1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

Jamesway Incubator
B

Detail Drawings Sheet List


P1 Schedule
C
P2 Schedule
P3 HVAC - Top View
P4 HVAC Isometric View
P5 HVAC Incubator and Hatcher Sections
P6 HVAC Wash/Pull/Chick Rooms Sections
D
P7 Cold Water Pipping Layout
P8 Cold Water Pipping - Incubator Room
P9 Cold Water Pipping Isometric View
P10 Cold Water Pipping - Hatcher Room
E P11 Pipping Details - Incubator Rooms
P12 Pipping Details - Hatcher Rooms
P13 Humidity & Compressed Air
P14 HVAC Isometric View
P15 Guardian Controls - Low Voltage
F P16 Guardian Controls - Pressure
P17 Guardian Controls - High Voltage
P18 Guardian Controls - Isometric View
P19 Guardian Controls Section
P20 Guardian Controls Notes
G P21 Backup Alarm Layout
P22 Backup Alarm - Isometeric View
P23 Hatchcom Layout ADDRESS
PROJECT NUMBER

P24 Hatchcom - Isometric View Sample Project #


DATE

Drawings 02/16/17
H

1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT

A
Mechanical Equipment Schedule TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


DRAWING AND ANY SITE
Cooling Heating DIMENSIONS/SPECIFICATIONS, THIS MUST BE
REPORTED BEFORE ANY OF THE WORK SHOWN ON
No. of Supply Air Total Total Shipping THIS DRAWING IS COMMENCED.

Mark Manufacturer Location Type Cooling Stages Heating CFM Tonnage Capacity Voltage Phase Hertz FLA Weight THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT
OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
RTU-1 Aaon, Inc. Egg Room RNB-011 Mechanical 2 Natural 4400 CFM 11 156000 Btu 220 V 3 60 Hz 48 A 1735.00 lb
B
Gas NOTES

RTU-2 Aaon, Inc. Incubator Room 2 RNC-016 Mechanical 2 Natural 6400 CFM 16 328000 Btu 220 V 3 60 Hz 20 A 2514.00 lb
Gas
RTU-3 Aaon, Inc. Incubator Room 1 RNC-016 Mechanical 2 Natural 6400 CFM 16 328000 Btu 220 V 3 60 Hz 20 A 2514.00 lb
Gas
C RTU-4 Aaon, Inc. Hatcher Room 2 RNA-008 Mechanical 2 Natural 3200 CFM 8 102400 Btu 220 V 3 60 Hz 40 A 1191.00 lb
Gas
RTU-5 Aaon, Inc. Hatcher Room 1 RNA-008 Mechanical 2 Natural 3200 CFM 8 102400 Btu 220 V 3 60 Hz 40 A 1191.00 lb
Gas
RTU-6 Aaon, Inc. Pull Room RNB-011 Mechanical 2 Natural 4400 CFM 11 156000 Btu 220 V 3 60 Hz 48 A 1735.00 lb
D Gas
RTU-7 Aaon, Inc. Wash Room RNA-008 Mechanical 2 Natural 3200 CFM 8 102400 Btu 220 V 3 60 Hz 40 A 1191.00 lb
Gas
RTU-8 Aaon, Inc. Chick Room RNB-013 Mechanical 2 Natural 5200 CFM 13 68300 Btu 220 V 3 60 Hz 63 A 1869.00 lb
Gas
E RTU-9 Aaon, Inc. Chick Room RNB-013 Mechanical 2 Natural 5200 CFM 13 68300 Btu 220 V 3 60 Hz 63 A 1869.00 lb
Gas

F
Exhaust Fans
Location Mark Manufacturer Count Type Shutter Part

Schedule
Egg Room EF-1 Multi-Fan 1 4E30Q - 12" HV1092 PROJECT DETAILS JAMESWAY Incubator
Company Inc
Hatcher Room 2 EF-2 Multi-Fan 1 4E34Q - 14" HV1093 30 High Ridge Court
Cambridge, Ontario, Canada

G Hatcher Room 1 EF-3 Multi-Fan 1 4E34Q - 14" HV1093 N1R 7L3


Tel 519 624 4646
Fax 519 624 5803
Incubator Room 1 EF-4 Multi-Fan 1 4E40Q - 16" HV1094 [email protected]
www.jamesway.com

Incubator Room 2 EF-5 Multi-Fan 1 4E40Q - 16" HV1094 DRAWN BY


CR
CHECKED BY
DM
DRAWING NUMBER
P1
REV.

Pull Room EF-6 Multi-Fan 1 4E34Q - 14" HV1093 SCALE DATE


02/02/17
PROJECT NUMBER
Project #

Clean Room EF-7 Multi-Fan 1 4E30Q - 12" HV1092 CLIENT NAME Jamesway Incubator
Sample
H Chick Room EF-8 Multi-Fan 1 4E40Q - 16" HV1094 Drawings

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT

A
Duct Schedule Duct Schedule Air Terminal Schedule TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


DRAWING AND ANY SITE
System Type Size Length System Type Size Length Type Count Size DIMENSIONS/SPECIFICATIONS, THIS MUST BE
REPORTED BEFORE ANY OF THE WORK SHOWN ON
Return Air 20"x26" 7' - 3 3/8" Chick Room THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


Return Air 15"x20" 11' - 9 31/32" Supply Air 22"x22" 4' - 11 13/32" Return Filter 20x25x2 6 20"x25" OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
Return Air 21"x50" 11 27/32" Supply Air 25"x36" 1 1/2" Supply Grill 24x24 2 22"x22" WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

