled.
Otherwise, discrimination by waveform distortion is enabled.
In order to prevent unwanted operation of steady state percentage differential protection caused
by transient or steady state saturation of CT during external fault, composite harmonics of
secondary differential current is used for the protection equipment to discriminate saturation of CT.
The expression is as following:
Where:
When fault occurs, if DPFC of restraint current and DPFC of differential current appear
simultaneously, this is an internal fault. If DPFC of restraint current appears before DPFC of
differential current, this maybe an external fault and criterion of CT saturation shall be adopted in
this case. So unwanted operation of percentage differential protection due to CT saturation can be
prevented.
3.3.2.7 Differential Current Abnormality Alarm and CT Circuit Failure Blocking Function
Differential current abnormality alarm with percentage restraint (refer to section 4.1.3.2) and
instant CT circuit failure blocking function are equipped with the equipment.
When a transformer is overexcited, the exciting current will increase sharply which may result in
unwanted operation of differential protection. Therefore the overexcitation shall be discriminated
to block the current differential protection. The fifth harmonic of differential current is used as
Where:
Note!
[Flg_UIDP]
[En_InstDiff_Tr]
[FD_Diff_Tr]
[Flg_Inrush_Tr]
[Flg_HSDP_Tr]
&
[EBI_Diff_Tr] & &
[En_PcntDiff_Tr]
[Flg_CTS]
[FD_Diff_Tr]
[Flg_CTsat] ≥1 [Op_PcntDiff_Tr]
[Flg_Inrush]
[Flg_SPDP_Tr]
& & &
[EBI_Diff_Tr]
[En_PcntDiff_Tr]
[Flg_CTS]
[Flg_OvExc_Tr]
[FD_Diff_Tr]
The above logic diagram is also suit for differential protection of step-down transformer.
Where:
[Flg_UIDP _Tr] is the flag indicating whether or not the criterion of UIDP element is met.
[Flg_HSDP _Tr] is the flag indicating whether or not the criterion of HSDP element is met.
[Flg_SPDP _Tr] is the flag indicating whether or not the criterion of SPDP element is met.
[Flg_Inrush] is the flag indicating whether or not the criterion of inrush current detection is met.
[Flg_OvExc_Tr] is the flag indicating whether or not the transformer is in overexcitation state.
Where:
ΔI dt is floating threshold which increases progressively along with DPFC increasing. Take its
multiple as 1.25 can ensure threshold voltage always a bit higher than imbalance current. So that
unwanted operation of the equipment can be avoided during power swing and frequency
deviation conditions.
Generally, for differential protection of main transformer, ΔI1 , ΔI 2 , ΔI 3 and ΔI 4 are DPFCs of
currents of sides 1 and 2 at HVS of main transformer, generator terminal and HV side of
step-down transformer respectively. But for some specific design, ΔI1 can represent the HVS
For differential protection of generator, ΔI1 and ΔI 2 are currents at the terminal of generator
Note!
DPFC differential protection is equipped to each phase of generator, but user should know
that the restraint DPFC quantity for every phase is the same maximum value among the
three phases.
ΔId
0.75
0.6
Icdqd
restraint current
2 Ie ΔIr
When fault occurs, the operation criterion will be discriminated phase by phase and percentage
differential protection will operate if the criterion is met. For DPFC percentage differential
protection of main transformer, second harmonic or waveform inrush current blocking and fifth
harmonic over excitation blocking are adopted. It can prevent influence of steady state and
transient CT saturation during external fault due to its percentage restraint characteristic.
This protective element has high ability to eliminate the effect of transient and steady saturation of
CT during the external fault because the restraint coefficient is set at a higher value.
[Flg_DPFC_Diff_Tr]
0 20
& &
[EBI_Diff_Tr]
& [Op_DPFC_Diff_Tr]
[En_Diff_Tr]
[En_DPFC_Diff_Tr]
[Flg_InstanCTS]
0 500
[FD_DPFC_Diff_Tr]
Where:
[Flg_DPFC_Diff_Tr] is the flag indicating whether or not the criterion of DPFC differential element
is met.
[EBI_Diff_Tr]: is enabling binary input for all kinds of differential protection of generator.
[En_Diff_Tr]: general logic setting for enabling differential protection of generator.
[Flg_IntanCTS] is the internally generated flag indicating that CT supervision program detects
failure of CT circuit with no delay considered into account.
Settings of DPFC percentage differential protection is are fixed and need not to be set on site.
Figure 3.3-7 shows operation characteristic of impedance element. In this figure, I is phase
current, U is corresponding phase-to-phase voltage, Zn is reverse impedance setting, Zp is
forward impedance setting.
jX
I Zp
U I Zp
m
U
R
U I Zn
I Zn
Operation criterion:
• •
(U − I Z P )
90 < Arg
o
• •
< 270o (Equation 3.3-15)
(U + I Z n )
The fault detector of impedance protection adopts DPFC of phase current and negative sequence
current. Initiation of the fault detector will be lasted for 500 ms and will be kept if impedance relay
operates during this time interval. Operation criterion of the fault detector is
Where:
ΔI t is floating threshold which increases progressively along with DPFC increasing. Take its
multiple as 1.25 can ensure threshold current always a bit higher than imbalance current. So that
unwanted operation of the equipment can be avoided during system swing and frequency
deviation conditions.
I th is the fixed threshold. When DPFC of phase-to-phase current is higher than 0.3 Ie, the fault
detector operates.
The impedance protection will be disabled automatically if the VT circuit failure is discriminated.
[Flg_VTS ]
[Flg_Z1_Tr] &
&
[En_PPF_Tr]
t
& [Op_Z1_Tr]
[EBI_PPF_Tr ]
[FD_PPF_Tr]
Where:
[Flg_Z1_Tr] is internally generated flag indicating whether or not zone 1 of impedance protection
of transformer operates.
[Flg_VTS] is flag indicating whether or not the VT circuit fails. “1” means failure.
Function of overcurrent protection with composite voltage blocking is equipped with RCS-985BT.
This protection, consisting of 2 stages and 2 time delays per stage, is used for phase-to-phase
backup protection of main transformer. Of which, function of composite voltage element can be
enabled or disabled by logic setting.
The voltage control element is an element which will operate if phase-to-phase voltage is lower
than the setting [Vpp_UV_VCE_Tr] or negative sequence voltage is greater than its setting
[V_NegOV_VCE_ Tr].
Criteria:
Where:
All two stages of definite time overcurrent protection can be controlled by voltage element by
configuring related logic settings [En_VCE_Ctrl_OC1_Tr] and [En_VCE_Ctrl_OC2_Tr].
Meanwhile, User can decide by which side voltage overcurrent protection is controlled by
configuring related settings. For example, if the setting [En_LVS.VCE_Ctrl_OC_Tr] is set as “1”,
then the overcurrent protection is controlled not only by HV side voltage element but also by LV
side voltage element.
For self and parallel-excited generator, current will decrease so quick during fault that it may be
lower than overcurrent setting before tripping. So memorizing function for fault current is equipped
with this protection. Logic setting [En_Mem_Curr_Tr] is used for configure of this function.
Note!
When VT on one side is under maintenance or bus-tie breaker is used for the transformer but its
VT has not been switched over to the protection equipment, VT circuit failure is detected. Logic
setting [Opt_VTS_Ctrl_OC_Tr] is used to configure performance of voltage control element during
VT circuit failure. When this logic setting is set as “1”, if VT circuit failure is detected, the voltage
control element cannot pick up and the protection will not operate. When this logic setting is set as
“0”, if VT circuit failure is detected on this side, voltage control element is forced to be satisfied,
then the voltage controlled directional overcurrent protection controlled by voltage will becomes a
pure overcurrent protection.
Upp< [Vpp_VCE_Tr]
≥1
U2>[V_NegOV_VCE_ Tr] &
[Flg_VCE_Tr]
[Flg_VTS] ≥1
&
[Opt_VTS_Ctrl_OC_Tr]
&
[En_Mem_Curr_Tr]
[Flg_OC _Tr] ≥1
& [Op_OC _Tr]
[Flg_VCE_Tr] & t
≥1
[En_VCE_Ctrl_OCn_Tr]
[t_OC _Gen]
[En_PPF_Tr]
&
[EBI_PPF_Tr]
[FD_OC _Tr]
Where:
[Flg_VTS]: is the internally generated flag indicating whether or not the VT circuit fails.
[Opt_VTS_Ctrl_OC_Tr] is the setting to configure the VCE mode under VT circuit failure.
[Op_OCn_Tr] indicates that whether or not the stage n of overcurrent protection operates.
Zero-sequence overcurrent relay is mainly used as backup protection of ground fault for
transformer with neutral point earthed. Two stages and four time delays zero-sequence
overcurrent protection is equipped with RCS-985BT. The zero-sequence current is usually
adopted from neutral point CT.
By setting logic settings, following functions of any stages of this protection can be selected:
1. Direction element
The direction of zero sequence overcurrent protection points to system definitely with the reach
angle 75º. If the VT failure at HV side occurs, the directional element will be out of service.
The voltage used by directional relay is definitely the calculated voltage. The direction mentioned
above is based on the CT positive polarity for calculated zero sequence current being at the side
of busbar. The details are shown in Figure 1.3-1 and Figure 1.3-2.
Figure 3.3-10 shows operating characteristic of directional protection in which the hatched area is
operation zone.
3U0
φlm = 75°
Io
Point to system
Where:
[Flg_Dir_ROC_Tr] is flag indicating that whether or not the criterion of directional element is met.
[Flg_ROCn_Tr] is flag indicating that the zero sequence current is above the setting.
[EBI_EF_Tr] is the binary input to enable/disable the earth fault protection of transformer.
[Op_ROCn_Tr] indicates that the stage n of zero sequence overcurrent protection operates.
Gap zero-sequence overcurrent protection is used for backup protection of main transformer with
neutral point grounded through gap or small reactance. Gap zero-sequence overvoltage
protection is used for backup protection of main transformer with neutral point ungrounded or
grounded through gap or small reactance.
RCS-985BT provides one stage definite-time gap zero-sequence overcurrent protection and one
stage definite-time gap zero-sequence overvoltage protection.
During the gap broken down, gap zero-sequence overcurrent and gap zero-sequence overvoltage
will appear alternatively. Once gap zero-sequence overcurrent protection or gap zero-sequence
overvoltage operates, the protection device will keep the operating signal interactively so that the
protection device can operate reliably.
Gap zero-sequence overcurrent and overvoltage protection can be enabled by enabling binary
input from the protection panel as well as external contact input. If the setting
[En_BI_Ctrl_EF_Gap_HVS] is set as “0”, the gap zero-sequence overcurrent and overvoltage
protection are controlled by the enabling binary input [EBI_EF_Gap_Tr] only. If the setting
[En_BI_Ctrl_EF_Gap_HVS] is set as “1”, the gap zero-sequence overcurrent and overvoltage
protection are enabled only when both the enabling binary input [EBI_EF_Gap_Tr] is energized
and binary external input [BI_Ext_Ctrl_EF_Gap_Tr] is “1”.
According to the case that circuit breaker is equipped at the terminal of generator, a
zero-sequence voltage alarm can be provided on LV side of main transformer as the supervision
of earthing fault. The voltage setting is usually set as 10V~15V. The alarm can be enabled or
disabled by logic setting [En_Alm_ROV_LVS_Tr]. The function outputs alarm signals.
Some protection functions, such as overload alarm, initial cooling and overcurrent output, are
equipped with backup protection of HV side of main transformer. Overload alarm, initial cooling
and overcurrent output can be enabled or disabled by corresponding logic settings. After the initial
cooling operates, it will output two normally open contacts. After overcurrent output operates, it
will output a normally open contact and a normally closed contact.
One stage for trip purpose and one stage for alarm purpose are equipped for definite-time
over-excitation protection. Their time delay can be configured independently.
Where:
Upu and Fpu are per unit value of voltage and frequency respectively.
Figure 3.3-13 shows logic diagram of definite time over excitation protection.
The over excitation multiple settings n (= U/F) are within range of 1.0~1.5 in general. Maximum
time delay t is considered as long as 3000s. Relation between various settings of n and t are:
n0 ≥ n1 ≥ n2 ≥ n3 ≥ n4 ≥ n5 ≥ n6 ≥ n7
t0 ≤ t1 ≤ t2 ≤ t3 ≤ t4 ≤ t5 ≤ t6 ≤ t7
[En_OvExc_Tr]
t Alm_OvExc_Gen
&
U/F > [k_Alm_OvExc_Tr]
[t_Alm_OvExc_Gen]
U/F > [k_OvExc_Gen]
& t Op_OvExc_Gen
[En_OvExc_Tr] &
[t_OvExc_Gen]
[TrpLog_OvExc_Tr].Bit0
&
[EBI_OvExc_Tr]
[FD_OvExc_Tr]
The current used by breaker flashover protection is from breaker CT at HV side of main
transformer. Its criterion is:
3. Excitation has been applied to generator, and generator voltage is greater than the setting
After this protection operates, it will shut off excitation and initiate breaker failure protection.
Take the first time delay of stage 1 of circuit breaker A as an example. The logic diagram of
breaker flashover protection is shown in Figure 3.3-15.
Where:
The current criterion of breaker failure initiation (BFI) in RCS-985 can be one of three elements:
phase overcurrent element, zero-sequence current element or negative-sequence current
element.
Figure 3.3-16 shows logic diagram of breaker failure initiation. Take circuit breaker A as an
example.
[BI_52b_CB_HVS1_Tr]
≥1
En_CB_Ctrl_BFP_CB_HVS_Tr
[BI_ExtTrp_Ctrl_BFP]
≥1
[En_ExtTrp_Ctrl_BFP_CB_HVS_Tr]
I>[I_BFP1_CB_HVS_Tr]
I2>[I_NegOC1_BFP_CB_HVS_Tr] &
[t_BFP11_CB_HVS_Tr]
& ≥1 &
[En_NegOC_Ctrl_BFP_CB_HVS_Tr] & t Op_BFP11_CB1_HVS_Tr
3I0>[I_ROC_BFP1_CB_HVS_Tr]
&
[En_ROC_Ctrl_BFP_CB_HVS_Tr] t Op_BFP12_CB1_HVS_Tr
[t_BFP12_CB_HVS_Tr]
[En_BFP_CB_HVS]
&
[EBI_BFP_CB_HVS_Tr]
[FD_BFP/Flash_CB_HVS_Tr]
For internal fault of windings at HV side of main transformer, the protection device provides
percentage winding differential protection. The operation characteristic is shown in Figure 3.3-17.
Percentage winding differential protection can clear phase-to-phase fault and earth fault of
winding and outgoing line.
Ifd
Ifcdsd
kfbl
Ifcdqd
0
It Ifr
⎧ I >I
⎪ fd fcdqd
⎪ I > K ×I
⎪ fd fbl fr
⎪
⎪ I fh + I fw
⎨I =
⎪ fr 2
⎪
⎪ • • (Equation 3.3-19)
⎪ I fd = I fh + I fw
⎪
⎩
Where:
Ifh and Ifw are the currents of breaker CT at HV side of main transfer and winding CT at HV side
of main transformer respectively
These criteria are checked phase by phase, the winding differential protection will operate if
above equation is met. The polarity mark of breaker CT at HV side of main transformer should be
at busbar side and the polarity mark of winding CT at HV side of main transformer should be at
opposite side of neutral point of main transformer, otherwise, the above description will be
different with practical situation.
When differential current of any phase is greater than the setting [I_InstWdgDiff_Tr], the
protection device will operate to trip immediately
3.3.8.3 Differential Current Abnormality Alarm and CT Circuit Failure Blocking Function
Differential current abnormality alarm with percentage restraint (refer to section 4.1.3.2) and
instant CT circuit failure blocking function are equipped with the protective device.
[Flg_UIWDP]
&
[En_InstWdgDiff_Tr] & Op_InstWdgDiff_Tr
[Flg_PWDP]
&
[En_PcntWdgDiff_Tr]
&
[Flg_CTsat] & Op_PcntWdgDiff_Tr
[En_WdgDiff_Tr]
&
[EBI_WdgDiff_Tr] &
[FD_WdgDiff_Tr]
Where:
[Flg_UIWDP] is the flag indicating whether or not the criterion of UIWDP is met.
[Flg_PWDP] is the flag indicating whether or not the criterion of PWDP is met.
[EBI_WdgDiff_Tr]: binary input for enabling winding differential protection of main transformer
[En_WdgDiff_Tr]: logic setting for enabling winding differential protection of main transformer
REF is used for earth fault at HV side of main transformer (wye connection). When REF is formed
by the calculated zero-sequence current at HV side and the measured zero-sequence current at
neutral point, its operation criteria are as follows:
⎧I 0d > I 0 cdqd
⎪I > K 0b1 × I 0 r
⎪⎪ 0 d
⎨I 0r = max{ I 01 , I 02 , I 0 n } (Equation 3.3-20)
⎪ • • •
⎪I 0d = I 01 + I 02 − I 0 n
⎪⎩
Where:
When REF is formed by the calculated zero-sequence current at HV side and the calculated
zero-sequence current at neutral point, its operation criteria are as follows:
⎧ I 0d > I 0cdqd
⎪
⎪ I 0d > K 0b1 × I 0r
⎪⎪ I 0r = max{ I 01 , I 02 , I 0n }
⎨
⎪ • • • (Equation 3.3-21)
⎪ I 0d = I 01 + I 02 + I 0n
⎪
⎪⎩
Where:
For HV side of main transformer, there is only one branch I01 which is the sum of three-phase
currents derived from backup CT at HV side of main transformer, and other branches have no
definition.
