Design - Column Design Zambonga

This document provides the design calculations for a tied column in a two-storey residential house in Pagadian City, Philippines. The column has an axial demand of 1550 kN, moment demand of 150 kN-m, and shear demand of 60 kN. The design checks that the column's axial and flexural capacities exceed the demands and that the vertical tie spacing of 400 mm satisfies code requirements. All capacity/demand ratios are compliant.

Uploaded by

Health Master
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
112 views

Design - Column Design Zambonga

This document provides the design calculations for a tied column in a two-storey residential house in Pagadian City, Philippines. The column has an axial demand of 1550 kN, moment demand of 150 kN-m, and shear demand of 60 kN. The design checks that the column's axial and flexural capacities exceed the demands and that the vertical tie spacing of 400 mm satisfies code requirements. All capacity/demand ratios are compliant.

Uploaded by

Health Master
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Prepared by : Arnel H. Sinconigue, C.

E
NSCP 2010 A.S Structural and Engineering Services Date : Oct. 13, 2011
Specification Structural Engineers and Project Manager PRC # : 116853
and TIN # : 406-365-953-000
Equation No. Sheet Content : Design of Tied Column Issued On: 3/24/2011
Date : Nov. 27, 2011 Issued At: Quezon City

Project Title : Two Storey Resedential House


Location : Brgy. Banale, Pagadian City, Zamboanga Del Sur

Client : Engr. Arnel H. Sinconiegue


Address : Dagat-Dagatan, Caloocan City, Metro Manila

Design Refference : NSCP Volume 1, Fourth Edition 2010


: Design of Reinforce Concrete, 2 ND Edition by Jack C. McCormac
: Fundamentals of Reinforced Concrete (Using USD Method, NSCP 2001) by Besavilla

I. Design Inputs :

Axial Demand, Pu = 1550.00 KN


Moment Demand, Mu = 150.00 KN.m
Shear Demand, Vu = 60.00 KN
Unsupported Length, lu = 2.90 m
409.4.2.2 Flexure Capacity Reduction Factor, ɸ = 0.65
409.4.2.3 Shear Capacity Reduction Factor, ɸ = 0.75
410.3.7.3 Compressive Block Deep Factor, β 1 = 0.85

II. Material Properties

Compressive Concrete Strength, fc' = 20.70 Mpa


Steel Yeild Strenght Main Bar, fy = 415.00 Mpa
Steel Yeild Strenght Tie Bar, fst = 415.00 Mpa
Modulus Elasticity of steel, Es = 200000.00 Mpa

III. Design Assumption

Column Width, b = 450.00 mm


Column Depth, h = 450.00 mm
Concrete cover, cc = 40.00 mm
Main Bar diameter, Ø = 25.00 mm
Tie Bar diameter , Øst 10.00 mm
410.10.1 Stee ratio, ρact = 0.02
410.13.1.3 Effective height factor, k 1.00
411.8.4.3 Modification factor, λ 1.00

IV. Desgin Calculation ( using static eqautions )

Calculation for concrete gross area, Ag

2
Ag = b*h 202500.00 mm

Calculation for steel area, Ast

2
Ast = ρact*Ag 4050.00 mm

Calculatin for db area, Adb

2
Adb = π*(Ø)2/4 490.87 mm

Calculation for No. of db, N

N = Ast / Adb 8.25 pcs say 8 pcs

Calculation for eccentricity, e

e = Mu/Pu 96.77 mm Small Eccentricity

Calculation for balance yeild strain, ϵy


ϵy = fy/Es 0.0021

Calculation for d1

d1 = h - cc - Ø/2 397.50 mm

Calculation for Neutral Axis, c

410.3.7.2 c = (0.003/(0.003+ϵy))*d 234.98 mm

Calculation for compressive block depth, a

410.3.7.1 a = β1*c 199.73 mm

V. Check for Slenderness Effect in Compression Members

Calculation for slenderness effect

410.11.1.2 r = 0.3*h 135.00 mm

410.11.1 klu/r = 21.48 Neglect Slendeness

VI. Internal forces and moment

Note : drawings are editable and it depends on what calculated above.


designers should arrange the reinforcement at his/her instance.
calculation done below are also variable it should be incorporated to the drawing.

y
0.003 0.85fc'
fs3 Fs3
ϵs3 a Pu
C C
Pu c
e Mu
d ϵs2
x fs2 Fs2

ϵs1 fs1 Fs1

b
Section Strain Nominal Stresses Forces & Moment Arms

Calculation of Strains,ϵs

Note: This formula was done by similar triangle

410.3.3 ϵs3 = 0.003( c - (cc+Ø/2))/c 0.0023

410.3.3 ϵs2 = 0.003*(c-h/2)/c 0.000127

ϵs1 = ϵy 0.0021

Calculation of Nominal Stresses

410.3.4 fs3 = ϵs3*Es 465.94 Mpa

410.3.4 fs2 = ϵs2*Es 25.47 Mpa

410.3.4 fs1 = ϵs1*Es 415.00 Mpa

Calculation of Internal Forces

N3 = 3.00 pcs
N2 = 2.00 pcs
N1 = 3.00 pcs
2
As3 = (π*(Ø)2/4)*(N3) 1472.62 mm
2
As2 = (π*(Ø)2/4)*(N2) 981.75 mm
2
As1 = (π*(Ø)2/4)*(N1) 1472.62 mm

Fs3 = As3*fs3 686.16 KN


Fs2 = As2*fs2 25.01 KN
Fs1 = As1*fs1 611.14 KN

410.3.7 C = 0.85fc'*a*b 1581.40 KN

VII. Check for Axial & Flexural Capacity/Demand ratio,C/D

Calculation for Axial Capacity, Pu

ΣFv = 0

Pu = Fs3 + Fs2 + C - Fs1 1681.43 KN

Calculation for Flexure Capacity, Mu

ΣM@ bottom steel = 0

Mu = Fs3(0.32) + Fs2(0.16) + C(0.273) - Pu(0.256) 224.85 KN.m

Calculation for Axial = C/D 1.08 Complaint


Calculation for Flexure = C/D 1.50 Compliant

VIII. Design Vertical Tie Spacing,S

407.11.5.2 16*Ø = 400.00 mm


407.11.5.2 48*Øst = 480.00 mm
407.11.5.4 least dimension, b = 450.00 mm

Actual Spacing = 400.00 mm

Check for shear capacity

Shear Demand, Vu = 60.00 KN

411.4.1.2 Vc = 0.17 * ( 1 + Nu/14Ag )*λ*sqrt(fc')*b*d 213.99 KN

411.6.6 0.5*ɸ*Vc = 80.25 KN Satisfy NSCP 407.11.5

411.2.1 ɸ*Vc = 160.50 KN Compliant

Calculation of min. shear reinforcement,Avmin

N.A N.A N.A mm2

Calculation for area of ties, Aøst

N.A N.A mm2

Calculation for number of ties, N

N.A N.A pcs

IX. Design of lap splices, ld

412.17.1 ld = 0.071*fy*db 736.63 mm

412.17.1 actual length of splice,ld 958.00 mm