Bending Moment Calculation - Anticreep Center, One Cantilever, Tangent Track

This document provides input data and calculations to determine bending moments on a cantilever mast structure for an overhead line. It includes dimensions, weights, tensions, and loads from wires, wind, brackets, and other equipment. Calculations summarize total vertical loads, bending moments from radial tensions, wind loads parallel and perpendicular to the track, and compressive stresses on the mast to check if it is within permissible safety limits.

Uploaded by

Ankit Agarwal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views7 pages

Bending Moment Calculation - Anticreep Center, One Cantilever, Tangent Track

This document provides input data and calculations to determine bending moments on a cantilever mast structure for an overhead line. It includes dimensions, weights, tensions, and loads from wires, wind, brackets, and other equipment. Calculations summarize total vertical loads, bending moments from radial tensions, wind loads parallel and perpendicular to the track, and compressive stresses on the mast to check if it is within permissible safety limits.

Uploaded by

Ankit Agarwal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 7

Bending Moment Calculation - Anticreep Center, One Cantilever, Tangent Track

Input Data Sheet

STRUCTURE BFB Actual Condition


Wind Pressure Kg/m2 150
Wt of Section kg\m 52 Height of Mast m 8.1
Width of Se. m 0.206 Catenary Wire Height (H2) m 7
Width of Se. m 0.203 Contact Wire Height (H1) m 5.8
Weight of BA kg 60 RC Height m
Height of RC from Top of
Length of Mast m 9.5 Mast m
σac Kg/cm2 568 Earth Wire Height (OPC) m 7.33
σbcx Kg/cm 2
1616
σbcy Kg/cm2 2242 Stagger at CW OHE1 0.2
Ixx cm4 5263 Mean Span : Main Line (L) m 45
Iyy cm 4
1770 Right Span m 45
Zxx cm3 510 Left Span m 45
Distance of Cat W from Mast
Zyy cm3 174 (a) i m 2.75
2
Area cm 66.4
Shape Factor 1 Distance of mast from ACC m 0
Weight of Man Kg 60
Guy Rod Assembly Kg 30
Height Anti creep m 7
Weight of RC Fitting Kg

Wire & Cables Nominal Tension Dia(m) Weight(K


tension With Wind gf)

Catenary Wire 1200 1200 0.0105 0.605


Contact Wire 1200 1200 0.01224 0.952
Earth Wire(OPC) 400 400 0.01227 0.318
Anticreep Wire 400 400 0.0125 0.731
RC Wire
Cable Factor 0.67

Typical Mast Calculation


Vertical Axial Loads
Load (Kgf)
Mast (WxL) 421.2
Half Bracket 30
Earth Wire 14
RC Wire 0
Guy Rod Assembly 30
Guy Rod Vertical Componant 400

Total T1 896 Kgf

Vertical Non Axial Loads


Lever Arm Load Bending Moment
m Kgf X- Axis Y - Axis
Half Bracket (30Kg) 1 2.75 30 83 0
Man (60Kg) 2.75 60 165 0
OHE (P1 ) 2.75 70 193 0
RC & Fittings (PR) 0 0 0
160.065
Total Vertical Load 1055.575
Total BM Due to Vertical Load (Kgf-m) 440 0

Radial Tension Location XX-Axis YY- Axis


Lever arm Load BM BM
m Kgf Kgfm Kgf-m
d*BM/i
Contact Wire 1 5.8 21.33 123.73 0
Catenary Wire 7 21.33 149.33 0
Anti Creep Wire 7 25.35 177.43
Anticreep Anchor 4.5 20.44 92.00
Total Horizental Load 68.01
Total BM Due to Radial Tension(Kgf-m) 542 0

Wind Blowing
Parpendicular to Wind Blowing Parallel
Wind Loads Lever Arm Load track to Moment
Bending track -Y
Bending Moment axis
m (Kgf) X- Axis Y - Axis Load BM(Kgf-m)
IR Catenary + 1/2 Dropper 7 47 332 0
IR Contact Wire + 1/2 Dropper 5.8 55 321 0
Earth Wire 7.33 55 407
AntiCreep Wire 7 28 198
Mast (WxL) 4.05 250 1014 247 998.91
Bracket 7.1 40 284
Total Wind Load 334.05 40.00
Total BM Due to Wind Load (Kgf-m) 2272 0 1283
For Normal Mast

