Split System

Cooling
Product Data

XR16
4TTR6

2, 3, 4 & 5 Tons

PUB. NO. 22-1864-03


Features and
Benefits

• CLIMATUFF™ 2-stage scroll • Liquid line filter/drier


compressor • Low sound with advanced PSC fan
• Efficiency up to 18.0 SEER motor
• All Aluminum SPINE FIN™ coil • Service valve cover
• DURATUFF™ weather proof and • R-410A refrigerant
rust proof base • From 70 to 100% capacity
• COMFORT ”R”™ mode approved modulation
for better comfort indoors • 100% run test in the factory
• QUICK-SESS™ cabinet, • Low ambient cooling to 55° as
service access and refrigerant shipped
connections with full coil
protection • Extended warranties available
• WEATHERGUARD™ fasteners
• Glossy corrosion resistant finish
tarpaulin gray cabinet with
anthracite gray top
• Internal compressor high/low
pressure & temperature protection

© 2013 Trane 2 22-1864-03


Contents

Features and Benefits 2

General Data 4
Product Specifications 4
A-weighted Sound Power Level [dB(A)] 4
Accessory Description and Usage 5
AHRI Standard Capacity Rating Conditions 5
Model Nomenclature 6
Electrical Data 7
Dimensions 8
Mechanical ­Specifications 9

22-1864-03 3
General
Data

Product Specifications
Model No. 1 4TTR6024A1000B 4TTR6036A1000B 4TTR6048A1000A 4TTR6060A1000A
Electrical Data V/Ph/Hz 2 208/230/1/60 208/230/1/60 208/230/1/60 208/230/1/60
Min Cir Ampacity 18 24 28 41
Max Fuse Size (Amps) 20 35 45 60
Compressor CLIMATUFF® - SCROLL CLIMATUFF® - SCROLL CLIMATUFF® - SCROLL CLIMATUFF® - SCROLL
No. Compress. – No. Stages 1 -2 1-2 1-2 1-2
RL AMPS - LR AMPS 13.0 - 52 17.0 - 82 21.2 - 104 32.1 - 152.9
Outdoor Fan FL Amps 0.74 0.74 1.00 1.30
Fan HP 1/8 1/8 1/5 1/4
Fan Dia (inches) 27.6 27.6 27.6 27.6
Coil Spine Fin™ Spine Fin™ Spine Fin™ Spine Fin™
Refrigerant R-410A 9/13-LB/OZ 9/13-LB/OZ 12/9-LB/OZ 12/9-LB/OZ
Line Size - (in.) O.D. Gas 3 5/8 3/4 7/8 1-1/8
Line Size - (in.) O.D. Liquid 3 3/8 3/8 3/8 3/8
Dimensions H x W x D (Crated) 46.4 x 35.1 x 38.7 51.0 x 35.1 x 38.7 51.0 x 35.1 x 38.7 51.0 x 35.1 x 38.7
Weight - Shipping 276 283 308 312
Weight - Net 240 245 271 275
Start Components NO NO NO NO
Sound Enclosure NO NO NO NO
Compressor Sump Heat NO NO NO NO
Optional Accessories: 4
Rubber Isolator Kit BAYISLT101 BAYISLT101 BAYISLT101 BAYISLT101
Snow Leg - Base & Cap 4" High BAYLEGS002 BAYLEGS002 BAYLEGS002 BAYLEGS002
Snow Leg - 4" Extension BAYLEGS003 BAYLEGS003 BAYLEGS003 BAYLEGS003
Hard Start Kit Scroll BAYKSKT260 BAYKSKT260 BAYKSKT263 BAYKSKT263
Crankcase Heater Kit BAYCCHT301 BAYCCHT301 BAYCCHT301 BAYCCHT301
Extreme Condition Mounting Kit BAYECMT004 BAYECMT004 BAYECMT004 BAYECMT004
Vertical Discharge Air Kit Base 4 BAYVDTA003 BAYVDTA004 BAYVDTA004 BAYVDTA004
Auto Charge Solenoid Kit BAYCAKT001 BAYCAKT001 BAYCAKT001 BAYCAKT001
Refrigerant Lineset 5 TAYREFLN9* TAYREFLN7* TAYREFLN3* TAYREFLN4*
1 Certified in accordance with the Air-Source Unitary Heat Pump Equipment certification program which is based on AHRI Standard 210/240.
2 Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses.
3 Standard line lengths - 60'. Standard lift - 25' Suction and Liquid line.
For Greater lengths and lifts refer to refrigerant piping software Pub# 32-3312-0†. (†denotes latest revision)
4 For accessory description and usage, see page 5.
5 * = 15, 20, 25, 30, 40 and 50 foot lineset available.