The polarity mark of breaker CT at HV side of main transformer should be at busbar side and the
polarity mark of winding CT at HV side of main transformer should be at opposite side of neutral
point of main transformer, otherwise, the above description will be different with practical situation.
The polarity mark of CT at neutral point of main transformer should be at side of neutral point of
main transformer.
When equation above is satisfied, the percentage REF will operate. Figure 3.3-19 shows
operation characteristic of percentage REF.
The aim of unrestrained instantaneous REF for main transformer is to accelerate clearing the
transformer’s inner earth fault with high fault resistance. So the element does not need any block
element, but the setting should be greater than maximum inrush current.
This protection operates to trip all breakers at all sides of main transformer when any unrestrained
zero-sequence differential current is higher than its setting [I_InstREF_Tr]. Figure 3.3-19 shows
operation characteristic of this unrestrained instantaneous REF.
I0d
K0bl
I0cdqd
I0r
Ith
Where:
Ith will be automatically changed according to the pickup current [I_Pkp_PcntREF_Tr] and restrict
coefficient [Slope_PcntREF_Tr].
3.3.9.3 Differential Current Abnormality Alarm and CT Circuit Failure Blocking Function
Differential current abnormality alarm with percentage restraint (refer to section 4.1.3.2) and
instant CT circuit failure blocking function are equipped with the protective device.
When the bit3 implicit configuration setting [Cfg_REF_Tr] is set as “1”, it means that the
zero-sequence current of neutral point of main transformer is from the measured zero-sequence
current, and instant CT circuit failure will not be distinguished.
The logic scheme of REF for HV side of main transformer is shown in the following figure.
InstREF
&
[En_InstREF_Tr] & Op_InstREF_Tr
PcntREF
&
[En_PcntREF_Tr]
&
[Flg_CTsat] & Op_PcntREF_Tr
[EBI_REF_Tr]
&
[En_REF_Tr] &
[FD_REF_Tr]
Where:
[EBI_REF_Tr]: enabling binary input of REF of main transformer through closing the isolator link
Function of voltage controlled overcurrent protection for step-down transformer is equipped with
RCS-985BT. This protection, consisting of 2 stages and 1 time delay per stage, is used for
phase-to-phase backup protection of step-down transformer. Of which, function of composite
voltage element can be enabled or disabled by configuration of logic setting.
This protection, consisting of 2 stages and 1 time delay per stage, is used for phase-to-phase
backup protection of step-down transformer. Of which, function of composite voltage element can
be enabled or disabled by configuration of logic setting.
Two stages zero sequence current protection with delay used for tripping is equipped for LV side
of step-down transformer.
Overload alarm and initial cooling are equipped for backup protection of step-down transformer.
These functions can be set by logic settings. One normally open contact is used for output of
initial cooling.
4.1 Self-supervision
If hardware failure of the equipment itself is detected, protection functions of the equipment will be
blocked and equipment blocking alarm will be issued. Hardware failure includes those on RAM,
EPROM, settings, power supply, DSP and tripping coil.
When following abnormal status is detected, abnormal warning will be issued: AC voltage or
current circuit failure, persist pickup, mismatch state of pickup between CPU and DSP and alarm
of protection element.
The relay includes a number of self-monitoring functions to check the operation of its hardware
and software when it is in service. These are included so that if an error or fault occurs within the
relay’s hardware or software, the relay is able to detect and report the problem and attempt to
resolve it by performing a re-boot. This involves the relay being out of service for a short period of
time that is indicated by the “HEALTHY” LED on the faceplate of the relay being extinguished and
the watchdog contact at the rear operating. If the restart fails to resolve the problem, then the relay
will take itself permanently out of service. Again this will be indicated by the “ALARM” LED and
watchdog contact. If a problem is detected by the self-monitoring functions, the relay attempts to
store a maintenance record in battery backed-up SRAM to allow the nature of the problem to be
notified to the user.
The self-monitoring is implemented in two stages: firstly a thorough diagnostic check which is
performed when the relay is booted-up, e.g. at power-on, and secondly a continuous self-checking
operation which checks the operation of the relay’s critical functions whilst it is in service.
The integrity of the flash memory is verified using a checksum before the program code and data
stored in it is copied into SRAM to be used for execution by the processor. When the copy has
been completed the data then held in SRAM is compared to that in the flash to ensure that the two
are the same and that no errors have occurred in the transfer of data from flash to SRAM. The
entry point of the software code in SRAM is then called which is the relay initialization code.
The initialization process includes the operations of initializing the processor registers and
interrupts, starting the watchdog timers (used by the hardware to determine whether the software
is still running), starting the real-time operating system and creating and starting the supervisor
task. In the course of the initialization process the relay checks:
1. The integrity of the battery backed-up SRAM that is used to store event, fault and disturbance
records
3. The correctness of the settings that ensures relay’s proper response to fault
5. The voltage level of the field voltage supply which is used to drive the opto-isolated inputs
At the conclusion of the initialization software the supervisor task begins the process of starting the
platform software.
In starting the platform software, the relay checks the integrity of the data held in non-volatile
memory with a checksum. The final test that is made concerns the input and output of data, the
presence and healthy condition of the input board is checked and the analog data acquisition
system is checked through sampling the reference voltage.
At the successful conclusion of all of these tests the relay is entered into service and the protection
started-up.
1. The flash containing all program code, setting values and language text is verified by a
checksum
2. The code and constant data held in SRAM is checked against the corresponding data in flash
to check for data corruption
3. The SRAM containing all data other than the code and constant data is verified with a
checksum
5. The integrity of the digital signal I/O data from the opto-isolated inputs and the relay contacts
is checked by the data acquisition function every time it is executed. The operation of the
analog data acquisition system is continuously checked by the acquisition function every time
it is executed, by means of sampling the reference voltages.
In the unlikely event that one of the checks detects an error within the relay’s subsystems, the
platform software is notified and it will attempt to log a maintenance record in battery backed-up
SRAM. If the problem is of no importance (no possibility of leading to maloperation), the relay will
continue in operation. However, for problems detected in any important area the relay will initiate a
shutdown and re-boot. This will result in a period of up to 5 seconds when the protection is
unavailable, but the complete restart of the relay including all initializations should clear most
problems that could occur. As described above, an integral part of the start-up procedure is a
thorough diagnostic self-check. If this detects the same problem that caused the relay to restart, i.e.
the restart has not cleared the problem, and then the relay will take itself permanently out of
service. This is indicated by the “HEALTHY” LED on the front of the relay, which will extinguish,
and the watchdog contact that will operate.
If the alarm is issued, the alarm signal can be reset only when the failure is removed and the
equipment is reset by pressing “RESET” button on panel or re-power it up.
3. Overload alarm
On condition that the relay does not picks up, adding current in excess of the setting of overload
protection, alarm messages are displayed and “ALARM” LED is lit after the timer stage duration
has elapsed.
Tripping output relay driving transistor is always monitored in normal program, and blocking
message will be issued when the equipment finds abnormality of the tripping output circuit.
Where:
If the above criterion is met, CT circuit abnormality alarm will be issued with a time delay of 10s.
The abnormality alarm will be reset after 10s if the protective device returns to normal condition.
This function is enabled only when relevant differential protection logic setting is set as enabled. If
the criterion is met, the alarm will be sent by delay 10 s and corresponding differential protection
will not be blocked. When the differential current eliminates, the alarm will be reset by delay 10s.
In order to increase sensitivity of this alarm, percentage restraint differential current alarm criterion
is adopted as shown as below.
⎧ I d > I dbjzd
⎨ (Equation 4.1-2)
⎩I d > k bj × I res
If the differential current reaches its threshold and reaches differential alarm level of percentage
restraint factor multiplied by restraint current, the differential current alarm will be issued.
If internal fault occurs, at least one of following four conditions will be present:
2. Any phase current of a certain side increases after fault detector operating
3. Maximum phase current is greater than 1.2Ie after fault detector operating
If none of above four conditions occurs within 40ms after differential protection’s fault detectors
picks up, the protection treats it as CT circuit failure. If the corresponding logic setting is set as “1”,
the relevant differential protection will be blocked and alarm will be issued. If this logic setting is set
as “0”, the relevant differential protection will trip and alarm will be issued simultaneously.
If the alarm is issued, the signal can be removed only when the failure is removed and the
equipment is reset by manual.
of VT circuit supervision is to detect faults in the secondary circuits of VT and confirm whether VT
secondary circuit is in good condition. It can avoid influence on the operation of corresponding
protection functions which are based on voltage.
2. 3U2>8V
For VT at LV side and HV side of main transformer, when any of above conditions is met, VT circuit
abnormality alarm will be issued with a time delay of 10s. The abnormality alarm will be reset
automatically after 10s if the protective device returns to normal condition.
For VT at LV side of step-down transformer, when any of above conditions is met, VT circuit
abnormality alarm will be issued with a time delay of 10s. The abnormality alarm needs to be reset
manually if the protective device returns to normal condition.
25 Alm_CTS_LVS_Tr ● ● ●
26 Alm_CTS_Bak_HVS_Tr ● ● ●
27 Alm_CTS_Wdg_HVS_Tr ● ● ●
28 Alm_Diff_Tr ● ●
29 Alm_REF_Tr ● ●
30 Alm_WdgDiff_Tr ● ●
31 Alm_Diff_GTU ● ●
32 Alm_VTS_Br1_ST1 ● ● ●
33 Alm_VTS_Br2_ST1 ● ● ●
34 Alm_VTS_Br1_ST2 ● ● ●
35 Alm_VTS_Br2_ST2 ● ● ●
36 Alm_BO_OC_HVS_ST1 ● ●
37 Alm_BO_OC_HVS_ST2 ● ●
38 Alm_OvLd_ST1 ● ●
39 Alm_InitCool_OvLd_ST1 ● ●
40 Alm_OvLd_ST2 ● ●
41 Alm_InitCool_OvLd_ST2 ● ●
42 Alm_PM_DSP2_CPUBrd ●
43 Alm_CTS_Diff_ST1 ● ● ●
44 Alm_CTS_Diff_ST2 ● ● ●
45 Alm_CTS_HVS_ST1 ● ● ●
46 Alm_CTS_Br1_ST1 ● ● ●
47 Alm_CTS_Br2_ST1 ● ● ●
48 Alm_CTS_HVS_ST2 ● ● ●
49 Alm_CTS_Br1_ST2 ● ● ●
50 Alm_CTS_Br2_ST2 ● ● ●
51 Alm_Diff_ST1 ● ●
52 Alm_Diff_ST2 ● ●
53 Alm_RAM_CPUBrd ●
54 Alm_ROM_CPUBrd ●
55 Alm_EEPROM_CPUBrd ●
56 Alm_InvalidSetting ●
57 Alm_ModifiedSetting ●
58 Alm_PwrLoss_Opto ●
59 Alm_TripOutput ●
60 Alm_InnerComm ● ●
61 Alm_DSP_CPUBrd ●
62 Alm_PersistFD_CPUBrd ● ●
63 Alm_InconsistFD ● ●
64 Alm_Sample_CPUBrd ●
65 Alm_BI_CPUBrd ● ●
66 Alm_Reboot_CPUBrd ●
67 Alm_RAM_MONBrd ●
68 Alm_ROM_MONBrd ●
69 Alm_EEPROM_MONBrd ●
70 Alm_DSP_MONBrd ●
71 Alm_PersistFD_MONBrd ● ●
72 Alm_MONBrd ● ●
73 Alm_Sample_MONBrd ●
74 Alm_Reboot_MONBrd ●
at HV side of step-down
transformer is abnormal.
The DSP chip in CPU board Inform manufacturer for
12 Alm_PM_DSP1_CPUBrd
damaged. maintenance.
Alarm indicating the
differential current is
13 Alm_CTS_Diff_Tr abnormal in differential
protection of main
transformer.
Alarm indicating the
differential current is
14 Alm_CTS_REF_Tr abnormal in zero-sequence
Disable the link and
differential protection of main
check the secondary
transformer.
circuit. After clear the
Alarm indicating the
error, reset the relay.
differential current is
15 Alm_CTS_WdgDiff_Tr abnormal in winding
differential protection of main
transformer.
Alarm indicating secondary
circuit failure of CT in
16 Alm_CTS_Diff_GTU
differential protection of
generator-transformer unit.
Alarm indicating operation of
17 Alm_MechRly1
mechanical repeater 1.
Alarm indicating operation of
18 Alm_MechRly2 Treat according to
mechanical repeater 2.
specific application
Alarm indicating operation of
19 Alm_MechRly3 requirement.
mechanical repeater 3.
Alarm indicating operation of
20 Alm_MechRly4
mechanical repeater 4.
Alarm indicating power loss of Check if the power
21 Alm_PwrLoss_MechRly
mechanical relay. circuit of BI module is
Alarm indicating circuit of connected correctly with
22 Alm_Inconsist_MechRly
mechanical is abnormal. PWR module.
Alarm indicating secondary
circuit failure of CT at branch
23 Alm_CTS_HVS1_Tr
1 of HV side of main
transformer.
Check the metering and
Alarm indicating secondary
secondary circuit.
circuit failure of CT at branch
24 Alm_CTS_HVS2_Tr
2 of HV side of main
transformer.
25 Alm_CTS_LVS_Tr Alarm indicating secondary
4.2 Metering
The relay produces a variety of both directly and calculated power system quantities. These
measurement values are updated on a per half second basis and can be viewed in the menu
“VALUES” of the relay or via relay communication.
This relay is able to measure and display the following quantities as summarized:
Here are “VALUES” available in the relay for viewing of measurement quantities. All the
measurement quantities can be divided into CPU quantities or DSP quantities by their origin where
they are derived. These can also be viewed with RCSPC (see RCSPC User Manual) and are
shown below:
Note!
The quantities listed in following tables are to be displayed on LCD for RCS-985BT, but for
a certain application, some of these quantities may be eliminated due to the scheme user
required, so please look up the devices on site for actual quantities displayed.
Note!
The contents inside the first window are the default display seen by user entering this
submenu. User can navigate to the following items by scrolling the arrow keys on the
faceplate of the relay. What user meets similar to this case later can be dealt with in same
way.
transformer 1.
Phase angle between phase A and B, B and C, C and A of
3 φipp_CT_HVS_ST1 current derived from CT at HV side of step-down transformer
1.
Phase angle between phase A and B, B and C, C and A of
4 φipp_Br1_ST1
currents of Br1 side of step-down transformer 1.
Phase angle between phase A and B, B and C, C and A of
5 φipp_Br2_ST1
currents of Br2 side of step-down transformer 1.
Phase angle between phase A and B, B and C, C and A of
6 φvpp_Br1_ST1
voltages of Br1 side of step-down transformer 1.
Phase angle between phase A and B, B and C, C and A of
7 φvpp_Br2_ST1
voltages of Br2 side of step-down transformer 1.
main transformer.
Enabling binary input of earth fault protection of main
3 EBI_EF_Tr
transformer.
Enabling binary input of gap zero-sequence protection of main
4 EBI_EF_Gap_Tr
transformer.
Enabling binary input of restricted earth-fault protection of
5 EBI_REF_Tr
main transformer.
Enabling binary input of winding differential protection of main
6 EBI_WdgDiff_Tr
transformer.
Enabling binary input of breaker failure protection at HV side
7 EBI_BFP_CB_HVS_Tr
of main transformer.
Enabling binary input of over-excitation protection of main
8 EBI_OvExc_Tr
transformer.
Enabling binary input of breaker flashover protection at HV
9 EBI_Flash_CB_HVS_Tr
side of main transformer.
The real time clock within the relay provides the time tag to each event, to a resolution of 1ms. The
event records are available for viewing either via the front plate LCD or remotely, via the
communications ports (courier and Modbus versions only).
Local viewing on the LCD is achieved in the menu column entitled “REPORT”. This column allows
viewing of event and fault records and is shown by setting sequence No. of the event or fault
report by user. Refer to Chapter 7 for details of operation method.
Where “Record No.” means the sequence No. of the record which is generated by RCS-985BT
automatically. “Date: DD-MM-YY” and “Time: HH:MM:SS:MS” commonly comprise the absolute
time tag of the record. “Binary input name” shows the name of the binary input whose state
changes. “Changing manner” shows how to change of the state of the binary input. For instance:
All the binary input that may be shown in the menu can be found in section 4.3, here list them
again.
The above figure shows the abbreviated description that is given to the various alarm conditions
and also a corresponding value between 0 and 31. This value is appended to each alarm event in
a similar way as for the input events previously described. It is used by the event extraction
software, such as RCSPC, to identify the alarm and is therefore invisible if the event is viewed on
the LCD.
The following table shows all of the alarm elements that may be displayed in this item.
Where:
“Record No.” means the sequence No. of the record which is generated by RCS-985BT
automatically. “Date: YYYY-MM-DD” and “Time: HH:MM:SS:MS” commonly comprise the absolute
time tag of the record. “Operation element” shows the name of the operation element. If there are
more than one elements operating, they will scroll one by one to display on LCD. “xxx ms” shows
the relative time of operation element to fault detector of the relay.
The following table lists all the operation elements that may be displayed on LCD.