B
Supply Air 20"x20" 13' - 8 19/32" Hatcher Room 1 Clean room
NOTES
Chick Room Return Air 13"x20" 2' - 5" Supply Grill 20x20 5 18"x18"
Return Air 20"x20" 21' - 10 7/16" Return Air 13"x32" 2' - 0 7/16" Return Filter 20x25x2 2 20"x25"
Return Air 45"x14" 7' - 6 23/32" Supply Air 20"x20" 3' - 0 5/16" Egg Room
Supply Air 24"x24" 17' - 2 19/32" Supply Air 25"x22" 10 3/16" Supply Grill 22x22 1 20"x20"
C Supply Air 36"x25" 3' - 10 5/16" Hatcher Room 2 Return Filter 20x25x2 7 20"x25"
Clean Room Return Air 13"x20" 2' - 5" Hatcher Room 1
Supply Air 20"x20" 3' - 6" Return Air 13"x32" 2' - 0 7/16" Supply Grill 20x20 1 18"x18"
Supply Air 22"x25" 9 1/16" Supply Air 20"x20" 3' - 0 5/16" Return Filter 20x20x2 1 20"x20"
Clean room Supply Air 25"x22" 10 3/16" Hatcher Room 2
D Return Air 14"x20" 6' - 8" Pull Room Supply Grill 20x20 1 18"x18"
Return Air 20"x14" 2' - 0 7/16" Return Air 18"x20" 10' - 1 3/8" Return Filter 20x20x2 1 20"x20"
Egg Room Supply Air 22"x22" 2' - 11 3/32" Pull Room
Return Air 14"x45" 2' - 1 19/32" Supply Air 22"x36" 3 29/32" Supply Grill 22x22 1 20"x20"
Return Filter 20x25x2 3 20"x25"
E

Circulating Pumps
Flow Disconnect
Rate FT. of Horse Disconnect Switch Switch Size
F
Manufacturer Model Count (GPM) Head Power RPM Model (AMP)
Goulds 3ST1H5B4 2 100 60 3 3500 LBSRLT163PMZ33 16
Goulds 4SH2L45A0 2 144 136 10 3450 LBSRLT163PMZ33 16 Schedule

PROJECT DETAILS JAMESWAY Incubator


Company Inc
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803

Chiller Specification DRAWN BY CHECKED BY


[email protected]
www.jamesway.com

DRAWING NUMBER REV.


CR DM P2
ELECTRICAL Flow Rate SCALE DATE PROJECT NUMBER
02/02/17 Project #
Count Make Model Freq. Volt. Phase Comments (GPM) Weight (lb) CLIENT NAME Jamesway Incubator

H 1 Trane CGAM035 60 Hz 220 V 3 35 Ton 45 1750 Sample


Drawings

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A DRAWING AND ANY SITE
Duct Size 2 DIMENSIONS/SPECIFICATIONS, THIS MUST BE

Duct Size
13"x20"
20"x20" REPORTED BEFORE ANY OF THE WORK SHOWN ON
P5
Hatcher Room1
THIS DRAWING IS COMMENCED.
RTU-5
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT
OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

B EF-3
NOTES
EF-2

Duct Size
Duct Size

13"x20"
20"x20"

RTU-4 Hatcher Room2


C

1
RTU-6

Incubator Room 2
P6

Incubator Room 1
D EF-6
Duct Size
18"x20"

Duct Size
22"x22"
E Duct Size EF-4 Duct Size Pull Room
15"x20" 15"x20" Duct Size
14"x20" 3
Duct Size Duct Size
20"x20"

P6

Duct Size Duct Size


RTU-3

20"x20" 20"x20"
EF-7 RTU-7
20"x20"

RTU-2 Duct Size


20"x20"

F
1 Clean room
Duct Size Duct Size
P5 20"x20" 20"x20"

RTU-8 HVAC - Top View


Chick Room PROJECT DETAILS JAMESWAY Incubator
Duct Size Duct Size Company Inc

Egg Room 24"x24" 24"x24" 30 High Ridge Court


Cambridge, Ontario, Canada
N1R 7L3
G EF-8 Tel 519 624 4646

EF-5 RTU-8 RTU-9 Fax 519 624 5803


[email protected]
2 www.jamesway.com

P6 EF-1 DRAWN BY
CR
CHECKED BY
DM
DRAWING NUMBER
P3
REV.

Duct Size
Duct Size
22"x22"

20"x26" SCALE DATE PROJECT NUMBER


1 : 250 02/02/17 Project #
CLIENT NAME Jamesway Incubator
HVAC RTU-1 Sample
H 1 Drawings
1 : 250

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

B
NOTES

HVAC Isometric View

PROJECT DETAILS JAMESWAY Incubator


Company Inc
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


CR DM P4
SCALE DATE PROJECT NUMBER
02/17/17 Project #
HVAC Isometric View
1 CLIENT NAME Jamesway Incubator
Sample
H Drawings

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
RTU-3
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT
OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
EF-4 WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

B
NOTES
Roof
Duct Size Duct Size
15'
15.00'
- 0"
20"x20" 20"x20"

Incubator Room1
C

P120

Ground
Level 1
D 0.00'
0"
Incubator Room
1
1/8" = 1'-0"

E
RTU-4
RTU-5
14 13 12
Roof
Duct Size
F 20"x13" 15'
15.00'
- 0"
Supply Grill 20x20 Supply Grill 20x20

HVAC Incubator and Hatcher Sections


Return Filter 20x20x2 EF-2 EF-3 Return Filter 20x20x2
PROJECT DETAILS JAMESWAY Incubator
Company Inc
30 High Ridge Court
Cambridge, Ontario, Canada
Future expansion N1R 7L3
G
Hatcher Room2 Hatcher Room1 Tel 519 624 4646
Fax 519 624 5803
P40 hatcher P40 hatcher [email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


Ground
Level 1 CR DM P5

0.00'
0" SCALE
1/8" = 1'-0"
DATE
02/02/17
PROJECT NUMBER
Project #
CLIENT NAME
Hatcher Rooms Jamesway Incubator

H 2 Sample
Drawings
1/8" = 1'-0"

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

3 WHERE A DISCREPANCY OCCURS BETWEEN THIS


A RTU-9
P6 RTU-7 DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
16 17 18 REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


RTU-7 OF JAMESWAY INCUBATOR COMPANY INC AND MUST

Duct Size
NOT BE REPRODUCED IN WHOLE OR IN PART
Roof

Duct Size
14"x20"
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN

14"x45"
15'
15.00'
- 0" AND RECEIVED.

