Powerflex 70 Reference Manual
Powerflex 70 Reference Manual
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
Notes:
Chapter 1
Preface Manual Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter 2
Detailed Drive Operation Accel Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Advanced Tuning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Auto/Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Auto Restart (Reset/Run) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Autotune. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Bus Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Cable, Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Cable, Motor Lengths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Cable, Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Cable Trays and Conduit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Carrier (PWM) Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
CE Conformity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Copy Cat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Current Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Datalinks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
DC Bus Voltage / Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Decel Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Digital Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Digital Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Direction Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
DPI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Drive Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Drive Ratings (kW, Amps, Volts) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Droop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Economizer (Auto-Economizer) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Fan Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Flux Braking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Flux Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Notes:
Preface
Manual Conventions To help differentiate parameter names and LCD display text from other text, the
following conventions will be used:
• Parameter Names will appear in [brackets]. For example: [DC Bus Voltage].
• Display Text will appear in “quotes.” For example: “Enabled.”
• The following words are used throughout the manual to describe an action:
Word Meaning
Can Possible, able to do something
Cannot Not possible, not able to do something
May Permitted, allowed
Must Unavoidable, you must do this
Shall Required and necessary
Should Recommended
Should Not Not recommended
• The following symbols are used throughout the manual to indicate specific
drive imformation.
Symbol Description
Standard Indicates that the information presented is specific to the Standard Control Option
Vector This information only applies to PowerFlex 700 drives with the Vector Control option
Vector FV Applies to PowerFlex 700 drives with [Motor Cntl Sel] set to “FVC Vector.”
Indicates that the information presented is specific to the PowerFlex 70 Enhanced Control
EC
Option.
Additional Resources These documents contain additional information concerning related products
from Rockwell Automation.
Resource Description
PowerFlex 700 Standard Control User Manual, Provides detailed information on:
publication 20B-UM001 • Parameters and programming
• Faults, alarms, and troubleshooting
PowerFlex 70 AC Drive Technical Data, publication This publication provides detailed drive specifications,
20A-TD001 option specifications and input protection device ratings.
PowerFlex 700 AC Drive Technical Data, publication
20B-TD001
PowerFlex Comm Adapter Manuals, publication These publications provide information on configuring,
20COMM-UM… using, and troubleshooting PowerFlex communication
adapters.
PowerFlex 70 Enhanced Control and PowerFlex 700 These publications provide detailed application specific
Vector Control Reference Manual, publication information for programming and configuring the
PFLEX-RM004 PowerFlex 700 drive.
Wiring and Grounding Guidelines for Pulse Width Provides basic information needed to properly wire and
Modulated (PWM) AC Drives, publication DRIVES-IN001 ground PWM AC drives.
Safety Guidelines for the Application, Installation and Provides general guidelines for the application,
Maintenance of Solid State Control, publication SGI-1.1 installation, and maintenance of solid-state control.
Guarding Against Electrostatic Damage, publication Provides practices for guarding against Electrostatic
8000-4.5.2 damage (ESD)
General Precautions ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts
! and assemblies. Static control precautions are required when installing, testing,
servicing or repairing this assembly. Component damage may result if ESD
control procedures are not followed. If you are not familiar with static control
procedures, reference A-B publication 8000-4.5.2, “Guarding Against
Electrostatic Damage” or any other applicable ESD protection handbook.
ATTENTION: An incorrectly applied or installed drive can result in component
! damage or a reduction in product life. Wiring or application errors, such as,
undersizing the motor, incorrect or inadequate AC supply, or excessive ambient
temperatures may result in malfunction of the system.
ATTENTION: Only qualified personnel familiar with adjustable frequency AC
! drives and associated machinery should plan or implement the installation,
start-up and subsequent maintenance of the system. Failure to comply may
result in personal injury and/or equipment damage.
ATTENTION: To avoid an electric shock hazard, verify that the voltage on the
! bus capacitors has discharged before performing any work on the drive.
Measure the DC bus voltage at the +DC & –DC terminals of the Power Terminal
Block (refer to the Installation Instructions for location). The voltage must be
zero.
Two accel times exist to allow the user to change acceleration rates “on the fly” via
PLC command or digital input. The selection is made by programming [Accel
Time 1] & [Accel Time 2] and then using one of the digital inputs ([Digital Inx
Sel]) programmed as “Accel 2” (see Table 9 for further information). However, if
a PLC is used, manipulate the bits of the command word as shown below.
(1)
(1)
(1)
Sp Ref 2
De Ref 1
De l 2 0
Fo rse trl
g ult
D
d ID
ce ID
ve n
Sp Dec
Sp Ref I
Re l Co
Cle ard
Jo r Fa
Lo Inc
Ac l 1
Ac l 2
Mo el 1
ce
ce
rw
ca
Sto t
P
p
a
p
r
d
d
c
MO
Sta
0 0 0 0 1 1 1 0 1 0 0 0 1 1 0 0 1 = Condition True
0 = Condition False
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 x = Reserved
Bit #
0 0 0 1 Accel 1
0 0 1 0 Accel 2
0 1 0 0 Decel 1
1 0 0 0 Decel 2
The effectiveness of these bits or digital inputs can be affected by [Accel Mask].
See Masks on page 113 for more information.
Times are adjustable in 0.1 second increments from 0.0 seconds to 3600.0
seconds.
In its factory default condition, when no accel select inputs are closed and no
accel time bits are “1,” the default acceleration time is Accel Time 1 and the rate is
determined as above.
The following parameters can only be viewed when “2, Unused” is selected in
parameter 196, [Param Access Lvl].
Related
Group
File
No.
Parameter Name & Description Values
500 [KI Current Limit] Default: 1500
Current Limit Integral gain. This gain is applied to the Min/Max: 0/10000
current limit error signal to eliminate steady state current Units: 1
limit error. A larger value increases overshoot during a
step of motor current/load.
501 [KD Current Limit] Default: 500
Current Limit Derivative gain. This gain is applied to the Min/Max: 0/10000
sensed motor current to anticipate a current limit Units: 1
condition. A larger value reduces overshoot of the current
relative to the current limit value.
502 [Bus Reg ACR Kp] Default: 450
This proportional gain, in conjunction with P160, adjusts Min/Max: 0/10000
the output frequency of the drive during a bus limit or Units: 1
inertia ride through condition. The output frequency is
adjusted in response to an error in the active, or torque
producing, current to maintain the active bus limit, or
inertia ride through bus reference. A larger value of gain
reduces the dynamic error of the active current.
503 [Jerk] Default: 900
This parameter allows you to adjust the amount of Min/Max: 2/30000
S-Curve, or “Jerk” applied to the Acc/Dec rate. To enable Units: 1
Diag-Motor Cntl
Related
Group
File
No.
Parameter Name & Description Values
509 [Lo Freq Reg KpId] Default: 64
This proportional gain adjusts the output voltage at very Min/Max: 0/32767
low frequency in response to the reactive, or d-axis, Units: 1
motor current. A larger value increases the output
voltage change.
510 [Lo Freq Reg KpIq] Default: 64
The proportional gain adjusts the output voltage at very Min/Max: 0/32767
low frequency in response to the active, or q-axis, motor Units: 1
current. A larger value increases the output voltage
change.
511 [Ki Cur Reg] Default: 44
This integral gain adjusts the output voltage in response Min/Max: 0/32767
to the q and d axis motor currents. A larger value Units: 1
increases the output voltage change.
512 [Kp Cur Reg] Default: 1600
This proportional gain adjusts the output voltage in Min/Max: 0/32767
response to the q and d axis motor currents. A larger Units: 1
value increases the output voltage change.
Diag-Motor Cntl
Related
Group
File
No.
Parameter Name & Description Values
525 [Torq Adapt Speed] Default: 10.0%
Selects the operating frequency/speed at which the Min/Max: 0.0/100.0%
adaptive torque control regulators become active as a Units: 0.1%
percent of motor nameplate frequency.
526 [Torq Reg Enable] Default: 1
Enables or disables the torque regulator Min/Max: 0/1
Units: 1
527 [Kp Torq Reg] Default: 32
Proportional gain for the torque regulator Min/Max: 0/32767
Units: 1
528 [Ki Torq Reg] Default: 128
Integral gain for the torque regulator Min/Max: 0/32767
Units: 1
529 [Torq Reg Trim] Default: 1.0
Torque Regulator trim gain. A larger value increases the Min/Max: 0.5/1.5
developed torque. Typically used to compensate for Units: 0.1
losses between developed and shaft torque.
530 [Slip Reg Enable] Default: 1
Enables or disables the slip frequency regulator. Min/Max: 0/1
Units: 1
531 [Kp Slip Reg] Default: 256
Proportional gain for the slip frequency regulator. Min/Max: 0/32767
Units: 1
Diag-Vector Cnt
Alarms Alarms are indications of situations that are occurring within the drive or
application that should be annunciated to the user. These situations may affect
the drive operation or application performance. Conditions such as Power Loss
or Analog input signal loss can be detected and displayed to the user for drive or
operator action.
• Type 1 Alarms are conditions that occur in the drive or application that may
require alerting the operator. These conditions, by themselves, do not cause
the drive to “trip” or shut down, but they may be an indication that, if the
condition persists, it may lead to a drive fault.
• Type 2 Alarms are conditions that are caused by improper programming and
they prevent the user from Starting the drive until the improper programming
is corrected. An example would be programming one digital input for a 2-wire
type control (Run Forward) and another digital input for a 3-wire type
control (Start). These are mutually exclusive operations, since the drive could
not determine how to properly issue a “Run” command. Because the
programming conflicts, the drive will issue a type 2 alarm and prevent Starting
until the conflict is resolved.
Two 16 bit Drive Alarm parameters are available to indicate the status of any
alarm conditions. Both Type 1 and Type 2 alarms are indicated.
A “1” in the bit indicates the presence of the alarm and a “0” indicates no alarm is
present
Configuration
In order for a drive alarm to be annunciated to the “outside” world, it must first
be “configured” or activated. Configuration parameters contain a configuration
bit for each Type 1 alarm. Type 2 alarms are permanently configured to
annunciate. The configuration word is a mirror image of the Drive Alarm word;
that is, the same bits in both the Drive Alarm Word and the Alarm Configuration
Word represent the same alarm.
Drive Alarm
1 1 1
Alarm Config
1 0 0
X X
The configuration bits act as a mask to block or pass through the alarm condition
to the active condition. An active alarm will be indicated on the LCD HIM and
will cause the drive alarm status bit to go high (“1”) in the Drive Status word (Bit
6, parameter 209). This bit can then be linked to a digital output for external
annunciation. As default, all configuration bits are high (“1”). Note that setting a
configuration bit to “0” to “mask” an alarm does not affect the status bit in the
Drive Alarm parameter, only its ability to annunciate the condition.
Application
A process is being controlled by a PowerFlex drive. The speed reference to the
drive is a 4-20 mA analog signal from a sensor wired to Analog Input 1.
=V mA
mA
1 0 1=
1=
An 0=V
2
An
x x x x x x x x x x x x x x 0 0 1 =Current
0 =Voltage
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 x =Reserved
Bit #
Factory Default Bit Values
Analog In Config
0 1
The input is scaled for 4-20 mA by setting [Analog In 1 Lo] to “4” mA and
[Analog In 1 Hi] to “20” mA.
The signal is designated as the active speed reference by setting [Speed Ref A Sel]
to its factory default value of “1”
090 [Speed Ref A Sel] Default: 2 “Analog In 2” 002
Selects the source of the speed reference to the drive Options: 1 “Analog In 1” 091
unless [Speed Ref B Sel] or [Preset Speed 1-7] is 2 “Analog In 2” thru
selected. 3-6 “Reserved” 093
7 “Pulse In” 101
(1) See User Manual for DPI port locations. 8 “Encoder” thru
9 “MOP Level” 107
117
Speed References
10 “Reserved”
11 “Preset Spd1” thru
12 “Preset Spd2” 120
13 “Preset Spd3” 192
14 “Preset Spd4” thru
15 “Preset Spd5” 194
16 “Preset Spd6” 213
17 “Preset Spd7” 272
18 “DPI Port 1”(1) 273
19 “DPI Port 2”(1) 320
20 “DPI Port 3”(1) 361
21 “DPI Port 4”(1) thru
22 “DPI Port 5”(1) 366
The input is configured to recognize a loss of signal and react accordingly to the
programming.
324 [Analog In 1 Loss] Default: 0 “Disabled” 091
327 [Analog In 2 Loss] 0 “Disabled” 092
Selects drive action when an analog signal loss is Options: 0 “Disabled”
detected. Signal loss is defined as an analog signal less 1 “Fault”
than 1V or 2mA. The signal loss event ends and normal 2 “Hold Input”
operation resumes when the input signal level is greater 3 “Set Input Lo”
than or equal to 1.5V or 3mA. 4 “Set Input Hi”
5 “Goto Preset1”
6 “Hold OutFreq”
The loss action is chosen as Hold Input, meaning that the last received signal will
be maintained as the speed reference.