The MON board can store up to 4 seconds (24 sampling points per cycle) or 8 seconds (12
sampling points per cycle) continual waveform, which including all channels analog quantities
(sampled data, differential currents and so on), all the binary input changing state, binary output,
pick up flags of fault detectors, alarm signals, operation signals and tripping signals. Disturbance
records continue to be recorded until the available memory is exhausted, at which time the oldest
record(s) are overwritten to make space for the newest one.
It is not possible to view the disturbance records locally via the LCD; they must be extracted using
suitable software such as RCSPC.
The CPU board can also record latest 8 cycles of waveform in normal operation condition, which is
composed of three phases current, corrected current of each side for differential protection, three
phases voltage and zero sequence voltage of each side. This function can help user to check the
pole’s correctness of secondary circuit by comparing the phase of related quantities shown in
wave figure. This manual gives the detail instruction of getting normal operation waveform in
section 7.3.
The protection’s hardware is based on a modular design whereby the relay is made up of an
assemblage of several modules that are drawn from a standard range. Some modules are
essential while others are optional depending on the user’s requirements.
The case materials of the relay are constructed from pre-finished steel that has a conductive
covering of aluminum and zinc. This provides good earthing at all joints giving a low impedance
path to earth that is essential for performance in the presence of external noise.
The boards and modules use a multi-point earthing strategy to improve the immunity to external
noise and minimize the effect of circuit noise. Ground planes are used on boards to reduce
impedance paths and spring clips are used to ground the module metalwork. Heavy duty terminal
blocks are used at the rear of the relay for the current and voltage signal connections. Medium
duty terminal blocks are used for the digital logic input signals, the output relay contacts, the power
supply and the rear communication port. A BNC connector may be used for the optional IRIG-B
signal. 9-pin female D-connector is used at the front of the relay for data communication.
Inside the protection the PCBs plug into the connector blocks at the rear, and can be removed
from the rear of the relay only. The connector blocks to the relay’s CT inputs are provided with
internal shorting links inside the relay which will automatically short the current generator circuits
before they are broken when the board is removed. The front panel consists of a membrane
keypad with tactile dome keys, an LCD and 5 LEDs mounted on an aluminum face plate.
Components mounted on its front include a 320×240 dot matrix LCD, a 9 button keypad, 5 LED
indicators and a DB9 connector for communication with HELP-90A or PC.
As to the buttons of the keypad, “ENT” is “enter”, “GRP” is “setting group selector” and “ESC” is
“escape”.
C P L D
output
HMI CPU1 relay
LCD
CPU module
HMI-CPU
QDJ
comm ports and
port to printer
E+
HMI
DSP3 opto-
binary status
LPF A/D coupler input
DSP4
D C 220 V
or 110 V
+ 5V
C P L D
DC/DC
± 12 V
+ 24 V
HMI CPU2
± 24 V to
optic-coupler management module
The equipment RCS-985BT uses Motorola 32 bits monolithic microprocessor MC68332 as control
kernel for output logic and management functions, and high-speed digital signal processor DSP for
protection calculation. Sampling rate of the equipment is 24 points per cycle. Real time data are
processed parallel for all algorithms during whole process of fault. So the equipment can ensure
very high inherent reliability and security.
AC currents and voltages of CT and VT are transferred to low voltage signals by isolating
transformers and are inputted to CPU module and MON module. Data and logic are processed
respectively in these two modules with same hardware. The CPU module carries out functions of
protection algorithms, tripping logic, event record and printing. The MON module comprises
general fault detector and fault recorder. The fault detector will connect positive pole of power
supply of output relays after pickup. Format of the record is compatible with COMTRADE, and the
data recorded can be uploaded via separate serial port for communication or printing.
AC current and voltage are converted to low voltage signals in modules AI1, AI2, AI3 and AI4. Two
ratings of AC current are option, 1A or 5A. It shall be stated definitely during ordering and checked
during commissioning.
Binary output of tripping commands, tripping signal output and status binary input parts are
comprised in five modules: SIG1, SIG2, SIG3, SIG4 and RLY. 24V and 250/220/125/110V
Briefly, the equipment is composed of twelve modules to achieve the work of generator or
generator-transformer unit protection. The modules are AC voltage and current input module1
(AI1), AC current input modules (AI2, AI3 and AI4), management/record module (MON), protection
CPU module (CPU), power supply module (PWR), signal modules (SIG1, SIG2, SIG3 and SIG4),
tripping contacts output (RLY) and human machine interface (HMI).
The relay hardware is based on a modular design whereby the relay is made up of an assemblage
of several modules.
Connectors with 30 pins are used for DC power supply, binary input, communication and printer,
tripping, alarm and other signal output and AC voltage input. Numbers of these connectors are 1A,
1B, 2A, 2B, 3A, 3B, 4A, 4B, 5B, 6B, 7B, 8B, 9B and 10B.
Connectors with 18 pins are used for AC voltage input and current input. Numbers of these
connectors are 9C, 10C, 11B, 11C, 12B and 12C.
For showing the relation of each terminal clearly, the terminal’s location shown in the figure may be
different from the real physical location, and we needn’t figure out the blank terminals.
transformer 1 tripping
backup protection of branch1 at LV side of step-down
3A4-3A22 BO_Bak_Br1_ST1
transformer 1 tripping
backup protection of branch1 at LV side of step-down
3A4-3A28 BO_Bak_Br1_ST2
transformer 2 tripping
Binary output of event recorder
3A5 common terminal 1 Local signal: common terminal 1
earth-fault protection of branch1 at LV side of
3A5-3A11 BO_EF_Br1_ST1
step-down transformer 1 tripping
earth-fault protection of branch1 at LV side of
3A5-3A17 BO_EF_Br1_ST2
step-down transformer 2 tripping
earth-fault protection of branch2 at LV side of
3A5-3A23 BO_EF_Br2_ST1
step-down transformer 1 tripping
earth-fault protection of branch2 at LV side of
3A5-3A29 BO_EF_Br2_ST2
step-down transformer 2 tripping
3A6 common terminal 2 common terminal 2
step-down transformer 1 differential protection
3A6-3A12 BO_Diff_ST1
tripping
backup protection at HV side of step-down
3A6-3A18 BO_Bak_HVS_ST1
transformer 1 tripping
backup protection of branch1 at LV side of step-down
3A6-3A24 BO_Bak_Br1_ST1
transformer 1 tripping
backup protection of branch1 at LV side of step-down
3A6-3A30 BO_Bak_Br1_ST2
transformer 2 tripping
+ _
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
+24V
0V
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
+ _
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
DC/DC
+24V 0V
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Communication port
7B1/8B1 RS485A
For GPS clock synchronizing
7B3/8B3 RS485B
7B5/8B5 RS485A
For SAS or RTU (first)
7B7/8B7 RS485B
7B9/8B9 RS485A
For SAS or RTU (Second)
7B11/8B11 RS485B
7B21/8B21 RS232TX
For printer
7B23/8B23 RS232RX
7B27/8B27 Ground of communication
7B30/8B30 Ground of chassis
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
U1A U1B U1C U1N U2A U2B U2C U2N U3A U3B U3C U3N
Voltage input
9B1
9B26
Blank
9B28
9B30
9B3 Zero-sequence voltage input at LV side of main transformer (polarity mark)
9B5 Zero-sequence voltage input at LV side of main transformer
9B7 Backup zero-sequence voltage input 1 (polarity mark)
9B9 Backup zero-sequence voltage input 1
9B11 Backup zero-sequence voltage input 2 (polarity mark)
9B13 Backup zero-sequence voltage input 2
9B23 Zero-sequence voltage input at HV side of main transformer (polarity mark)
9B25 Zero-sequence voltage input at HV side of main transformer
9B2 Phase A voltage input at LV side main transformer
9B4 Phase B voltage input at LV side main transformer
9B6 Phase C voltage input at LV side main transformer
9B8 Neutral point voltage input at LV side main transformer
9B10 Backup phase A voltage input
9B12 Backup phase B voltage input
9B14 Backup phase C voltage input
9B16 Backup neutral point voltage input
9B18 Phase A voltage input at HV side main transformer
9B20 Phase B voltage input at HV side main transformer
9B22 Phase C voltage input at HV side main transformer
9B24 Neutral point voltage input at HV side main transformer
Current input
9C1 IA’ , phase A of three-phase current input---channel 13
9C2 IA , phase A of three-phase current input---channel 13 (polarity mark)
9C3 IB’ , phase B of three-phase current input---channel 13
9C4 IB , phase B of three-phase current input---channel 13 (polarity mark)
9C5 IC’ , phase C of three-phase current input---channel 13
9C6 IC , phase C of three-phase current input---channel 13 (polarity mark)
9C7 IA’ , phase A of three-phase current input---channel 14
9C8 IA , phase A of three-phase current input---channel 14 (polarity mark)
9C9 IB’ , phase B of three-phase current input---channel 14
9C10 IB , phase B of three-phase current input---channel 14 (polarity mark)
9C11 IC’ , phase C of three-phase current input---channel 14
9C12 IC , phase C of three-phase current input---channel 14 (polarity mark)
9C13 3I0’, Zero-sequence current---channel 5
9C14 3I0, Zero-sequence current---channel 5 (polarity mark)
9C15 3I0’, Zero-sequence current---channel 6
9C16 3I0, Zero-sequence current---channel 6(polarity mark)
9C17 3I0’, Zero-sequence current---channel 7
9C18 3I0, Zero-sequence current---channel 7(polarity mark)
UA UB UA UB UA UB UA UB
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
UB UC UB UC UB UC UB UC
Voltage input
10B1 UA , phase A voltage from branch 1 of LV side VT of step-down transformer1
10B2 UB , phase B voltage from branch 1 of LV side VT of step-down transformer1
10B3 UB , phase B voltage from branch 1 of LV side VT of step-down transformer1
10B4 UC, phase C voltage from branch 1 of LV side VT of step-down transformer1
10B5 UA , phase A voltage from branch 2 of LV side VT of step-down transformer1
10B6 UB , phase B voltage from branch 2 of LV side VT of step-down transformer1
10B7, 10B8 Reserved
10B9 UB , phase B voltage from branch 2 of LV side VT of step-down transformer1
10B10 UC, phase C voltage from branch 2 of LV side VT of step-down transformer1
10B11 UA , phase A voltage from branch 1 of LV side VT of step-down transformer2
10B12 UB , phase B voltage from branch 1 of LV side VT of step-down transformer2
10B13 UB , phase B voltage from branch 1 of LV side VT of step-down transformer2
10B14 UC, phase C voltage from branch 1 of LV side VT of step-down transformer2
10B15-10B18 Reserved
10B19 UA , phase A voltage from branch 2 of LV side VT of step-down transformer2
10B20 UB , phase B voltage from branch 2 of LV side VT of step-down transformer2
10B21 UB , phase B voltage from branch 2 of LV side VT of step-down transformer2
10B22 UC, phase C voltage from branch 2 of LV side VT of step-down transformer2
10B23-10B30 Reserved
For RCS-985BT, the current and the voltage of rotor are not used, so this connector (10C) does
not need to be connected and only hardware circuit is reserved.
Current input
11B1 IA’ , phase A of three-phase current input---channel 7
11B2 IA , phase A of three-phase current input---channel 7 (polarity mark)
11B3 IB’ , phase B of three-phase current input---channel 7
11B4 IB , phase B of three-phase current input---channel 7 (polarity mark)
11B5 IC’ , phase C of three-phase current input---channel 7
11B6 IC , phase C of three-phase current input---channel 7 (polarity mark)
11B7 IA’ , phase A of three-phase current input---channel 8
11B8 IA , phase A of three-phase current input---channel 8 (polarity mark)
11B9 IB’ , phase B of three-phase current input---channel 8
11B10 IB , phase B of three-phase current input---channel 8 (polarity mark)
11B11 IC’ , phase C of three-phase current input---channel 8
11B12 IC , phase C of three-phase current input---channel 8 (polarity mark)
11B13 IA’ , phase A of three-phase current input---channel 9
11B14 IA , phase A of three-phase current input---channel 9 (polarity mark)
11B15 IB’ , phase B of three-phase current input---channel 9
11B16 IB , phase B of three-phase current input---channel 9(polarity mark)
11B17 IC’ , phase C of three-phase current input---channel 9
11B18 IC , phase C of three-phase current input---channel 9 (polarity mark)
Current input
11C1 IA’ , phase A of three-phase current input---channel 10
11C2 IA , phase A of three-phase current input---channel 10 (polarity mark)
11C3 IB’ , phase B of three-phase current input---channel 10
11C4 IB , phase B of three-phase current input---channel 10 (polarity mark)
11C5 IC’ , phase C of three-phase current input---channel 10
11C6 IC , phase C of three-phase current input---channel 10 (polarity mark)
Current input
12B1 IA’ , phase A of three-phase current input---channel 1
12B2 IA , phase A of three-phase current input---channel 1 (polarity mark)
12B3 IB’ , phase B of three-phase current input---channel 1
12B4 IB , phase B of three-phase current input---channel 1 (polarity mark)
12B5 IC’ , phase C of three-phase current input---channel 1
12B6 IC , phase C of three-phase current input---channel 1 (polarity mark)
12B7 IA’ , phase A of three-phase current input---channel 2
12B8 IA , phase A of three-phase current input---channel 2 (polarity mark)
12B9 IB’ , phase B of three-phase current input---channel 2
12B10 IB , phase B of three-phase current input---channel 2 (polarity mark)
12B11 IC’ , phase C of three-phase current input---channel 2
12B12 IC , phase C of three-phase current input---channel 2 (polarity mark)
12B13 IA’ , phase A of three-phase current input---channel 3
12B14 IA , phase A of three-phase current input---channel 3 (polarity mark)
Current input
12C1 IA’ , phase A of three-phase current input---channel 4
12C2 IA , phase A of three-phase current input---channel 4 (polarity mark)
12C3 IB’ , phase B of three-phase current input---channel 4
12C4 IB , phase B of three-phase current input---channel 4(polarity mark)
12C5 IC’ , phase C of three-phase current input---channel 4
12C6 IC , phase C of three-phase current input---channel 4 (polarity mark)
12C7 IA’ , phase A of three-phase current input---channel 5
12C8 IA , phase A of three-phase current input---channel 5 (polarity mark)
12C9 IB’ , phase B of three-phase current input---channel 5
12C10 IB , phase B of three-phase current input---channel 5(polarity mark)
12C11 IC’ , phase C of three-phase current input---channel 5
12C12 IC , phase C of three-phase current input---channel 5 (polarity mark)
12C13 3I0’ , zero-sequence current input---channel 1
12C14 3I0, zero-sequence current input---channel 1(polarity mark)
12C15 3I0’ , zero-sequence current input---channel 2
12C16 3I0, zero-sequence current input---channel 2(polarity mark)
12C17 3I0’ , zero-sequence current input---channel 3
12C18 3I0, zero-sequence current input---channel 3(polarity mark)
following figure. These tripping relays can be configured by tripping output logic setting, and
practical and flexible tripping modes can be provided by each protective function then. Tripping
output logic setting is a specific setting of each certain protective function. Please refer to Chapter
7 for details of setting.
The tripping output logic setting is a 4 digits hexadecimal number or a 16 bits binary number. Every
bit corresponds to a circuit breaker. The breaker will be tripped if the corresponding bit is set as “1”
and not tripped if the bit is set as “0”.
Outputs of TrpOutp1, 2, 5, 6 are instantaneous contacts, which can be used to trip CB or initial
failure of CB. While other outputs are expand 140ms after contacts operate.
Group 4
BO_Alm_InitCool1_OvLd_Tr BO_OC_HVS_ST1
4B09 4B11 2B20 2B22
BO_Alm_InitCool1_OvLd_Tr BO_OC_HVS_ST2
4B13 4B15 3B20 3B22
BO_Alm_InitCool1_OvLd_ST1 BO_Alm_OC1_HVS_Tr
4B17 4B19 4A27 4A29
BO_Alm_InitCool2_OvLd_ST1 BO_Alm_OC2_HVS_Tr
4B21 4B23 4A28 4A30
BO_Alm_InitCool1_OvLd_ST2 BO_Alm_InitCool2_OvLd_Tr
4B25 4B27 4B01 4B03
BO_Alm_InitCool2_OvLd_ST2 BO_Alm_InitCool2_OvLd_Tr
4B29 4B30 4B05 4B07
Chapter 6 Settings
6.1 Overview
The relay must be configured to the system and application by means of appropriate settings. The
settings of this relay include system parameters, protection element settings and scheme logic
settings.
Setting List
Note!
Symbols of the parameter listed in above table are used for communication, printing and
displaying on LCD.
Setting Description
1. Active_Grp
Two setting groups can be configured for the equipment, and only one is active at one time.
However, equipment parameters and system parameters are common for all protection setting
groups.
2. Equip_ID
The setting consists of ASCII codes, which is identification for report printing only. It can be
configured according to the name or number of generator.
3. Comm_Addr
The address used for the host computer to identify the equipment, usually provided by substation
system. If the equipment is not connected to automation system, equipment address may be
random.
4. COM1_Baud
The baud rate of serial port 1 shall be selected from specified range.
5. COMBaud
The baud rate of serial port 2 shall be selected from specified range.
6. Printer_Baud
The baud rate used for printer port shall be selected from specified range.
