SK 1-Waterproof Dual-Relay Access Control: User Manual

The document provides information about the SK1 dual-entry access controller, including its keypad, proximity card reader, wiring connections, relay functions, and operation modes. The SK1 supports up to 1100 users with card, PIN, or combined authentication. It has two relays that can be used to operate locks, alarms, lights, or a door bell in either pulse or toggle mode. The zone 2 wiring can connect to a door bell to activate it when pressing the # key on the keypad.

Uploaded by

jose pasten
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
516 views1 page

SK 1-Waterproof Dual-Relay Access Control: User Manual

The document provides information about the SK1 dual-entry access controller, including its keypad, proximity card reader, wiring connections, relay functions, and operation modes. The SK1 supports up to 1100 users with card, PIN, or combined authentication. It has two relays that can be used to operate locks, alarms, lights, or a door bell in either pulse or toggle mode. The zone 2 wiring can connect to a door bell to activate it when pressing the # key on the keypad.

Uploaded by

jose pasten
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

INTRODUCTION Keypad 12 Key (3*4) Wiring Remarks: the Zone 2, it can be used to operate the door bell when

12 Key (3*4) Wiring Remarks: the Zone 2, it can be used to operate the door bell when no need
to operate a second door. The wiring is connecting the door bell to NO2 and.
The SK1 is a dual- entry multi-function Access Controller with integrated Proximity Card Reader EM Wall Anchors
Wire Color Function Notes COM2. Press #, the keypad will send out a switching signal to the door bell, as
keypad and card reader. It is designed and manufactured to perform in a wide Radio Technology 125 KHz Industry Standard Proximity Card long as you press the” #”, the door bell will continuous operate, it will stop
Basic Standalone Wiring
SK 1-Waterproof range of indoor, outdoor, and harsh environments.

The SK1 supports up to 1100 users in multiple access configurations (Card,


Read Range 3-6cm
Electric Lock, Exit Button,
Screw Driver Red AC&DC 12~24V DC/12-18V AC Regulated Power Input
until you release the ” #”

Wiring Connections Black AC&DC 12~24V DC/12-18V AC Regulated Power Input Connect the negative pole of the lock to NC is for Fail –safe lock.
PIN, or Card + PIN). The built in card reader supports EM 125KHz frequency DOTL, External Alarm, Door Bell
Dual-relay Access Control cards.
Relay Two (NO, NC, COM)
Grey&Black
Blue
GND
NO 1
Negative Pole
Normally Open Relay 1 output
Connect the negative pole of the lock to NO is for Fail-secure lock.