Finally, a Digital Output relay is configured to annunciate an alarm by turning on
a flashing yellow light mounted on the operator panel of the process control area.
380 [Digital Out1 Sel] Default: 1 “Fault” 381
384 [Digital Out2 Sel] 4 “Run” 385
388 Vector [Digital Out3 Sel] 4 “Run” 382
Selects the drive status that will energize a (CRx) output Options: 1 “Fault”(1) 386
relay. 2 “Alarm”(1) 383
3 “Ready”
(1)Contacts shown in User Manual are in drive powered 4 “Run”
state with condition present. Refer to “Fault” and 5 “Forward Run”
“Alarm” information. 6 “Reverse Run”
(2)Vector Control Option Only. 7 “Auto Restart”
8 “Powerup Run” 002
INPUTS & OUTPUTS
While the process is normal and running from the analog input, everything
proceeds normally. However, if the wire for the analog input should be severed or
the sensor malfunction so that the 4-20mA signal is lost, the following sequence
occurs:
2. An active Type 1 Alarm is created and the last signal value is maintained as the
speed reference.
3. The alarm activates the digital output relay to light the alarm light for the
operator.
4. The operator uses the HIM to switch the drive to Manual Control (see Auto/
Manual).
5. The operator manually brings the process to a controlled stop until the signal
loss is repaired.
[Current Lmt Sel] allows an analog input to control the set point while [DC Brk
Levl Sel] allows an analog input to define the DC hold level used when
Ramp-to-Stop, Ramp-to-Hold, or Brake-to-Stop is active.
To provide local adjustment of a master command signal or to provide improved
resolution the input to analog channel 1 or 2 can be defined as a trim input.
Setting [Trim In Select] allows the selected channel to modify the commanded
frequency by ±10%. The speed command will be reduced by 10% when the input
level is at [Anlg In x Lo] with it linearly increasing to 10% above command at
[Anlg In xHi].
Feedback can be used to control an operation using the “Process PI”
(proportional-integral) feature of the control. In this case one signal, defined
using [PI Reference Sel], provides a reference command and a second, defined
using [PI Feedback Sel], provides a feedback signal for frequency compensation.
Please refer to the Process PI Loop on page 135 for details on this mode of
operation.
Analog In 1 Hi
Analog Input Volts or mA Parameter
Cal Analog 1
1 Scale
Analog In 2 Lo Processing
Analog In 2 Hi Selection/Control
Analog Input Volts or mA
Cal Analog 2
2 Scale
Speed Ref A Sel Speed Ref B Sel Trim In Select TB Man Ref Sel PI Reference Sel PI Feedback Sel Current Lmt Sel DC Brk Levl Sel Sleep-Wake Ref Torque Ref A Sel Torque Ref B Sel
Speed Ref A Lo
Speed Ref A Hi
Speed Ref B Lo Sleep Level Torque Ref A Lo Torque Ref B Lo
Ref A Brake Level
Scale/Limit Speed Ref B Hi Scale/Limit Wake Level Torque Ref A Hi Torque Ref B Hi
Trim Lo
Ref B Sleep Level Torque Ref A Torque Ref B
Scale/Limit Trim Hi Compare Div Mult
Trim
Scale/Limit
TB Manual
Hz Scale/Limit
Current Limit
+
Scale/Limit
Reference A Reference B TB Manual PI Reference PI Feedback Current Limit DC Brake Sleep/Wake Torque Ref A Torque Ref B
Input/Output
Parameter
Processing
Selection/Control
Analog 1
Current 0-20mA Current Loss Limit
Square
Cal 1 Detect 4-20mA
Root
21
Analog Inputs
Analog Inputs
Analog Scaling
[Analog In Hi]
[Analog In Lo]
A scaling operation is performed on the value read from an analog input in order
to convert it to units usable for some particular purpose. The user controls the
scaling by setting parameters that associate a low and high point in the input
range (i.e. in volts or mA) with a low and high point in the target range (e.g.
reference frequency).
Two sets of numbers may be used to specify the analog input scaling. One set
(called the “input scaling points”) defines low and high points in terms of the
units read by the input hardware, i.e. volts or mA.
The second set of numbers (called the “output scaling points”) used in the analog
input scaling defines the same low and high points in units appropriate for the
desired use of the input. For instance, if the input is to be used as a frequency
reference, this second set of numbers would be entered in terms of Hz. For many
features the second set of numbers is fixed. The user sets the second set for speed
and reference trim.
The 0-10 volt input scaling can be adjusted using the following parameters:
• [Analog In x Lo]
• [Analog In x Hi]
Configuration #1:
This is the default setting, where minimum input (0 volts) represents 0 Hz and
maximum input (10 volts) represents 60 Hz (it provides 6 Hz change per input
volt).
12
10
Input Volts
6
0 6 12 18 24 30 36 42 48 54 60
Output Hertz
Analog Scaling
[Speed Reference A Sel] = “Analog In 1”
[Analog In 1 Hi] [Speed Ref A Hi]
10V 60 Hz
[Analog In 1 Lo] [Speed Ref A Lo]
0V 0 Hz
Configuration #2:
10
8
Input Volts
0 6 12 18 24 30 36 42 48 54 60
Output Hertz
Analog Scaling
[Speed Reference A Sel] = “Analog In 1”
[Analog In 1 Hi] [Speed Ref A Hi]
10V 30 Hz
[Analog In 1 Lo] [Speed Ref A Lo]
0V 0 Hz
Configuration #3:
20
16
Input mA
12
0 6 12 18 24 30 36 42 48 54 60
Output Hertz
Configuration #4:
This configuration is used to invert the operation of the input signal. Here,
maximum input (10 Volts) represents 0 Hz and minimum input (0 Volts)
represents 60 Hz.
10
Input Volts
6
0 6 12 18 24 30 36 42 48 54 60
Output Hertz
Analog Scaling
[Speed Reference A Sel] = “Analog In 1”
[Analog In 1 Hi] [Speed Ref A Hi]
10V 0 Hz
[Analog In 1 Lo] [Speed Ref A Lo]
0V 60 Hz
Configuration #5:
This configuration is used when the input signal is 0-5 volts. Here, minimum
input (0 Volts) represents 0 Hz and maximum input (5 Volts) represents 60 Hz.
This allows full scale operation from a 0-5 volt source.
4
Input Volts
0 6 12 18 24 30 36 42 48 54 60
Output Hertz
Analog Scaling
[Speed Reference A Sel] = “Analog In 1”
[Analog In 1 Hi] [Speed Ref A Hi]
5V 60 Hz
[Analog In 1 Lo] [Speed Ref A Lo]
0V 0Hz
10
8
Input Volts
Analog Scaling
[Torque Ref A Sel] = “Analog In 1”
[Analog In 1 Hi] [Torque Ref A Hi]
10V 200%
[Analog In 1 Lo] [Torque Ref A Lo]
0V 0%
Square Root
[Anlg In Sqr Root]
For both analog inputs, the user can enable a square root function for an analog
input through the use of [Analog In Sq Root]. The function should be set to
enabled if the input signal varies with the square of the quantity (i.e. drive speed)
being monitored.
If the mode of the input is bipolar voltage (–10v to 10v), then the square root
function will return 0 for all negative voltages.
The square root function is scaled such that the input range is the same as the
output range. For example, if the input is set up as a unipolar voltage input, then
the input and output ranges of the square root function will be 0 to 10 volts, as
shown in figure below.
10
Output (Volts)
0 2 4 6 8 10
Input (Volts)
Signal Loss
[Analog In 1, 2 Loss]
Signal loss detection can be enabled for each analog input. The [Analog In x
Loss] parameters control whether signal loss detection is enabled for each input
and defines what action the drive will take when loss of any analog input signal
occurs.
One of the selections for reaction to signal loss is a drive fault, which will stop the
drive. All other choices make it possible for the input signal to return to a usable
level while the drive is still running.
• Hold input
• Set input Lo
• Set input Hi
• Goto Preset 1
• Hold Output Frequency
Value Action on Signal Loss
0 Disabled (default)
1 Fault
2 Hold input (continue to use last frequency command.)
3 Set Input Hi - use [Minimum Speed] as frequency command.
4 Set Input Lo - use [Maximum Speed] as frequency command.
5 use [Preset 1] as frequency command.
6 Hold Out Freq (maintain last output frequency)
If the input is in current mode, 4 mA is the normal minimum usable input value.
Any value below 3.2 mA will be interpreted by the drive as a signal loss, and a
value of 3.8 mA will be required on the input in order for the signal loss
condition to end.
4 mA
3.8 mA
3.2 mA
If the input is in unipolar voltage mode, 2V is the normal minimum usable input
value. Any value below 1.6 volts will be interpreted by the drive as a signal loss,
and a value of 1.9 volts will be required on the input in order for the signal loss
condition to end.
No signal loss detection is possible while an input is in bipolar voltage mode. The
signal loss condition will never occur even if signal loss detection is enabled.
2V
1.9V
1.6V
Trim
An analog input can be used to trim the active speed reference (Speed Reference
A/B). If analog is chosen as a trim input, two scale parameters are provide to scale
the trim reference. The trim is a +/- value which is summed with the current
speed reference. See also Speed Reference on page 167.
• [Trim In Select]
• [Trim Out Select]
• [Trim Hi]
• [Trim Lo]
Value Display
Parameters are available in the Monitoring Group to view the actual value of an
analog input regardless of its use in the application. Whether it is a current limit
adjustment, speed reference or trim function, the incoming value can be read via
these parameters.
The value displayed includes the input value plus any factory hardware
calibration value, but does not include scaling information programmed by the
user (i.e. [Analog In 1 Hi/Lo]). The units displayed are determined by the
associated configuration bit (Volts or mA)
016 [Analog In1 Value] Default: Read Only
017 [Analog In2 Value]
Metering
Min/Max: 0.000/20.000 mA
Value of the signal at the analog inputs. –/+10.000V
Display: 0.001 mA
0.001 Volt
Cable Selection
Refer to “Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)
AC Drives,” publication DRIVES-IN001 for detailed information on Cable
Selection.
How [Analog Inx Hi/Lo] & [Speed Ref A Hi/Lo] Scales the Frequency
Command Slope with [Minimum/Maximum Speed]
Example 1:
This operation is similar to the 0-10 volts creating a 0-60 Hz signal until the
minimum and maximum speeds are added. [Minimum Speed] and [Maximum
Speed] limits will create a command frequency deadband.
Command Frequency
2. Determine the frequency span between the Minimum and Maximum Speed
limits and Speed Ref A Hi and Lo.
[Speed Ref A Hi] – [Maximum Speed] = 60 – 45 = 15 Hz and . . .
[Minimum Speed] – [Speed Ref A Lo] = 15 – 0 = 15 Hz.
Therefore the command frequency from 0 to 2.5 volts on the analog input will be
15 Hz. After 2.5 volts, the frequency will increase at a rate of 0.16667 volts per
hertz to 7.5 volts. After 7.5 volts on the analog input the frequency command will
remain at 45 Hertz.
Example 2:
Consider the following setup:
• [Anlg In Config], bit 0 = “0” (voltage)
• [Speed Ref A Sel] = “Analog In 1”
• [Analog In1 Hi] = 10V
• [Analog In1 Lo] = 0V
• [Speed Ref A Hi] = 50hz
• [Speed Ref A Lo] = 0hz
• [Maximum Speed] = 45hz
• [Minimum Speed] = 15hz
The only change from Example 1 is the [Speed Ref A Hi] is changed to 50 Hz.
[Minimum Speed] [Maximum Speed]
[Analog In1 Hi]
10V
Command Frequency
2. Determine the frequency span between the minimum and maximum speed
limits and the Speed Ref A Hi and Lo.
[Speed Ref A Hi] – [Maximum Speed] = 50 – 45 = 5 Hz and . . .
[Minimum Speed] – [Speed Ref A Lo] = 15 – 0 = 15 Hz
The user selects the analog output source by setting [Analog Out Sel].
342 [Analog Out1 Sel] Default: 0 “Output Freq” 001
345 Vector [Analog Out2 Sel] Options: See Table 002
Selects the source of the value that drives the analog 003
output. 004
005
007
[Analog Out1 Lo] Value 006
Options Param. 341 = Signed Param. 341 = Absolute [Analog Out1 Hi] Value
012
0 “Output Freq” –[Maximum Speed] 0 Hz +[Maximum Speed]
1 “Command Freq” –[Maximum Speed] 0 Hz +[Maximum Speed]
135
1* “Command Spd” –[Maximum Speed] 0 Hz/RPM +[Maximum Speed] 136
2 “Output Amps” 0 Amps 0 Amps 200% Rated 137
INPUTS & OUTPUTS
Configuration
The PowerFlex 70 standard I/O analog output is permanently configured as a
0-10 volt output. The output has 10 bits of resolution yielding 1024 steps. The
analog output circuit has a maximum 1.3% gain error and a maximum 7 mV
offset error. For a step from minimum to maximum value, the output will be
within 0.2% of its final value after 12ms.