7. Protocol
The logic setting consists of 16 binary digits but four hexadecimal digits can be viewed through
device LCD screen. Every digit has a dedicated meaning and some digits have no definition.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
B: Modbus
B: LFP
A: Modbus
A: LFP
A: 103
The definitions of digits are:
Bit Definition
0 communication port A using protocol IEC 60870-5-103
1 communication port A using proprietary protocol LFP
2 communication port A using MODBUS protocol
3 No definition
4 No definition
5 communication port B using proprietary protocol LFP
6 communication port B using MODBUS protocol
7-15 No definitions
For example, if logic setting [Protocol] is set as “0041”, it means communication port A use IEC
60870-5-103 protocol, and port B use MODBUS protocol.
8. En_Auto_Print
This setting shall be set as “1” if automatic report printing is expected after the relay operates
when a fault occurs. Otherwise it shall be set as “0”. It is suggested that the user may set this
parameter of the equipment as “1” (i.e. automatic printing), if the equipment is always connected
directly with a printer, or set as “0” (i.e. not automatic printing) if the equipment is connected with a
printer by through switch on panel.
9. En_Net_Print
Set it as “1” if shared network printer is used for printing. Set it as “0” if dedicated printer is used.
Network printer means several protection equipments share one printer through a printer
management unit and RS-485 port. Dedicated printer means the protection equipment connected
with a printer through RS232 port directly.
10. En_Remote_Cfg
Set it as “0” if only local configuration is permitted. Set it as “1” if local and remote configurations
are both permitted.
11. GPS_Pulse
Set it as “1” for minute pulse and “0” for second pulse.
Access Path
Setting List
15 En_Bak_Br1_ST2 0/1
16 En_Bak_Br2_ST2 0/1
17 En_MechRly 0/1
18 En_TestMode(#) 0/1
Symbols of the parameter listed in above table are used for communication, printing and
displaying on LCD. Setting marked with “#” means that it is can not be seen on LCD or by printing
and only can be seen through RCSPC software.
Setting Description
1. En_Diff_Tr
2. En_REF_Tr
3. En_WdgDiff_Tr
This logic setting is used to enable/disable winding differential protection of main transformer.
4. En_PPF_Tr
This logic setting is used to enable/disable phase-to-phase fault protection of main transformer.
5. En_EF_Tr
6. En_OvExc_Tr
7. En_Flash_CB_HVS
This logic setting is used to enable/disable breaker flashover protection at HV side of main
transformer.
8. En_BFP_CB_HVS
This logic setting is used to enable/disable breaker failure protection at HV side of main
transformer.
9. En_Diff_ST1
10. En_Bak_HVS_ST1
This logic setting is used to enable/disable backup protection at HV side of step-down transformer
1.
11. En_Bak_Br1_ST1
This logic setting is used to enable/disable backup protection of branch 1 at HV side of step-down
transformer 1.
12. En_Bak_Br2_ST1
This logic setting is used to enable/disable backup protection of branch 2 at HV side of step-down
transformer 1.
13. En_Diff_ST2
14. En_Bak_HVS_ST2
This logic setting is used to enable/disable backup protection at HV side of step-down transformer
2.
15. En_Bak_Br1_ST2
This logic setting is used to enable/disable backup protection of branch 1 at HV side of step-down
transformer 2.
16. En_Bak_Br2_ST2
This logic setting is used to enable/disable backup protection of branch 2 at HV side of step-down
transformer 2.
17. En_MechRly
18. En_TestMode(#)
This logic setting is configured especially for equipment debugging status. It is only seen by
RCSPC, which is used for generating messages of alarm or operation element for remote PC.
“Enable”: enable sending all tripping contacts signals, protection tripping signals, alarm signals
and monitoring signals through the software RCSPC.
Access path
Setting List
Setting Description
1. Sn_Tr
2. U1n_HVS_Tr
System rated voltage at HV side of main transformer. This setting is used for calculating the rated
current of main transformer. It should be set according to the real operating voltage of the power
system
3. U1n_LVS_Tr
4. U1n_VT_HVS_Tr
5. U2n_VT_HVS_Tr
6. U2n_DeltVT_HVS_Tr
7. I1n_CT_HVS_Tr
8. I2n_CT_HVS_Tr
9. I1n_CT_Bak_HVS_Tr
10. I2n_CT_Bak_HVS_Tr
11. I1n_CT_LVS_Tr
12. I2n_CT_LVS_Tr
13. I1n_CT#_HVS_ST1
14. I2n_CT#_HVS_ST1
15. I1n_CT#_HVS_ST2
16. I2n_CT#_HVS_ST2
17. I1n_CT_NP_Tr
19. I1n_CT_Gap_Tr
20. I2n_CT_Gap_Tr
21. Yd11_Conn_Tr
The connection mode of main transformer is Yd-11 mode. The current input for HV side is only
one.
22. Yyd11_Conn_Tr
The connection mode of main transformer is Yd-11 mode. The currents input for HV side are two
CTs, such as 3/2 breakers of HV bus.
23. Yd1_Conn_Tr
24. Yyd1_Conn_Tr
The currents input for HV side are two CTs, such as 3/2 breakers of HV bus.
25. Opt_GCB
“1” means there is a circuit breaker at terminal of generator. “0” means there isn’t a circuit breaker
at terminal of generator.
Access Path
Setting List
Step-down Transformer 1
Step-down Transformer 2
Setting Description
1. Sn_ST1(2)
Capacity of the exciter or step-down transformer shall be configured as its name plate stated
2. U1n_HVS_ST1(2)
3. U1n_Br1_ST1(2) or U1n_Br2_ST1(2)
4. U1n_VT_Br1_ST1(2) or U1n_VT_Br2_ST1(2)]
5. U2n_VT_Br1_ST1(2) or U2n_VT_Br2_ST1(2)]
6. I1n_CT_HVS_ST1(2)
Rated primary current of CT1 with small ratio at HV side of step-down transformer
7. I2n_CT_HVS_ST1(2)
Rated secondary current of CT1 with small ratio at HV side of step-down transformer
8. I1n_CT_Br1_ST1(2) or I1n_CT_Br2_ST1(2)
9. I2n_CT_Br1_ST1(2) or I2n_CT_Br2_ST1(2)
10. I1n_CT_NP_Br_ST1(2)
11. I2n_CT_NP_Br_ST1(2)
12. Yyy12_Conn_ST
13. Ddd12_Conn_ST
14. Dyy11_Conn_ST
15. Ydd11_Conn_ST
16. Dyy1_Conn_ST
Access Path
Setting List
1. Opt_SLD
This is the logic setting of connection type between bus, main transformer and step-down
transformer, which decides the default LCD displaying in normal operation condition. Each bit from
0 to 3 represents a unique figure displayed on LCD if the bit is set as “1”. The following table gives
the actual meaning of each bit. Only one bit can be set as “1” simultaneously.
2. Cfg_Polar_CT
Generally, CT polarity definition is shown as the below table. However if some CT polarity direction
is reversed by incorrect wiring connecting, there is still chance to correct it by configuring this logic
setting easily. Please set the corresponding digit of the logic setting. Bit01~Bit15 are
corresponding to 15 three-phase current channels one by one. If any bit is set as “0”, the program
will reverse the current polarity of this channel before calculation.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Three-phase channel 15
Three-phase channel 14
Three-phase channel 13
Three-phase channel 12
Three-phase channel 10
Three-phase channel 11
Three-phase channel 9
Three-phase channel 8
Three-phase channel 7
Three-phase channel 6
Three-phase channel 5
Three-phase channel 4
Three-phase channel 3
Three-phase channel 2
Three-phase channel 1
No definition
3. Cfg_CT_HVS1_Tr
Configurable setting for deciding which channel is chosen to input three-phase current of HVS1
side of main transformer
Following table gives all the choices that user can decide. Only one bit at most can be set as “1”
simultaneously.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Three-phase channel 15
Three-phase channel 14
Three-phase channel 13
Three-phase channel 12
Three-phase channel 10
Three-phase channel 11
Three-phase channel 9
Three-phase channel 8
Three-phase channel 7
Three-phase channel 6
Three-phase channel 5
Three-phase channel 4
Three-phase channel 3
Three-phase channel 2
Three-phase channel 1
No definition
4. Cfg_CT_HVS2_Tr
Configurable setting for deciding which channel is chosen to input three-phase current of HVS2
side of main transformer
5. Cfg_CT_Bak_HVS_Tr
Configurable setting for deciding which channel is chosen to input three-phase current of HVS
side of main transformer
This current is specially used for backup protection of main transformer. The definition is the same
to the above table except for the bit0. In this setting, if the bit0 is set as “1”, the protection will
recognize this directly input current as the whole current of HVS side of main transformer,
otherwise, the protection will automatically add HVS1 and HVS2 side currents mentioned above to
be the whole current of HVS side and ignoring the current input from this channel.
6. No.6~No. 27
Configurable setting for deciding which channel is chosen to input each current
The definition of each bit is the same to that of No.4. The actual meaning of each setting is given in
the following table.
step-down transformer 1
Channel selection for the current at HV side of step-down
8 Cfg_CT_HVS_ST2
transformer 2
Channel selection for the current of branch 1 at LV side of
9 Cfg_CT_Br1_ST2
step-down transformer 2
Channel selection for the current of branch 2 at LV side of
10 Cfg_CT_Br2_ST2
step-down transformer 2
Channel selection for zero-sequence current obtained for
11 Cfg_CT_NP_Tr
neutral point of main transformer
Channel selection for gap zero-sequence current obtained
12 Cfg_CT_Gap_Tr
for main transformer
Channel selection for zero-sequence current obtained for
13 Cfg_CT_NP_Br1_ST1 neutral point of branch 1 at LV side of step-down transformer
1
Channel selection for zero-sequence current obtained for
14 Cfg_CT_NP_Br2_ST1 neutral point of branch 2 at LV side of step-down transformer
1
Channel selection for zero-sequence current obtained for
15 Cfg_CT_NP_Br1_ST2 neutral point of branch 1 at LV side of step-down transformer
2
Channel selection for zero-sequence current obtained for
16 Cfg_CT_NP_Br2_ST2 neutral point of branch 2 at LV side of step-down transformer
2
7. Cfg_CT_Diff_Tr
Logic setting of selecting three-phase current channels for differential protection of main
transformer
If the bit is set as “1”, it means this group is used in the differential protection of main transformer.
Following will be seen on PC through RCSPC software.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
CT#_HVS_ST
CT_HVS2_Tr
CT_HVS1_Tr
CT_HVS_ST
CT_LVS_ST
CT_LVS_Tr
8. Cfg_REF_Tr
Logic setting of selecting three-phase current channels for zero-sequence differential protection of
main transformer
If the bit is set as “1”, it means this group is used in the zero-sequence differential protection of
main transformer. Following will be seen on PC through RCSPC software.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
CT_Bush_HVS_Tr
CT_Wdg_HVS_Tr
CT_NP_HVS_Tr
CT_HVS2_Tr
CT_HVS1_Tr
9. Cfg_CT_WdgDiff_Tr
Logic setting of selecting three-phase current channels for winding differential protection of main
transformer
If the bit is set as “1”, it means this group is used in the winding differential protection of main
transformer. Following will be seen on PC through RCSPC software.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
CT_Wdg_HVS_Tr
CT_HVS2_Tr
CT_HVS1_Tr
10. Opt_WaveRec_MON CT_HVS_ST
11. Opt_Debug_MON
This logic setting is provided especially for software developing, not for ordinary users.
12. Opt_Dur_WaveRec_MON
13. En_Displ_Pickup
This logic setting is provided especially for software developing, not for ordinary users.
The protection settings are used to determine the characteristic of each protection.
Setting List
Setting Description
1. I_Pkp_PcntDiff_Tr
This is pickup setting of percentage current differential protection, which is also the setting of fault
detector of percentage differential protection. It shall be higher than maximum unbalanced current
of the transformer during normal rated load, i.e.
Where:
K er is the ratio error of CT (=0.03X2, for class 10P; =0.01X2, for class 5P and class TP);
ΔU is the maximum deviation (in percentage of rated voltage) due to tap changing.
Δm is the error caused by the difference between ratios of CT at all side, 0.05 is recommended.
For practical engineering application, I cdqd =(0.3 - 0.5) I e is reasonable and unbalanced current
2. I_InstDiff_Tr
Setting of unrestrained instantaneous differential protection, which is used to clear serious internal
fault quickly and prevent operation delay caused by CT saturation. The setting I cdsd (i.e.
[I_InstDiff]) shall be greater than inrush current and maximum unbalanced current due to external
fault or asynchronous closing, generally
Where:
according to the phase-to-phase solid short circuit fault in normal operation condition at installed
3. Slope1_PcntDiff_Tr
Where:
K er is the error of current ratio of CT, no more than 0.1. K bl1 is 0.10-0.20 generally.
The sensitivity coefficient K sen shall be calculated according to phase-to-phase short circuit on
outlet of transformer protected by the differential relay in minimum operation mode. From the
calculated minimum short circuit current I k . min and relevant restraint current I res , corresponding
pickup current I op will be found in the operation characteristic curve of percentage differential
K sen = I k . min / I op
(Equation 6.4-4)
K sen ≥2 is required.
4. Slope2_PcntDiff_Tr
Where:
I k . max is the maximum value of fundamental component of external short circuit fault current
(secondary).
K ap is the coefficient of DC component. K ap = 1.0 if CT at both sides are class TP, or K ap = 1.5 -
Where:
ΔU h are maximum deviations (in percentage of rated voltage) on HV side due to tap changing.
I k . max is the maximum value of fundamental component of short circuit secondary current flowing
I k .h. max is the maximum value of fundamental component of short circuit secondary current flowing
I k .I . max and I k .II . max are the fundamental components of secondary currents flowing through CT at
ΔmI and ΔmII are errors caused by difference between ratios of CT (auxiliary CT included if any)
at relevant sides.
Where:
Definition of I unb. max* , I cdqd * and I k . max* are almost same to I unb. max , I cdqd and
I k . max mentioned above, and the only difference is they are per unit values. I e (secondary
5. k_Harm_PcntDiff_Tr
This parameter is the blocking threshold of second harmonics involving in differential current to
against inrush current when the transformer is energized. The differential protection will be
blocked when the percentage of second harmonics reaches the threshold because the percentage
of second harmonics is high in inrush current but low in fault current. It is recommended that the
parameter is set to be 15% -20%.
6. TrpLog_DIff_Tr
Tripping output logic setting of differential protection is used to specify which breaker or breakers
will be tripped by this protection.
7. En_InstDiff_Tr
Unrestrained instantaneous differential protection enabled. If this setting is set as “1”, it means this
protection is enabled. Otherwise, it means the protection is disabled.
8. En_PcntDiff_Tr
Percentage differential protection enabled. If this setting is set as “1”, it means this protection is
enabled. Otherwise, it means the protection is disabled.
9. En_DPFC_Diff_Tr
DPFC percentage differential protection enabled. If this setting is set as “1”, it means this
protection is enabled. Otherwise, it means the protection is disabled.
10. Opt_Inrush_Ident_Tr
11. Opt_CTS_Blk_PcntDiff_Tr
If this logic setting is set as “1”, it means percentage differential protection will be blocked when CT
circuit failure happens. Otherwise, it means the function is disabled.
12. Opt_Diff_GTU/Tr
Access Path
Overview
Setting Description
1. I_Pkp_PcntREF_Tr
The calculation of this setting is based on secondary rated current of CT. The pickup current of
REF shall be greater than the maximum unbalance current while main transformer works under
normal rated load, i.e.
Where:
K er is the ratio errors of CT (for type 10P, K er =0.03X2, for class 5P and class TP, K er =0.01X2)
Δm is the error caused by the difference between ratios of CT at all side, 0.05 is recommended
For practical engineering calculation, Iocdqd =(0.2 - 0.5)In is reasonable and unbalance current in
Please note that calculation of zero-sequence differential current settings is based on the
secondary rated current of CT. If a setting value got from calculation is together with its unit
Ampere, this setting shall be divided by secondary rated current of this side of CT, to get per unit
value.
Sensitivity of percentage REF shall be checked with the solid earthed short circuit in its protected
zone. K sen ≥ 2 is required. In solid earthed system, distribution of zero-sequence current for single
phase to ground fault depends on the configuration of zero-sequence network of power system.
Magnitude of the single-phase ground fault current depends on not only zero-sequence distance
of system but also positive and negative sequence distance or power system operation mode.
When power system is in maintenance status, in order to remain the zero-sequence network
unchanged and increase sensitivity for earth fault protection, the 220kV power system is generally
compensated by properly changing earth mode of main transformer. Neutral point of main
transformer of 400kV power system is now generally earthed with small reactance. Therefore,
sensitivity of REF shall be checked in minimum operation mode for 220kV power system and
minimum operation mode or small maintenance mode for 400kV power system.
Note!
Positive polarity of CT is at busbar side on HV side and at neutral point for serial-winding.
2. I_InstREF_Tr
3. Slope_PcntREF_Tr
4. TrpLog_REF_Tr
5. En_InstREF_Tr
6. En_PcntREF_Tr
7. Opt_CTS_Blk_PcntREF_Tr
If this logic setting is set as “1”, it means percentage REF will be blocked when CT circuit failure
happens. Otherwise, it means the function is disabled.
Access Path
Setting List
Setting Description
1. I_Pkp_PcntWdgDiff_Tr
This is pickup setting of percentage winding differential protection, which is also the setting of fault
detector of percentage differential protection. It shall be higher than maximum unbalanced current
of the transformer during normal rated load, i.e.