B
NOTES

Supply Grill 20x20


EF-8
Supply Grill 24x24
Return Filter 20x25x2
Pull Room Chick Room Return Filter 20x25x2
C

Ground
Level 1
0.00'
0"

Chick/Wash Room
D 1
1/8" = 1'-0"

1
P6
E
RTU-1 RTU-6

2 1 3 4 6 8
Roof
F Duct Size Supply Grill 22x22
Supply Grill 22x22 15'
15.00'
- 0"
26"x20" Return Filter 20x25x2

EF-1 EF-6
HVAC Wash/Pull/Chick Rooms Sections

PROJECT DETAILS JAMESWAY Incubator


Return Filter 20x25x2
Pull Room
Company Inc

Egg Room
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


Ground CR DM P6

0.00'
0" SCALE
1/8" = 1'-0"
DATE
02/02/17
PROJECT NUMBER
Project #
CLIENT NAME
Egg room Pull Room Jamesway Incubator

H 2 3 Sample
Drawings
1/8" = 1'-0" 1/8" = 1'-0"

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.
Balancing Valve
WHERE A DISCREPANCY OCCURS BETWEEN THIS
A DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
Pressure Gauge REPORTED BEFORE ANY OF THE WORK SHOWN ON
Pressure Gauge THIS DRAWING IS COMMENCED.

Cold Water Pipping


1 THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT
OF JAMESWAY INCUBATOR COMPANY INC AND MUST
1 : 250 NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN

2"ø
2"ø
AND RECEIVED.

B 1 1/4"ø
Pressure Gauge Check Valve NOTES:
1. THE WATER PIPING SYSTEM SHOULD
Balancing Valve INCLUDE PROPER PLUMBING HARDWARE TO
MINIMIZE WATER HAMMER EFFECT. THIS

2"ø
SYSTEM IS DESIGNED ONLY FOR
12 P120 IINCUBATORS AND 6 P40 HATCHERS
2 1 1/4"ø 2. CONNECT TO THE FACILITY'S WATER
SYSTEM. A FILTRATION SYSTEM IS STRONGLY
P10 RECOMMENDED TO MINIMIZE FUTURE
3"ø BLOCKAGE IN LINES OR LEAKS THROUGH

C
Cold Water Pipping Legend SOLENOIDS.
3. PLEASE REFER TO CONNECTION IMAGES FOR
Balancing Valve
Pump 144 GPM Pump 100 GPM 1/8" = 1'-0" DETAILS.
4. SYSTEM WATER PUMPS: SPECIFICATIONS TO

4"ø
Chiller BE DETERMINED. PLEASE USE CHILLER
MANUFACTURER'S SPECIFIC
RECOMMENDATIONS.
3"ø Balancing Valve 5. BALANCE VALVES & SYSTEM TO ACHIEVE
144 US gal/min MINIMUM THROUGH EACH
INCUBATOR ECU AND 140 US gal/min
Check Valve
2 1/2"ø

2 1/2"ø
2 1/2"ø

MINIMUM THROUGH EACH HATCHER ECU, IF


PRESENT.
(a) WHERE AMBIENT TEMPERATURE GOES
D Shut-Off Valve BELOW FREEZING, GLYCOL TO BE ADDED.

2 1/2"ø
(b) ALL PIPE WORK TO BE INSULADED.
6. FLUSH SYSTEM OF DEBRIS BEFORE
4"ø Pressure Gauge CONNECTING TO INCUBATORS.
7. PROVIDE PIPING SYSTEM AS PER ALL LOCAL
CODES. ALL PIPES, GAUGES, VALVES, FITTINGS
Tank - 800 Gal ETC. SUPPLIED BY OTHERS.
800 Gallons tank 8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).
OFFICIAL START UP OF CHILLERS/BOILERS IS
NOT PERFORMED BY JAMESWAY. THIS IS TO BE
Pump DONE BY A CERTIFIED PLUMBER.
9. ALL PIPING CONNECTIONS TO INCUBATORS
ARE MADE WITH 1/2" DIA. COPPER PIPE.
E PROVIDE FLEXIBLE HOSE CONNECTION FROM
SUPPLY PIPING TO INCUBATOR & HATCHERS
CONNECTIONS.

2 1/2"ø
10. ALL PIPE DIMENSIONS LISTED ARE
INTERNAL DIAMETER.
11. PIPES CAN BE COPPER, PVC OR PEX FOR

2 1/2"ø
COLD WATER.
12. PIPES CAN BE COPPER, CPVC OR PEX FOR
HOT WATER.
13. INSTALL AIR VENTS AT THE HIGHEST POINT

2 1/2"ø
OF EACH BRANCH & ANY OTHER REQUIRED
1 LOCATIONS.
F
P11 Check Valve 14. DRAWINGS ARE SCHEMATIC
REPRESENTATIONS; ACTUAL EQUIPMENT
LOCATIONS TO BE DETERMINED BY CERTIFIED
PLUMBER.
Pressure Gauge
2 1/2"ø

Cold Water Pipping Layout


Balancing Valve
2 1/2"ø

PROJECT DETAILS JAMESWAY Incubator


Company Inc
30 High Ridge Court
2 1/2"ø

Cambridge, Ontario, Canada


N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com
2 1/2"ø

2 1/2"ø

DRAWN BY CHECKED BY DRAWING NUMBER REV.