A. Radial Tension Units

i) In St. Stretch, Due to stagger of CW only


V = 2T x 2 x Stagger/Span 21.33 Kgf

ii)Anticreep Anchor 20.4444444444


ii)Anticreep Wire 25.3 Kgf

B. Wind Load (Wind Perpandiculer the Track)

i) On the mast 250.29 Kgf

ii)On the OHE


a) Wind load on Cat. 47.49 Kgf
Wind Load is increased by 5% for wind load
on Droppers at Both Wire.

b)Wind load on Contact Wire 55.36 Kgf

c) Wind Load on earth Wire 55.5 Kgf

d) Wind Load on RC 0.0 Kgf

e) Anticreep Anchor 0.0

e)Wind Load on Anti Creep wire 28 Kgf

C.Wind Load (Wind parallel to the Track


a) Wind Load on Mast 247 Kgf
b)Wind load on BA 40 Kgf
Movement (Longitudinal) of the Bracket tip

Elongation of the Ohe Conductors due to rise of Temprature

d=D x β X (T'-T) 0m

Where
D = Distance of the mast from the anticreep 0
β = Co-efficient of linear expension 1.7E-05
T' = Maximum Temprature =65 oC 65
T = Avg. Normal Temprature =35 oC 35

Due to all the loads acting on the bracket will produce BM along YY' axis of
the BFB
BM at the base due to horizntal loads = Horizental Load X (d/a) X Ht above
the Foundation
BM at the base due to vertical load W = Wxd (OHE)

BM at the base due to vertical load W = Wxd/2 (Cant.)


To Check the Saftey of mast

1st Step Sum up the all Loads and Moments

∑V Sum of all vertical Loads 1055.575 Kgf

Sum of all the horizental Forces Acting on the mast Perpendicular


∑Hx to the track 68.01333 Kgf

∑Hy Sum of all the horizental Forces Acting parallel to the track Kgf

∑Mxx Sum of all the Moments Acting Perpendicular to the track 3254.421 Kgf-m

∑Myy Sum of all the Moments Acting parallel to the track 0.00 Kgf-m

Permissible axial compressive stress in the member subject to


σac axial compression load only. 568 Kgf/cm2

σac.cal Calculated avg. axial compressive stress 15.90 Kgf/cm2

σbcx.cal Calculated bending compressive stress in the extreme fibre 638.12 Kgf/cm2
σbcy.cal Calculated bending compressive stress in the extreme fibre 0.00 Kgf/cm2
σbcx Premissible bending compressive stress in extreme fibre. 1616 Kgf/cm2
σbcy Premissible bending compressive stress in extreme fibre. 2242 Kgf/cm2

The Worst stressed section is obviously near the top of the foundation

Therefore

Axial stress fa = ∑V/a 15.90 Kgf/cm2

Bending Stress fbx =∑Mxx/Zxx 638.12 Kgf/cm2

Bending Stress fby =∑Myy/Zyy 0.00 Kgf/cm2

σac =Theortical Value 568 Kgf/cm2

σac.cal 15.90 Kgf/cm2


Ratio of σac.cal/σac 0.028

If Ratio (𝜎𝑎𝑐.𝑐𝑎𝑙)/𝜎𝑎𝑐≤0.15

and

(𝜎𝑎𝑐.𝑐𝑎𝑙)/𝜎𝑎𝑐+(𝜎𝑏𝑐𝑥.𝑐𝑎𝑙)/𝜎𝑏𝑐𝑥+(𝜎𝑏𝑐𝑦.𝑐𝑎𝑙)/𝜎𝑏𝑐𝑦≤1.0

0.42

Hence Mast is safe


Type of Load Wind perp. to track Wind parallel to Track
XX-Axis YY- Axis XX-Axis YY- Axis
Load Moment
Kgf-m Kgf-m Kgf-m Kgf-m

Due to Vertical Non Axial Load 440 0.00 542 0


Due to Radial Tension 542.49 0.00 440 0
Due to Wind load 2271.75 0 1283

Total Bending Moment Kgf.m 3254 0 983 1283