Jamesway Incubator: Detail Drawings Sheet List
Jamesway Incubator: Detail Drawings Sheet List
Jamesway Incubator
B
Drawings 02/16/17
H
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
A
Mechanical Equipment Schedule TO BE USED FOR CONSTRUCTION.
Mark Manufacturer Location Type Cooling Stages Heating CFM Tonnage Capacity Voltage Phase Hertz FLA Weight THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT
OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
RTU-1 Aaon, Inc. Egg Room RNB-011 Mechanical 2 Natural 4400 CFM 11 156000 Btu 220 V 3 60 Hz 48 A 1735.00 lb
B
Gas NOTES
RTU-2 Aaon, Inc. Incubator Room 2 RNC-016 Mechanical 2 Natural 6400 CFM 16 328000 Btu 220 V 3 60 Hz 20 A 2514.00 lb
Gas
RTU-3 Aaon, Inc. Incubator Room 1 RNC-016 Mechanical 2 Natural 6400 CFM 16 328000 Btu 220 V 3 60 Hz 20 A 2514.00 lb
Gas
C RTU-4 Aaon, Inc. Hatcher Room 2 RNA-008 Mechanical 2 Natural 3200 CFM 8 102400 Btu 220 V 3 60 Hz 40 A 1191.00 lb
Gas
RTU-5 Aaon, Inc. Hatcher Room 1 RNA-008 Mechanical 2 Natural 3200 CFM 8 102400 Btu 220 V 3 60 Hz 40 A 1191.00 lb
Gas
RTU-6 Aaon, Inc. Pull Room RNB-011 Mechanical 2 Natural 4400 CFM 11 156000 Btu 220 V 3 60 Hz 48 A 1735.00 lb
D Gas
RTU-7 Aaon, Inc. Wash Room RNA-008 Mechanical 2 Natural 3200 CFM 8 102400 Btu 220 V 3 60 Hz 40 A 1191.00 lb
Gas
RTU-8 Aaon, Inc. Chick Room RNB-013 Mechanical 2 Natural 5200 CFM 13 68300 Btu 220 V 3 60 Hz 63 A 1869.00 lb
Gas
E RTU-9 Aaon, Inc. Chick Room RNB-013 Mechanical 2 Natural 5200 CFM 13 68300 Btu 220 V 3 60 Hz 63 A 1869.00 lb
Gas
F
Exhaust Fans
Location Mark Manufacturer Count Type Shutter Part
Schedule
Egg Room EF-1 Multi-Fan 1 4E30Q - 12" HV1092 PROJECT DETAILS JAMESWAY Incubator
Company Inc
Hatcher Room 2 EF-2 Multi-Fan 1 4E34Q - 14" HV1093 30 High Ridge Court
Cambridge, Ontario, Canada
Clean Room EF-7 Multi-Fan 1 4E30Q - 12" HV1092 CLIENT NAME Jamesway Incubator
Sample
H Chick Room EF-8 Multi-Fan 1 4E40Q - 16" HV1094 Drawings
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
A
Duct Schedule Duct Schedule Air Terminal Schedule TO BE USED FOR CONSTRUCTION.