Absolute (default)
Certain quantities used to drive the analog output are signed, i.e. the quantity can
be both positive and negative. The user has the option of having the absolute
value (value without sign) of these quantities taken before the scaling occurs.
Absolute value is enabled separately for each analog output via the bitmapped
parameter [Anlg Out Absolut].
Important: If absolute value is enabled but the quantity selected for output is
not a signed quantity, then the absolute value operation will have no
effect.
Scaling Blocks
The user defines the scaling for the analog output by entering analog output
voltages into two parameters, [Analog Out1 Lo] and [Analog Out1 Hi]. These
two output voltages correspond to the bottom and top of the possible range
covered by the quantity being output. The output voltage will vary linearly with
the quantity being output. The analog output voltage will not go outside the
range defined by [Analog Out1 Lo] and [Analog Out1 Hi].
10V
[Analog Out1 Hi]
Output Current vs.
Analog Analog Output Voltage
Output Voltage
Marker Lines
Note that analog output value never goes outside the range defined by [Analog
Out1 Lo] and [Analog Out1 Hi]. This is true in all cases, including all the
following examples.
10V
[Analog Out1 Lo]
Output Current vs.
Analog Analog Output Voltage
Output Voltage
Marker Lines
This example shows that you can have [Analog Out1 Lo] greater than [Analog
Out1 Hi]. The result is a negative slope on the scaling from original quantity to
analog output voltage. Negative slope could also be applied to any of the other
examples in this section.
10V
[Analog Out1 Hi]
– 200% 0% 200%
Output Torque Current
10V
[Analog Out1 Hi]
– 200% 0% 200%
Output Torque Current
Filtering
Software filtering will be performed on the analog outputs for certain signal
sources, as specified in Table 1. “Filter A” is one possible such filter, and it is
described later in this section. Any software filtering is in addition to any
hardware filtering and sampling delays.
Table 1 Software Filters
Quantity Filter
Output Frequency No extra filtering
Commanded Frequency No extra filtering
Output Current Filter A
Output Torque Current Filter A
Output Flux Current Filter A
Output Power Filter A
Output Voltage No extra filtering
DC Bus Voltage Filter A
PI Reference No extra filtering
PI Feedback No extra filtering
PI Error No extra filtering
PI Output No extra filtering
Analog output software filters are specified in terms of the time it will take the
output of the filter to move from 0% to various higher levels, given an
instantaneous step in the filter input from 0% to 100%. The numbers describing
filters in this document should be considered approximate; the actual values will
depend on implementation.
Filter A is a single pole digital filter with a 162ms time constant. Given a 0% to
100% step input from a steady state, the output of Filter A will take 500ms to get
to 95% of maximum, 810 ms to get to 99%, and 910 ms to get to 100%.
Output Scaling
A new scaling feature has been added to allow scaling. Prior to this feature,
[Analog Outx Lo] and [Analog Outx Hi] limited only the voltage. This voltage
range was scaled to the selected option range listed in [Analog Outx Sel]. With
the new feature, [Analog Outx Lo] and [Analog Outx Hi] still set the voltage
range, but the scaling parameter now scales the range of the [Analog Outx Sel]
selection. See the following example.
Analog Outputs
Vector v3 Min/Max: [Analog Out1 Sel]
Sets the high value for the range of analog out scale. Units: 0.01
Entering 0.0 will disable this scale and max scale will be
used. Example: If [Analog Out Sel] = “Commanded Trq,”
a value of 150 = 150% scale in place of the default
800%.
Example
Setup
• [Analog Out1 Sel], parameter 342 = 14 “Commanded Torque”
• [Analog Out1 Hi], parameter 343 = 10.000 Volts
• [Analog Out1 Lo], parameter 344 = 0.000 Volts
• [Anlg Out1 Scale], parameter 354 = 100.0
If [Analog Out1 Lo] = –10.000 Volts the output will be –10.0 to +10.0V DC for
–100% to +100% Commanded Torque.
If [Anlg Out1 Scale] = 0.0, the default scaling listed in [Analog Out1 Sel] will be
used. This would be 0-1.25V DC for 0-100% Torque or 0-800% for 0-10V DC.
Example
Analog Output 2 set for 0-10V DC for Heat Sink Temp 0-100 Degrees C. using
Scale Block 1.
Setup
• Link [Scale1 In Value], parameter 476 to [Testpoint 1 Data], param. 235
• [Testpoint 1 Sel], parameter 234 = 2 “Heat Sink Temp”
• [Analog Out2 Sel], parameter 345 = 20 “Scale Block 1”
• [Analog Out2 Hi], parameter 346 = 10.000 Volts
• [Analog Out2 Lo], parameter 347 = 0.000 Volts
• [Scale1 In Hi], parameter 477 = 100
• [Scale1 In Lo], parameter 478 = 0
Example
Setup
• [Data In C1], parameter = 304 “Analog Output 1 Setpoint”
• [Analog Out1 Sel], parameter 342 = 24 “Parameter Control”
• [Analog Out1 Hi], parameter 343 = 10.000 Volts
• [Analog Out1 Lo], parameter 344= 0.000 Volts
The device that writes to DataLink C1 now controls the voltage output of
Analog Out1. For example: 2500 = 2.5V DC, 5000 = 5.0V DC, 7500 = 7.5V
DC.
Auto/Manual The intent of Auto/Manual is to allow the user to override the selected reference
(referred to as the “auto” reference) by either toggling a button on the
programming terminal (HIM), or continuously asserting a digital input that is
configured for Auto/Manual.
The HIM manual reference can be preloaded from the auto source by
enabling the [Man Ref Preload] parameter. With the preload function
enabled, when the HIM requests Manual control, the current value of the
auto source is loaded into the HIM reference before manual control is
granted. This allows the manual control to begin at the same speed as the auto
source, creating a smooth transition. If the preload function is disabled, the
speed will ramp to whatever manual reference was present in the HIM at the
time manual control was granted.
• Digital Input
The TB manual reference is selected in [TB Man Ref Sel]. The choices for
this parameter are:
– Analog Input 1
– Analog Input 2
– MOP Level
– Analog Input 3 (PF700 Only)
– Pulse Input (PF700 Only)
– Encoder input (PF700 Only)
– Releasing this input sends the control back to the Auto source.
General Rules
The following rules apply to the granting and releasing of Manual control:
3. Manual control can only be granted to a terminal if no other device has Local
control already asserted (i.e. no other device has ownership of the Local
control function).
4. A HIM (or TB) with Manual control active can have it taken away if another
DPI port requests, and is granted Local control. In this case when Local
control is released the drive will not go back to Manual control, Manual
control must be again requested (edge based request, see 1. above). This is true
for both the HIM and the TB (i.e. if the TB switch was in the Manual
position it must be switched to Auto and back to Manual to get Manual
control again).
5. The status indicator (point LED on LED HIM & Text on LCD HIM) will
indicate when that particular terminal has been granted Manual control, not
the fact any terminal connected has Manual control and not the fact that the
particular terminal has simply asked for Manual control.
6. When Manual control is granted, the drive will latch and save the current
reference value prior to entering Manual. When Manual control is then
released the drive will use that latched reference for the drive until another
DPI device arbitrates ownership and changes the reference to a different
value.
7. If a terminal has Manual control and clears its DPI reference mask (disallows
reference ownership), then Manual control will be released. By extension, if
the drive is configured such that the HIM can not select the reference (via
reference mask setting), then the drive will not allow the terminal to acquire
Manual control.
8. If a terminal has Manual control and clears its DPI logic mask (allowing
disconnect of the terminal), then Manual control will be released. By
extension if the drive is configured such that the HIM can be unplugged (via
logic mask setting), then the drive will not allow the terminal to acquire
Manual control. The disconnect also applies to a DPI HIM that executes a
soft “Logout.”
9. If a com loss fault occurs on a DPI that has Manual control, then Manual
control will be released as a consequence of the fault (on that port which had
Manual control).
10.There will be no way to request and hence no support of the Auto/Manual
feature on old SCANport based HIMs.
11.You can not acquire Manual control if you are already an assigned source for
the DPI port requesting Manual.
12.When a restore factory defaults is performed Manual control is aborted.
Auto Restart (Reset/Run) The Auto Restart feature provides the ability for the drive to automatically
perform a fault reset followed by a start attempt without user or application
intervention. This allows remote or “unattended” operation. Only certain faults
are allowed to be reset. Certain faults (Type 2) that indicate possible drive
component malfunction are not resettable.
Caution should be used when enabling this feature, since the drive will attempt to
issue its own start command based on user selected programming.
Configuration
This feature is configured through two user parameters
174 [Auto Rstrt Tries] Default: 0 175
Sets the maximum number of times the drive attempts Min/Max: 0/9
to reset a fault and restart. Display: 1
ATTENTION: Equipment damage and/or personal injury may result if
this parameter is used in an inappropriate application. Do Not use this
! function without considering applicable local, national and
international codes, standards, regulations or industry guidelines.
175 [Auto Rstrt Delay] Default: 1.0 Secs 174
Sets the time between restart attempts when [Auto Min/Max: 0.5/30.0 Secs
Rstrt Tries] is set to a value other than zero. Display: 0.1 Secs
Setting [Auto Rstrt Tries] to a value greater than zero will enable the Auto Restart
feature. Setting the number of tries equal to zero will disable the feature.
The [Auto Rstrt Delay] parameter sets the time, in seconds, between each reset/
run attempt.
Diagnostics
Au Lim eg
Au ctiv tdn
UTILITY
Cu req ld
DB Rst ct
Bu r Ov k
Sto raki g
Jo ping g
to T e *
s F er
R
B in
to A
A C
p n
to 0
to it
Mo at 50
Ac ing
DC u n
Ru ing
Au Rst
Re e
y
nn
tiv
ad
gg
rr
I
DP
x x 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 =Condition True
0 =Condition False
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 x =Reserved
Bit # * Vector firmware 3.001 & later
2. After the number of seconds in [Auto Rstrt Delay], the drive will
automatically perform an internal Fault Reset, resetting the faulted condition.
3. The drive will then issue an internal Start command to start the drive.
4. If another auto-resettable fault occurs the cycle will repeat itself up to the
number of attempts set in [Auto Rstrt Tries].
5. If the drive faults repeatedly for more than the number of attempts set in
[Auto Rstrt Tries] with less than five minutes between each fault, the
auto-reset/run is considered unsuccessful and the drive remains in the faulted
state.
6. Aborting an Auto-Reset/Run Cycle (see Aborting an Auto-Reset/Run Cycle
for details).
7. If the drive remains running for five minutes or more since the last reset/run
without a fault, or is otherwise stopped or reset, the auto-reset/run is
considered successful. The entire process is reset to the beginning and will
repeat on the next fault.
• Issuing a stop command from any source. (Note: Removal of a 2-wire run-fwd
or run-rev command is considered a stop assertion).
• Issuing a fault reset command from any source.
• Removal of the enable input signal.
• Setting [Auto Rstrt Tries] to zero.
• The occurrence of a fault which is not auto-resettable.
• Removing power from the drive.
• Exhausting an Auto-Reset/Run Cycle
After all [Auto Rstrt Tries] have been made and the drive has not successfully
restarted and remained running for five minutes or more, the auto-reset/run
cycle will be considered exhausted and therefore unsuccessful. In this case the
auto-reset/run cycle will terminate and an additional fault, “Auto Rstrt Tries”
(Auto Restart Tries) will be issued if bit 5 of [Fault Config 1] = “1.”
[IR Voltage Drop] is set by the IR voltage drop test. [IR Voltage Drop] is used by
the IR Compensation procedure to provide additional voltage at all frequencies
to offset the voltage drop developed across the stator resistance. An accurate
calculation of the [IR Voltage Drop] will ensure higher starting torque and better
performance at low speed operation. The motor should not rotate during this
test.
[Ixo Voltage Drop] is set by the leakage inductance test. This test measures the
inductance characteristics of the motor. A measurement of the motor inductance
is required to determine references for the regulators that control torque. The
motor should not rotate during this test.
[Total Inertia] is set by the inertia test. [Total Inertia] represents the time in
seconds, for the motor coupled to a load to accelerate from zero to base speed at
rated motor torque. During this test, the motor is accelerated to about 2/3 of base
motor speed. This test is performed during the Start-up mode, but can be
manually performed by setting [Inertia Autotune] to “Inertia Tune”. The [Total
Inertia] and [Speed Desired BW] automatically determine the [Ki Speed Loop]
and [Kp Speed Loop] gains for the speed regulator.