White COM1 Common Connection for Relay 1 output


Both of the two relays on board can operate in Pulse Mode (suitable for Adjustable Relay Output Time 1-99 Seconds (5 seconds default) FUNCTION DESCRIPTION
access control) or Toggle Mode (suitable for arming/disarming alarms, Adjustable Alarm Output Time 1-3 minutes (1 minute default) Manager Card Green NC 1 Normally closed Relay 1 Output
Relay operation (Pulse mode and Toggle mode)
switching lights, machines….etc) Lock Output Load 3 Amp Maximum Yellow OPEN1 Request to Exit input 1(REX) Both of the two relays on board can operate in Pulse Mode (suitable for
Alarm Output Load 3 Amp Maximum Advanced Input and Output Features access control) or Toggle Mode (suitable for arming/disarming alarms,
The SK1 offers advanced programming features like: block enrollment, Blue&Black NO 2 Normally Open Relay 2 Output switching lights, machines….etc) SK1- Simplified Instruction
advanced relay programming, and door bell.These features make it an ideal Environment Meets IP66
White&Black COM2 Common Connection for Relay 2 Output Function Description Operation
choice for door access not only for small shops and domestic households but Operating Temperature -30℃~60℃,or -22°F~140°F
10%~90% Non-Condensing Green&Black NC 2 Normally closed Relay 2 Output Every time a valid tag/card read or Pin input in Pulse Mode, the relay will
also for commercial and industrial applications such as factories, warehouses, Operating Humidity (Master Code) #
operate, for the pre-set relay pulse time.
laboratories, banks and prisons. INSTALLATION Yellow&Black OPEN2 Request to Exit input 2(REX) Enter the Programming Mode (666666 is the default factory
Physical Zinc-Alloy Enclosure Grey Alarm Alarm Negative master code)
Surface Finish Powder Coat > Remove the back cover from the unit Every time a valid tag/card read or Pin input in Toggle Mode, the relay
Features > Drill 2 holes(A,C) on the wall for the screws and one hole for the cable Brown D_IN Door status detecting changes state, which will not turn back until read card or input pin again. 0 (New Master Code) # (Repeat
Dimensions L 120 X W 76 X H 25 (mm)
> Waterproof(IP66) Unit Weight 600g > Knock the supplied rubber bungs to the screw holes(A,C) Change the Master Code New Master Code) # (code: 4-6
Shipping Weight 700g > Fix the back cover firmly on the wall with 4 flat head screws Master Card digits)
> Vandal Resistant Enclosure
> Thread the cable through the cable hole(B) Connection Diagram SK1 master can use master cards to program user cards into and out of the
> Backlit Keypad Power 1 (Read Card) # ( for Zone 1)
> Attach the unit to the back cover. system. There are two pre-programmed master cards (an Add Card, and a Add Card User
> Multi-color LED status display 12-24V DC/12-18V AC/5A 2 (Read Card) # ( for Zone 2)
SK 1 Delete Card) to allow rapid card enrollment. It is for Zone 1 only.
> Two Programmable Relay Output
Carton Inventory
> 1100 Users (Card/PIN/ Card+PIN) 1 (User ID 1~1000) # (PIN)#
Anti Tamper Alarm
> Card Block enrollment Grey&Black GND
( for Zone 1)
+ The SK1 uses a LDR (light dependent resistor) as an anti tamper alarm.
> Integrated Alarm Buzzer & Output Grey ALARM 1 (User ID 1001 ~1100) # (PIN) #
Exit Button of Zone 2
-
If the keypad is removed from the cover then the tamper alarm will operate. Add PIN User
> Low power consumption (55mA) A Yellow & Black OPEN2 Alarm ( for Zone 2)
> Anti-Tamper Alarm Exit Button of Zone 1
The PIN is any 4-6 digits between
Yellow OPEN1
> Latch Mode to hold door or gate open SK1 Access Controller 0000 ~ 999999
> Relay 2 supports external door bell Brown D_IN
Door Status Detecting
PROGRAMMING
> 12-24V DC/12-18V AC Power input Red AC&DC
Configure the Keypad 3 (Read Card) #
B Delete User
Black AC&DC Change the configure settings according to your application (optional). 3 (User ID) #
+
Specifications Blue & Black NO2 Electric Lock Diode Multiple configuration settings can be changed at one time: enter program Exit from the programming mode
-
mode, change desired settings, then exit program mode.
User Capacity 1100 Cards/PINS Diode IN4004 (For relay circuit protection) C
White & Black COM2 How to be granted access.
Zone 1 1000 Green & Black NC2 NO 2 Set Master Code Card User Read card
Zone 2 100 Blue NO1 COM 2 The 4-6 digit Master Code is used to prevent unauthorized access to the Enter (PIN) #
PIN User
Operating Voltage 12~24V DC / 12~18V AC Self Tapping Screws White COM1 Door Bell system. To interface with the SK1, the manager will need a Master Code
Green NC1
Door Bell installation & usage: (factory default code: 666666). We highly recommend immediate update
Idle Current 55mA Connect door bell with wires:NO2 COM2.
Press ‘#’,the SK1 reader will and recording of your Master Code.
User Manual Active Current 80mA send outa signal to the door bell.