B
Supply Air 20"x20" 13' - 8 19/32" Hatcher Room 1 Clean room
NOTES
Chick Room Return Air 13"x20" 2' - 5" Supply Grill 20x20 5 18"x18"
Return Air 20"x20" 21' - 10 7/16" Return Air 13"x32" 2' - 0 7/16" Return Filter 20x25x2 2 20"x25"
Return Air 45"x14" 7' - 6 23/32" Supply Air 20"x20" 3' - 0 5/16" Egg Room
Supply Air 24"x24" 17' - 2 19/32" Supply Air 25"x22" 10 3/16" Supply Grill 22x22 1 20"x20"
C Supply Air 36"x25" 3' - 10 5/16" Hatcher Room 2 Return Filter 20x25x2 7 20"x25"
Clean Room Return Air 13"x20" 2' - 5" Hatcher Room 1
Supply Air 20"x20" 3' - 6" Return Air 13"x32" 2' - 0 7/16" Supply Grill 20x20 1 18"x18"
Supply Air 22"x25" 9 1/16" Supply Air 20"x20" 3' - 0 5/16" Return Filter 20x20x2 1 20"x20"
Clean room Supply Air 25"x22" 10 3/16" Hatcher Room 2
D Return Air 14"x20" 6' - 8" Pull Room Supply Grill 20x20 1 18"x18"
Return Air 20"x14" 2' - 0 7/16" Return Air 18"x20" 10' - 1 3/8" Return Filter 20x20x2 1 20"x20"
Egg Room Supply Air 22"x22" 2' - 11 3/32" Pull Room
Return Air 14"x45" 2' - 1 19/32" Supply Air 22"x36" 3 29/32" Supply Grill 22x22 1 20"x20"
Return Filter 20x25x2 3 20"x25"
E
Circulating Pumps
Flow Disconnect
Rate FT. of Horse Disconnect Switch Switch Size
F
Manufacturer Model Count (GPM) Head Power RPM Model (AMP)
Goulds 3ST1H5B4 2 100 60 3 3500 LBSRLT163PMZ33 16
Goulds 4SH2L45A0 2 144 136 10 3450 LBSRLT163PMZ33 16 Schedule
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
Duct Size
13"x20"
20"x20" REPORTED BEFORE ANY OF THE WORK SHOWN ON
P5
Hatcher Room1
THIS DRAWING IS COMMENCED.
RTU-5
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT
OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
B EF-3
NOTES
EF-2
Duct Size
Duct Size
13"x20"
20"x20"
1
RTU-6
Incubator Room 2
P6
Incubator Room 1
D EF-6
Duct Size
18"x20"
Duct Size
22"x22"
E Duct Size EF-4 Duct Size Pull Room
15"x20" 15"x20" Duct Size
14"x20" 3
Duct Size Duct Size
20"x20"
P6
20"x20" 20"x20"
EF-7 RTU-7
20"x20"
F
1 Clean room
Duct Size Duct Size
P5 20"x20" 20"x20"
P6 EF-1 DRAWN BY
CR
CHECKED BY
DM
DRAWING NUMBER
P3
REV.
Duct Size
Duct Size
22"x22"
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
B
NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
B
NOTES
Roof
Duct Size Duct Size
15'
15.00'
- 0"
20"x20" 20"x20"
Incubator Room1
C
P120
Ground
Level 1
D 0.00'
0"
Incubator Room
1
1/8" = 1'-0"
E
RTU-4
RTU-5
14 13 12
Roof
Duct Size
F 20"x13" 15'
15.00'
- 0"
Supply Grill 20x20 Supply Grill 20x20
0.00'
0" SCALE
1/8" = 1'-0"
DATE
02/02/17
PROJECT NUMBER
Project #
CLIENT NAME
Hatcher Rooms Jamesway Incubator
H 2 Sample
Drawings
1/8" = 1'-0"
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
Duct Size
NOT BE REPRODUCED IN WHOLE OR IN PART
Roof
Duct Size
14"x20"
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
14"x45"
15'
15.00'
- 0" AND RECEIVED.
B
NOTES
Ground
Level 1
0.00'
0"
Chick/Wash Room
D 1
1/8" = 1'-0"
1
P6
E
RTU-1 RTU-6
2 1 3 4 6 8
Roof
F Duct Size Supply Grill 22x22
Supply Grill 22x22 15'
15.00'
- 0"
26"x20" Return Filter 20x25x2
EF-1 EF-6
HVAC Wash/Pull/Chick Rooms Sections
Egg Room
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com
0.00'
0" SCALE
1/8" = 1'-0"
DATE
02/02/17
PROJECT NUMBER
Project #
CLIENT NAME
Egg room Pull Room Jamesway Incubator
H 2 3 Sample
Drawings
1/8" = 1'-0" 1/8" = 1'-0"
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
2"ø
2"ø
AND RECEIVED.