The user must enter motor nameplate data into the following parameters for the
Autotune procedure to obtain accurate results:
• [Motor NP Volts]
• [Motor NP Hertz]
• [Motor NP Power]
The static and dynamic tests can be performed during the Start-up routine on the
LCD HIM. The tests can also be run manually by setting the value of the
[Autotune] parameter to 1 “Static Tune” or 2 “Rotate Tune”.
Alternate Methods to Determine [IR Voltage Drop] & [Flux Current Ref]
If it is not possible or desirable to run the Autotune tests, there are three other
methods for the drive to determine the [IR Voltage Drop] and [Flux Current]
parameters:
• The first method is used when the motor nameplate parameters are left at
default. When the drive is initially powered up, the [Autotune] parameter is
defaulted to a value of 3 “Calculate”. The values for [IR Voltage Drop] and
[Flux Current] are calculated based on the default motor nameplate data.
This is the least preferred method.
• The second method calculates them from the user-entered motor nameplate
data parameters. When [Autotune] is set to 3 “Calculate”, any changes made
by the user to motor nameplate HP, Voltage, or Frequency activates a new
calculation. This calculation is based on a typical motor with those nameplate
values.
• Finally, if the stator resistance and flux current of the motor are known, the
user can calculate the voltage drop across the stator resistance. Then set
[Autotune] to 0 “Ready” and directly enter these values into the [Flux
Current] and [IR Voltage Drop] parameters.
Motor nameplate data must be entered into the following parameters for the
Autotune procedure to obtain accurate results:
• [Motor NP Volts]
• [Motor NP FLA]
• [Motor NP Hertz]
• [Motor NP RPM]
• [Motor NP Power]
• [Motor Poles]
• Dynamic - the motor shaft will rotate during this test. The dynamic autotune
procedure determines the stator resistance, motor flux current, and leakage
inductance. The test to identify the motor flux current requires the load to be
uncoupled from the motor to find an accurate value. If this is not possible
then the static test can be performed.
• Static - the motor shaft will not rotate during this test. The static test
determines only [IR Voltage Drop] and [Ixo Voltage Drop]. This test does not
require the load to be uncoupled from the motor.
The static and dynamic tests can be performed during the Start-up routine on the
LCD HIM. The tests can also be run manually by setting the value of [Autotune]
to “1,” (Static Tune) or “2” (Rotate Tune), respectively, and then starting the
drive.
After the Static or Dynamic Autotune the Inertia test should be performed. The
motor shaft will rotate during the inertia test. During the inertia test the motor
should be coupled to the load to find an accurate value. The inertia test can be
performed during the Start-up routine on the LCD HIM. The inertia test can
also be run manually by setting [Inertia Autotune] to 1 “Inertia Tune”, and then
starting the drive.
Block Diagrams
PowerFlex 700VC
Block Diagrams
Speed Control - Reference (2.0ms)
Speed Control - Regulator (1.0ms)
2 Commanded Speed
Trim In Select 117 Speed Reference
2 Commanded Freq
Speed Ref A Sel 90 Jog Speed 1 100 23
272 Drive Ref Rslt
Speed Ref B Sel 93 Jog Speed 2 108 PI Regulator Lead Lag
22 Ramped Speed 25 Lead Lag
Analog 1/2
S Spd Ref A 273 Drive Ramp Rslt Speed
Enc/Pulse O +
Linear Feedback
U
10 10 (From Encoder)
MOP R Trim Ramp &
C 01 01 Min/Max
Kp Speed Loop 446
Presets 1-7 S Curve
Control drive.
E +
S Spd Ref B + Logic Logic Limits Ki Speed Loop 445
DPI Port 1-6
Kf Speed Loop 447
PI Excl PI Speed
Mode Trim
PI Excl
Mode
Encoder Slip Comp Open Loop
Process Control (2ms) PI Output Meter
PI Regulator
10
PI Feedback
01
Limit Logic
Speed Reference Output Freq V/Hz
23 + 1
Current
Processing
Figure 2 PowerFlex 700VC Block Diagrams (2)
V/Hz Mode with Speed Control Read Only Parameter with Bit Enumeration
45
Block Diagrams
46
Trim In Select 117 Speed Control - Reference
Trim Out Select
Speed Ref A Sel 90 (Trim Ref A) Drive Logic Rslt
(Spd Ref ID)
(2.0 ms)
Block Diagrams
22 11 108
DPI Port 5 DPI Port 5 DPI Port 3 Port 3 Manual TB Jog 2
HIM Jog Speed 2
23 Preload 12
DPI Port 6 DPI Port 6 DPI Port 4 Port 4 Manual
13
Save HIM Ref DPI Port 5 Port 5 Manual
Figure 3 PowerFlex 700VC Block Diagrams (3)
0
(0) Not Saved Command Ref
Man Ref Preload 193
1
(NVS) Saved
Speed Control - Reference
(2.0 ms)
Direction Mode
190
From Reference
(3H2)
1 1
Bipolar
0 2
Max Reverse Dis Limit Drive Logic Rslt
(0)
(Jog)
Internal 0
X Unipolar
Autotune Drive Status 1 Rev Speed Limit 271 02
(Command Dir)
454
1
209 2 Jog Ref
Max Speed 82 0
X Rev Spd Limit Zero 0
1 (-1) Min Spd Limit
(+1) Unipol Fwd
≠0
Rev Speed Limit 454 Rev Spd Limit Non-Zero
0 Limit
(-1) Unipol Rev
Minimum Speed 81
X
(-1)
47
Block Diagrams
48
Speed Control - Regulator
(1.0 ms)
Block Diagrams
kf
FeedFwd
+ ki
416 621 Testpoint 621
- s
Fdbk Filter Sel
I Gain
445
Ki Speed Loop
Droop 620 Testpoint 620
From Torque Trim >0 Notch Filter Freq 419 Control Status
[7H5] 4 Notch
Max
Notch Filter K 420
Torque Ref A 427 5
Torq Ref A Div 430
/
Speed Feedback 25 Pos Torque Limit 436
+ 6
+
Torque Ref B 431 Min
X
Torque Ref B Mult 434 Abs
Min Power
Limit Calc
Rated Volts 27
Bus Volt
DC Bus Memory 13 Regulator Limit
Max
Iq Actual Lim -1
Bus Reg Mode A 161
Limit
Bus Reg Mode B 162
153 Neg Torque Limit 437
DC Bus Voltage 12 Regen Power Lim
Torque
Current Torque Reg Kp
Calc Torque Reg Enable
Observe Sts
Output Frequency 1 527 P Gain
124 14 526
Torque Current 4
kp
Torque 1 1 +
Flux Current 5 + Torque Ref Out
Estimator Torque Est.
Vds Cmd 234/6 506 - 0 0 234/6 517 Mtr Tor Cur Ref
234/6 518 ki 0 0 *Iq Rated
235/7 235/7 441
s Drive Rated
235/7 NegTrqCurLim
Vqs Cmd 234/6 509 NTC to
528 I Gain
234/6 04 Iq Scale Limit 440 0 Rate Lim Motor
Mi Rated Amps
235/7 Control
Torque Reg Ki 235/7 28 440 1
Calc DC Bus Voltage 12
Motor NP Volts 41 Active PWM Freq PosTrqCurLim
Iq Rated
X
Output Freq 1
Motor NP Amps 42
Figure 6 PowerFlex 700VC Block Diagrams (6)
(-1)
Rs Gain Peak Torq Current Limit 154
Motor NP PWM Frequency 151
49
Block Diagrams
50
Process Trim
(2.0 ms)
Block Diagrams
From Reference
PI Reference Sel
Selectable Source(s)
126
PI Ref Meter
Out - Lo
135
Hi - Lo
Scale
Selector
PI Reference Hi 460
PI Reference Lo 461
PI Configuration
(Invert Error)
From Feedback
Selectable Source(s) PI Feedback Sel 124 01
128 PI Error Meter
Error PI Output Meter
+ 0
Out - Lo 137 kp
Hi - Lo
SqRt 136 - Filter + 138
1
PI Fdback Meter -1 BW P Gain
Scale Enable Limit 134 03
Selector 124 05 139 130 PI Status
PI Upper Limit 132 (In Limit)
PI Configuration PI BW Filter PI Prop Gain
(Feedback SqRt) PI Lower Limit 131
PI Configuration PI Status
PI Feedback Hi 462 (Preload Mode) (PI Enabled)
PI Feedback Lo 463 124 02 134 00 ki
s 1 0
0 0
0 I Gain (0)
125 01 1
1 PI Control
133 125 04
PI Integral Time 129 (PI Hold)
PI Preload PI Control
(Zero Clamp)
To PI Output
[4D3]
PI Configuration
(Torque Trim)
Figure 7 PowerFlex 700VC Block Diagrams (7)
PI Configuration 124 08
0 1
1
(0)
Drive Logic Rslt
(Mop Inc)
271 7
0 Add Rate
(0)
1
(1)
To MOP Output
MOP Rate 195 [3B2] [3D4]
194 0
0 Power Up
(0) Not Saved
Preload
1
(NVS) Saved
Selector Selector
Analog In1 Lo
95 Speed Ref B Lo
98 TB Man Ref Lo
120 Trim Lo
Analog In2 Lo
95 Speed Ref B Lo
98 TB Man Ref Lo
120 Trim Lo
53
Block Diagrams
54
Stop Owner Control Logic
288
Stop
Owner (2.0ms)
Block Diagrams
Logic
Start Owner
Terminal Block
289
Configuration Start
Transition
AND Owner
Settings Detection
Logic
[9Dx] 277 2-Wire
Jog Owner Stop
Start Mask Control
290
Jog
Transition
AND Owner
Detection
Logic
278
Local Dir Owner
DPI Port 1 (HIM) Jog Mask Mask
Evaluation 291
Single Dir
Logic Mask AND Owner Owner Drive Logic Rslt
Eval Logic Logic
276 279 271
Reference Owner Evaluation
Direction Mask
292
Single Ref
DPI Port 2 AND Owner Owner
Eval Logic
280
6 Accel Owner
AND / Reference Mask
293
Accel
AND Owner
Logic
DPI Port 3 281
Decel Owner
Accel Mask
294 Drive
Decel
Owner Sequencer
AND
Logic State
282
Fault Clr Owner
Decel Mask
DPI Port 4 Fault 295
Clear
AND Owner
Logic
283
MOP Owner
Fault Clr Mask
296
MOP
AND Owner
Logic
DPI Port 5 284
Single Local
AND Owner Owner
Eval Logic
285 297
Local Mask Local Owner
Inverter Over Load (IT)
Power Device
Characteristics
234/6 02 Heatsink Temp Inverter Overload IT
NTC
235/7
Pwr EE Data
Heat sink and
Duty Cycle Junction degree
234/6 03 Active Cur Limit
Calculator
235/7
DC Bus Voltage 12
235/7
PWM Frequency 151 Fault x Code Mtr Over Load (I2T)
(see torque block) (Drive Overload)
243
Output Current 3 (Heatsink OvrTemp) Motor
Alarm x Code 245 Current
Current Limit 220 Motor OL Count
Value 148 243 (Inv OL Level 1) 247
(Inv OL Level 2)
245 249
247 251
150% right of curve Fault x Code
249 253
243 (Motor Overload)
251 255 102%
245
253 257
60 (Hot) time (sec) 247
255 180 (Cold)
Motor
Current 249
257
251
1.0 - 2.0
Motor OL Factor 48 (1.025 Typ) 253
X
Motor NP FLA 42 255
DB resistor
257
50%
Fault x Code
249
Alarm x Code
251
243 (IntDBRes OvrHeat)
253
245
255
247
257
249
251
253
255
257
55
Block Diagrams
Bus Regulation
Some applications, such as the hide tanning shown here, create an intermittent
regeneration condition. When the hides are being lifted (on the left), motoring
current exists. However, when the hides reach the top and fall onto a paddle, the
motor regenerates power back to the drive, creating the potential for a nuisance
overvoltage trip.
When an AC motor regenerates energy from the load, the drive DC bus voltage
increases unless there is another means (dynamic braking chopper/resistor, etc.)
of dissipating the energy.
Motoring Regenerating
Without bus regulation, if the bus voltage exceeds the operating limit established
by the power components of the drive, the drive will fault, shutting off the output
devices to protect itself from excess voltage.
Single Seq 500 S/s 0V Fault @Vbus Max
3
Drive Output Shut Off
With bus regulation enabled, the drive can respond to the increasing voltage by
advancing the output frequency until the regeneration is counteracted. This
keeps the bus voltage at a regulated level below the trip point.