Where:
K er is the ratio error of CT (=0.03X2, for class 10P; =0.01X2, for class 5P and class TP);
ΔU is the maximum deviation (in percentage of rated voltage) due to tap changing
Δm is the error caused by the difference between ratios of CT at all side, 0.05 is recommended
For practical engineering application, I cdqd =(0.3 - 0.5) I e is reasonable and unbalanced current
The sensitivity coefficient K sen shall be calculated according to phase-to-phase short circuit on
outlet of transformer protected by the differential relay in minimum operation mode. From the
calculated minimum short circuit current I k . min and relevant restraint current I res , corresponding
pickup current I op will be found in the operation characteristic curve of percentage differential
K sen = I k . min / I op
(Equation
6.4-10)
K sen ≥2 is required.
2. I_InstWdgDiff_Tr
3. Slope_PcntWdgDiff_Tr
4. TrpLog_WdgDiff_Tr
5. En_InstWdgDiff_Tr
6. En_PcntWdgDiff_Tr
7. Opt_CTS_Blk_PcntWdgDiff
If this logic setting is set as “1”, it means percentage winding differential protection will be blocked
when CT circuit failure happens. Otherwise, it means the function is disabled.
Access Path
Setting List
The current is gained from the current input channel at HV side of main transformer. For double
busbar arrangement at HV side of main transformer, usually it is the current at HV side of main
transformer. For 3/2 breaker arrangement at HV side of main transformer, it is either bushing
current at HV side of main transformer or the summation of current from double breaker CTs at HV
side of main transformer
Setting Description
1. V_NegOV_VCE_Tr
This is setting of negative sequence voltage control element of main transformer. Setting and
displayed value of negative sequence voltage are U2.
Setting of this relay shall be higher than measured imbalance voltage during normal operation
condition, generally
Where:
U k .2. min
K sen = (Equation
U op.2
6.4-12)
Where U k .2. min is minimum secondary negative sequence voltage at location of the relay during
phase-to-phase metallic short circuit fault at end of backup protected zone. K sen ≥2.0 is required
for near backup protection and K sen ≥1.5 for remote backup protection.
Note!
When sensitivity factor is checked for current relay and voltage relay, unfavorable normal
system operation condition and unfavorable type of short circuit fault shall be adopted. If
sensitivity factor of under voltage relay is not high enough, function of composite voltage
on LV side initiation can be enabled. Voltage is taken from LV side by configure logic
setting [En_LVS.VCE_Ctrl_OC_Tr].
2. Vpp_UV_VCE_Tr
Voltage of voltage control element is taken from LV side usually (logic setting
[En_LVS.VCE_Ctrl_OC_TR] is set as 1.). Undervoltage setting shall be higher than the lowest
voltage during starting process of the largest motor connected with the LV busbar.
Setting shall be higher than possible minimum voltage during normal operation, namely
U min
U op = (Equation 6.4-13)
K rel ⋅K r
Where K rel is reliability factor, 1.10 – 1.20; K r is release factor, 1.05 – 1.25; U min is possible
minimum voltage during normal operation, 0.9 times of secondary rated line voltage generally.
When VT on HV side of the transformer is used for the under voltage relay
Where:
When step-up transformer is used in a power plant and VT on generator side is used for under
voltage relay, its setting shall be higher than under voltage during operation of generator without
excitation,
Where:
U op
K sen = (Equation 6.4-16)
U c. max
Where:
U c.max is maximum secondary residual voltage at location of the relay when phase-to-phase
metallic short circuit fault occurs at the check point during operation condition for calculation.
K sen ≥1.5 is required for near backup protection and K sen ≥1.2 for remote backup protection.
3. I_OC1_Tr
K rel
I op = Ie (Equation 6.4-17)
Kr
Where:
K rel is reliability factor, 1.2 generally; K r is release factor, 0.85 – 0.95; I e is secondary rated
current.
I k( 2.min
)
K sen = (Equation 6.4-18)
I op
Where:
I k( 2.min
)
is minimum fault current through location of the relay during phase-to-phase metallic short
circuit at end of backup protected section. K sen ≥ 1.3 is required for near backup protection and
4. t_OC1_Tr
It shall coordinate with main protection only and oscillation period is not needed to be considered.
It is set as 0.5 s generally.
5. TrpLog_OC1_Tr
Tripping output logic setting of the time delay of over current protection stage 1
6. I_OC2_Tr
7. t_OC2_Tr
8. TrpLog_OC2_Tr
Tripping output logic setting of the first time delay of over current protection stage 2
9. Z1_Fwd_Tr
Here positive direction means the direction is pointing to the transformer instead of generator
itself.
If the value of this setting is greater than the next one, then the characteristic of distance protection
is set as excursive impedance circle; if it is equal to the next one, the characteristic is whole
impedance circle; if the next one is set as “0”, the characteristic becomes directional impedance.
Generally, low impedance protection is considered as the backup protection of transformer in case
that voltage-controlled overcurrent protection cannot satisfy the sensitivity requirement of
transformer.
Setting of this impedance relay shall coordinate with that of HV side outlet, namely
Where K rel is reliability factor, 0.8 generally; Kinf is enhanced factor, taking minimum value of
Z op
K sen = (Equation 6.4-20)
Z
Where Z is equivalent secondary impedance value of designated protected section. K sen ≥1.3
Is required.
The forward setting can be based on enough sensitivity for fault on terminal of generator and
referred to equation hereinabove. Reverse impedance equals to 5% - 10% of forward impedance.
Reverse setting shall be lower than setting of the shortest zone 1 of impedance protection of outlet
from this side busbar.
10. Z1_Rev_Tr
In general, this setting is set as 5-10% of the positive direction impedance setting.
11. t_Z1_Tr
12. TrpLog_Z1_Tr
13. Z2_Fwd_Tr
14. Z2_Rev_Tr
15. t_Z2_Tr
16. TrpLog_Z2_Tr
17. I_Alm_OvLd_Tr
18. t_Alm_OvLd_Tr
19. I_InitCool1_OvLd_Tr
20. t_InitCool1_OvLd_Tr
21. I_InitCool1_OvLd_Tr
22. t_InitCool1_OvLd_Tr
23. I_InitCool2_OvLd_Tr
24. t_InitCool2_OvLd_Tr
25. I_BO_OC_HVS_Tr
26. t_BO_OC_HVS_Tr
27. En_VCE_Ctrl_OC1_Tr
28. En_VCE_Ctrl_OC2_Tr
29. En_LVS.VCE_Ctrl_OC_Tr
30. En_Mem_Curr_Tr
Note!
For generator with self parallel excitation system, the memory function of transformer is
usually disabled for phase to phase backup protection. But if it is enabled, the overcurrent
protection must be configured as voltage controlled overcurrent protection.
31. Opt_VTS_Ctrl_OC_Tr
“1”: when VT circuit failure at one side is detected, voltage control element at the same side will be
disabled but overcurrent relay on the same side can still be controlled by voltage control elements
of other side if corresponding logic setting is set as “1”.
“0”: when VT circuit failure at one side is detected, the overcurrent relay will become an
overcurrent relay without voltage element control.
32. En_OvLd_Tr
33. En_InitCool1_OvLd_Tr
34. En_InitCool2_OvLd_Tr
35. En_BO_OC_HVS_Tr
Access Path
Setting List
Setting Description
1. V_ROV_VCE_Tr
Setting (3U0) of zero-sequence voltage control element for zero-sequence overcurrent protection.
2. I_ROC1_Tr
This setting shall coordinate with unrestraint main protection or stage 1 or 2 of zero sequence
overcurrent relay of adjacent power line.
Where:
K brI is branch factor of zero sequence current which is ratio of zero sequence current passing
through the relay and passing through the faulty line during ground fault at end of protected zone
of stage 1 of power line zero sequence overcurrent protection, maximum value for various
operation conditions being Taken;
3I k .o. min
K sen = (Equation 6.4-22)
I op.o
Where:
3I k .o. min is minimum secondary zero sequence current passing through location of the relay
during ground fault at end of protected zone; I op.o is this setting. K sen ≥1.5 Is required.
3. t_ROC11_Tr
When earth fault occurs on near end of HV side outlet of startup/standby transformer, it is
protected by both this protection and zero-sequence overcurrent protection stage 2 on remote end,
so the time delay setting of this protection is
t = t II − Δt (Equation 6.4-23)
Where:
Tripping output logic setting of zero-sequence overcurrent protection stage 1 with time delay 1
5. t_ROC12_Tr
6. TrpLog_ROC12_Tr
Tripping output logic setting of zero-sequence overcurrent protection stage 1 with time delay 2
7. I_ROC2_Tr
The setting shall coordinate with operating current of zero-sequence overcurrent protection of HV
side feeders for remote end earth fault:
(3I 0 ) op
I op.o.II = K c 0 C 0' (Equation 6.4-24)
nTA
Where:
(3I o ) op is the primary operating current of backup zone of zero-sequence overcurrent protection
C 0' is the distribution coefficient of zero sequence current that is equal to the ratio of zero
sequence current passing through this end protection and that passing through the power line,
takes the maximum value in various operation modes; and nTA is current ratio of CT.
8. t_ROC21_Tr
9. TrpLog_ROC21_Tr
Tripping output logic setting of zero-sequence overcurrent protection stage 2 with time delay 1
10. t_ROC22_Tr
11. TrpLog_ROC22_Tr
Tripping output logic setting of zero-sequence overcurrent protection stage 2 with time delay 2
12. V_ROV_Gap_HVS_Tr
13. t_ROV_Gap_HVS_Tr
14. TrpLog_ROV_Gap_HVS_Tr
15. I_ROC_Gap_HVS_Tr
16. t_ROC_Gap_HVS_Tr
17. TrpLog_ROC_Gap_HVS_Tr
18. V_Alm_ROV_LVS_Tr
19. t_Alm_ROV_LVS_Tr
20. En_VCE.ROC_Ctrl_ROC1_Tr
21. En_VCE.ROC_Ctrl_ROC2_Tr
22. En_Dir_Ctrl_ROC1_Tr
23. En_Dir_Ctrl_ROC2_Tr
24. En_Calc_3I0_ROC1_HVS
25. En_Calc_3I0_ROC2_HVS
26. En_Alm_ROV_LVS_Tr
27. En_BI_Ctrl_EF_Gap_HVS
28. Opt_CT_Calc_3I0_HVS
Access Path
Setting List
Setting Description
1. k_OvExc1_Tr
U
B U gn
N = = = U ∗ / f ∗ = 1.3 or data provided by the factory
Bn f
f gn
2. t_OvExc1_Tr
3. TrpLog_OvExc1_Tr
Tripping output logic setting of stage 1 of definite time over excitation protection of main
transformer
The function of this protection is used for islanding, excitation shutting or programming, excitation
reducing etc
4. k_Alm_OvExc_Tr
Setting of alarm shall be lower than that of over excitation protection. 1.1 is recommended.
5. t_Alm_OvExc_Tr
6. k0_InvOvExc_Tr
The upper limit of inverse-time over-excitation protection of main transformer (at point n0)
7. t0_InvOvExc_Tr
Time delay of upper limit of inverse-time over-excitation protection of main transformer (at point
n0)
8. k1_InvOvExc_Tr
Setting range of various inverse-time over-excitation coefficient s is 1.1~2.0. However the upper
limit of inverse-time over-excitation protection (No.6) shall be higher than the factor at point n1 of
inverse-time over-excitation curve, and the factor at point n1 of inverse-time over-excitation curve
shall be higher than that of point n2, etc.. Finally, the factor at point n6 of inverse-time
over-excitation curve (No.18) shall be higher than the lower limit of inverse-time over-excitation
protection (No.20).
[k0_InvOvExc_Tr]>[k1_InvOvExc_Tr]>[k2_InvOvExc_Tr]>[k3_InvOvExc_Tr]>[k4_InvOvExc_Tr]>[
k5_InvOvExc_Tr]>[k6_InvOvExc_Tr]>[k7_InvOvExc_Tr]
9. t1_InvOvExc_Tr
The range of time delay of various inverse-time over-excitation protection is 0s~6000s, i.e.,
0~50min. Time delay of upper limit of inverse-time over-excitation protection (No.7) shall be
shorter than time delay at point n1 of inverse-time over-excitation curve, and time delay of at point
n1 shall be shorter than that of point n2, etc.. Finally, time delay at point n6 of inverse-time
over-excitation curve (No.19) shall be shorter than that time delay of lower limit of inverse-time
over-excitation protection (No.21).
[t0_InvOvExc_Tr]<[t1_InvOvExc_Tr]<[t2_InvOvExc_Tr]<[t3_InvOvExc_Tr]<[t4_InvOvExc_Tr]<[t5
_InvOvExc_Tr]<[t6_InvOvExc_Tr]<[t7_InvOvExc_Tr]
10. k2_InvOvExc_Tr
11. t2_InvOvExc_Tr
12. k3_InvOvExc_Tr
13. t3_InvOvExc_Tr
14. k4_InvOvExc_Tr
15. t4_InvOvExc_Tr
16. k5_InvOvExc_Tr
17. t5_InvOvExc_Tr
18. k6_InvOvExc_Tr
19. t6_InvOvExc_Tr
20. k7_InvOvExc_Tr
The lower limit of inverse-time over-excitation protection of main transformer (at point n7)
21. t7_InvOvExc_Tr
Time delay of lower limit of inverse-time over-excitation protection of main transformer (at point n7)
22. TrpLog_InvOvExc_Tr
Access Path
Setting List
Setting Description
1. I_NegOC_Flash1_CB_HVS
2. t_Flash11_CB_HVS
The first time delay of breaker flashover protection at HV side of main transformer
3. TrpLog_Flash11_CB_HVS
Tripping output logic setting of breaker flashover protection at HV side of main transformer (the
first time delay)
4. t_Flahs12_CB_HVS
The second time delay of breaker flashover protection at HV side of main transformer
5. TrpLog_Flash12_CB_HVS
Tripping output logic setting of breaker flashover protection at HV side of main transformer (the
second time delay)
Access Path
Setting List
7 TrpLog_BFP12_CB_HVS_Tr 0000~FFFF 1
Logic setting “1” - enable, “0” – disable
1 En_ROC_Ctrl_BFP_CB_HVS_Tr 0/1
2 En_NegOC_Ctrl_BFP_CB_HVS_Tr 0/1
3 En_ExtTrp_Ctrl_BFP_CB_HVS_Tr 0/1
4 En_CB_Ctrl_BFP_CB_HVS_Tr 0/1
Setting Description
1. I_BFP1_CB_HVS_Tr
2. I_ROC_BFP1_CB_HVS_Tr
3. I_NegOC1_BFP_CB_HVS_Tr
4. t_BFP11_CB_HVS_Tr
The first time delay of breaker failure protection at HV side of main transformer
5. TrpLog_BFP11_CB_HVS_Tr
Tripping output logic setting of breaker failure protection at HV side of main transformer (the first
time delay)
6. t_BFP12_CB_HVS_Tr
The second time delay of breaker failure protection at HV side of main transformer
7. TrpLog_BFP12_CB_HVS_Tr
Tripping output logic setting of breaker failure protection at HV side of main transformer (the
second time delay)
8. En_ROC_Ctrl_BFP_CB_HVS_Tr
The logic setting used to enable zero-sequence current criterion of breaker failure protection at HV
side of main transformer
9. En_NegOC_Ctrl_BFP_CB_HVS_Tr
The logic setting used to enable negative-sequence current criterion of breaker failure protection
at HV side of main transformer
10. En_ExtTrp_Ctrl_BFP_CB_HVS_Tr
The logic setting of enable breaker failure protection at HV side of main transformer controlled by
external binary input from tripping contact
11. En_CB_Ctrl_BFP_CB_HVS_Tr
The logic setting of enable breaker failure protection at HV side of main transformer controlled by
external binary input from CB open position
Access Path
Setting List
Step-down Transformer 1
No. Symbol Range Step
1 I_Pkp_PcntDiff_ST1 0.10~1.50 (Ie) 0.01 (Ie)
2 I_InstDiff_ST1 2.0~14.0 (Ie) 0.01 (Ie)
3 Slope1_PcntDiff_ST1 0.10~ 0.50 0.01
4 Slope2_PcntDiff_ST1 0.50 ~0.80 0.01
5 k_Harm_PcntDiff_ST1 0.10~ 0.35 0.01
6 TrpLog_Diff_ST1 0000~FFFF 1
Logic setting “1” - enable, “0” – disable
1 En_InstDiff_ST1 0/1
2 En_PcntDiff_ST1 0/1
3 Opt_Inrush_Ident_ST1 0/1
4 Opt_CTS_Blk_PcntDiff_ST1 0/1
Step-down Transformer 2
No. Symbol Range Step
1 I_Pkp_PcntDiff_ST2 0.10~1.50 (Ie) 0.01 (Ie)
2 I_InstDiff_ST2 2.0~14.0 (Ie) 0.01 (Ie)
3 Slope1_PcntDiff_ST2 0.10 ~0.50 0.01
4 Slope2_PcntDiff_ST2 0.50~0.80 0.01
5 k_Harm_PcntDiff_ST2 0.10~0.35 0.01
6 TrpLog_Diff_ST2 0000~FFFF 1
Logic setting “1” - enable, “0” – disable
1 En_InstDiff_ST2 0/1
2 En_PcntDiff_ST2 0/1
3 Opt_Inrush_Ident_ST2 0/1
4 Opt_CTS_Blk_PcntDiff_ST2 0/1
Setting Description
12. I_Pkp_PcntDiff_ST1(2)
13. I_InstDiff_ST1(2)
14. Slope1_PcntDiff_ST1(2)
15. Slope2_PcntDiff_ST1(2)
16. k_Harm_PcntDiff_ST1(2)
17. TrpLog_Diff_ST1(2)
18. En_InstDiff_ST1(2)
19. En_PcntDiff_ST1(2)
20. Opt_Inrush_Ident_ST1(2)
21. Opt_CTS_Blk_PcntDiff_ST1(2)
Access Path
Setting List
Step-down Transformer 1
No. Symbol Range Step
1 V_NegOV_VCE_HVS_ST1 1.00~20.00 V 0.01 V
2 Vpp_UV_VCE_ HVS_ST1 10.00~100.00 V 0.01 V
3 I_OC1_HVS_ST1 0.10~50.00 A 0.01 A
5 En_Alm_OvLd_HVS_ST2 0/1
6 En_InitCool_OvLd_HVS_ST2 0/1
7 En_BO_OC_HVS_ST2 0/1
8 En_LVSProt_Blk_OC1_HVS_ST2 0/1
Setting Description
1. V_NegOV_VCE_HVS_ST1(2)
Negative sequence voltage setting of composite voltage control element at HV side of step-down
transformer
2. Vpp_UV_VCE_HVS_ST1(2)
3. I_OC1_HVS_ST1(2)
4. t_OC1_HVS_ST1(2)
5. TrpLog_OC1_HVS_ST1(2)
6. I_OC2_HVS_ST1(2)
7. t_OC2_HVS_ST1(2)
8. TrpLog_OC2_HVS_ST1(2)
9. I_Alm_OvLd_HVS_ST1(2)
10. t_Alm_OvLd_HVS_ST1(2)
11. I_InitCool_OvLd_HVS_ST1(2)
12. t_InitCool_OvLd_HVS_ST1(2)
13. I_BO_OC_HVS_ST1(2)
14. t_BO_OC_HVS_ST1(2)
18. Opt_VTS_Ctrl_OC_HVS_ST1(2)
“1”: when VT circuit failure at one side is detected, voltage control element at the same side will be
disabled but overcurrent relay on the same side can still be controlled by voltage control elements
of other side if corresponding logic setting is set as “1”.