CR DM P7
SCALE DATE PROJECT NUMBER
As indicated 02/02/17 Project #
CLIENT NAME Jamesway Incubator
Sample
H Drawings

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

Cold Water Pipping over Incubators


1 THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT
TO BE USED FOR CONSTRUCTION.
1 : 45
WHERE A DISCREPANCY OCCURS BETWEEN THIS
A
Cold Water Pipping Legend DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE

2 1/2"ø
1/8" = 1'-0" REPORTED BEFORE ANY OF THE WORK SHOWN ON

2 1/2"ø
2 1/2"ø
THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


Balancing Valve OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
Check Valve AND RECEIVED.

B P120 Shut-Off Valve NOTES:


Shut-Off Valve 1. THE WATER PIPING SYSTEM SHOULD
INCLUDE PROPER PLUMBING HARDWARE TO
Pressure Gauge MINIMIZE WATER HAMMER EFFECT. THIS
3/4" ø SYSTEM IS DESIGNED ONLY FOR
12 P120 IINCUBATORS AND 6 P40 HATCHERS
2. CONNECT TO THE FACILITY'S WATER
800 Gallons tank SYSTEM. A FILTRATION SYSTEM IS STRONGLY
3/4"ø 3/4" ø RECOMMENDED TO MINIMIZE FUTURE
BLOCKAGE IN LINES OR LEAKS THROUGH
Shut-Off Valve Pump SOLENOIDS.
C 3. PLEASE REFER TO CONNECTION IMAGES FOR
DETAILS.
4. SYSTEM WATER PUMPS: SPECIFICATIONS TO
BE DETERMINED. PLEASE USE CHILLER
MANUFACTURER'S SPECIFIC
RECOMMENDATIONS.
5. BALANCE VALVES & SYSTEM TO ACHIEVE
144 US gal/min MINIMUM THROUGH EACH
14 15 INCUBATOR ECU AND 140 US gal/min
MINIMUM THROUGH EACH HATCHER ECU, IF
PRESENT.
(a) WHERE AMBIENT TEMPERATURE GOES
D BELOW FREEZING, GLYCOL TO BE ADDED.
(b) ALL PIPE WORK TO BE INSULADED.
6. FLUSH SYSTEM OF DEBRIS BEFORE
CONNECTING TO INCUBATORS.
7. PROVIDE PIPING SYSTEM AS PER ALL LOCAL
CODES. ALL PIPES, GAUGES, VALVES, FITTINGS
ETC. SUPPLIED BY OTHERS.
8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).
OFFICIAL START UP OF CHILLERS/BOILERS IS
NOT PERFORMED BY JAMESWAY. THIS IS TO BE
DONE BY A CERTIFIED PLUMBER.
9. ALL PIPING CONNECTIONS TO INCUBATORS
ARE MADE WITH 1/2" DIA. COPPER PIPE.
E PROVIDE FLEXIBLE HOSE CONNECTION FROM
SUPPLY PIPING TO INCUBATOR & HATCHERS
CONNECTIONS.
10. ALL PIPE DIMENSIONS LISTED ARE
INTERNAL DIAMETER.
11. PIPES CAN BE COPPER, PVC OR PEX FOR
Shut-Off Valve
2 1/2"ø COLD WATER.
2 1/2"ø 12. PIPES CAN BE COPPER, CPVC OR PEX FOR
HOT WATER.
13. INSTALL AIR VENTS AT THE HIGHEST POINT
OF EACH BRANCH & ANY OTHER REQUIRED

F Incubator Room1 LOCATIONS.


14. DRAWINGS ARE SCHEMATIC
REPRESENTATIONS; ACTUAL EQUIPMENT
LOCATIONS TO BE DETERMINED BY CERTIFIED
Balancing Valve PLUMBER.

P120 P120 Cold Water Pipping - Incubator Room

PROJECT DETAILS JAMESWAY Incubator


Company Inc
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


CR DM P8
SCALE DATE PROJECT NUMBER
As indicated 02/02/17 Project #
CLIENT NAME Jamesway Incubator
Sample
H Drawings
Cold Water Pippiping - Incubator Room
section
2
1 : 50
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

B
NOTES:
1. THE WATER PIPING SYSTEM SHOULD
INCLUDE PROPER PLUMBING HARDWARE TO
MINIMIZE WATER HAMMER EFFECT. THIS
SYSTEM IS DESIGNED ONLY FOR
12 P120 IINCUBATORS AND 6 P40 HATCHERS
2. CONNECT TO THE FACILITY'S WATER
SYSTEM. A FILTRATION SYSTEM IS STRONGLY
RECOMMENDED TO MINIMIZE FUTURE
BLOCKAGE IN LINES OR LEAKS THROUGH
SOLENOIDS.
3. PLEASE REFER TO CONNECTION IMAGES
C FOR DETAILS.
4. SYSTEM WATER PUMPS: SPECIFICATIONS
TO BE DETERMINED. PLEASE USE CHILLER
MANUFACTURER'S SPECIFIC
RECOMMENDATIONS.
5. BALANCE VALVES & SYSTEM TO ACHIEVE
144 US gal/min MINIMUM THROUGH EACH
INCUBATOR ECU AND 140 US gal/min
MINIMUM THROUGH EACH HATCHER ECU, IF
PRESENT.
(a) WHERE AMBIENT TEMPERATURE GOES
BELOW FREEZING, GLYCOL TO BE ADDED.
D (b) ALL PIPEWORK TO BE ADDED.
6. FLUSH SYSTEM OF DEBRIS BEFORE
CONNECTING TO INCUBATORS.
7. PROVIDE PIPING SYSTEM AS PER ALL
LOCAL CODES. ALL PIPES, GAUGES, VALVES,
FITTINGS ETC. SUPPLIED BY OTHERS.
8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).
OFFICIAL START UP OF CHILLERS/BOILERS IS
NOT PERFORMED BY JAMESWAY. THIS IS TO
BE DONE BY A CERTIFIED PLUMBER.
9. ALL PIPING CONNECTIONS TO INCUBATORS
ARE MADE WITH 1/2" DIA. COPPER PIPE.
PROVIDE FLEXIBLE HOSE CONNECTION FROM
E SUPPLY PIPING TO INCUBATOR & HATCHERS
CONNECTIONS.
10. ALL PIPE DIMENSIONS LISTED ARE
INTERNAL DIAMETER.
11. PIPES CAN BE COPPER, PVC OR PEX FOR
COLD WATER.
12. PIPES CAN BE COPPER, CPVC OR PEX FOR
HOT WATER.
13. INSTALL AIR VENTS AT THE HIGHEST
POINT OF EACH BRANCH & ANY OTHER
REQUIRED LOCATIONS.
14. DRAWINGS ARE SCHEMATIC
F REPRESENTATIONS; ACTUAL EQUIPMENT
LOCATIONS TO BE DETERMINED BY CERTIFIED
PLUMBER.

