Quick Start Guide

Before you
start using ICAD:

Quick Start Guide


24 Volt d.c.
ICAD 600A / ICAD 1200A ONLY

1 Terminal box -
not supplied
by Danfoss
2

Oil Tighten CW

Ref. Colour Description


A Black – Common Alarm
B Brown – ICM fully open Digital
Ouput
C Red – ICM fully closed

3
D Orange – GND ground
E Yellow + 0/4 - 20 mA Input
0/2-10V input or digital input for
F Green +
on/off control
G Blue + 0/4 - 20 mA Output

Fail safe supply


I Black +
Battery / UPS* 19 V d.c.
II White + Supply voltage
III Brown – 24 V d.c.
* Uninterruptable Power Supply

Please observe cable voltage drop


Distance between the applied d.c. trans-
former and the ICAD terminal box may cause
a voltage drop. Cross section of cables and
size of d.c. transformer must be calculated
so that the voltage at all time at the ICAD
terminal box*, both during standstill and
during operation of ICAD, is within this
24 Volt d.c. range:
ONLY
Prefabricated ICAD cable length 1.5 m 3m 10 m 15 m
Code number 027H0426 027H0438 027H0427 027H0435
Voltage ICAD terminal Min. 21 22 23 24
(600A/1200A) [V d.c.] Max. 26.4

* Do not measure inside the ICAD itself.

© Danfoss | DCS (MWA) | 2016.09 DKRCI.PI.HV0.J4.02 / 520H4887 / 027R9801 1


Decrease Edit / Increase
value Enter value
Note:

Programming the ICAD If the keypad is not operated within 20 seconds;


time out will automatically exit programming mode.

Valve size setup (mandatory)


When powering up the ICAD, A1 will flash in the display 4
; 01 ; 10 11 ; 26

Hold down for Press and Press until Press until


2 seconds to enter go to parameter 10. you reach 11 (pass- you reach parameter 26
programming mode. Press word). Press Press
1: ICM 20 with ICAD 600A 6: ICM 65 with ICAD 1200A
2: ICM 25 with ICAD 600A 7: ICM 100 with ICAD 1200A

0 3: ICM 32 with ICAD 600A


4: ICM 40 with ICAD 1200A
8: ICM 125 with ICAD 1200A
9: ICM 150 with ICAD 1200A ; 26 CA
5: ICM 50 with ICAD 1200A 10: CVE pilot with ICAD 1200A
Valve label ID:
ICM 20 ICM 25-65 ICM 100-150

Press or ICM/CVE & ICAD Hold down for


to select ICM size or CVE. is now calibrating. 2 seconds to exit
Press programming mode.

Changing analogue input signal (optional)


5
; 01 ; 03 2 1: 0-20 mA ; 03
2: 4-20 mA*
3: 0-10 V
4: 2-10 V
* default factory setting

Hold down for Press until you Press or Press


2 seconds to enter reach parameter 03. to select analogue
programming mode. Press input signal.

; 03 A3 Factory reset of ICAD


Disconnect power 
Press down and 
simultaneously while
Hold down for If A3 alarm occurs reconnecting power 
2 seconds to exit the analogue input
programming mode. signal is out of range. Release and 

Note:
For further functions, If factory reset has been performed the
programming possibilities ICAD will start flashing A1 in the display.
and factory settings;
24 Volt d.c. ONLY please see ICAD instruction.

2 DKRCI.PI.HV0.J4.02 / 520H4887 / 027R9801 © Danfoss | DCS (MWA) | 2016.09