Since the same integrator is used for bus regulation as for normal frequency ramp
operation, a smooth transition between normal frequency ramp operation and
bus regulation is accomplished.
The regulator senses a rapid rise in the bus voltage and activates prior to actually
reaching the internal bus voltage regulation set point Vreg. This is important
since it minimizes overshoot in the bus voltage when bus regulation begins
thereby attempting to avoid an over-voltage fault.
The bus voltage regulation set point (Vreg) in the drive is fixed for each voltage
class of drive. The bus voltage regulation set points are identical to the internal
dynamic brake regulation set points VDB's.
DB Bus
Motor Speed
Output Frequency
The bus voltage regulator is shown in the lower one-third of Figure 13. The
inputs to the bus voltage regulator are the bus voltage, the bus voltage regulation
set point Vreg, proportional gain, integral gain, and derivative gain. The gains are
intended to be internal values and not parameters. These will be test points that
are not visible to the user. Bus voltage regulation is selected by the user in the Bus
Reg Mode parameter.
Operation
Bus voltage regulation begins when the bus voltage exceeds the bus voltage
regulation set point Vreg and the switches shown in Figure 13 move to the
positions shown in Table 2.
Table 2 Switch Positions for Bus Regulator Active
SW 1 SW 2 SW 3 SW 4 SW 5
Bus Regulation Limit Bus Reg Open Closed Don’t Care
Current Limit
U Phase Motor Current
Derivative Gain Magnitude
Block Calculator W Phase Motor Current
SW 3
I Limit,
No Bus Reg
Proportional Channel
Integral Channel
Limit
0
SW 1
No Limit
I Limit,
No Bus Reg
+ Frequency
Acc/Dec Rate Jerk Jerk No Limit Frequency Reference Frequency Output Frequency
Ramp Clamp Ramp
(Integrator) + + Limits
SW 2
Bus Reg +
+ Speed
SW 5 Control
Frequency Set Point Mode
Proportional Channel
SW 4
Bus Reg On
The derivative term senses a rapid rise in the bus voltage and activates the bus
regulator prior to actually reaching the bus voltage regulation set point Vreg. The
derivative term is important since it minimizes overshoot in the bus voltage when
bus regulation begins thereby attempting to avoid an over-voltage fault. The
integral channel acts as the acceleration or deceleration rate and is fed to the
frequency ramp integrator. The proportional term is added directly to the output
of the frequency ramp integrator to form the output frequency. The output
frequency is then limited to a maximum output frequency.
Bus voltage regulation is the highest priority of the three components of this
controller because minimal drive current will result when limiting the bus voltage
and therefore, current limit will not occur.
PowerFlex 70/700
The user selects the bus voltage regulator using the Bus Reg Mode parameters.
The available modes include:
• off
• frequency regulation
• dynamic braking
• frequency regulation as the primary regulation means with dynamic braking
as a secondary means
• dynamic braking as the primary regulation means with frequency regulation
as a secondary means
The bus voltage regulation setpoint is determined off of bus memory (a means to
average DC bus over a period of time). The following graph and tables describe
the operation.
Table 3
Voltage Class DC Bus Memory DB On Setpoint DB Off Setpoint
240 < 342V DC 375V DC On – 4V DC
> 342V DC Memory + 33V DC
480 < 685V DC 750V DC On – 8V DC
> 685V DC Memory + 65V DC
600 < 856V DC 937V DC On – 10V DC
> 856V DC Memory + 81V DC
600/690V < 983V DC 1076V DC On – 11V DC
PowerFlex 700 Frames > 983V DC Memory + 93V DC
5 & 6 Only
880
815
DB Turn On
750
DB Turn Off
DC Volts
685
1 2
e# e#
650
C urv Curv
eg eg
sR sR
Bu Bu ory
M em
Bus
509
453
320 360 460 484 528 576
AC Volts
The Dynamic Brake Regulator is enabled. In “Dynamic Brak” mode the Bus
Voltage Regulator is turned off. The “DB Turn On” and turn off curves apply
(Table 3). For example, with a DC Bus Memory at 684V DC, the Dynamic Brake
Regulator will turn on at 750V DC and turn back off at 742V DC.
Both regulators are enabled, and the operating point of the Bus Voltage Regulator
is lower than that of the Dynamic Brake Regulator. The Bus Voltage Regulator
setpoint follows the “Bus Reg Curve 2” below a DC Bus Memory of 650V DC
and follows the “DB Turn Off ” curve above a DC Bus Memory of 650V DC
(Table 4). The Dynamic Brake Regulator follows the “DB Turn On” and turn off
curves (Table 3). For example, with a DC Bus Memory at 684V DC, the Bus
Voltage Regulator setpoint is 742V DC and the Dynamic Brake Regulator will
turn on at 750V DC and back off at 742V DC.
The Bus Voltage Regulator is enabled. The Bus Voltage Regulator setpoint
follows “Bus Reg Curve 1” below a DC Bus Memory of 650V DC and follows
the “DB Turn On” above a DC Bus Memory of 650V DC (Table 4). For
example, with a DC Bus Memory at 684V DC, the adjust frequency setpoint is
750V DC.
Both regulators are enabled, and the operating point of the Dynamic Brake
Regulator is lower than that of the Bus Voltage Regulator. The Bus Voltage
Regulator setpoint follows the “DB Turn On” curve (Table 3). The Dynamic
Brake Regulator follows the “DB Turn On” and turn off curves (Table 3). For
example, with a DC Bus Memory at 684V DC, the Bus Voltage Regulator
setpoint is 750V DC and the Dynamic Brake Regulator will turn on at 750V DC
and back off at 742V DC.
Table 4
Voltage Class DC Bus Memory Bus Reg Curve #1 Bus Reg Curve #2
240 < 325V DC Memory + 50V DC Curve 1 – 4V DC
325V DC ≤ DC Bus Memory ≤ 342V DC 375V DC
> 342V DC Memory + 33V DC
480 < 650V DC Memory + 100V DC Curve 1 – 8V DC
650V DC ≤ DC Bus Memory ≤ 685V DC 750V DC
> 685V DC Memory + 65V DC
600 < 813V DC Memory + 125V DC Curve 1 – 10V DC
813V DC ≤ DC Bus Memory ≤ 856V DC 937V DC
> 856V DC Memory + 81V DC
600/690V < 933V DC Memory + 143V DC Curve 1 – 11V DC
PowerFlex 700 933V DC ≤ DC Bus Memory ≤ 983V DC 1076V DC
Frames 5 & 6 Only > 983V DC Memory + 93V DC
Cable, Control Refer to “Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)
AC Drives,” publication DRIVES-IN001 for detailed information on Cable,
Control.
Cable, Motor Lengths Refer to “Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)
AC Drives,” publication DRIVES-IN001 for detailed information on Cable,
Motor Lengths.
Cable, Power Refer to “Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)
AC Drives,” publication DRIVES-IN001 for detailed information on Cable,
Power.
Cable Trays and Conduit Refer to “Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)
AC Drives,” publication DRIVES-IN001 for detailed information on Cable
Trays and Conduit.
Carrier (PWM) Frequency In general, the lowest possible switching frequency that is acceptable for any
particular application is the one that should be used. There are several benefits to
increasing the switching frequency. Refer to Figure 14 and Figure 15. Note the
output current at 2 kHz and 4 kHz. The “smoothing” of the current waveform
continues all the way to 10 kHz.
Figure 14 Current at 2 kHz PWM Frequency
The benefits of increased carrier frequency include less motor heating and lower
audible noise. An increase in motor heating is considered negligible and motor
failure at lower switching frequencies is very remote. The higher switching
frequency creates less vibration in the motor windings and laminations thus,
lower audible noise. This may be desirable in some applications.
General Notes
• If the adhesive label is removed from the top of the drive, the drive must be
installed in an enclosure with side openings less than 12.5 mm (0.5 in.) and
top openings less than 1.0 mm (0.04 in.) to maintain compliance with the LV
Directive.
• The motor cable should be kept as short as possible in order to avoid
electromagnetic emission as well as capacitive currents.
• Use of line filters in ungrounded systems is not recommended.
• PowerFlex drives may cause radio frequency interference if used in a
residential or domestic environment. The user is required to take measures to
prevent interference, in addition to the essential requirements for CE
compliance listed below, if necessary.
• Conformity of the drive with CE EMC requirements does not guarantee an
entire machine or installation complies with CE EMC requirements. Many
factors can influence total machine/installation compliance.
• PowerFlex drives can generate conducted low frequency disturbances
(harmonic emissions) on the AC supply system.
Frame
Restrict Motor Cable Internal Filter External Input
Drive Description to 40 m (131 ft.) Option Filter (1) Ferrite (2)
A Drive Only ✔ – ✔ –
Drive with any Comm Option ✔ – ✔ –
Drive with Remote I/O ✔ – ✔ ✔
B Drive Only ✔ ✔ – –
Drive with any Comm Option ✔ ✔ – –
Drive with Remote I/O ✔ ✔ – ✔
C Drive Only ✔ – – –
Drive with any Comm Option ✔ – – –
Drive with Remote I/O ✔ – – ✔
D Drive Only ✔ – – –
Drive with any Comm Option ✔ – – –
Drive with Remote I/O ✔ – – ✔
E Drive Only ✔ – – –
Drive with any Comm Option ✔ – – –
Drive with Remote I/O ✔ – – ✔
Restrict Motor Cable to 30 m (98 ft.) Restrict Motor Cable to 150 m (492 ft.)
Any Drive and Option Any Drive and Option External Filter Required
0-6 ✔ ✔ ✔
(1) External filters for First Environment installations and increasing motor cable lengths in Second Environment
installations are available. Roxburgh models KMFA (RF3 for UL installations) and MIF or Schaffner FN3258
and FN258 models are recommended. Refer to Table 8 and http://www.deltron-emcon.com and http://
www.mtecorp.com (USA) or http://www.schaffner.com, respectively.
(2) Two turns of the blue comm option cable through a Ferrite Core (Frames A, B, C Fair-Rite #2643102002, Frame
D Fair-Rite #2643251002 or equivalent).
(3) Refer to the 1321 Reactor and Isolation Transformer Technical Data publication, 1321-TD001x for 1321-Mxxx
selection information.
Copy Cat Some PowerFlex drives have a feature called Copy Cat, which allows the user to
upload a complete set of parameters to the LCD HIM. This information can
then be used as backup or can be transferred to another drive by downloading the
memory.
Generally, the transfer process manages all conflicts. If a parameter from HIM
memory does not exist in the target drive, if the value stored is out of range for
the drive or the parameter cannot be downloaded because the drive is running,
the download will stop and a text message will be issued. The user than has the
option of completely stopping the download or continuing after noting the
discrepancy for the parameter that could not be downloaded. These parameters
can then be adjusted manually.
The LCD HIM will store a number of parameter sets (memory dependant) and
each individual set can be named for clarity.
There are 6 ways that the drive can protect itself from overcurrent or overload
situations:
The frequency adjust or fold back operation consists of two modes. In the
primary mode of current limit operation, motor phase current is sampled and
compared to the Current Limit setting in the [Current Lmt Val]. If a current
“error” exists, error is scaled by an integral gain and fed to the integrator. The
output of this integrator is summed with the proportional term and the active
speed mode component to adjust the output frequency and the commanded
voltage. The second mode of current limit operation is invoked when a
frequency limit has been reached and current limit continues to be active. At
this point, a current regulator is activated to adjust the output voltage to limit
the current. When the current limit condition ceases or the output voltage of
the current regulator attempts to exceed the open loop voltage commands,
control is transferred to the primary current limit mode or normal ramp
operation.
4. Overload Protection I2T - This is a software feature that monitors the output
current over time and integrates per IT. The base protection is 110% for 1
minute or the equivalent I2T value (i.e. 150% for 3 seconds, etc.). If the IT
integrates to maximum, an F64 “Drive Overload” fault will occur. The
approximate integrated value can be monitored via the [Drive OL Count]
parameter.
5. Heatsink Temperature Protection - The drive constantly monitors the
heatsink temperature. If the temperature exceeds the drive maximum, a
“Heatsink OvrTemp” fault will occur. The value is fixed by hardware at a
nominal value of 100 degrees C. This fault is generally not used for
overcurrent protection due to the thermal time constant of the heatsink. It is
an overload protection.
6. Thermal manager (see Drive Overload on page 94).
Datalinks A Datalink is one of the mechanisms used by PowerFlex drives to transfer data to
and from a programmable controller. Datalinks allow a parameter value to be
changed without using an Explicit Message or Block Transfer. Datalinks consist
of a pair of parameters that can be used independently for 16 bit transfers or in
conjunction for 32 bit transfers. Because each Datalink consists of a pair of
parameters, when enabled, each Datalink occupies two 16 or 32-bit words in
both the input and output image tables, depending on configuration. A user
enters a parameter number into the Datalink parameter. The value that is in the
corresponding output data table word in the controller is then transferred to the
parameter whose number has been placed in the Datalink parameter. The
following example demonstrates this concept. The object of the example is to
change Accel and Decel times “on the fly” under PLC control.