Cold Water Pipping Isometric View

PROJECT DETAILS JAMESWAY Incubator


Company Inc
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


CR DM P9
SCALE DATE PROJECT NUMBER
Cold Water Pipping Isometric View 02/02/17 Project #
1 CLIENT NAME Jamesway Incubator
Sample
H Drawings

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
EF-2 REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

P40 hatcher P40 hatcher NOTES:


1. THE WATER PIPING SYSTEM SHOULD
INCLUDE PROPER PLUMBING HARDWARE TO
MINIMIZE WATER HAMMER EFFECT. THIS
SYSTEM IS DESIGNED ONLY FOR
12 P120 IINCUBATORS AND 6 P40 HATCHERS
Pressure Gauge 2. CONNECT TO THE FACILITY'S WATER
Check Valve SYSTEM. A FILTRATION SYSTEM IS STRONGLY
RECOMMENDED TO MINIMIZE FUTURE
BLOCKAGE IN LINES OR LEAKS THROUGH
1 1/4"ø SOLENOIDS.
C 3. PLEASE REFER TO CONNECTION IMAGES FOR
DETAILS.
4. SYSTEM WATER PUMPS: SPECIFICATIONS TO
1 1/4"ø BE DETERMINED. PLEASE USE CHILLER
MANUFACTURER'S SPECIFIC

3/4"ø
3/4"ø
Balancing Valve RECOMMENDATIONS.
5. BALANCE VALVES & SYSTEM TO ACHIEVE
1 1/4"ø 144 US gal/min MINIMUM THROUGH EACH
INCUBATOR ECU AND 140 US gal/min
MINIMUM THROUGH EACH HATCHER ECU, IF
Shut-Off Valve Shut-Off Valve PRESENT.
(a) WHERE AMBIENT TEMPERATURE GOES
D BELOW FREEZING, GLYCOL TO BE ADDED.
(b) ALL PIPE WORK TO BE INSULADED.
6. FLUSH SYSTEM OF DEBRIS BEFORE
CONNECTING TO INCUBATORS.
7. PROVIDE PIPING SYSTEM AS PER ALL LOCAL
Cold Water Sections over Hatchers CODES. ALL PIPES, GAUGES, VALVES, FITTINGS
1 ETC. SUPPLIED BY OTHERS.
1 : 40 8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).
OFFICIAL START UP OF CHILLERS/BOILERS IS
NOT PERFORMED BY JAMESWAY. THIS IS TO BE

2 21 3 DONE BY A CERTIFIED PLUMBER.


9. ALL PIPING CONNECTIONS TO INCUBATORS
ARE MADE WITH 1/2" DIA. COPPER PIPE.
E PROVIDE FLEXIBLE HOSE CONNECTION FROM
SUPPLY PIPING TO INCUBATOR & HATCHERS
CONNECTIONS.
10. ALL PIPE DIMENSIONS LISTED ARE
INTERNAL DIAMETER.
11. PIPES CAN BE COPPER, PVC OR PEX FOR
COLD WATER.
12. PIPES CAN BE COPPER, CPVC OR PEX FOR
Balancing Valve HOT WATER.
13. INSTALL AIR VENTS AT THE HIGHEST POINT
Check Valve OF EACH BRANCH & ANY OTHER REQUIRED
LOCATIONS.
F
Shut-Off Valve 14. DRAWINGS ARE SCHEMATIC
REPRESENTATIONS; ACTUAL EQUIPMENT
1 1/4"ø LOCATIONS TO BE DETERMINED BY CERTIFIED
1 1/4"ø PLUMBER.

1/2"ø
Cold Water Pipping - Hatcher Room

PROJECT DETAILS JAMESWAY Incubator


Company Inc
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G
P40 hatcher P40 hatcher P40 hatcher Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


CR DM P10
SCALE DATE PROJECT NUMBER
As indicated 02/02/17 Project #
CLIENT NAME Jamesway Incubator
Sample
H
Hatcher Room 2 Drawings
2
1 : 70

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


Incubator Room 1 TO BE USED FOR CONSTRUCTION.
1
A
1 : 58 WHERE A DISCREPANCY OCCURS BETWEEN THIS
DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
Incubator Room1 WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

B
NOTES:
P120 P120 P120 1. THE WATER PIPING SYSTEM SHOULD
INCLUDE PROPER PLUMBING HARDWARE TO
MINIMIZE WATER HAMMER EFFECT. THIS
SYSTEM IS DESIGNED ONLY FOR
12 P120 IINCUBATORS AND 6 P40 HATCHERS
2. CONNECT TO THE FACILITY'S WATER
SYSTEM. A FILTRATION SYSTEM IS STRONGLY
RECOMMENDED TO MINIMIZE FUTURE
BLOCKAGE IN LINES OR LEAKS THROUGH
SOLENOIDS.
3. PLEASE REFER TO CONNECTION IMAGES
C FOR DETAILS.
4. SYSTEM WATER PUMPS: SPECIFICATIONS
TO BE DETERMINED. PLEASE USE CHILLER
MANUFACTURER'S SPECIFIC
RECOMMENDATIONS.
5. BALANCE VALVES & SYSTEM TO ACHIEVE
144 US gal/min MINIMUM THROUGH EACH
INCUBATOR ECU AND 140 US gal/min
MINIMUM THROUGH EACH HATCHER ECU, IF

