Implementation of Single Phase Shunt Active Filter For Low Voltage Distribution System
Implementation of Single Phase Shunt Active Filter For Low Voltage Distribution System
Abstract— The use of power electronic circuits in a wide range of An unavoidable increase of nonlinear loads in industrial,
applications has resulted in distorted current in the power commercial and residential applications requires local supply
system. Custom power device such as shunt active filter is used to of reactive and harmonic powers in order to reduce the power
improve the quality of power in distribution system by injecting loss and maintain the quality of power in the system.
reactive and harmonic currents. Hysteresis current control is one
of the simplest techniques used to control the magnitude and
Traditional compensation methods such as passive filters,
phase angle of the current injected by shunt active filter. In this synchronous condensers, phase advancers, etc. were employed
paper, simulation and hardware implementation of single phase to improve the power quality. The shunt passive LC filters are
Shunt Active Filter (SAF) is carried out. The simulation results used to improve power factor and to suppress current
presented in this paper illustrate the performance of shunt active harmonics. One of the major disadvantages of passive filters is
filter in mitigating the source current harmonics and improving the non changeable compensation characteristics.
the input power factor. The simulation is carried out using
MATLAB/SIMULINK and laboratory implementation is done Other traditional controllers also possess several
using DSP Controller TMS320LF2407. In the present work, there
disadvantages like bulkiness, electromagnetic interference,
is no separate measurement for the phase angle of supply voltage,
which makes the controller implementation simple in real time. resonance, etc. These disadvantages urged to further research
Hardware results confirm the simulation results under practical in developing adjustable and dynamic solutions using custom
conditions. power devices. Custom power devices are power conditioning
equipment using static power electronic converters to improve
Keywords – Power Quality, Current distortion, Nonlinear Loads, the power quality. Shunt active filter (SAF) is one among the
Harmonics, Power factor, Shunt Active Filter (SAF). various types of custom power devices proposed to improve
the power quality [2].
NOMENCLATURE
Various current control methods were proposed for shunt
Vs = Source voltage, V active filter. Hysteresis current control method is the most
Rs = Line resistance, Ω popular one in terms of quick current controllability,
Ls = Line inductance, mH versatility and easy implementation [1]. For implementing
Lf = Filter inductance, mH hysteresis current control, Digital Signal Processor has good
Rd = Load resistance, Ω dynamic and fast response among many digital controllers [3].
Ld = Load inductance, mH DSP 2407 is employed in the present work for the prototype
is = Source current, A implementation of single phase shunt active filter.
iL = Load current, A
if = Filter current, A
SHUNT ACTIVE FILTER
INTRODUCTION
A. Principle of Operation
Power Quality (PQ) is an important measure of an electrical
power system. The term PQ means to maintain purely The shunt active filter shown in Fig. 1 is a current
sinusoidal current in phase with a purely sinusoidal voltage. controlled voltage source inverter (VSI), which is connected in
The power generated at the generating station is purely parallel with the load. It is controlled in such a way to generate
sinusoidal in nature. The quality of electric power is the required reactive and harmonic currents of the load.
deteriorating mainly due to current and voltage harmonics, Hence, the utility needs to supply only the active part of the
zero and negative sequence components, voltage sag, voltage fundamental component of the load current and thus the power
swell, flicker, voltage interruption, etc. [1]. pollution problem along the power line could be avoided.
The authors would like to thank the Department of Science and Technology
(DST), New Delhi, India for the financial support.
R S L S P C C The switching frequency of the hysteresis current control
is iL R d
method described above depends on how fast the current
V S
if changes from upper limit to lower limit of the hysteresis band,
Ld or vice versa. Therefore the switching frequency does not
remain constant throughout the switching operation, but varies
along with the current waveform. Furthermore, the filter
N O N L I N E A R L O A D
Lf
ADC
Iinv
If Iload
Compare
HARDWARE IMPLEMENTATION
Iinv > phb NO
The hardware implementation of the considered
distribution network along with SAF is shown in Fig. 5. Iinv < nhb
A DPST is used to connect the shunt active filter, which
includes a shunt transformer, VSI, associated filters and the
YES YES
DSP controller, with the system.
Stop triggering the Trigger the switches
switches of VSI of VSI
NO
Fig. 8 (a) Load / Source current without SAF Fig. 8 (b) Load /Source Current without SAF
Fig. 13 (b) Source voltage(C1), Load current(C2) and Source current (C3)
Fig. 13 (a) Source voltage(C1), Load current(C2) and Source current (C3)
Fig. 14 (a) Harmonic spectrum of source current before compensation Fig. 14 (b) Harmonic spectrum of source current before compensation
Fig. 15 (b) Harmonic spectrum after compensation