The user makes the following PowerFlex drive parameter settings:
Parameter 300 [Data In A1] = 140 (the parameter number of [Accel Time 1]
Parameter 301 [Data In A2] = 142 (the parameter number of [Decel Time 1]
Output Image
Block Transfer
Logic Command
Analog Reference Parameter/Number
Datalink A
WORD 3 Data In A1 300
WORD 4 Data In A2 301
WORD 5 Datalink A
WORD 6 Data Out A1 310
WORD 7 Data Out A2 311
Input Image
Block Transfer
Logic Status
Analog Feedback
WORD 3
WORD 4
WORD 5
WORD 6
WORD 7
In the PLC data Table, the user enters Word 3 as a value of 100 (10.0 Secs) and
word 4 as a value of 133 (13.3 seconds). On each I/O scan, the parameters in the
PowerFlex drive are updated with the value from the data table:
Accel Time P140 = 10.0 seconds (value from output image table Word 3) Decel
Time P142 = 13.3 seconds (value from output image table Word 4).
Any time these values need to be changed, the new values are entered into the
data table, and the parameters are updated on the next PLC I/O scan.
2. Only one communications adapter can use each set of Datalink parameters in
a PowerFlex drive. If more than one communications adapter is connected to a
single drive, multiple adapters must not try to use the same Datalink.
3. Parameter settings in the drive determine the data passed through the
Datalink mechanism
4. When you use a Datalink to change a value, the value is not written to the
Non-Volatile Storage (EEprom memory). The value is stored in volatile
memory (RAM) and lost when the drive loses power.
To read (and/or write) a 32-bit parameter using 16-bit Datalinks, typically both
Datalinks (A,B,C,D) are set to the 32-bit parameter. For example, to read
Parameter 09 - [Elapsed MWh], both Datalink A1 and A2 are set to “9.”
Datalink A1 will contain the least significant word (LSW) and Datalink A2 the
most significant word (MSW). In this example, the parameter 9 value of
5.8MWh is read as a “58” in Datalink A1
Datalink Most/Least Significant Word Parameter Data (decimal)
A1 LSW 9 58
A2 MSW 9 0
Regardless of the Datalink combination, x1 will always contain the LSW and x2
will always contain the MSW.
Even if non-consecutive Datalinks are used (in the next example, Datalinks A1
and B2 would not be used), data is still returned in the same way.
Datalink Most/Least Significant Word Parameter Data (decimal)
A2 MSW 242 13
B1 LSW 242 32573
Example
Parameter 242 - [Power Up Marker] = 88.4541 hours
MSW = 13decimal = 1101binary = 216 + 218 + 219 = 851968
LSW = 32573
851968 + 32573 = 884541
DC Bus Voltage / Memory [DC Bus Voltage] is a measurement of the instantaneous value. [DC Bus
Memory] is a heavily filtered value or “nominal” bus voltage. Just after the
pre-charge relay is closed during initial power-up bus pre-charge, bus memory is
set equal to bus voltage. Thereafter it is updated by ramping at a very slow rate
toward Vbus. The filtered value ramps at approximately 2.4V DC per minute
(for a 480V AC drive).
Bus memory is used as the base line to sense a power loss condition. If the drive
enters a power loss state, the bus memory will also be used for recovery (i.e.
pre-charge control or inertia ride through upon return of the power source) upon
return of the power source. Update of the bus memory is blocked during
deceleration to prevent a false high value caused by a regenerative condition.
Two decel times exist to allow the user to change rates “on the fly” via PLC
command or digital input. The selection is made by programming [Decel Time
1] & [Decel Time 2] and then using one of the digital inputs ([Digital Inx Sel])
programmed as “Decel 2” (see Table 9 for further information). However, if a
PLC is used, manipulate the bits of the command word as shown below.
(1 )
(1 )
(1 )
Sp Ref 2
De ef 1
De l 2 0
Fo rse trl
g ult
D
d R ID
ce ID
ve n
Sp Dec
Sp Ref I
Re l Co
Cle ard
Jo r Fa
Lo Inc
Ac l 1
Ac l 2
Mo el 1
ce
ce
rw
ca
Sto t
P
p
a
p
r
d
d
c
MO
Sta
0 0 0 0 1 1 1 0 1 0 0 0 1 1 0 0 1 = Condition True
0 = Condition False
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 x = Reserved
Bit #
0 0 0 1 Accel 1
0 0 1 0 Accel 2
0 1 0 0 Decel 1
1 0 0 0 Decel 2
The effectiveness of these bits or digital inputs can be affected by [Decel Mask].
See Masks on page 113 for more information.
Times are adjustable in 0.1 second increments from 0.0 seconds to 3600.0
seconds.
In its factory default condition, when no decel select inputs are closed and no
time bits are “1,” the default deceleration time is [Decel Time 1] and the rate is
determined as above.
Wiring Examples
Refer to the appropriate PowerFlex user manual for wiring diagrams.
PowerFlex 70
Each digital input has a maximum response/pass through/function execution
time of 25ms. For example, no more than 25ms should elapse from the time the
level changes at the Start input to the time voltage is applied to the motor.
There is both hardware and software filtering on these inputs. The hardware
provides an average delay of 12ms from the time the level changes at the input to
the earliest time that the software can detect the change. The actual time can vary
between boards from 7 to 17ms, but any particular board should be consistent to
within 1% of its average value. The amount of software filtering is not alterable by
the user.
PowerFlex 700
Each digital input has a maximum response/pass through/function execution
time of 25ms. This means that, for example, no more than 25ms should elapse
from the time the level changes at the Start input to the time voltage is applied to
the motor.
12 “Jog Reverse”
3 2 1 Auto Reference Source 13 “Stop Mode B” 156
0 0 0 Reference A 14 “Bus Reg Md B” 162
0 0 1 Reference B 15 “Speed Sel 1”(4)
0 1 0 Preset Speed 2
0 1 1 Preset Speed 3 16 “Speed Sel 2”(4)
1 0 0 Preset Speed 4 17 “Speed Sel 3”(4)
1 0 1 Preset Speed 5
1 1 0 Preset Speed 6
18 “Auto/ Manual”(5) 096
1 1 1 Preset Speed 7 19 “Local”
20 “Acc2 & Dec2” 140
To access Preset Speed 1, set [Speed Ref A Sel]
or [Speed Ref B Sel] to “Preset Speed 1”.
21 “Accel 2”
22 “Decel 2”
Type 2 Alarms
Some digital input programming may cause
23 “MOP Inc” 194
conflicts that will result in a Type 2 alarm. Example: 24 “MOP Dec”
[Digital In1 Sel] set to 5 “Start” in 3-wire control and 25 “Excl Link” 380
[Digital In2 Sel] set to 7 “Run” in 2-wire. 26 “PI Enable” 384
Refer to Alarm Descriptions in the User Manual for 27 “PI Hold” 388
information on resolving this type of conflict. 28 “PI Reset” 124
(5) Auto/Manual - Refer to User Manual for details.
(6) Opening an “Enable” input will cause the motor to
coast-to-stop, ignoring any programmed Stop
modes.
(7) A “Dig In ConflictB” alarm will occur if a “Start”
input is programmed without a “Stop” input.
If the “Clear Faults” input function is configured at the same time as “Stop -
Clear Faults”, then it will not be possible to reset faults with the “Stop - Clear
Faults” input.
• Run Forward, Run Reverse
The table below describes the basic action taken by the drive in response to
particular states of these input functions.
Run Forward Run Reverse Action
Open Open Drive stops, terminal block relinquishes direction ownership.
Open Closed Drive runs in reverse direction, terminal block takes direction ownership.
Closed Open Drive runs in forward direction, terminal block takes direction ownership.
Closed Closed Drive continues to run in current direction, but terminal block maintains
direction ownership.
If one of these input functions is configured and the other one isn’t, the above
description still applies, but the unconfigured input function should be
considered permanently open.
The terminal block bit must be set in the [Start Mask], [Direction Mask], and
[Logic Mask] parameters in order for the terminal block to start or change the
direction of the drive using these inputs.
An open to closed transition on this input while drive is stopped will cause the
drive to run in the currently selected direction unless the “Stop - Clear Faults”
input function is configured and open.
The purpose of this input function is to allow a 2-wire start while the
direction is being controlled by some other means.
The terminal block bit must be set in the [Start Mask] and [Logic Mask]
parameters in order for the terminal block to start the drive using this input.
If the “Run” input function is configured, it will not be possible to start or jog
the drive from any other control device. This is true irrespective of the state of
the [Start Mask], [Direction Mask], and [Logic Mask] parameters.
The “Run/Stop” and “Run Fwd/Rev” start modes are also called “2-wire”
start modes, because they allow the drive to be started and stopped with only a
single input and two wires. When a “2-wire” terminal block start mode is put
into effect by the user, the drive can no longer be started or jogged from any
other control device (i.e. HIM, network card, etc.). This restriction persists as
long as one or more of “Run”, “Run Forward”, and “Run Reverse” are
configured. This is true even if the configuration is otherwise illegal and
causes a configuration alarm. See page 109 for typical 2 and 3-wire
configurations.
• Start
An open to closed transition while the drive is stopped will cause the drive to
run in the current direction, unless the “Stop – Clear Faults” input function is
open.
The terminal block bit must be set in the [Start Mask] and [Logic Mask]
parameters in order for the terminal block to start or change the direction of
the drive using these inputs.
• Forward/Reverse
This function is one of the ways to provide direction control when the Start /
Stop / Run functions of the drive are configured as 3 – wire control.
The terminal block bit must be set in the [Direction Mask] and [Logic Mask]
parameters in order for the terminal block to select the direction of the drive
using this input function.
• Jog
The drive will not jog while running or while the “Stop - Clear Faults” input is
open. Start has precedence.
The terminal block bit must be set in the [ Jog Mask] and [Logic Mask]
parameters in order for the terminal block to cause the drive to jog using this
input function.
If one of these input functions is configured and the other one isn’t, the above
description still applies, but the unconfigured input function should be
considered permanently open.
The drive will not jog while drive is running or while “Stop - Clear Faults”
input is open. Start has precedence.
The terminal block bit must be set in the [ Jog Mask], [Direction Mask], and
[Logic Mask] parameters in order for the terminal block to cause the drive to
jog using these input functions.
and [Logic Mask] parameters, the terminal block becomes direction owner as
soon as one (or both) of the “Jog Forward” or “Jog Reverse” input functions is
closed.
One, two, or three digital input functions can be used to select the speed
reference used by the drive, and they are called the Speed Select input
functions. The current open/closed state of all Speed Select input functions
combine to select which source is the current speed reference. There are 8
possible combinations of open/closed states for the three input functions, and
thus 8 possible parameters can be selected. The 8 parameters are: [Speed Ref
A Sel], [Speed Ref B Sel], and [Preset Speed 2] through [Preset Speed 7].
If the Speed Select input functions select [Speed Ref A Sel] or [Speed Ref B
Sel], then the value of that parameter further selects a reference source. There
are a large number of possible selections, including all 7 presets.
If the input functions directly select one of the preset speed parameters, then
the parameter contains a frequency that is to be used as the reference.
The terminal block bit must be set in the [Reference Mask] and [Logic Mask]
parameters in order for the reference selection to be controlled from the
terminal block using the Speed Select inputs functions.
The Speed Select input function configuration process involves assigning the
functionality of the three possible Speed Select input functions to physical
digital inputs. The three Speed Select inputs functions are called “Speed
Select 1”, “Speed Select 2”, and “Speed Select 3”, and they are assigned to
physical inputs using the [Digital Inx Sel] parameters.
The table below describes the various reference sources that can be selected
using all three of the Speed Select input functions.
Speed Select 3 Speed Select 2 Speed Select 1 Parameter that determines Reference
Open Open Open [Speed Ref A Sel]
Open Open Closed [Speed Ref B Sel]
Open Closed Open [Preset Speed 2]
Open Closed Closed [Preset Speed 3]
Closed Open Open [Preset Speed 4]
Closed Open Closed [Preset Speed 5]
Closed Closed Open [Preset Speed 6]
Closed Closed Closed [Preset Speed 7]
If any of the three Reference Select input functions are not configured, then
the software will still follow the table, but will treat the unconfigured inputs as
if they are permanently open.
• Auto/Manual
If the “Auto/Manual” input function is closed, then the drive will use one of
the analog inputs (defined by [TB Man Ref Sel]) as the reference, ignoring the
normal reference selection mechanisms. This mode of reference selection is
called “Terminal Block Manual Reference Selection Mode”.