P120 4
Pipping Incubator Room View Details PRESENT.
(a) WHERE AMBIENT TEMPERATURE GOES
BELOW FREEZING, GLYCOL TO BE ADDED.
D (b) ALL PIPEWORK TO BE ADDED.
6. FLUSH SYSTEM OF DEBRIS BEFORE
Shut-Off Valve CONNECTING TO INCUBATORS.
ø
/2"
7. PROVIDE PIPING SYSTEM AS PER ALL

21
LOCAL CODES. ALL PIPES, GAUGES, VALVES,
FITTINGS ETC. SUPPLIED BY OTHERS.
4"ø 8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).
/2 "ø 3/ OFFICIAL START UP OF CHILLERS/BOILERS IS
21 "ø
NOT PERFORMED BY JAMESWAY. THIS IS TO
BE DONE BY A CERTIFIED PLUMBER.
1/2 9. ALL PIPING CONNECTIONS TO INCUBATORS
ARE MADE WITH 1/2" DIA. COPPER PIPE.
E 2"ø PROVIDE FLEXIBLE HOSE CONNECTION FROM
SUPPLY PIPING TO INCUBATOR & HATCHERS
CONNECTIONS.
10. ALL PIPE DIMENSIONS LISTED ARE
21 INTERNAL DIAMETER.
3/4 /2" 11. PIPES CAN BE COPPER, PVC OR PEX FOR
"ø ø COLD WATER.
12. PIPES CAN BE COPPER, CPVC OR PEX FOR
HOT WATER.
13. INSTALL AIR VENTS AT THE HIGHEST
1/2 Shut-Off Valve POINT OF EACH BRANCH & ANY OTHER
"ø REQUIRED LOCATIONS.
21 14. DRAWINGS ARE SCHEMATIC
F /2"
ø REPRESENTATIONS; ACTUAL EQUIPMENT
LOCATIONS TO BE DETERMINED BY CERTIFIED
PLUMBER.

Pipping Details - Incubator Rooms

PROJECT DETAILS JAMESWAY Incubator


Company Inc
21 3/4" ø 30 High Ridge Court
Cambridge, Ontario, Canada
/2" "ø
G ø 1/2
N1R 7L3
Tel 519 624 4646
"ø Fax 519 624 5803
1/2 "ø [email protected]
3/4 www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


CR DM P11
SCALE DATE PROJECT NUMBER
1 : 58 02/02/17 Project #
CLIENT NAME
3/4" ø Jamesway Incubator
Pipping - Incubator Rooms Sample
H 2 Drawings

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A DRAWING AND ANY SITE
Pipping - Hatcher Room 2 Pipping - Hatcher Room 2 Detailed DIMENSIONS/SPECIFICATIONS, THIS MUST BE
1 2 REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
Balancing Valve
B
NOTES:
1. THE WATER PIPING SYSTEM SHOULD
INCLUDE PROPER PLUMBING HARDWARE TO
Pressure Gauge MINIMIZE WATER HAMMER EFFECT. THIS
SYSTEM IS DESIGNED ONLY FOR
12 P120 IINCUBATORS AND 6 P40 HATCHERS
2. CONNECT TO THE FACILITY'S WATER
SYSTEM. A FILTRATION SYSTEM IS STRONGLY
RECOMMENDED TO MINIMIZE FUTURE
BLOCKAGE IN LINES OR LEAKS THROUGH
SOLENOIDS.
3. PLEASE REFER TO CONNECTION IMAGES
C FOR DETAILS.
Check Valve 4. SYSTEM WATER PUMPS: SPECIFICATIONS
TO BE DETERMINED. PLEASE USE CHILLER
MANUFACTURER'S SPECIFIC
RECOMMENDATIONS.
5. BALANCE VALVES & SYSTEM TO ACHIEVE
144 US gal/min MINIMUM THROUGH EACH
INCUBATOR ECU AND 140 US gal/min
MINIMUM THROUGH EACH HATCHER ECU, IF
PRESENT.

D 11
11
/4"
ø
P40 hatcher (a) WHERE AMBIENT TEMPERATURE GOES
BELOW FREEZING, GLYCOL TO BE ADDED.

/4" Shut-Off Valve (b) ALL PIPEWORK TO BE ADDED.


6. FLUSH SYSTEM OF DEBRIS BEFORE
11 ø CONNECTING TO INCUBATORS.
/4" 7. PROVIDE PIPING SYSTEM AS PER ALL
ø LOCAL CODES. ALL PIPES, GAUGES, VALVES,
FITTINGS ETC. SUPPLIED BY OTHERS.
8. ALL PIPING SYSTEM SUPPLIED (BY OTHERS).
OFFICIAL START UP OF CHILLERS/BOILERS IS
NOT PERFORMED BY JAMESWAY. THIS IS TO
BE DONE BY A CERTIFIED PLUMBER.
9. ALL PIPING CONNECTIONS TO INCUBATORS
ARE MADE WITH 1/2" DIA. COPPER PIPE.
PROVIDE FLEXIBLE HOSE CONNECTION FROM
E SUPPLY PIPING TO INCUBATOR & HATCHERS
CONNECTIONS.
10. ALL PIPE DIMENSIONS LISTED ARE
INTERNAL DIAMETER.
11. PIPES CAN BE COPPER, PVC OR PEX FOR
COLD WATER.
12. PIPES CAN BE COPPER, CPVC OR PEX FOR
HOT WATER.
13. INSTALL AIR VENTS AT THE HIGHEST
POINT OF EACH BRANCH & ANY OTHER
REQUIRED LOCATIONS.
14. DRAWINGS ARE SCHEMATIC
F REPRESENTATIONS; ACTUAL EQUIPMENT
LOCATIONS TO BE DETERMINED BY CERTIFIED
PLUMBER.