B 1 1/4"ø
Pressure Gauge Check Valve NOTES:
1. THE WATER PIPING SYSTEM SHOULD
Balancing Valve INCLUDE PROPER PLUMBING HARDWARE TO
MINIMIZE WATER HAMMER EFFECT. THIS
2"ø
SYSTEM IS DESIGNED ONLY FOR
12 P120 IINCUBATORS AND 6 P40 HATCHERS
2 1 1/4"ø 2. CONNECT TO THE FACILITY'S WATER
SYSTEM. A FILTRATION SYSTEM IS STRONGLY
P10 RECOMMENDED TO MINIMIZE FUTURE
3"ø BLOCKAGE IN LINES OR LEAKS THROUGH
C
Cold Water Pipping Legend SOLENOIDS.
3. PLEASE REFER TO CONNECTION IMAGES FOR
Balancing Valve
Pump 144 GPM Pump 100 GPM 1/8" = 1'-0" DETAILS.
4. SYSTEM WATER PUMPS: SPECIFICATIONS TO
4"ø
Chiller BE DETERMINED. PLEASE USE CHILLER
MANUFACTURER'S SPECIFIC
RECOMMENDATIONS.
3"ø Balancing Valve 5. BALANCE VALVES & SYSTEM TO ACHIEVE
144 US gal/min MINIMUM THROUGH EACH
INCUBATOR ECU AND 140 US gal/min
Check Valve
2 1/2"ø
2 1/2"ø
2 1/2"ø
2 1/2"ø
(b) ALL PIPE WORK TO BE INSULADED.
6. FLUSH SYSTEM OF DEBRIS BEFORE
4"ø Pressure Gauge CONNECTING TO INCUBATORS.
7. PROVIDE PIPING SYSTEM AS PER ALL LOCAL
CODES. ALL PIPES, GAUGES, VALVES, FITTINGS
Tank - 800 Gal ETC. SUPPLIED BY OTHERS.
800 Gallons tank 8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).
OFFICIAL START UP OF CHILLERS/BOILERS IS
NOT PERFORMED BY JAMESWAY. THIS IS TO BE
Pump DONE BY A CERTIFIED PLUMBER.
9. ALL PIPING CONNECTIONS TO INCUBATORS
ARE MADE WITH 1/2" DIA. COPPER PIPE.
E PROVIDE FLEXIBLE HOSE CONNECTION FROM
SUPPLY PIPING TO INCUBATOR & HATCHERS
CONNECTIONS.
2 1/2"ø
10. ALL PIPE DIMENSIONS LISTED ARE
INTERNAL DIAMETER.
11. PIPES CAN BE COPPER, PVC OR PEX FOR
2 1/2"ø
COLD WATER.
12. PIPES CAN BE COPPER, CPVC OR PEX FOR
HOT WATER.
13. INSTALL AIR VENTS AT THE HIGHEST POINT
2 1/2"ø
OF EACH BRANCH & ANY OTHER REQUIRED
1 LOCATIONS.
F
P11 Check Valve 14. DRAWINGS ARE SCHEMATIC
REPRESENTATIONS; ACTUAL EQUIPMENT
LOCATIONS TO BE DETERMINED BY CERTIFIED
PLUMBER.
Pressure Gauge
2 1/2"ø
2 1/2"ø
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
2 1/2"ø
1/8" = 1'-0" REPORTED BEFORE ANY OF THE WORK SHOWN ON
2 1/2"ø
2 1/2"ø
THIS DRAWING IS COMMENCED.
B
NOTES:
1. THE WATER PIPING SYSTEM SHOULD
INCLUDE PROPER PLUMBING HARDWARE TO
MINIMIZE WATER HAMMER EFFECT. THIS
SYSTEM IS DESIGNED ONLY FOR
12 P120 IINCUBATORS AND 6 P40 HATCHERS
2. CONNECT TO THE FACILITY'S WATER
SYSTEM. A FILTRATION SYSTEM IS STRONGLY
RECOMMENDED TO MINIMIZE FUTURE
BLOCKAGE IN LINES OR LEAKS THROUGH
SOLENOIDS.
3. PLEASE REFER TO CONNECTION IMAGES
C FOR DETAILS.
4. SYSTEM WATER PUMPS: SPECIFICATIONS
TO BE DETERMINED. PLEASE USE CHILLER
MANUFACTURER'S SPECIFIC
RECOMMENDATIONS.