“0”: when VT circuit failure at one side is detected, the overcurrent relay will become an
overcurrent relay without voltage element control.
19. En_Alm_OvLd_HVS_ST1(2)
20. En_InitCool_OvLd_HVS_ST1(2)
21. En_BO_OC_HVS_ST1(2)
22. En_LVSProt_Blk_OC1_HVS_ST1(2)
Access Path
Setting List
Setting Description
1. V_NegOV_VCE_Br1(2)_ST1(2)
Negative sequence voltage setting of composite voltage control element of branch 1 or branch 2 of
step-down transformer
2. Vpp_UV_VCE_Br1(2)_ST1(2)
3. I_OC1_Br1(2)_ST1(2)
4. t_OC1_Br1(2)_ST1(2)
5. TrpLog_OC1_Br1(2)_ST1(2)
6. I_OC2_Br1(2)_ST1(2)
7. t_OC2_Br1(2)_ST1(2)
8. TrpLog_OC2_Br1(2)_ST1(2)
9. I_ROC1_Br1(2)_ST1(2)
10. t_ROC1_Br1(2)_ST1(2)
11. TrpLog_ROC1_Br1(2)_ST1(2)
Tripping output logic setting of stage 1 of definite time zero sequence overcurrent protection
12. I_ROC2_Br1(2)_ST1(2)
13. t_ROC2_Br1(2)_ST1(2)
14. TrpLog_ROC2_Br1(2)_ST1(2)
Tripping output logic setting of stage 2 of definite time zero sequence overcurrent protection
17. Opt_VTS_Ctrl_OC_Br1(2)_ST1(2)
“1”: when VT circuit failure at one side is detected, voltage control element at the same side will be
disabled but overcurrent relay on the same side can still be controlled by voltage control elements
of other side if corresponding logic setting is set as “1”.
“0”: when VT circuit failure at one side is detected, the overcurrent relay will become an
overcurrent relay without voltage element control.
Access Path
Setting List
Setting Description
1. t_MechRly1
2. TrpLog_MechRly1
3. t_MechRly2
4. TrpLog_MechRly2
5. t_MechRly3
6. TrpLog_MechRly3
7. t_MechRly4
8. TrpLog_MechRly4
9. En_Supv_MechRly
Access Path
The settings listed in the following tables calculated by the RCS-985BT itself automatically, they
need not to be set by user. The settings are calculated according to the system parameters that
user input, include primary rated currents, secondary rated currents, secondary rated voltages and
correction coefficients used in all kinds of differential protection relays. Listing of the calculated
settings is only for reference of setting check or commission.
Setting List
Setting Description
1. I1b_SnTr_CT_HVS_Tr
Sn
The equation is I b1n =
3U b1n
2. I1b_SnTr_CT_LVS_Tr
3. I1b_SnST_CT_HVS_ST1
4. I1b_SnST_CT_Br1_ST1
5. I1b_SnST_CT_Br2_ST1
6. I1b_SnST_CT_HVS_ST2
7. I1b_SnST_CT_Br1_ST2
8. I1b_SnST_CT_Br2_ST2
Access Path
Setting List
11 I2b_SnST_CT_Br2_ST2 0-600 A
Setting Description
1. I2b_SnTr_CT_HVS_Tr
I b1n
The equation is I b 2 n =
nbLH
2. I2b_SnTr_CT_LVS_Tr
3. I2b_SnTr_CT_ST1
4. I2b_SnTr_CT_ST2
5. I2b_SnTr_CT_Bak_HVS_Tr
6. I2b_SnST_CT_HVS_ST1
7. I2b_SnST_CT_Br1_ST1
8. I2b_SnST_CT_Br2_ST1
9. I2b_SnST_CT_HVS_ST2
10. I2b_SnST_CT_Br1_ST2
11. I2b_SnST_CT_Br2_ST2
Access Path
Setting List
Setting Description
1. V2b_VT_HVS_Tr
2. U2b_DeltVT _HVS_Tr
3. U2b_VT_Br1_ST1
4. U2b_VT_Br1_ST2
5. U2b_VT_Br2_ST1
6. U2b_VT_Br2_ST2
Access Path
Setting List
9 k_Br1_Diff_ST2 0-60
10 k_Br2_Diff_ST2 0-60
11 k_Calc_REF_HVS 0-60
12 k_NP_REF_HVS 0-60
13 k_HVS_WdgDiff 0-60
14 k_Wdg_WdgDiff 0-60
Setting Description
1. k_TrHVS_Diff _Tr
2. k_TrLVS_Diff _Tr
Differential coefficient of LVS of main transformer for differential protection of main transformer, the
base side is LV side.
3. k_ST1_Diff_Tr
4. k_ST2_Diff_Tr
5. k_HVS_Diff_ST1
6. k_Br1_Diff_ST1
7. k_Br2_Diff_ST1
8. k_HVS_Diff_ST2
9. k_Br1_Diff_ST2
10. k_Br2_Diff_ST2
11. k_NP_REF_Tr
Differential coefficient of neutral point of main transformer for REF of main transformer
12. k_Calc_REF_Tr
13. k_HVS_WdgDiff
14. k_Wdg_WdgDiff
Access Path
6 I2b2_SnST_CT_HVS_ST1 0-600 A
7 I2b2_SnST_CT_Br1_ST1 0-600 A
8 I2b2_SnST_CT_Br2_ST1 0-600 A
9 I2b2_SnST_CT_HVS_ST2 0-600 A
10 I2b2_SnST_CT_Br1_ST2 0-600 A
11 I2b2_SnST_CT_Br2_ST2 0-600 A
Inner secondary rated currents and differential coefficients are used in differential protection. All
parameters have the same meaning with those of calculated secondary rated current and
differential coefficient.
This chapter describes human machine interface (HMI), menu tree and LCD display. At the same
time how to input settings using keypad is described in detail. Finally, this chapter introduces the
RCSPC software and wave analysis software.
The settings and functions of the RCS-985BT can be accessed both from the front panel keypad
and LCD and via the front and rear communication ports. Information on each of these methods is
given in this section to describe how to start using the relay.
RCS-985 5
GENERATOR-TRANSFORMER UNIT
PROTECTION
2
HEALTHY
VT ALARM
GRP
CT ALARM
ALARM
ENT 3
ESC
1 TRIP
The front panel of the relay includes the following, as indicated in Figure 7.1-1:
7.1.2 LCD
A 320×240 dots liquid crystal display (LCD) with LED backlight. The backlight can be switched on
automatically whenever the keypad is operated or operation or alarm issued. Backlight will be
turned off after a while.
The front panel menu has a default display under normal state after powered-up. If there is no
keypad activity for the 5 minutes timeout period, the default will return again and the LCD backlight
will turn off. To provide more information, the default display a typical single-line scheme generator
system and relevant quantities in operation condition, as shown below.
2001-12-19 10:28:03
1
0.00A 0.00A DIMT: 0.00Ie
6
2
DIFC: 0.00In 7
3 0.00V DIT0: 0.00In 8
DIAT: 0.00Ie 9
4
DIBT: 0.00Ie 10
No. Description
1 Real clock
2 The current of HV side
Whenever there is an un-eliminated fault record in the relay, the default display will be replaced by
fault report.
Whenever there is an un-eliminated internal failure record in the relay, the default display will be
replaced by alarm report.
Whenever there is state change of any binary input, the default display will be replaced by change
report of binary input as shown as below.
7.1.3 Keypad
The keypad and keys on the front panel of the equipment provide convenience to the operator to
view a certain data or change the device’s setting.
The keypad contains nine keys, and each key has different function to the other one. Figure 7.1-3
shows the keypad and keys.
Note!
Any setting change operation should start with simply pressing “+”, “◄”, “▲” and “-” in
sequence, as a password. Without the operation, modifying settings is invalid.
Report delete operation should executed by pressing “+”, “-”, “+”, “-” and “ENT” in
HEALTHY
VT ALARM
CT ALARM
ALARM
TRIP
1. “HEALTHY” (Green)
The LED indicates that the relay is in correct working order, and should be on at all times. It will be
extinguished when some internal error in hardware or software have been detected by
self-diagnosing facilities, such as setting error, RAM or ROM error, power source failure, output
circuit failure and so on. The state of the LED “HEALTHY” is reflected by the watchdog contact at
the rear terminals of the relay. The LED “HEALTHY” cannot light again automatically even if the
failure is eliminated except that the relay is reset or powered up by manual.
The LED “VT ALARM” indicates that the relay has found any failure of VT circuit.
The LED “CT ALARM” indicates that the relay has found any failure of CT circuit.
4. “ALARM” (Yellow)
The LED “ALARM” indicates that the relay has registered an alarm. This may be triggered by one
of the following failures: defective pickup, failure of analog or digital input circuit, optical isolator
power loss and so on. The LED “ALARM” will constantly illuminate, and will extinguish, when the
alarms have been cleared.
5. “TRIP” (RED)
The LED “TRIP” will be lit up once the corresponding relays operate and remain lit even after the
trip commands go off. It can be turned off by pressing the button “RESET” on the protection panel
to energized binary input [BI_RstTarg], or by remote resetting command.
Under normal condition, the default display is always on LCD. Press key “▲” to enter the main
menu of the device. If the current display is the latest report display or self-supervision report,
please do as same as above.
N A R I - R E L A Y S
MON METERING
PRINT
MON BI STATE
SETTINGS
PHASE ANGLE
CLOCK
VERSION
DEBUG
The default display can be replaced by the menu when press“▲” or “ESC”.
The menu of this relay is arranged as a tree-shaped cascade structure. See Figure 7.2-2. The
menu can be browsed using the keypad.
Starting at the default display, to enter into main menu, press “▲”.
To select the required item, use the “▲” and “▼” keys.
To enter the lower level menu, select the required item and press “ENT”.
The menu can be browsed using the four arrow keys, following the structure shown in Figure 7.2-1.
Thus, starting at the default display the “▲” key will display the first column heading. To select the
required column heading use the “▲”and “▼” keys. To return to the default display, press the clear
key “ESC” from any of the column headings.
MAIN MENU
PHASE ANGLE
TR PHASE ANGLE
ST1 PHASE ANGLE
ST2 PHASE ANGLE
The above figure shows the menu tree structure of this equipment.
The password is 4 digits. The factory default passwords is sequent pressing of the keys “+”, “◄”,
“▲”, “-” and “ENT”.
The following contents are to tell user how to make use of each submenu in detail.
Navigate the menu through the following path and you will see the interface of LCD as shown in
Figure 7.3-1.
A scroll bar appears on the right means there are more rows needed to be displayed. Please press
key “▼” to see the next page and press key “ESC” to exit to the upper level submenu.
For instance, navigate the menu through the following path and you will see the interface of LCD
The angles displayed is that the former value leading to the later one, which varies from
-180~+180, as shown as figure below for example.
TR PHASE ANGLE
o
φi_HVS1_&_LVS_Tr: 000 000 000
o
φi_HVS2_&_LVS_Tr: 000 000 000
o
φi_ST1_&_LVS_Tr: 000 000 000
o
φi_ST2_&_LVS_Tr: 000 000 000
o
φipp_HVS1_Tr: 000 000 000
o
φipp_HVS2_Tr: 000 000 000
o
φipp_Bak_HVS_Tr: 000 000 000
o
φipp_LVS_Tr: 000 000 000
Scrolling the cursor to this submenu and press “ENT” key, the LCD will display the latest trip report
if exist; otherwise a clew of “NO TRIP REPORT” will appear. If there are several trip reports stored
in memory, user can look up historical record one by one by pushing “▲” key.
RCS-985BT can store up to 32 latest trip reports. When the available space is exhausted, the
oldest report is automatically overwritten by the new one.
Scrolling the cursor to this submenu and press “ENT” key, the LCD will display the latest alarm
report if exist, otherwise a clew of “NO ALARM REPORT” will appear. If there are several alarm
reports stored in memory, user can look up historical record one by one by pushing “▲” key.
RCS-985BT can store up to 32 latest alarm reports. When the available space is exhausted, the
oldest report is automatically overwritten by the new one.
Scrolling the cursor to this submenu and press “ENT” key, the LCD will display the last BI CHG
report if exist, otherwise a clew of “NO BI CHG REPORT” will appear. If there are several BI CHG
reports stored in memory, user can look up historical record one by one by pushing “▲” key.
RCS-985BT can store up to 32 latest signaling reports. When the available space is exhausted,
the oldest report is automatically overwritten by the new one
Operating steps:
Press keys “+”, “-”, “+”, “-”, “ENT” in sequence in the main menu to make LCD display Figure 7.3-5.
Press key “ENT” to delete all records or press key “ESC” to exit to main menu. If key “ENT” is
pressed, LCD will display Figure 7.3-6 when equipment is deleting all records. If key “ESC” is
pressed, Figure 7.3-4 will be displayed. LCD will automatically return to Figure 7.3-4 in 3 seconds
without pressing any key.
Used for printing of trip report of protection. User can select the report that he wants to print by
pushing “▲” and “▼” keys to select the SOE number.
Used for printing of alarm. User can select the report that he wants to print by pushing “▲” and “▼”
keys.
Used for printing of signaling report. User can select the report that he wants to print by pushing
“▲” and “▼” keys.
Used for printing of present values of relay, including sampled binary inputs, analog quantities and
so on. If you want to see the normal recording waveform, please follow the operating steps.
Operating steps:
Press key “▲” or “▼” to select “PRINT” item by scrolling the cursor upward or downward and then
press the “ENT” to the lower level submenu.
Then press key “▲” or “▼”to select “PRESENT WAVE” by scrolling the cursor upward or
downward. Press key “ENT” to enter the lower level submenu.
Press “TRIGGER” submenu to start recording. The equipment will record 5-cycle waveform after
pressing the key.
Please select the other items in the submenu “PRESENT WAVE” by scrolling cursor to print the
waveform.
To change one of the equipment settings, first navigate the “SETTING” menu to display the
relevant cell. Press “ENT” to enter the submenu, and then proceed to “EQUIP SETTINGS”
submenu. Keys “▲” and “▼” are used to select which kind of the settings to be modified by
scrolling the cursor upward or downward. Press key “◄” or “►” to move the cursor to the digit to
be modified. Press key “+” and “–” to modify data. Press key “ESC” to return back without
modification. Pressing key “ENT” the LCD will prompt to input confirm password, then enter
password mentioned in section 7.2.2 and quit to default display by pressing “ESC” key. After a
period of extinguishing of the “HEALTHY” LED and blocking of relay itself, RCS-985BT is ready for
new operation to fault according to new settings, the modification is completed. The following
figure shows the path to access this submenu.
To change the value of a setting, first navigate the menu to “SETTING” then corresponding
submenu to display the relevant cell. Please locate the setting you want to change after entering
the right submenu by operating the keypad as described before. Then go on to operate as
following steps.
Press key “◄” or “►” to move the cursor to the digit to be modified. Pressing key “+” and “–” to
change the digit. Press key “+” once to add 1 to the digit and press key “–” once to subtract 1 from
the digit.
Press key “ESC” to cancel the modification and return to upper level submenu.
Press key “ENT” to confirm the modification and the LCD will prompt you to input confirm code.
Press keys “+”, “◄”, “▲” and “–” in sequence to complete the modification. If the password input is
wrong, prompt for password will appear again. If no operation in 3 seconds, LCD will return to last
display.