Pipping Details - Hatcher Rooms

PROJECT DETAILS JAMESWAY Incubator


Company Inc
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


CR DM P12
SCALE DATE PROJECT NUMBER
02/02/17 Project #
CLIENT NAME Jamesway Incubator
Sample
H Drawings

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
1/2"ø
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT
OF JAMESWAY INCUBATOR COMPANY INC AND MUST
3/4" NOT BE REPRODUCED IN WHOLE OR IN PART
ø WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
1/2" AND RECEIVED.
2 ø
Connect to Facility's compressor
B P10 1/2"ø 1/2"ø 3/4" dia. pipping NOTES

1. HUMIDITY WATER SUPPLY PER

2. ONE 1/2" (13mm) COPPER PIPE OR 1/2" (13mm)


RIGID PVC PIPE CAN BE USED. NOT PROVIDED BY
Regulator & Filter 3/4"ø 3/4"ø Connect to Facility's water system JAMESWAY
1/2" dia. pipping Regulator & Filter 3. HUMIDITY LINE DROP IS TO BE FITTED WITH A
SHUT-OFF VALVE
C Regulator & Filter 4. DRILL A 1/2" (13mm) HOLE 2" FRON THE COLD
WATER RETURN, TOWARDS THE CENTRE
EXTRUSION, AND IN LINE WITH THE COLD WATER
PIPES.

5. CONNECT TO THE INCOMING HUMIDITY WATER


LINE USING A 3/8" (9.5mm) TUBE TO 1/4" (6.3mm) mpt
FITTING. NOT PROVIDED BY JAMESWAY.

6. THE PRESSURE MUST BE 60 TO 100 psig AT ALL

P120 TIMES. A BOOSTER PUMPS MAY BE NECESSARY


ON THE WATER LINE TO ENSURE MINIMUM

1/2"ø
D
1/2"ø

PRESSURE IS MAINTAINED.

3/4"ø
3/4"ø

7. TO AVOID EXCESSIVE SCALE BUILD UP, PLEASE


REFER TO PAGE 30 & 31 OF THE HATCHERY
DESIGN MANUAL FOR WATER QUALITY.

8. IF A REVERSE OSMOSIS (RO) SYSTEM IS TO BE


USED, ALL PIPING SHOULD BR PVC. RO WATER
WILL DAMAGE COPPER PIPES.

E 1
P11 Hum & Compressed Air
1
1 : 250

F
Regulator and Filter View
3/4"ø

Humidity & Compressed Air


Shut-Off Valve
1/2"ø P120 PROJECT DETAILS JAMESWAY Incubator
Company Inc
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com
1/2"ø
DRAWN BY CHECKED BY DRAWING NUMBER REV.
CR DM P13
SCALE DATE PROJECT NUMBER
As indicated 02/02/17 Project #
CLIENT NAME Jamesway Incubator
Sample
H Drawings
Hum & Compressed Air Detail
3
1 : 50

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC
RTU-3
THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT
TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

B
NOTES

RTU-2

EF-4
P120
RTU-4

P120 P120
Du
c
13 t Size
"x2
0"

E
RTU-6 e
Siz "
P120 Supply Grill 20x20 ct
P120 Du "x20
20
Return Filter 20x20x2

F P120
P40 hatcher

HVAC Isometric View

PROJECT DETAILS JAMESWAY Incubator


Company Inc
P40 hatcher 30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


P40 hatcher CR DM P14
SCALE DATE PROJECT NUMBER
02/02/17 Project #
HVAC - Incubators and Hatcher Rooms
1 CLIENT NAME Jamesway Incubator
Sample
H Drawings

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
Guardian Controls - Low Voltage REPORTED BEFORE ANY OF THE WORK SHOWN ON
1 THIS DRAWING IS COMMENCED.
1 : 230
SP-P 3 SP-A 3 THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT
OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

B
SP-P 2 SP-A 2

CP 2

SP-P 1 SP-A 1 CP 1 SP-B 1


E
SP-B 2

3VSD

SP-A 4
F

Guardian Controls - Low Voltage

PROJECT DETAILS JAMESWAY Incubator


SP-C 1 Company Inc
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


CR DM P15
SCALE DATE PROJECT NUMBER
1 : 230 02/10/17 Project #
CLIENT NAME Jamesway Incubator
Sample
H Drawings

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

SP-P 3 SP-A 3 THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A Guardian Controls - Pressure DRAWING AND ANY SITE
1 DIMENSIONS/SPECIFICATIONS, THIS MUST BE
1 : 230 REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


BB 3 OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.
BB 2
B
SP-A 2

SP-P 2

OAR 1

BB 1 SP-B 1
E SP-B 2

SP-P 1 SP-A 1

SP-A 4
F

Guardian Controls - Pressure

PROJECT DETAILS JAMESWAY Incubator


SP-C 1 Company Inc
30 High Ridge Court
OAR 2 Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


CR DM P16
SCALE DATE PROJECT NUMBER
1 : 230 02/13/17 Project #
CLIENT NAME Jamesway Incubator
Sample
H Drawings

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

Guardian Controls - High Voltage WHERE A DISCREPANCY OCCURS BETWEEN THIS


A 1 DRAWING AND ANY SITE
1 : 230 DIMENSIONS/SPECIFICATIONS, THIS MUST BE
REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


D OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
D AND RECEIVED.