5. BALANCE VALVES & SYSTEM TO ACHIEVE
144 US gal/min MINIMUM THROUGH EACH
INCUBATOR ECU AND 140 US gal/min
MINIMUM THROUGH EACH HATCHER ECU, IF
PRESENT.
(a) WHERE AMBIENT TEMPERATURE GOES
BELOW FREEZING, GLYCOL TO BE ADDED.
D (b) ALL PIPEWORK TO BE ADDED.
6. FLUSH SYSTEM OF DEBRIS BEFORE
CONNECTING TO INCUBATORS.
7. PROVIDE PIPING SYSTEM AS PER ALL
LOCAL CODES. ALL PIPES, GAUGES, VALVES,
FITTINGS ETC. SUPPLIED BY OTHERS.
8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).
OFFICIAL START UP OF CHILLERS/BOILERS IS
NOT PERFORMED BY JAMESWAY. THIS IS TO
BE DONE BY A CERTIFIED PLUMBER.
9. ALL PIPING CONNECTIONS TO INCUBATORS
ARE MADE WITH 1/2" DIA. COPPER PIPE.
PROVIDE FLEXIBLE HOSE CONNECTION FROM
E SUPPLY PIPING TO INCUBATOR & HATCHERS
CONNECTIONS.
10. ALL PIPE DIMENSIONS LISTED ARE
INTERNAL DIAMETER.
11. PIPES CAN BE COPPER, PVC OR PEX FOR
COLD WATER.
12. PIPES CAN BE COPPER, CPVC OR PEX FOR
HOT WATER.
13. INSTALL AIR VENTS AT THE HIGHEST
POINT OF EACH BRANCH & ANY OTHER
REQUIRED LOCATIONS.
14. DRAWINGS ARE SCHEMATIC
F REPRESENTATIONS; ACTUAL EQUIPMENT
LOCATIONS TO BE DETERMINED BY CERTIFIED
PLUMBER.
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
3/4"ø
3/4"ø
Balancing Valve RECOMMENDATIONS.
5. BALANCE VALVES & SYSTEM TO ACHIEVE
1 1/4"ø 144 US gal/min MINIMUM THROUGH EACH
INCUBATOR ECU AND 140 US gal/min
MINIMUM THROUGH EACH HATCHER ECU, IF
Shut-Off Valve Shut-Off Valve PRESENT.
(a) WHERE AMBIENT TEMPERATURE GOES
D BELOW FREEZING, GLYCOL TO BE ADDED.
(b) ALL PIPE WORK TO BE INSULADED.
6. FLUSH SYSTEM OF DEBRIS BEFORE
CONNECTING TO INCUBATORS.
7. PROVIDE PIPING SYSTEM AS PER ALL LOCAL
Cold Water Sections over Hatchers CODES. ALL PIPES, GAUGES, VALVES, FITTINGS
1 ETC. SUPPLIED BY OTHERS.
1 : 40 8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).
OFFICIAL START UP OF CHILLERS/BOILERS IS
NOT PERFORMED BY JAMESWAY. THIS IS TO BE
1/2"ø
Cold Water Pipping - Hatcher Room
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
B
NOTES:
P120 P120 P120 1. THE WATER PIPING SYSTEM SHOULD
INCLUDE PROPER PLUMBING HARDWARE TO
MINIMIZE WATER HAMMER EFFECT. THIS
SYSTEM IS DESIGNED ONLY FOR
12 P120 IINCUBATORS AND 6 P40 HATCHERS
2. CONNECT TO THE FACILITY'S WATER
SYSTEM. A FILTRATION SYSTEM IS STRONGLY
RECOMMENDED TO MINIMIZE FUTURE
BLOCKAGE IN LINES OR LEAKS THROUGH
SOLENOIDS.
3. PLEASE REFER TO CONNECTION IMAGES
C FOR DETAILS.
4. SYSTEM WATER PUMPS: SPECIFICATIONS
TO BE DETERMINED. PLEASE USE CHILLER
MANUFACTURER'S SPECIFIC
RECOMMENDATIONS.