A-weighted Sound Power Level [dB(A)]


SOUND POWER A-WEIGHTED FULL OCTAVE SOUND POWER LEVEL dB - [dB(A)]
MODEL
LEVEL [dB(A)]
63 125 250 500 1000 2000 4000 8000
4TTR6024A 72 43.7 52.6 54.3 62.4 60.4 57 54.1 46.6
4TTR6036A 72 38 50.4 56.8 60.4 59.8 57.2 55.2 49.2
4TTR6048A 73 44.2 50.4 58.9 63.1 63 57.4 53.6 47.4
4TTR6060A 74 42.2 53.8 57.8 66 65.7 57.7 58.4 51.7
Note: Rated in accordance with AHRI Standard 270-2008.

4 22-1864-03
General
Data

Accessory Description and Usage AHRI Standard Capacity Rating Conditions


Rubber Isolators — 5 rubber donuts to isolate condens- AHRI STANDARD 210/240 RATING CONDITIONS —
ing unit from mounting frame or pad. Use on any application (A) Cooling 80°F DB, 67°F WB air entering indoor coil,
where sound transmission needs to be minimized. 95°F DB air entering outdoor coil.
(B) High Temperature Heating 47°F DB, 43°F WB air entering
Extreme Conditions Mounting Kit — Bracket kits to secure- outdoor coil, 70°F DB air entering indoor coil.
ly mount condensing unit to a frame or pad without removing (C) Low Temperature Heating 17°F DB, 15°F WB air entering
any panels. Use in areas with high winds, or on commercial outdoor coil, 70°F DB air entering indoor coil.
rooftops, etc. (D) Rated indoor airflow for heating is the same as for cooling.
Low Ambient Cooling — For low ambient cooling below 55° AHRI STANDARD 270 RATING CONDITIONS — (Noise
see Application Guide APP-APG013-EN. rating numbers are determined with the unit in cooling opera-
tion.) S
­ tandard Noise Rating number is at 95°F outdoor air.

22-1864-03 5
Model
Nomenclature

4 T T R 6 0 3 6 A 1 0 0 0 A A Air Handler G A M 5 A 0 B 3 6 M 3 1 S A A
Outdoor Units

Refrigerant Type Brand


T = Better
4 = R-410A G = Good
Product Type
TRANE A = Air Handler
Product Type Convertability
W = Split Heat Pump M = Multi-poise 4-way
T = Split Cooling F = Upflow Front Return, 3-way
T = 3-way
Product Family Product Tier
Z = Leadership – Two Stage 2 = Good, Entry Level Feature Set
X = Leadership 4 = Better, Retail Replacement Mid Effy.
R = Replacement/Retail 5 = Better, Entry Level High Effy., Multi-Speed
M or B = Basic 7 = Best, Retail Replacement High Effy.,
A = Light Commercial Variable-Speed
8 = Best, Retail Ultimate High Effy.,
Family SEER Variable-Speed
3 = 13 6 = 16 0 = 20 Major Design Change
4 = 14 8 = 18
5 = 15 9 = 19 No Descriptor
0 = Air Handler / Coil
Split System Connections 1-6 Tons
0 = Brazed Size (Footprint)
A = 17.5 x 21.5
Nominal Capacity in 000s of BTUs B = 21.0 x 21.5
C = 23.5 x 21.5
Major Design Modifications
Cooling Size: Air Handler or Coil
Power Supply 0-9 = AH Coil - 1000 BTU’s (18, 24, 30, 36, 42, 48, 60)
1 = 200-230/1/60 or 208-230/1/60
Airflow Type & Capability
3 = 200-230/3/60 S = Low Effy PSC, 1-5 - nom. Tonnage (cfm/ton)
4 = 460/3/60 M = Mid Effy Multi-Speed, 1-5 - nom. Tonnage (cfm/ton)
Secondary Function H = High Effy Multi-Speed, 1-5 - nom. Tonnage (cfm/ton)
V = High Effy Variable, 1-5 - nom. Tonnage (cfm/ton)
Minor Design Modifications Power Supply
Unit Parts Identifier 1 = 208-230/1/60
System Control Type
S = Standard - 24 VAC
C = CLII 13.8 VDC
Minor Design Change
Gas Furnaces T U D 1 B 0 8 0 A 9 H 3 1 A A Unit Parts Identifier