CPX - High Volt. Power Supply


(120/240 VAC, 1 phase, 50/60 H

VSDX - High Volt. Power Supply


(120/240 VAC, 1 phase, 50/60 H

D
D

D CP 2

CP 1
D
E
3VSD

F
D

Guardian Controls - High Voltage

PROJECT DETAILS JAMESWAY Incubator


D Company Inc
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com
D
DRAWN BY CHECKED BY DRAWING NUMBER REV.
CR DM P17
SCALE DATE PROJECT NUMBER
As indicated 02/13/17 Project #
CLIENT NAME Jamesway Incubator
Sample
H Drawings

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

B
NOTES

Guardian Controls - Isometric View

PROJECT DETAILS JAMESWAY Incubator


Company Inc
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


3D Guardian Controls CR DM P18
1 SCALE DATE PROJECT NUMBER
02/10/17 Project #
CLIENT NAME Jamesway Incubator
Sample
H Drawings

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
3 REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.
P19
THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT
RTU-2 RTU-3 OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

B SP-A 1 SP-P 1
NOTES

OAR 1
3VSD BB 1

C Incubator Room2 Incubator Room1

CP 1 P120 P120

Guardian Control - Incubator Room1 & 2


1
1 : 100
1
P19
E
RTU-2
RTU-4
EF-4

D
SP-A 1 BB 1 Incubator Room2 SP-A 2 BB 2
Guardian Controls Section

PROJECT DETAILS JAMESWAY Incubator


Company Inc
BB 3 30 High Ridge Court
Cambridge, Ontario, Canada

G P120 P120 P120 P40 hatcher N1R 7L3


Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


CR DM P19
SCALE DATE PROJECT NUMBER
1 : 100 02/10/17 Project #

Guardian Controls - Incubators/Hatcher CLIENT NAME Jamesway Incubator


Sample
H Rooms Drawings
3
1 : 100

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

Guardian Controls Notes

PROJECT DETAILS JAMESWAY Incubator


Company Inc
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


CR DM P20
SCALE DATE PROJECT NUMBER
02/10/17 Project #
CLIENT NAME Jamesway Incubator
Sample
H Drawings

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
Backup Alarm REPORTED BEFORE ANY OF THE WORK SHOWN ON
1 THIS DRAWING IS COMMENCED.
1 : 150 THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT
OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

- EACH BACK UP ALARM PANEL REQUIRES A


SEPARATE 115V/230V POWER CIRCUIT
(SEVERAL PANELS CAN SHARE THE SAME
CIRCUIT).

Hatcher Room2 - EACH BACK UP ALARM PANEL REQUIRES A


BELL OR SIREN AND A 12VDC/24VDC POWER
CIRCUIT. BELL OR SIREN PROVIDED BY
CUSTOMER.
C
- CABLES AND ALL WIRING MATERIALS TO BE
Back Up Alarm Panel LAID IN PLACE BY CUSTOMER. JAMESWAY TO
MAKE CONTROL WIRING CONNECTIONS AND
PERFORM INITIAL START-UP OF PANELS.

- BACK UP ALARM PANEL

- BACK UP ALARM CABLE PT 2185

F
Pull Room

Chick Room
Backup Alarm Layout

PROJECT DETAILS JAMESWAY Incubator


Company Inc

Incubator Room1 30 High Ridge Court


Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com

Clean room DRAWN BY


CR
CHECKED BY
DM
DRAWING NUMBER
P21
REV.

Egg Room SCALE DATE PROJECT NUMBER


Chick Room 1 : 150 02/10/17 Project #
CLIENT NAME Jamesway Incubator
Sample
H Drawings

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

B
NOTES

Backup Alarm - Isometeric View

PROJECT DETAILS JAMESWAY Incubator


Company Inc
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


CR DM P22
SCALE DATE PROJECT NUMBER
02/10/17 Project #
CLIENT NAME Jamesway Incubator
Sample
H Drawings

3D Backup Alarm
1

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A Hatchcom DRAWING AND ANY SITE
1 DIMENSIONS/SPECIFICATIONS, THIS MUST BE

Hatcher Room2 1 : 190 REPORTED BEFORE ANY OF THE WORK SHOWN ON


THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

B
Ethernet Hub
- ETHERNET CABLES MUST BE KEPT SEPARATE
FROM POWER WIRING AND ARE TYPICALLY RUN IN
THEIR OWN CABLE TRAY.

- ETHERNET CABLES SHOULD BE KEPT AWAY FROM


LIGHT FIXTURES.

- MAXIMUM DISTANCE FROM A MACHINE TO AN


ETHERNET HUB I 328 FT (100M)
C

- CONDUIT

- ETHERNET HUB (NOT PROVIDED BY JAMESWAY)


D

Pull Room

Incubator Room1
F

Hatchcom Layout

PROJECT DETAILS JAMESWAY Incubator


Company Inc

Chick Room
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646

Egg Room Fax 519 624 5803


[email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


Computer Station CR DM P23
SCALE DATE PROJECT NUMBER
1 : 190 02/10/17 Project #
CLIENT NAME Jamesway Incubator
Sample
H Drawings

1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 JAMESWAY INCUBATOR COMPANY INC

THIS DRAWING IS FOR QUOTATION ONLY; IT IS NOT


TO BE USED FOR CONSTRUCTION.

WHERE A DISCREPANCY OCCURS BETWEEN THIS


A DRAWING AND ANY SITE
DIMENSIONS/SPECIFICATIONS, THIS MUST BE
REPORTED BEFORE ANY OF THE WORK SHOWN ON
THIS DRAWING IS COMMENCED.

THE CONTENTS OF THIS DRAWING IS THE COPYRIGHT


OF JAMESWAY INCUBATOR COMPANY INC AND MUST
NOT BE REPRODUCED IN WHOLE OR IN PART
WITHOUT THEIR WRITTEN CONSENT BEING GIVEN
AND RECEIVED.

B
NOTES

Hatchcom - Isometric View

PROJECT DETAILS JAMESWAY Incubator


Company Inc
30 High Ridge Court
Cambridge, Ontario, Canada
N1R 7L3
G Tel 519 624 4646
Fax 519 624 5803
[email protected]
www.jamesway.com

DRAWN BY CHECKED BY DRAWING NUMBER REV.


CR DM P24
SCALE DATE PROJECT NUMBER
02/10/17 Project #
CLIENT NAME Jamesway Incubator
Sample
H Drawings

3D Hatchcom
1
1 2 3 4 5 6 7 8 9 10