5. BALANCE VALVES & SYSTEM TO ACHIEVE
144 US gal/min MINIMUM THROUGH EACH
INCUBATOR ECU AND 140 US gal/min
MINIMUM THROUGH EACH HATCHER ECU, IF
P120 4
Pipping Incubator Room View Details PRESENT.
(a) WHERE AMBIENT TEMPERATURE GOES
BELOW FREEZING, GLYCOL TO BE ADDED.
D (b) ALL PIPEWORK TO BE ADDED.
6. FLUSH SYSTEM OF DEBRIS BEFORE
Shut-Off Valve CONNECTING TO INCUBATORS.
ø
/2"
7. PROVIDE PIPING SYSTEM AS PER ALL
21
LOCAL CODES. ALL PIPES, GAUGES, VALVES,
FITTINGS ETC. SUPPLIED BY OTHERS.
4"ø 8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).
/2 "ø 3/ OFFICIAL START UP OF CHILLERS/BOILERS IS
21 "ø
NOT PERFORMED BY JAMESWAY. THIS IS TO
BE DONE BY A CERTIFIED PLUMBER.
1/2 9. ALL PIPING CONNECTIONS TO INCUBATORS
ARE MADE WITH 1/2" DIA. COPPER PIPE.
E 2"ø PROVIDE FLEXIBLE HOSE CONNECTION FROM
SUPPLY PIPING TO INCUBATOR & HATCHERS
CONNECTIONS.
10. ALL PIPE DIMENSIONS LISTED ARE
21 INTERNAL DIAMETER.
3/4 /2" 11. PIPES CAN BE COPPER, PVC OR PEX FOR
"ø ø COLD WATER.
12. PIPES CAN BE COPPER, CPVC OR PEX FOR
HOT WATER.
13. INSTALL AIR VENTS AT THE HIGHEST
1/2 Shut-Off Valve POINT OF EACH BRANCH & ANY OTHER
"ø REQUIRED LOCATIONS.
21 14. DRAWINGS ARE SCHEMATIC
F /2"
ø REPRESENTATIONS; ACTUAL EQUIPMENT
LOCATIONS TO BE DETERMINED BY CERTIFIED
PLUMBER.
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
D 11
11
/4"
ø
P40 hatcher (a) WHERE AMBIENT TEMPERATURE GOES
BELOW FREEZING, GLYCOL TO BE ADDED.
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
1/2"ø
D
1/2"ø
PRESSURE IS MAINTAINED.
3/4"ø
3/4"ø
E 1
P11 Hum & Compressed Air
1
1 : 250
F
Regulator and Filter View
3/4"ø
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
RTU-3
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT
TO BE USED FOR CONSTRUCTION.
B
NOTES
RTU-2
EF-4
P120
RTU-4
P120 P120
Du
c
13 t Size
"x2
0"
E
RTU-6 e
Siz "
P120 Supply Grill 20x20 ct
P120 Du "x20
20
Return Filter 20x20x2
F P120
P40 hatcher
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
B
SP-P 2 SP-A 2
CP 2
3VSD
SP-A 4
F
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
SP-P 2
OAR 1
BB 1 SP-B 1
E SP-B 2
SP-P 1 SP-A 1
SP-A 4
F
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
D
D
D CP 2
CP 1
D
E
3VSD
F
D
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
B
NOTES
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
B SP-A 1 SP-P 1
NOTES
OAR 1
3VSD BB 1
CP 1 P120 P120
D
SP-A 1 BB 1 Incubator Room2 SP-A 2 BB 2
Guardian Controls Section
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
F
Pull Room
Chick Room
Backup Alarm Layout
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
B
NOTES
3D Backup Alarm
1
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
B
Ethernet Hub
- ETHERNET CABLES MUST BE KEPT SEPARATE
FROM POWER WIRING AND ARE TYPICALLY RUN IN
THEIR OWN CABLE TRAY.
- CONDUIT
Pull Room
Incubator Room1
F
Hatchcom Layout
Chick Room
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
B
NOTES
3D Hatchcom
1
1 2 3 4 5 6 7 8 9 10