If this input function is open, then the terminal block does not request
manual control of the reference. If no control device (including the terminal
block) is currently requesting manual control of the reference, then the drive
will use the normal reference selection mechanisms. This is called “Automatic
Reference Selection” mode.
The drive arbitrates among manual reference requests from different control
devices, including the terminal block.
• Accel 2 / Decel 2
The terminal block bit must be set in the [Accel Mask] and [Logic Mask]
parameters in order for the acceleration rate selection to be controlled from
the terminal block. The terminal block bit must be set in the [Decel Mask]
and [Logic Mask] parameters in order for the deceleration rate selection to be
controlled from the terminal block.
There are two different schemes for using the Acc/Dec input functions. Each
one will be described in its own section.
• Accel 2, Decel 2
In the first scheme, one input function (called “Accel 2”) selects between
[Accel Time 1] and [Accel Time 2], and another input function (called
“Decel 2”) selects between [Decel Time 1] and [Decel Time 2]. The open
state of the function selects [Accel Time 1] or [Decel Time 1], and the closed
state selects [Accel Time 2] or [Decel Time 2].
Important: Acc/Dec Control is an “Exclusive Ownership” function (see
Owners). This means that only one control device (terminal
block, DPI device, HIM, etc.) at a time is allowed to select the
Acc/Dec rates. The terminal block must become Acc/Dec
“owner” before it can be used to control ramp rates. If another
device is currently the reference owner (as indicated by
[Reference Owner]), it will not be possible to select the reference
by using the terminal block digital inputs, and the Speed Select
Inputs will have no effect on which reference the drive is
currently using.
In the second scheme, the “1” rates are combined (Acc and Dec) and the “2”
rates are combined. A single input function is used to select between [Accel
Time 1]/[Decel Time 1] and [Accel Time 2]/[Decel Time 2]. This input
function is called “Acc 2 & Dec 2”.
If function is open, then drive will use [Accel Time 1] as the acceleration rate
and [Decel Time 1] as the deceleration rate. If function is closed, then drive
will use [Accel Time 2] as the acceleration rate and [Decel Time 2] as the
deceleration rate.
While the “MOP Increment” input is closed, MOP value will increase at rate
contained in [MOP Rate]. Units for rate are Hz per second.
While the “MOP Decrement” input is closed, MOP value will decrease at rate
contained in [MOP Rate]. Units for rate are Hz per second.
If both the “MOP Increment” and “MOP Decrement” inputs are closed,
MOP value will stay the same.
The terminal block bit must be set in the [MOP Mask] and [Logic Mask]
parameters in order for the MOP to be controlled from the terminal block.
In order for the drive to use the MOP value as the current speed reference,
either [Speed Ref A Sel] or [Speed Ref B Sel] must be set to “MOP.”
• Stop Mode B
This digital input function selects between two different drive stop modes.
See also Stop Modes on page 197.
If the input is open, then [Stop Mode A] selects which stop mode to use. If the
input is closed, then [Stop Mode B] selects which stop mode to use. If this
input function is not configured, then [Stop Mode A] always selects which
stop mode to use.
• Bus Regulation Mode B
This digital input function selects how the drive will regulate excess voltage
on the DC bus. See also Bus Regulation.
If the input is open, then [Bus Reg Mode A] selects which bus regulation
mode to use. If the input is closed, then [Bus Reg Mode B] selects which bus
regulation mode to use. If this input function is not configured, then [Bus Reg
Mode A] always selects which bus regulation mode to use.
• PI Enable
If this input function is closed, the operation of the Process PI loop will be
enabled.
If this input function is open, the operation of the Process PI loop will be
disabled. See Process PI Loop on page 135.
• PI Hold
If this input function is closed, the integrator for the Process PI loop will be
held at the current value, which is to say that it will not increase.
If this input function is open, the integrator for the Process PI loop will be
allowed to increase. See Process PI Loop on page 135.
• PI Reset
If this input function is closed, the integrator for the Process PI loop will be
reset to 0.
If this input function is open, the integrator for the Process PI loop will
integrate normally. See Process PI Loop on page 135.
• Auxiliary Fault
The “Aux Fault” input function allows external equipment to fault the drive.
Typically, one or more machine inputs (limit switches, pushbuttons, etc.) will
be connected in series and then connected to this input. If the input function
is open, the software detects the change of state then the drive will fault with
the “Auxiliary Input” (F2) fault code.
If the “Aux Fault” input function is assigned to a physical digital input, that
input will be active regardless of any drive control masks. Also, the input will
be active even if a device other than the terminal block gains complete local
control of drive logic. See Local Control.
If this input function is not configured, then the fault will not occur.
• Local Control
The “Local Control” input function allows exclusive control of all drive logic
functions from the terminal block. If this input function is closed, the
terminal block has exclusive control (disabling all the DPI devices) of drive
logic, including start, reference selection, acceleration rate selection, etc. The
exception is the stop condition, which can always be asserted from any
connected control device.
The drive must be stopped in order for the terminal block to gain complete
local control.
• Clear Faults
The “Clear Faults” digital input function allows an external device to reset
drive faults through the terminal block. An open to closed transition on this
input will cause the current fault (if any) to be reset.
If this input is configured at the same time as “Stop - Clear Faults”, then only
the “Clear Faults” input can actually cause faults to be reset.
The terminal block bit must be set in the [Fault Mask] and [Logic Mask]
parameters in order for faults to be reset from the terminal block.
• Enable
If this input is closed, then the drive can run (start permissive). If open, the
drive will not start.
If the drive is already running when this input is opened, the drive will coast
and indicate “not enabled” on the HIM (if present). This is not considered a
fault condition, and no fault will be generated.
This input is not used for a fast output power removal. The drive will not stop
running until the software detects the open state of this input function.
If multiple “Enable” inputs are configured, then the drive will not run if any of
the inputs are open.
• Exclusive Link
This input function is used to activate the state of the input to control one of
the drive’s digital outputs. See Digital Outputs.
This choice is made when the user wishes to link the input to the output, but
desires that no other functionality be assigned to the input.
The state of any digital input can be “passed through” to a digital output by
setting the value of a digital output configuration parameter ([Digital Outx
Sel]) to “Input n Link”. The output will then be controlled by the state of the
input, even if the input is being used for a second function. If the input is
configured as “Not used” input function, the link to the input is considered
non-functional.
• Power Loss Level (PowerFlex 700 only)
When the DC bus level in the drive falls below a certain level, a “power loss”
condition is created in the drive logic. This input allows the user to select
between two different “power loss” detection levels dynamically.
If the physical input is closed, then the drive will take its power loss level from
[Power Loss Level]. If the physical input is open (de-energized), then the drive
will use a power loss level designated by internal drive memory, typically 82%
of nominal.
If the input function is not configured, then the drive always uses the internal
power loss level. This input function is used in PowerFlex 700 drives only. In
PowerFlex 70 drives, the power loss level is always internal and not selectable.
If the physical input is closed, this indicates that the drive is connected to
common DC bus and normal precharge handling can occur, and that the
drive can run (start permissive). If the physical input is open, this indicates
that the drive is disconnected from the common DC bus, and thus the drive
should enter the precharge state (precharge relay open) and initiate a coast
stop immediately in order to prepare for reconnection to the bus.
If this input function is not configured, then the drive assumes that it is always
connected to the DC bus, and no special precharge handling will be done.
This input function is used in PowerFlex 700 drive only. In PowerFlex 70
drives, the drive assumes it is always connected to the DC bus.
• User tries to configure both the “Start” input function and the “Run Forward”
input function at the same time. “Start” is only used in “3-wire” start mode,
and “Run Forward” is only used in “2-wire” run mode, so they should never be
configured at the same time
• User tries to assign a toggle input function (for instance “Forward/Reverse”)
to more than one physical digital input simultaneously.
• These alarms, called Type 2 Alarms, are different from other alarms in that it
will not be possible to start the drive while the alarm is active. It should not be
possible for any of these alarms to occur while drive is running, because all
configuration parameters are only changeable while drive is stopped.
Whenever one or more of these alarms is asserted, the drive ready status will
become “not ready” and the HIM will reflect a message signaling the conflict.
In addition, the drive status light will be flashing yellow.
There are three different digital input configuration alarms. They appear to the
user (in [Drive Alarm 2]) as “DigIn CflctA”, “DigIn CflctB”, and “DigIn CflctC”.
“DigIn CflctA” indicates a conflict between different input functions that are
not specifically associated with particular start modes.
The table below defines which pairs of input functions are in conflict.
Combinations marked with a “ ” will cause an alarm.
Important: There are combinations of input functions in Table 10 that will
produce other digital input configuration alarms. “DigIn CflctA”
alarm will also be produced if “Start” is configured and “Stop –
Clear Faults” is not.
Table 10 Input function combinations that produce “DigIn CflctA” alarm
Acc2/Dec2 Accel 2 Decel 2 Jog Jog Fwd Jog Rev Fwd/Rev
Acc2 / Dec2
Accel 2
Decel 2
Jog
Jog Fwd
Jog Rev
Fwd / Rev
“DigIn CflctB” indicates a digital Start input has been configured without a
Stop input or other functions are in conflict. Combinations that conflict are
marked with a “ ” and will cause an alarm.
“Digin CflctC” indicates that more than one physical input has been configured
to the same input function, and this kind of multiple configuration isn’t allowed
for that function. Multiple configuration is allowed for some input functions and
not allowed for others.
The input functions for which multiple configuration is not allowed are:
Forward/Reverse Run Forward Stop Mode B
Speed Select 1 Run Reverse Bus Regulation Mode B
Speed Select 2 Jog Forward Accel2 & Decel2
Speed Select 3 Jog Reverse Accel 2
Run Decel 2
There is one additional alarm that is related to digital inputs: the “Bipolar Cflct”
alarm occurs when there is a conflict between determining motor direction using
digital inputs on the terminal block and determining it by the polarity of an
analog speed reference signal.
Note that the drive will assert an alarm when the user sets up a illegal
configuration rather than refusing the first parameter value that results in such a
configuration. This is necessary because the user may have to change several
parameters one at a time in order to get to a new desired configuration, and some
of the intermediate configurations may actually be illegal. Using this scheme, the
user or a network device can send parameter updates in any order when setting up
the digital input configuration.
The “Bipolar Cflct” alarm occurs when there is a conflict between determining
motor direction using digital inputs on the terminal block and determining it by
some other means.
When [Direction Mode] is “Bipolar”, the drive uses the sign of the reference to
determine drive direction; when [Direction Mode] is “Reverse Dis”, then the
drive never permits the motor to run in the reverse direction. In both of these
cases, the terminal block inputs cannot be used to set direction, so this alarm is
asserted if any digital input function that can set motor direction is configured.
The “Bipolar Cflct” alarm will be asserted if both of the following are true:
Digital In Status
This parameter represents the current state of the digital inputs. It contains one
bit for each input. The bits are “1” when the input is closed and “0” when the
input is open.
Digital In Examples
PowerFlex 70
Figure 16 shows a typical digital input configuration that includes “3-wire” start.
The digital input configuration parameters should be set as shown.
Figure 16 Typical digital input configuration with “3-wire” start
Internal Power Source External Power Source
Digital Outputs Each drive provides digital (relay) outputs for external annunciation of a variety
of drive conditions. Each relay is a Form C (1 N.O. – 1 N.C. with shared
common) device whose contacts and associated terminals are rated for a
maximum of 250V AC or 220V DC. The table below shows specifications and
limits for each relay/contact.
PowerFlex 70 PowerFlex 700
Resistive Load Inductive Load Resistive Load Inductive Load
Rated Voltage 250V AC 250V AC 240V AC 240V AC
220V DC 220V DC 30V DC 30V DC
Maximum Current 3A 1.5 A 5A 3.5 A
Maximum Power AC - 50 VA AC - 25 VA 1200 VA 840 VA
DC - 60 W DC - 30 W 150W 105W
Minimum DC Current 10 μA 10 mA
Switching Time 8 ms 10 ms
Initial State De-energized De-energized
Number of relays 2 2 - Standard Control
(Standard I/O) 3 - Vector Control
Configuration
The outputs may be independently configured via the following parameters to
switch for various states of the drive.