Heat Pump/
Furnace Configuration 4 T X C B 0 36 A C 3 H C A A
TU = Upflow/Horizontal Cooling Coils
TD = Downflow/Horizontal
Type
E = 80% Induced Draft Standard Refrigerant Type
D = 80% Induced Draft Premium 4 = R-410A
C = 90% Condensing Standard
X = 90% Condensing Premium Series
H = 95% Condensing Premium T = Premium (Heat Pump or Convertible Coil)
C = Standard (Cooling Only)
Number of Heating Stages Coil Design
1 = Single Stage X = Direct Expansion Evaporator Coil
2 = Two Stage
M = Modulating Coil Feature
C = Cased A Coil
Cabinet Width A = Uncased A Coil
A = 14.5" Cabinet Width F = Cased Horizontal Flat Coil
B = 17.5" Cabinet Width
C = 21.0" Cabinet Width Coil Width (Cased/Uncased)
D = 24.5" Cabinet Width A = 14.5" /13.3"
B = 17.5" / 16.3"
Heating Input in 1000’s (BTUH) C = 21.0" / 19.8"
080 = 80,000 BTUH D = 24.5" / 23.3"
H = 10.5"
Major Design Change
Refrigerant Line Coupling
Voltage 0 = Brazed
9 = 115 Volts / 60 Hertz / Natural Gas
A = 115 Volts / 50 Hertz / Natural Gas Nominal Capacity in 1000's (BTUH)
C = 115 Volts / Natural Gas with Communicating System Control Major Design Change
F = 115 Volts / Natural Gas with Integrated Electronic Filter
D = 115 Volts / Natural Gas with Communicating System Control and Efficiency
Integrated Electronic Filter C = Standard
S = Hi Efficiency (derived from 10 SEER products)
Air Capacity for Cooling
Standard PSC Variable Speed High Efficiency Refrigerant Control
24 = 2 Tons V3 = 3 Tons H3 = 3 Tons 3 = TXV - Non-Bleed
36 = 3 Tons V4 = 4 Tons H4 = 4 Tons
42 = 3.5 Tons V5 = 5 Tons H5 = 5 Tons Coil Circuitry
45 = 4 Tons H = Heat Pump
48 = 4 Tons C = Cooling
54 = 5 Tons Airflow Configuration
60 = 5 Tons A = Upflow Only
72 = 6 Tons U = Upflow / Downflow
Draft Inducer Speeds H = Horizontal Only
1 = Single Speed C = Convertible - Upflow, Downflow, Left or Right Airflow
2 = Two Speed
V = Variable Speed Minor Design Change
Minor Design Change Service Digit - Not Orderable

Service Digit - Not Orderable

6 22-1864-03
Electrical
Data

Schematic Diagrams
(SEE LEGEND)

4TTR6024A, 036A

Printed from D157614P01

22-1864-03 7
Electrical
Data

Schematic Diagrams
(SEE LEGEND)

4TTR6048A, 060A

Printed from D156975P03

8 22-1864-03
Electrical
Data

Schematic Diagrams

LEGEND

22-1864-03 9
Dimensions

4TTR6 Outline Drawing


Note: All dimensions are in MM (Inches).

MODELS BASE A B C D E F G H J K

4TTR6024A 4 1045 (41 1/8) 946 (37-1/4) 870 (34-1/4) 5/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 711 (28)
4TTR6036A 4 1147 (45 1/8) 946 (37-1/4) 870 (34-1/4) 3/4 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 813 (32)
4TTR6048A 4 1147 (45 1/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 813 (32)
4TTR6060A 4 1147 (45 1/8) 946 (37-1/4) 870 (34-1/4) 1-1/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 813 (32)

From Dwg. D152635

10 22-1864-03
Mechanical
­Specifications

General Condenser Coil


The 4TTR6 is fully charged from the The outdoor coil provides low airflow
factory for matched indoor section resistance and efficient heat transfer.
and up to 15 feet of piping. This unit is The coil is protected on all four sides by
designed to operate at outdoor ambient louvered panels.
temperatures as high as 115°F. Cooling Low Ambient Cooling
capacities are matched with a wide se- As manufactured, this unit has a cooling
lection of air handlers and furnace coils capability to 55°F. For low ambient cool-
that are AHRI certified. The unit shall be ing below 55° see Application Guide.
certified to UL 1995. Exterior is designed
for outdoor application.
Casing
Unit casing is constructed of heavy
gauge, G60 galvanized steel and
painted with a weather-resistant powder
paint on all louvers and panels. Cor-
rosion and weatherproof CMBP-G30
DuraTuff™ base.
Refrigerant Controls
Refrigeration system controls include
condenser fan, compressor contactor
and high pressure switch. High and low
pressure controls are inherent to the
compressor. A factory installed liquid line
drier is standard.
Compressor
The Climatuff® 2-stage compressor
features internal over temperature and
pressure protection and hermetic motor.
Other features include: centrifugal oil
pump and modular plugs for electrical
connections.

22-1864-03 11

01/13
Trane Trane has a policy of continuous product and product data improvement and it reserves the right to change
www.trane.com design and specifications without notice.