If the password inputted is right, then equipment will check setting and Figure 7.3-8 will be
displayed temporarily. If there is no error in checking setting, Equipment will modify setting with
Figure 7.3-9 displayed temporarily. Then LCD will return to upper level submenu automatically.
Checking settings...
If errors in settings are detected, the LCD will display wrong setting warning for 3 s.
Then LCD will display the setting list for the operator to modify the wrong setting. The cursor will
stay at the first wrong setting needed to be modified.
Note!
If the group number or protection system parameter is changed, all protection settings will
be invalid and have to be configured again.
Attentions should be paid that before modifying the protection settings, the active group
number in “EQUIP SETTINGS” should modified firstly, otherwise what is modified will be
applied to current active group.
modification afterwards when necessary, so as to avoid entering all settings one by one. Please
copy settings as following steps.
Move cursor to “SETTINGS” item and press key “ENT” or key“►” to enter submenu.
VALUES
REPORT
EQUIP SETTINGS
PRINT
SYS SETTINGS
SETTINGS
PROT SETTINGS
CLOCK SETTINGS COPY
VERSION CALC SETTINGS
DEBUG
Move cursor to “SETTINGS COPY” item and press “ENT” to display following interface.
Press key “+” and “–” to change digit where the cursor stays. Pressing key “+” once will add 1 to
the digit and pressing key “–” once will subtract 1 from the digit. (For example: input 01)
Press “ENT” the LCD will prompt to input confirm code. Please see the figure below.
Please press keys “+”, “◄”, “▲” and “–” in sequence, and then the equipment will copy setting and
display following interface.
Then the contents of setting group 0 will be totally copied to setting group 1 and present active
setting group will be switched to Group1.
Note!
Press “ENT” to confirm, then settings group 0 will be totally copied to settings group 1 and
present active group will be switched to group 1.
After you press key “ENT”, the following will be displayed on the LCD.
Press keys “▲”, “▼”, “◄” and “►” to select the digit to be modified. Press key “+” and “–” to modify
data. Pressing key “+” once will add 1 to the digit and pressing key “–” once will subtract 1 from the
digit.
Press key “ENT” to confirm the modification and return to the main menu.
Main menu->VERSION
After you press key “ENT”, the follow will be displayed on the LCD.
VERSION
SUBQ_ID: 00056151
2009-9-4 15:54: shows that CPU software creating time is 15:54 Sept. 4th 2009.
2009-8-7 08:18: shows that MON software creating time is 10:20 Aug. 7th 2009.
2009-9-4 14:25: shows that HMI software creating time is 08:15 Sept. 4th 2009.
Note!
What Figure 7.3-17 shows is just an example to introduce the meaning of VERSION, the
actual program VERSION is application-specific.
This submenu is used to monitor communication condition of the equipment with external system.
Display of this submenu is as follows:
Columns 485A and 485B display communication condition of RS-485 port1 and RS-485 port2
respectively. If communication condition is normal, “Y” will flash in the related position. If there is
flashing “N” in the position, it mean there are some problems. Please check the communication.
“Received Data” means the equipment has received data from external system. If “N” flashes, it
means the circuit is open or no data is sent from external system.
“Valid Frame” means the equipment has received complete frame from external system. If “N”
flashes, it means Configuration of the baud rate or protocol is wrong.
“Valid Address” means the equipment has received related message from external system. If “N”
flashes, it means Configuration of the address is wrong.
“Sent Data” means the equipment has sent data to external system. If “N” flashes, it means there
is problem with the message.
2. MEMPRY DEBUG
The LCD displays real time value in memory of CPU, DSP1 and DSP2. These data are used
mainly for program debugging.
Chapter 8 Communication
This section outlines the remote data communication interfaces of the RCS-985BT relay. The relay
can supports IEC60870-5-103 and Modbus protocols.
The two rear EIA RS-485 standardized interfaces are isolated and are suitable for permanent
connection whichever protocol is selected. The advantage of this type of connection is that up to
32 relays can be “daisy chained” together using a simple twisted pair electrical connection.
It should be noted that the descriptions contained within this section do not aim to fully detail the
protocol itself. The relevant documentation for the protocol should be referred to for this
information. This section serves to describe the specific implementation of the protocol in the relay.
The protocol provided by the relay is indicated in the relay submenu in the “EQUIP SETTINGS”
column. Using the keypad and LCD, set the parameter [Protocol] to select the corresponding
protocol.
The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the
product. The connection is polarized and whilst the product’s connection diagrams indicate the
polarization of the connection terminals it should be borne in mind that there is no agreed
definition of which terminal is which. If the master is unable to communicate with the product, and
the communication parameters match, then it is possible that the two-wire connection is reversed.
The EIA RS-485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end
across the signal wires (see Figure 8.2-1). Some devices may be able to provide the bus
terminating resistors by different connection or configuration arrangements, in which case
separate external components will not be required. However, this product does not provide such a
facility, so if it is located at the bus terminus then an external termination resistor will be required.
EIA RS-485
The EIA RS-485 standard requires that each device is directly connected to the physical cable that
is the communications bus. Stubs and tees are expressly forbidden, such as star topologies. Loop
bus topologies are not part of the EIA RS-485 standard and are forbidden by it also.
Two-core screened cable is recommended. The specification of the cable will be dependent on the
application, although a multi-strand 0.5mm2 per core is normally adequate. Total cable length must
not exceed 500m. The screen must be continuous and connected to ground at one end, normally
at the master connection point; it is important to avoid circulating currents, especially when the
cable runs between buildings, for both safety and noise reasons.
This product does not provide a signal ground connection. If a signal ground connection is present
in the bus cable then it must be ignored, although it must have continuity for the benefit of other
devices connected to the bus. At no stage must the signal ground be connected to the cables
screen or to the product’s chassis. This is for both safety and noise reasons.
8.2.1.4 Biasing
It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal
level has an indeterminate state because the bus is not being actively driven. This can occur when
all the slaves are in receive mode and the master is slow to turn from receive mode to transmit
mode. This may be because the master purposefully waits in receive mode, or even in a high
impedance state, until it has something to transmit. Jabber causes the receiving device(s) to miss
the first bits of the first character in the packet, which results in the slave rejecting the message
and consequentially not responding. Symptoms of these are poor response times (due to retries),
increasing message error counters, erratic communications, and even a complete failure to
communicate.
Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1V. There
should only be one bias point on the bus, which is best situated at the master connection point.
The DC source used for the bias must be clean; otherwise noise will be injected. Note that some
devices may (optionally) be able to provide the bus bias, in which case external components will
not be required.
Note!
It is extremely important that the 120Ω termination resistors are fitted. Failure to do so will
result in an excessive bias voltage that may damage the devices connected to the bus.
As the field voltage is much higher than that required, NARI-RELAYS cannot assume
responsibility for any damage that may occur to a device connected to the network as a
result of incorrect application of this voltage.
Ensure that the field voltage is not being used for other purposes (i.e. powering logic inputs)
as this may cause noise to be passed to the communication network.
To use the rear port with IEC60870-5-103 communication, the relay’s relevant settings must be
configured. To do this use the keypad and LCD user interface. In the submenu “EQUIP
SETTINGS”, set the parameter [Protocol] as “0001”, then set the baud rate of each rear port.
To use the rear port with Modbus communication, the relay’s relevant settings must be configured.
To do this use the keypad and LCD user interface. In the submenu “EQUIP SETTINGS”, set the
parameter [Protocol] as “0008”, then set the baud rate of each rear port.
The IEC60870-5-103 interface over serial port is a master/slave interface with the relay as the
slave device. It is properly developed by NARI-RELAYS.
z Initialization (reset)
z Time synchronization
z General interrogation
z Disturbance records
z General Commands
Two EIA RS-485 standardized ports are available for IEC60870-5-103 in this relay. The
transmission speed is optional: 4800 bit/s, 9600 bit/s, 19200 bit/s or 38400 bit/s.
The link layer strictly abides by the rules defined in the IEC60870-5-103.
8.3.2 Initialization
Whenever the relay has been powered up, or if the communication parameters have been
changed, a reset command is required to initialize the communications. The relay will respond to
either of the two reset commands (Reset CU or Reset FCB), the difference is that the Reset CU
will clear any unsent messages in the relay’s transmit buffer.
The relay will respond to the reset command with an identification message ASDU 5, the COT
(Cause Of Transmission) of this response will be either Reset CU or Reset FCB depending on the
nature of the reset command.
In addition to the above identification message, if the relay has been powered up it will also
produce a power up event.
If the relay clock is synchronized using the IRIG-B input then it will not be possible to set the relay
time using the IEC60870-5-103 interface.
8.3.4 Setting
Settings are transferred via Generic Service. If the setting [En_Remote_Cfg] in the submenu
“EQUIP SETTINGS” is set as 0, to modify settings remotely will not be allowed. Moreover, “EQUIP
SETTINGS” & “SYSTEM SETTINS” are not allowed to be modified remotely whether the setting
[En_Remote_Cfg] is set as “1” or “0”.
The following tables contain a complete listing of all events produced by the relay.
Alarm reports consist of self-check alarm report and equipment operation alarm reports, which are
Referring the IEC60870-5-103 standard can get the enough details about general interrogation.
The generic services supported by this protective device are shown in the following table.
8.4.1 Overview
The RCS-985BT relay support several communications protocols to allow the connection to the
equipment such as personal computers, RTUs, SCADA masters, and programmable logic
controllers. The Modicon Modbus RTU protocol is the most basic protocol supported by the
RCS-985BT. Modbus is available via RS485 serial links or via Ethernet (using the Modbus/TCP
specification).
The following information is provided primarily for users who wish to develop their own master
communication drivers and applies to the serial Modbus RTU protocol. The characteristics are
listed below:
z Physical Layer Setup: RS485, 1 start bit,8 data bits, no bit for parity,1 stop bit
z Parity: no
The following Modbus function codes are supported but re-defined by the relay:
This function reads the ON/OFF status of discrete inputs in the slave. The status in the response
message is packed as one input per bit of the data field. Status is indicated as: 1 = ON; 0 = OFF.
The LSB of the first data byte contains the input addressed in the query. The other inputs follow
toward the high order end of this byte, and from ‘low order to high order’ in subsequent bytes.
Example 1: If the master wants to fetch Trip Information (0000H~0003H), the query frame would
be as follows (Suppose the slave address was 1):
01 02 00 00 00 04 79 C9
Start Start
Slave Function Num of Num of
Register Register CRC Lo CRC Hi
Addr Code Status Hi Status Lo
Addr Hi Addr Lo
The response fame would be as follows (Suppose the value of 0000H~0003H equal to 1,1,0,1
respectively):
01 02 01 0B E0 4F
Function
Slave Addr Length Status CRC Lo CRC Hi
Code
Example 2: If the master wants to fetch Trip Information (0002H~000DH), the query frame would
be as follows (Suppose the slave address was 1):
01 02 00 02 00 0C D9 CF
Start Start
Slave Function Num of Num of
Register Register CRC Lo CRC Hi
Addr Code Status Hi Status Lo
Addr Hi Addr Lo
The response fame would be as follows (Suppose the value of 0002H~000DH equal to
1,1,0,1,0,0,1,0,1,1,1,0 respectively):
01 02 02 07 4B FB BF
Function
Slave Addr Length Status Hi Status Lo CRC Lo CRC Hi
Code
The metering values in the response message are packed as two bytes per register. For each
register, the first byte contains the high order bits and the second contains the low order bits.
8.4.3.3 Tr Metering
1. Protection Configuration
2. Tr System Settings
101CH U2n_VT_Br1_ST1 V
101DH U1n_VT_Br2_ST1(decimal digits=2) kV
101EH U2n_VT_Br2_ST1 V
101FH I1n_CT_HVS_ST1(integer) A
1020H I2n_CT_HVS_ST1 A
1021H I1n_CT_Br1_ST1(integer) A
1022H I2n_CT_Br1_ST1 A
1023H I1n_CT_Br2_ST1(integer) A
1024H I2n_CT_Br2_ST1 A
1025H I1n_CT_NP_Br_ST1(integer) A
1026H I2n_CT_NP_Br_ST1 A
Bit0:Yyy12_Conn_ST1
Bit1:Ddd12_Conn_ST1
Control
1027H Bit2:Dyy11_Conn_ST1
Word
Bit3:Ydd11_Conn_ST1
Bit4:Dyy1_Conn_ST1
8.4.5 Diagnostics
Modbus function 08 provides a series of tests for checking the communication system between the
master and slave, or for checking various internal error conditions within the slave.
The function uses a two–byte sub-function code field in the query to define the type of test to be
performed. The slave echoes both the function code and sub-function code in a normal response.
The listing below shows the sub-function codes supported by the equipment.
Code Name
00H Return Query Data
01H Restart Comm Option
04H Force Listen Only Mode
0BH Return Bus Message Count
0CH Return Bus Comm. Error Count
0DH Return Bus Exception Error Cnt
0EH Return Slave Message Count
0FH Return Slave No Response Cnt
a normal response. If the slave receives the query without a communication error but the salve
cannot handle it (for example, if the request is to read a non–existent coil or register), the slave will
return an exception response informing the master of the nature of the error.
The listing below shows the exception codes supported by the equipment.
Code Description
01H Illegal Function
02H Illegal Data Address
03H Illegal Data Value
07H Negative Acknowledge
Chapter 9 Installation
The equipment must be shipped, stored and installed with the greatest care.
Choose the place of installation such that the communication interface and the controls on the
front of the device are easily accessible.
Air must circulate freely around the equipment. Observe all the requirements regarding place of
installation and ambient conditions given in this instruction manual.
Take care that the external wiring is properly brought into the equipment and terminated correctly
and pay special attention to grounding. Strictly observe the corresponding guidelines contained in
this section.
Modules and units may only be replaced by correspondingly trained personnel. Always observe
the basic precautions to avoid damage due to electrostatic discharge when handling the
equipment.
In certain cases, the settings have to be configured according to the demands of the engineering
configuration after replacement. It is therefore assumed that the personnel who replace modules
and units are familiar with the use of the operator program on the service PC.
Danger!
Only insert or withdraw the PWR module while the power supply is switched off. To this
end, disconnect the power supply cable that connects with the PWR module.
Warning!
Only insert or withdraw the other boards while the power supply is switched off.
Warning!
The modules of the RCS-985BT may only be inserted in its own slots. Components can be
damaged or destroyed by inserting boards in the wrong slots.
Danger!
Improper handling of the equipment can cause damage or an incorrect response of the
equipment itself or the primary plant.
Warning!
Industry packs and ribbon cables may only be replaced or the positions of jumpers be
changed on a workbench appropriately designed for working on electronic equipment. The
RCS-985BT modules, bus backplanes are sensitive to electrostatic discharge when not in
the unit's housing.
z Only hold electronic boards at the edges, taking care not to touch the components.
z Only works on boards that have been removed from the cubicle on a workbench designed for
electronic equipment and wear a grounded wristband. Do not wear a grounded wristband,
however, while inserting or withdrawing units.
z Always store and ship the electronic boards in their original packing. Place electronic parts in
electrostatic screened packing materials.
Check that the consignment is complete immediately upon receipt. Notify the nearest
NARI-RELAYS Company or agent, should departures from the delivery note, the shipping papers
or the order be found.
Visually inspect all the material when unpacking it. When there is evidence of transport damage,
lodge a claim immediately in writing with the last carrier and notify the nearest NARI-RELAYS
Company or agent.
If the equipment is not going to be installed immediately, store all the parts in their original packing
in a clean dry place at a moderate temperature. The humidity should not exceed 90% at a
maximum temperature of +55°C; the permissible storage temperature range in dry air is -40°C to
+70°C.
The necessary mounting kits will be provided, including screws, pincers and assembly
instructions.
A suitable drill and spanners are required to secure the cubicles to the floor using the plugs
provided (if RCS-985BT is mounted in cubicles).
The place of installation should permit easy access especially to front of the device, i.e. to the
human-machine interface of the equipment.
There should also be free access at the rear of the equipment for additions and replacement of
electronic boards.
Since every piece of technical equipment can be damaged or destroyed by inadmissible ambient
conditions, such as:
1) The location should not be exposed to excessive air pollution (dust, aggressive substances).
2) Severe vibration, extreme changes of temperature, high levels of humidity, surge voltages of
high amplitude and short rise time and strong induced magnetic fields should be avoided as
far as possible.
The equipment can in principle be mounted in any attitude, but it is normally mounted vertically
(visibility of markings).
Warning!
Excessively high temperature can appreciably reduce the operating life of the RCS-985BT.
The equipment adopts IEC standard chassis and is rack with modular structure. RCS-985BT
equipment is IEC 12U high and 19” wide. Figure 9.6-1 shows its dimensions and Figure 9.6-2
shows the panel cut-out.
465
450
531.5
457.2
190.5
8 - Φ 6.8
Note!
It is necessary to leave enough space top and bottom of the cut-out in the cubicle for heat
emission of the RCS-985BT.
As mentioned former (refer to Chapter 5), all modules must be plugged into the proper slots of the
RCS-985BT respectively. The safety instructions must be abided by when installing the boards,
see section 9.2.
In the case of equipment supplied in cubicles, place the cubicles on the foundations that have
been prepared. Take care while doing so not to jam or otherwise damage any of the cables that
have already been installed. Secure the cubicles to the foundations.
On the other hand, electronic apparatus can transmit interference that can disrupt the operation of
other apparatus.
In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.
Note!