Programming Step Keystroke Combination 1 User ID number # PIN # To delete Card users by user ID. To delete a Card and PIN user just 6 1 # OTHERS Sound and Light Indication
3 Read Card # or 3 User ID # To enable door open detection
1. Enter Program Mode (Master Code) # The ID number is any number This option can be used when a 3 User ID # delete the card It is optional to connect the D_IN Operation Status Red LED Green LED Bule LED Sounds
user has lost their card.
Using Master Cards
from 1~ 1000. line to LOCK1 or LOCK 2 Power on Flashing Short Single Beep
0 ( New Master Code) # To set users for Zone 2. ( 4 2 1 # )
2. Update Master Code The PIN is any 4~6 digits between The operation is the same as Zone 1. Keypad Lockout & Alarm Output options. If there are 10 invalid cards Using Master Card Stand by Flashing
( Repeat New Master Code) # 9 Input 8 digits or 10 digits Card
0000~999999 with the exception of or 10 incorrect PIN numbers in a 10 minute period either the keypad will (It is only available for Zone 1) Press Keypad Flashing Short Single Beep
To add PIN users number #
3. Exit Program Mode 1234 which is reserved. Users can To delete card users by card lockout for 10 minutes or the alarm will operate for 10 minutes, depending Enter Master
number Cards can be deleted continuously 1. (Read Master Add Card) ON Short Single Beep
be added continuously without To set Card user only.(in this mode, users can only be valid by card) on the option selected below. Code Entry Mode
without exiting from programming 2. (Read User Card)
SET ACCESS CONFIGURATION exiting programming mode as mode. Add a User Card Repeat Step 2 for additional user In program mode ON Single Flash Short Single Beep
4 1 2 # , Zone 1 Normal status: No keypad lockout
> Card or PIN (Default): The User must present a valid Card to the SK1 or follows: 1 User ID no 1 # PIN To set Card user only. 7 0 # (Factory default setting) cards
To set users for Zone 2. ( 4 2 0 # ) 4 2 2 # , Zone 2 or alarm Entered Program
enter their PIN code followed by the # key, in order to be granted access. # User ID no 2 # PIN # 3. (Read Master Add Card) ON Single Flash Short Single Beep
Entry is by Card only Keypad Lockout Step Successfully
> Card + PIN: The User must first present a valid Card to the SK1 and then 7 1 #
3 User ID number # To set Pin user for Zone 2 is the same as Zone 1, only the ID number is 1. (Read Master Delete Card) Entered Program
enter their PIN code followed by the # key, in order to be granted access. 1001-1100 for Zone 2. Alarm Output 7 2 # 3 Short Beeps
To delete PIN users Users can be deleted continuously 2. (Read User Card) Step Incorrectly
To set Card user for Zone 2 is the same as Zone 1, with the exception of Relay Setting (Pulse mode, Toggle mode)
without exiting programming mode. Alarm output time Delete a User Card Repeat Step 2 for additional user Exit from the
Programming Step Keystroke Combination adding Card users with auto-generated ID numbers and Block enrolment Pulse mode (Factory default) Flashing Short Single Beep
cards programming mode
1. Enter Program Mode (Master Code) # as below. To set the alarm output time (1-3 3. (Read Master Delete Card)
To change the PIN of a PIN user 8 1~3 # Entry Granted for
ID number # Old PIN # For Zone 1: 5 1 1~99 # minutes) Factory default is 1 minute ON Short Single Beep
2.Card or PIN (Note: This step must be done out 2 Read card # Zone 1
of programming mode) New PIN # Repeat new PIN # To add Card Users. (Method 1) For Zone 2: 5 2 1~99 #
Zone 1 410# Card can be added continuously Acoustic Signal
Auto-generated ID numbers. The door relay time is between Reset to Factory Default: Entry Granted for
Zone 2 420# without exiting programming mode. Pulse mode-Door relay time setting The acoustic signal can be set on or off. When on, the device will give the ON
To add Card Users. (Method 1) 1~99 seconds, the factory default This will reset the SK1 to the factory default but all card/PIN information will Zone 2
OR voice when press the keys; when off, the device will be in silent.
This is an easy way to enter cards 1 Read card # setting is 5 seconds. 1 means still be retained. This will also require reprogramming of the Master Add and Alarm Mode
