Page 1
IEEE 09 Bus System
1.0 Objective
IEEE bus systems are used by researchers to implement new ideas and concepts. This technical note describes the
details of the IEEE 9-bus system [1]. The system consists of loads, transmission lines, and generators as shown in
Figure 1.
P+jQ
T5_7
T6_9
Bus5 Bus6
Bus1
slack
RRL
Each machine (generator) is represented as a voltage source where its source impedance is set arbitarily as 1 Ohm.
Table 1 summarizes the perunitized terminal conditions of each source, with 100 [MVA] base.
Transmission lines are modelled using the Bergeron model. Table 2 summarizes the transmission line parameters.
Page 2
IEEE 09 Bus System
Line
R [pu/m] X [pu/m] B [pu/m]
From Bus To Bus
4 5 0.0100 0.0680 0.1760
4 6 0.0170 0.0920 0.1580
5 7 0.0320 0.1610 0.3060
6 9 0.0390 0.1738 0.3580
7 8 0.0085 0.0576 0.1490
8 9 0.0119 0.1008 0.2090
2.0 Validation
The PSCAD model was validated against the PSS/E power flow values from [1]. Table 4 depicts the line and source
power flow comparison.
Table 4 - Source and line power flow comparison of IEEE 9-bus system
PSS/E PSCAD
Bus
P [pu] Q [pu] P [pu] Q [pu]
1 0.716 0.279 0.7152 0.2761
2 1.630 0.049 1.6320 0.0454
3 0.850 -0.114 0.8512 -0.1170
From Bus To Bus
4 5 0.433 0.235 0.4322 0.2334
4 6 0.283 0.013 0.2830 0.0115
5 7 0.842 -0.104 0.8430 -0.1041
6 9 0.633 -0.178 0.6340 -0.1810
7 8 0.788 -0.008 0.7892 -0.0089
8 9 0.217 0.023 0.2172 0.0229
Page 3
IEEE 09 Bus System
This example is compatible with PSCAD v4.5.3 and beyond. The file
New_IEEE_09_CT.pscx
Page 4
IEEE 09 Bus System
Appendix 1
The line resistances and reactances are provided in [1] for each line segment of the test system. The
following table lists the approximate line length of each segment, based on typical line data (as listed
in Table A-2).
Table A-1 Approximate line lengths based on typical line reactance values as shown in Table A-2
Page 5
IEEE 09 Bus System
DOCUMENT TRACKING
Page 6