All these precautions can only be effective if the station ground is of good quality.
Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non-corroding.
Note!
If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of it
forming a resonant circuit at certain frequencies that would amplify the transmission of
interference by the devices installed and also reduce their immunity to induced
interference.
Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (see Figure 9.7-1).
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
Note!
For metallic connections please observe the voltage difference of both materials according
to the electrochemical code.
The cubicle ground rail must be effectively connected to the station ground rail by a grounding strip
(braided copper).
There are some ground terminals on some connectors of the RCS-985BT, and the sign is “GND”.
All the ground terminals are connected in the cabinet of this relay. So, the ground terminal on the
rear panel (see Figure 9.7-2) is the only ground terminal of this device.
The grounding strips must therefore be of (preferably tinned) braided copper and not round copper
conductors, as the cross-section of round copper would have to be too large.
Proper terminations must be fitted to both ends (press/pinch fit and tinned) with a hole for bolting
them firmly to the items to be connected.
The surfaces to which the grounding strips are bolted must be electrically conducting and
non-corroding.
When using screened cabling always use 360° full screen cable bushing to ensure screen
coupling. Ensure that all signals of the single circuit are in the same single cable. Avoid mixing
current and voltage measuring signals in the same cable. Also use separate cables for control and
measuring circuits.
Auxiliary power cords cross can be directly screwed fixed on the rear panel of DC board.
Welding terminals; those devices are supplied with sufficient M4 screws for making connections to
the rear mounted terminal blocks using ring terminals, with a recommended maximum of two ring
terminals per terminal.
To meet the insulation requirements of the terminal block, for the sake of safety, an insulating
sleeve should be fitted over the ring terminal after crimping.
The wire used for all connections to the welding terminal blocks and heavy duty terminal blocks,
except the RS-485 port, should have a minimum voltage rating of 300Vrms.
It is recommended that the auxiliary power circuit wiring should be protected by using a 16A high
rupture capacity (HRC) fuse of type NIT or TIA. For safety reasons, current transformer circuits
must never be open.
When using galvanic connection between the synchronizer equipment and communication
equipment or point-to-point galvanic connection between two equipments it is essential that the
cable installation is carefully done. This is true regardless of type of module used, only the
possible length of the cable differs. The factors that must be taken into account is the susceptibility
for noise disturbance, due to that the levels of the communication signal are very low. For a best
result, a cable with twisted pairs with screen should be used.
The IRIG-B input and BNC connector have a characteristic impedance of 50Ω. It is recommended
that connections between the IRIG-B equipment and the relay are made using coaxial cable of
type RG59LSF with a halogen free, fire retardant sheath.
Short term connections to the EIA(RS)232 port, located at the bottom of face cover, can be made
using a screened multi-core communication cable up to 15m long, or a total capacitance of 2500pF.
The cable should be terminated at the relay end with a 9-way, metal shelled, D-type male plug.
Chapter 10 Commissioning
This relay is fully numerical in their design, implementing all protection and non-protection
functions in software. The relay employ a high degree of self-checking and in the unlikely event of
a failure, will give an alarm. As a result of this, the commissioning test does not need to be as
extensive as with non-numeric electronic or electro-mechanical relays.
To commission numerical relays, it is only necessary to verify that the hardware is functioning
correctly and the application-specific software settings have been applied to the relay.
Blank commissioning test and setting records are provided at the end of this manual for
completion as required.
Before carrying out any work on the equipment, the user should be familiar with the contents of the
safety and technical data sections and the ratings on the equipment’s rating label.
Warning!
Warning!
Only qualified personnel shall work on and around this equipment after becoming
thoroughly familiar with all warnings and safety notices of this manual as well as with the
applicable safety regulations.
z The earthing screw of the device must be connected solidly to the protective earth conductor
before any other electrical connection is made.
z Hazardous voltages can be present on all circuits and components connected to the supply
voltage or to the measuring and test quantities.
z Hazardous voltages can be present in the device even after disconnection of the supply
voltage (storage capacitors!)
z The limit values stated in the technical data must not be exceeded at all, not even during
testing and commissioning.
z When testing the device with secondary test equipment, make sure that no other
measurement quantities are connected. Take also into consideration that the trip circuits and
maybe also close commands to the circuit breakers and other primary switches are
disconnected from the device unless expressly stated.
Danger!
Current transformer secondary circuits must have been short-circuited before the current
leads to the device are disconnected.
Warning!
Primary test may only be carried out by qualified personnel, who are familiar with the
commissioning of protection system, the operation of the plant and safety rules and
regulations (switching, earthing, etc.)
Multifunctional dynamic current and voltage injection test set with interval timer (For example,
Omicron CMC356).
Multimeter with suitable AC current range and AC/DC voltage ranges of 0-440V and 0-250V
respectively.
Note!
Modern test set may contain many of the above features in one unit.
Optional equipment:
An electronic or brushless insulation tester with a DC output not exceeding 500 V (for
insulation resistance test when required).
A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).
EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested).
At the same time, the calculated settings, substation configuration diagram, the protective device
diagram and the instruction manual is essential to test the protective device.
The relay has to be set before the testing can start. Only the functions that are used should be
tested.
All used setting groups should be tested. The user can release the functions to be tested and
prevent other functions from operation by setting the corresponding parameters.
The setting checks ensure that all of the application-specific protection settings (i.e. both the
protection’s function and programmable scheme logic settings), for the particular installation, have
been correctly applied to the protection.
When commissioning a RCS-985BT for the first time, sufficient time should be allowed to become
familiar with the method by which the settings are applied. The Chapter 7 contains a detailed
description of the menu structure of this relay.
With the front cover in place all keys are accessible. All menu cells can be read. LED indicators
and alarms can be reset. Protection or configuration settings can be changed, or fault and event
records cleared. However, menu cells will require the appropriate password to be entered before
changes can be made.
These product checks cover all aspects of the relay which should be checked to ensure that it has
not been physically damaged prior to commissioning, is functioning correctly and all input quantity
measurements are within the stated tolerances.
If the application-specific settings have been applied to the relay prior to commissioning, it is
advisable to make a copy of the settings so as to allow them restoration later. This could be done
by extracting the settings from the relay itself via printer or manually creating a setting record.
The following tests are necessary to ensure the normal operation of the equipment before it is first
put into service.
Hardware tests
These tests are performed for the following hardware to ensure that there is no hardware
defect. Defects of hardware circuits other than the following can be detected by
self-monitoring when the DC power is supplied.
Function tests
These tests are performed for the following functions that are fully software-based. Tests of
the protection schemes and fault locator require a dynamic test set.
Timers test
Conjunctive tests
The tests are performed after the relay is connected with the primary equipment and other
external equipment.
On load test.
After unpacking the product, check for any damage to the relay case. If there is any damage, the
internal module might also have been affected, contact the vendor. Following items listed is
necessary.
Protection panel
Carefully examine the protection panel, protection equipment inside and other parts inside to
see that no physical damage has occurred since installation.
The rated information of other auxiliary protections should be checked to ensure it is correct
Panel wiring
Check the conducting wire which is used in the panel to assure that their cross section
meeting the requirement.
Carefully examine the wiring to see that they are no connection failure exists.
Label
Check all the isolator binary inputs, terminal blocks, indicators, switches and push buttons to
make sure that their labels meet the requirements of this project.
Check each plug-in module of the equipments on the panel to make sure that they are well
installed into the equipment without any screw loosened.
Earthing cable
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator binary inputs and push buttons
work normally and smoothly.
Insulation resistance tests are only necessary during commissioning if it is required for them to be
done and they have not been performed during installation.
Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, The circuits need to be tested should include:
DC power supply
Output contacts
Communication ports
Test method:
To unplug all the terminals sockets of this protective device, and do the Insulation resistance test
for each circuit above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected
to the protection
In general, the jumpers of the relay have been set correctly before sent to user. While, checking
the jumpers is a good habit before the relay is brought to service.
Check that the external wiring is correct to the relevant relay diagram and scheme diagram.
Ensure as far as practical that phasing/phase rotation appears to be as expected.
Check the wiring against the schematic diagram for the installation to ensure compliance with the
customer’s normal practice.
The relay can be operated from either 110/125Vdc or 220/250Vdc auxiliary supply depending on
the relay’s nominal supply rating. The incoming voltage must be within the operating range
specified in the following table, before energizing the relay, measure the auxiliary supply to ensure
it within the operating range.
It should be noted that the relay can withstand an AC ripple of up to 15% of the upper rated voltage
on the DC auxiliary supply.
Warning!
Energize the relay only if the auxiliary supply is within the specified operating ranges.
The current and voltage transformer connections must remain isolated from the relay for these
checks. The trip circuit should also remain isolated to prevent accidental operation of the
associated circuit breaker.
The liquid crystal display (LCD) is designed to operate in a wide range of substation ambient
temperatures. For this purpose, this relay has an automatic “LCD contrast” adjusting feature,
which is capable to adjust LCD contrast automatically according to the ambient temperature.
Connect the relay to DC power supply correctly and turn the relay on. Check program version and
forming time displayed in command menu to ensure that are corresponding to what ordered.
If the time and date is not being maintained by substation automation system, the date and time
should be set manually.
Set the date and time to the correct local time and date using menu item “CLOCK”.
In the event of the auxiliary supply failing, with a battery fitted on CPU board, the time and date will
be maintained. Therefore when the auxiliary supply is restored the time and date will be correct
and not need to set again.
To test this, remove the auxiliary supply from the relay for approximately 30s. After being
re-energized, the time and date should be correct.
On power up, the green LED “HEALTHY” should have illuminated and stayed on indicating that
the relay is healthy.
The relay has latched signal relays which remember the state of the trip, auto-reclosing when the
relay was last energized from an auxiliary supply. Therefore these indicators may also illuminate
when the auxiliary supply is applied. If any of these LEDs are on then they should be reset before
proceeding with further testing. If the LED successfully reset, the LED goes out. There is no testing
required for that that LED because it is known to be operational.
It is likely that alarms related to voltage transformer supervision will not reset at this stage.
Apply the rated DC Power supply and check that the “HEALTHY” LED is lighting in green. We
need to emphasize that the “HEALTHY” LED is always lighting in operation course except that the
equipment find serious errors in it.
Produce one of the abnormal conditions listed in Table 4.4-2, the “ALARM” LED will light in yellow.
When abnormal condition reset, the “ALARM” LED extinguishes.
The “TRIP” LED can be tested by initiating a manual circuit breaker trip from the relay. However
the “TRIP” LED will operate during the setting checks (performed later). Therefore no further
testing of the “TRIP” LED is required at this stage.
This test verified that the accuracy of current measurement is within the acceptable tolerances.
Apply current equal to the line current transformer secondary winding rating to each current
transformer input of the corresponding rating in turn, see the following table or external connection
diagram for appropriate terminal numbers, checking its magnitude using a multimeter/test set
readout. The corresponding reading can then be checked in the relays menu.
The measurement tolerant error is in range of ±2.5% or 0.02In, whichever is greater. However an
additional allowance must be made for the accuracy of the test equipment being used.
This test verified that the accuracy of voltage measurement is within the acceptable tolerances.
Apply rated voltage to each voltage transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the relays menu.
The measurement tolerant error is in range of ±2.5% or 0.1V, whichever is greater. However an
additional allowance must be made for the accuracy of the test equipment being used.
This test checks that all the binary inputs on the relay are functioning correctly.
The binary inputs should be energized one at a time, see external connection diagrams for
terminal numbers.
Ensure that the voltage applied on the binary input must be within the operating range.
The status of each binary input can be viewed using menu item “CPU BI STATE” or “MON BI
STATE”. Sign “1” denotes an energized input and sign “0” denotes a de-energized input.
This test checks that all the output relays are functioning correctly. Connect a continuity tester
across the terminals corresponding to each output relays as given in external connection diagram.
Note!
The terminals mentioned below are of the relay other than terminals mounted on panel. It
is more convenient to connect test set through terminals mounted on panel.
Switch off the power of the protection equipment, and then normally closed watchdog contacts (i.e.
equipment being blocked contacts) can be tested, which are closed when the protection
equipment is powered off.
Simulate various abnormalities of equipment operation, such as VT circuit failure, CT circuit failure
and etc., and the corresponding alarm contact can be tested.
Simulate various faults to make every protection operate, and the corresponding signal contact
can be tested.
Please first configure one tripping matrix of some one protection to select all tripping output
channels. Then simulate a fault to make the protection operates and all tripping output contacts
can be tested
2. Fault related information, such as the maximum fault current, fault phase, etc.
3. Wave record of the variation of all the analog quantity and binary inputs during the course of
fault occurrence.
However, these checks can only be carried out if there are no restrictions preventing the
tenderization of the plant being protected.
Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has
been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the protection in order to
perform any of the foregoing tests, it should be ensured that all connections are replaced in
accordance with the relevant external connection or scheme diagram. Confirm current transformer
wiring.
If the protection is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. If a test block is installed, remove the
test plug and replace the cover so that the protection is put into service.
Ensure that all event records, fault records, disturbance records and alarms have been cleared
and LED’s has been reset before leaving the protection.
Chapter 11 Maintenance
This relays are self-supervised and so require less maintenance than earlier designs of relay. Most
problems will result in an alarm so that remedial action can be taken. However, some periodic
tests should be done to ensure that the relay is functioning correctly and the external wiring is
intact.
The relay is almost completely self-supervised. The circuits which can not be supervised are
binary input, output circuits and human machine interfaces. Therefore regular testing can be
minimized to checking the unsupervised circuits.
When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the alarm record.
Failures detected by supervision are traced by checking the “ALARM REPORT” screen on the
LCD. See section 4.1 for the details of the alarm events.
If the failure is identified to be in the relay module and the user has spare modules, the user can
recover the protection by replacing the failed modules.
Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.
Check that the replacement module has an identical module name (AI, PWR, CPU, MON, SIG, BI,
BO, etc.) and hardware type-form as the removed module. Furthermore, the CPU module
replaced should have the same software version. And AI and PWR module replaced should have
the same ratings.
The module name is indicated on the top front of the module. The software version is indicated in
LCD menu “VERSION”.
Warning!
Units and modules may only be replaced while the supply is switched off and only by
appropriately trained and qualified personnel. Strictly observe the basic precautions to
guard against electrostatic discharge.
Warning!
When handling a module, take anti-static measures such as wearing an earthed wrist band
and placing modules on an earthed conductive mat. Otherwise, many of the electronic
components could suffer damage. After replacing the CPU module, check the settings.
Danger!
After replacing modules, be sure to check that the same configuration is set as before the
replacement. If this is not the case, there is a danger of the unintended operation of
switchgear taking place or of protections not functioning correctly. Persons may also be
put in danger.
1. Replacing a module
3) Short circuit all AC current inputs and disconnect all AC voltage inputs
4) According to different module to take different operating steps, and please refer to following.
WARNING: Hazardous voltage can be present in the DC circuit just after switching off the
2) Unplug the ribbon cable on the front panel by pushing the catch outside.
6) After replacing the CPU module, input the application-specific setting values again.
Each relay has a battery to maintain status data and the correct time when the auxiliary supply
voltage fails. The data maintained includes event, fault and disturbance records.
This battery will periodically need changing. If the battery-backed facilities are not required to be
maintained during an interruption of the auxiliary supply, the steps below can be followed to
remove the battery.
CAUTION: Before carrying out any work on the equipment, the user should be familiar with
the contents of the safety and technique data sections and the ratings on the equipment’s
rating label.
2. Gently extract the battery from its socket. If necessary, use a small, insulated screwdriver to
prize the battery free.
3. Ensure that the metal terminals in the battery socket are free from corrosion, grease and dust.
4. The replacement battery should be removed from its packaging and placed into the battery
holder, taking care to ensure that the polarity markings on the battery agree with those
adjacent to the socket as shown as below.
Note!
Ensure that the battery is securely held in its socket and that the battery terminals are
making good contact with the metal terminals of the socket.
11.6 Cleaning
Before cleaning the relay, ensure that all AC/DC supplies, current transformer connections are
isolated to prevent any chance of an electric shock whilst cleaning. Use a smooth cloth to clean
the front panel. Do not use abrasive material or detergent chemicals.
The equipment may be cleaned using a lint-free cloth moistened with clean water. The use of
detergents, solvents or abrasive cleaners is not recommended as they may damage the relay’s
surface and leave a conductive residue.
11.7 Storage
The spare relay or module should be stored in a dry and clean room. Based on IEC standard
60255-6 the storage temperature should be from -40°C to +70°C, but the temperature of from 0oC
to +40oC is recommended for long-term storage.
12.1 Decommissioning
1. Switching off
To switch off the protective device, switch off the external miniature circuit breaker of the power
supply.
2. Disconnecting Cables
Disconnect the cables in accordance with the rules and recommendations made by relational
department.
Danger!
Before disconnecting the power supply cables that connected with the DC module of the
protective device, make sure that the external miniature circuit breaker of the power supply
is switched off.
Danger!
Before disconnecting the cables that are used to connect analog input module with the
primary CTs and VTs, make sure that the circuit breaker for the primary CTs and VTs is
switched off.
3. Dismantling
The protective device rack may now be removed from the system cubicle, after which the cubicles
may also be removed.
Danger!
When the station is in operation, make sure that there is an adequate safety distance to
live parts, especially as dismantling is often performed by unskilled personnel.
12.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste.
Note!
Strictly observe all local and national regulations when disposing of the device.
Manual History
Modification Recorder