2.Card + PIN Zone 1. 2 means Zone 2. 8 6 # (Factory default setting) Flashing Alarm
with auto-generated ID numbers. Card can be added continuously Normal status: On Delete Cards. NOTE: This is useful if the original Master Add and Delete Engaged
Zone 1 411# Card and PIN Mode
Zone 2 421# The ID number will start from 1 if no without exiting programming mode. Acoustic signal Off Cards have been lost.
8 7 #
user has been programmed To set users for Zone 1. ( 4 1 1 # )
3. Exit Program Mode Toggle mode Change Zone 2 to Door Bell 1. Power the SK1 down.
To add Card Users. (Method 2) Add the card as for a card user (When no need to operate a second door, Zone 2 can be set to operate 2. Press * and hold the button while power is restored to the keypad.
This is the alternative way to enter To Add a card and Pin user Press to exit from the For Zone 1: 5 1 0 # the Door Bell. The wiring is connecting the door bell to COM2 and NO2.
1 ID number # Card # Toggle mode 3. Release the button and wait until the amber LED shines.
User Settings cards using User ID Allocation. In (The PIN is any four digits between programming mode For Zone 2: 5 2 0 # Press #, the keypad will send the signal to the door bell.
this method a User ID is allocated The ID number can be any number 4. Present any 125KHz proximity EM card or the Master Add Card (provided)
To enter the programming mode 0000 & 999999 with the exception Then allocate the card a PIN as
Master code # to a card. Only one user ID can be among 1~ 1000. to the SK1. This card is now the Master Add Card.
of 1234 which is reserved.) follows: Read card 1234 # Zone 2 8 8 # (Factory default.)
To exit from the programming mode allocated to a single card. Door, Alarm, Acoustic Signal, Door Bell Settings 5. Present any 125KHz proximity EM card or the Master Delete Card (provided)
PIN # PIN # Door bell 8 9 # to the SK1. This card is now the Master Delete Card.
Note that to undertake the following programming, the master user To add a series cards 1 ID number # 8 digits or 10 Door Open Detection
To change a PIN in card and PIN To remove the alarm
must be logged in users-Block Enrolment Door Open Too Long (DOTL) warning. When used with an optional When the red LED begins to blink, the SK1 has been successfully reset.
digits Card number # mode (Method 1)
The card number must be Read Card Old PIN # magnetic contact or built-in magnetic contact of the lock, if the door is To reset the Door Forced Open
Note: Card quantity # Note that this is done outside Read valid card or Master Code #
consecutive. New PIN # New PIN # opened normally, but not closed after 1 minute, the inside buzzer will beep warning
When adding users, if the Card or Pin user has been enrolled already, you Card quantity is between 1-1000. programming mode so the user can Erase all Users
(This operation is only for Zone 1) automatically to remind people to close the door and continue for 1 minute
can not add it again on the same zone, or the device will give a bleep as undertake this themselves This will delete ALL User data of Zone1 or Zone 2 or Both.
before switching off automatically. To reset the Door Open Too Long Close the door or Read valid card
error. But it is ok to enroll the same card or Pin for the both zones. To delete Card users by cards. 3 Read card # Door Forced Open warning. When used with an optional magnetic contact warning 1, Enter Program Mode by press: *(Master Code) #.
To change a PIN in card and PIN or Master Code #
Note: Users can be deleted The device can automatically mode (Method 2) or built-in magnetic contact of the lock, if the door is forced open, the inside 2, Press 30000 # (for Zone 1)
continuously without exiting identify the card of Zone 1 or ID number # Old PIN # buzzer and alarm output will both operate. Or
Note that this is done outside
Factory default setting: Card or PIN mode programming mode. Zone 2. New PIN # New PIN # 2, Press 90000 # (for Zone 2)
programming mode so the user can
undertake this themselves To disable door open detection. 3, Exit: *
To set users for Zone 1. ( 4 1 0 # ) (Factory default setting) 6 0 #
All configuration data is retained.