Digital Outputs
11 “At Current” 002
12 “At Torque” 001
13 “At Temp” 003
14 “At Bus Volts” 004
15 “At PI Error” 218
16 “DC Braking” 012
17 “Curr Limit” 137
18 “Economize” 157
19 “Motor Overld” 147
20 “Power Loss” 053
21 “Input 1 Link” 048
22 “Input 2 Link” 184
23 “Input 3 Link”
24 “Input 4 Link”
25 “Input 5 Link”
26 “Input 6 Link”
The following drive conditions or status can be selected to cause the relay
activation:
Condition Description
Fault A drive Fault has occurred and stopped the drive
Alarm A Drive Type 1 or Type 2 Alarm condition exists
Ready The drive is powered, Enabled and no Start Inhibits exist. It is “ready” to run
Run The drive is outputting Voltage and frequency to the motor (indicates 3–wire control, either
direction)
Forward Run The drive is outputting Voltage and frequency to the motor (indicates 2–wire control in
Forward)
Reverse Run The drive is outputting Voltage and frequency to the motor (indicates 2–wire control in Reverse)
Reset/Run The drive is currently attempting the routine to clear a fault and restart the drive
Powerup Run The drive is currently executing the Auto Restart or “Run at Power Up” function
DC Braking The drive is currently executing either a “DC Brake” or a “Ramp to Hold” Stop command and the
DC braking voltage is still being applied to the motor.
Current Limit The drive is currently limiting output current
Economize The drive is currently reducing the output voltage to the motor to attempt to reduce energy costs
during a lightly loaded situation.
Mtr Overload The drive output current has exceeded the programmed [Motor NP FLA] and the electronic
motor overload function is accumulating towards an eventual trip.
Power Loss The drive has monitored DC bus voltage and sensed a loss of input AC power that caused the DC
bus voltage to fall below the fixed monitoring value (82% of [DC bus Memory]
2. The relay changes state because a particular value in the drive has exceeded a
preset limit.
The following drive values can be selected to cause the relay activation:
Condition Description
At Speed The drive Output Frequency has equalled the commanded frequency
The balance of these functions require that the user set a limit for the specified
value. The limit is set into one of two parameters: [Dig Out1 Level] and [Dig
Out2 Level] depending on the output being used. If the value for the specified
function (frequency, current, etc.) exceeds the user programmed limit, the
relay will activate. If the value falls back below the limit, the relay will
deactivate.
381 [Dig Out1 Level] Default: 0.0 380
385 [Dig Out2 Level] 0.0 384
389 Vector [Dig Out3 Level] Min/Max: 0.0/819.2 388
Sets the relay activation level for options 10 – 15 Units: 0.1
in [Digital Outx Sel]. Units are assumed to match
the above selection (i.e. “At Freq” = Hz, “At
Torque” = Amps).
Notice that the [Dig Outx Level] parameters do not have units. The drive
assumes the units from the selection for the annunciated value. For example, if
the chosen “driver” is current, the drive assumes that the entered value for the
limit [Dig Outx Level] is% rated Amps. If the chosen “driver” is Temperature,
the drive assumes that the entered value for the limit [Dig Outx Level] is
degrees C. No units will be reported to LCD HIM users, offline tools, devices
communicating over a network, PLC’s, etc.
The online and offline limits for the digital output threshold parameters will
be the minimum and maximum threshold value required for any output
condition.
If the user changes the currently selected output condition for a digital output,
then the implied units of the corresponding threshold parameter will change
with it, although the value of the parameter itself will not. For example, if the
output is set for “At Current” and the threshold for 100, drive current over
100% will activate the relay. If the user changes the output to “At Temp”, the
relay will deactivate (even if current > 100%) because the drive is cooler than
100 degrees C.
3. The relay changes state because a Digital Input link has been established and
the Input is closed.
Note that the output will continue to track or be controlled by the state of the
input, even if the input has been assigned a function (i.e. Start, Jog)
One timer (the ON timer) defines the delay time between a FALSE to TRUE
transition (condition appears) on the output condition and the corresponding
change in state of the digital output.
The second timer (the OFF timer) defines the delay time between a TRUE to
FALSE transition (condition disappears) on the output condition and the
corresponding change in the state of the digital output.
382 [Dig Out1 OnTime] Default: 0.00 Secs 380
386 [Dig Out2 OnTime] 0.00 Secs 384
390 Vector [Dig Out3 OnTime] Min/Max: 0.00/600.00 Secs 388
Sets the “ON Delay” time for the digital outputs. This is Units: 0.01 Secs
the time between the occurrence of a condition and
activation of the relay.
383 [Dig Out1 OffTime] Default: 0.00 Secs 380
387 [Dig Out2 OffTime] 0.00 Secs 384
391 Vector [Dig Out3 OffTime] Min/Max: 0.00/600.00 Secs 388
Sets the “OFF Delay” time for the digital outputs. This is Units: 0.01 Secs
the time between the disappearance of a condition and
de-activation of the relay.
Either timer can be disabled by setting the corresponding delay time to “0.”
If a transition on an output condition occurs and starts a timer, and the output
condition goes back to its original state before the timer runs out, then the timer
will be aborted and the corresponding digital output will not change state.
Relay Activates
CR1 On Delay = 2 Seconds
0 5 10
0 5 10
Ne DigO 3
t D ut2
ut1
ut
Ne igO
igO
tD
t
Ne
x x x x x x x x x x x x x 0 0 0 1 =Output Energized
0 =Output De-energized
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 x =Reserved
Bit #
Example
Digital Output 2 controlled by Data In B1
Setup
• [Data In B1], parameter 302 = 379 ([Dig Out Setpt] as the Data In target)
• [Digital Out2 Sel], parameter 384 = 30 "Param Cntl"
Direction Control Direction control of the drive is an exclusive ownership function. Thus only one
device can be commanding/controlling direction at a time and that device can
only command one direction or the other, not both. Direction is defined as the
forward (+) or reverse (–) control of the drive output frequency, not motor
rotation. Motor wiring and phasing determines its CW or CCW rotation.
Direction of the drive is controlled in one of four ways:
1. 2-Wire digital input selection such as Run Forward or Run Reverse (Figure
17 on page 86).
Refer to Digital Inputs on page 70 and Analog Inputs on page 18 for more detail
on the configuration and operating rules for direction control.
Important: The PowerFlex 700 Vector Control option only supports the DPI
communication protocol. It will not communicate with SCANport
peripheral devices.
Client/Server
Client/Server messages operate in the background (relative to other message
types) and are used for non-control purposes. The Client/Server messages are
based on a 10ms “ping” event that allows peripherals to perform a single
transaction (i.e. one C/S transaction per peripheral per time period). Message
fragmentation (because the message transaction is larger than the standard CAN
message of eight data bytes) is automatically handled by Client/Server operation.
The following types of messaging are covered:
Peer-to-Peer operation
Peer-to-Peer messaging allows two devices to communicate directly rather than
through the master or host (i.e. drive). They are the same priority as C/S
messages and will occur in the background. In the PowerFlex 70 drive, the only
Peer-to-Peer functionality supports proxy operations for the LED HIM. Since
the PowerFlex 700 drive does not support an LED HIM, it will not support
Peer-to-Peer proxy operations. The Peer-to-Peer proxy operation is only used so
that the LED HIM can access parameters that are not directly part of the
regulator board (e.g. DeviceNet baud rate, etc.). The LED HIM is not attached
to a drive through a CAN connection (as normal DPI or SCANport devices are),
so a proxy function is needed to create a DPI message to access information in an
off-board peripheral. If an LCD HIM is attached to the PowerFlex 70 or 700
drive, it will be able to directly request off-board parameters using Peer-to-Peer
messages (i.e. no proxy support needed in the drive). Because the PowerFlex 70
supports the LED HIM, only 4 communication ports can be used. PowerFlex
700 drives can use all 6 communication ports because Peer-to-Peer proxy
operations are not needed. All Peer-to-Peer operations occur without any
intervention from the user (regardless whether proxy or normal P/P operation),
no setup is required. No Peer-to-Peer proxy operations are required while the
drive is in Flash mode.
All the timing requirements specified in the DPI and SCANport System,
Control, and Messaging specifications are supported. Peripheral devices will be
scanned (“pinged”) at a 10ms rate. Drive status messages will be produced at a
5ms rate, while peripheral command messages will be accepted (by the drive) as
they occur (i.e. change of state). Based on these timings, the following worst case
conditions can occur (independent of the baud rate and protocol):
• Change of peripheral state (e.g. Start, Stop, etc.) to change in the drive – 10ms
• Change in reference value to change in drive operation – 10ms
• Change in Datalink data value to change in the drive – 10ms
• Change of parameter value into drive – 20ms times the number of attached
peripherals
The maximum time to detect the loss of communication from a peripheral device
is 500ms.
The Minimum Update Time (MUT), is based on the message type only. A
standard command and Datalink command could be transmitted from the same
peripheral faster than the MUT and still be O.K. Two successive Datalink
commands or standard commands will still have to be separated by the MUT,
however.
Drive Overload The drive thermal overload has two primary functions. The first requirement is
to make sure the drive is not damaged by abuse. The second is to perform the first
in a manor that does not degrade the performance, as long the drive temperature
and current ratings are not exceeded.
The purpose of is to protect the power structure from abuse. Any protection for
the motor and associated wiring is provided by a Motor Thermal Overload
feature.
The drive will monitor the temperature of the power module based on a
measured temperature and a thermal model of the IGBT. As the temperature
rises the drive may lower the PWM frequency to decrease the switching losses in
the IGBT. If the temperature continues to rise, the drive may reduce current limit
to try to decrease the load on the drive. If the drive temperature becomes critical
the drive will generate a fault.
If the drive is operated in a low ambient condition the drive may exceed rated
levels of current before the monitored temperature becomes critical. To guard
against this situation the drive thermal overload also includes an inverse time
algorithm. When this scheme detects operation beyond rated levels, current limit
may be reduced or a fault may be generated.
Operation
The drive thermal overload has two separate protection schemes, an overall RMS
protection based on current over time, and an IGBT junction thermal manager
based on measured power module temperature and operating conditions. The
drive may fold back current limit when either of these methods detects a
problem.
1.30
1.20
1.10
1.00
0.90
0.80
0.70
0.60
0.50
0.40
0.30
0.20
0.10
0.00
1.00 10.00 100.00 1,000.00
Time (Seconds)
The lower curve in Figure 19 shows the boundary of heavy duty operation. In
heavy duty, the drive is rated to produce 150% of rated current for 60 seconds,
200% for three seconds, and 220% for 100 milliseconds. The maximum value for
current limit is 200% so the limit of 220% for 100 milliseconds should never be
crossed. If the load on the drive exceeds the level of current as shown on the upper
curve, current limit may fold back to 100% of the drive rating until the 10/90 or
5/95 duty cycle has been achieved. For example, 60 seconds at 150% will be
followed by 9 minutes at 100%, and 3 seconds at 200% will be followed by 57
seconds at 100%. With the threshold for where to take action slightly above the
rated level the drive will only fold back when drive ratings are exceeded.
Again, if fold back of current limit is not enabled in the [Drive OL Mode], the
drive will generate a fault when operation exceeds the rated levels. This fault can
not be disabled. If current limit fold back is enabled then a fault is generated
when current limit is reduced.
Figure 19 Heavy Duty Boundary of Operation
2.50
2.25
2.00
1.75
Current Level (Per Normal)
1.50
1.25
1.00
0.75
0.50
0.25
0.00
1.00 10.00 100.00 1000.00 10000.00
Time (Seconds)
PWM Frequency
PWM Frequency as selected by the user can be reduced by the thermal manager.
The resulting Active PWM Frequency may be displayed in a test point parameter.
The active PWM frequency will change in steps of 2 kHz. It will always be less
than or equal to the value selected by the user, and will not be less than the drives
minimum PWM frequency. When drive temperature reaches the level where
PWM frequency would be limited, the Drv OL Lvl 1 Alarm is turned on. This
alarm will be annunciated even if the reduced PWM frequency is not enabled.
Current Limit
Current Limit as selected by the user can be reduced by the thermal manager. The
resulting active current limit may be displayed as a test point parameter.
The active current limit will always be less than or equal to the value selected by
the user, and will not be less than flux current. When drive temperature reaches
the level where current limit would be clamped, the Drv OL Lvl 2 Alarm is
turned on. This alarm will be annunciated even if reduced current limit is not
enabled.
The active current limit is used during normal operation and during DC
injection braking. Any level of current requested for DC injection braking is
limited by the Active Current Limit.
Configuration
The [Drive OL Mode] allows the user to select the action(s) to perform with
increased current or drive temperature. When this parameter is “Disabled,” the
drive will not modify the PWM frequency or current limit. When set to “Reduce
PWM” the drive will only modify the PWM frequency. “Reduce CLim” will only
modify the current limit. Setting this parameter to “Both-PWM 1st” the drive
will modify the PWM frequency and the current limit.
DTO Fault
For all possible settings of [Drive OL Mode], the drive will always monitor the Tj
and TDrive and generate a fault when either temperature becomes critical. If
TDrive is less than –20° C, a fault is generated. With these provisions, a DTO
fault is generated if the NTC ever malfunctions.
Temperature Display
The Drive’s temperature is measured (NTC in the IGBT module) and displayed
as a percentage of drive thermal capacity in [Drive Temp]. This parameter is
normalized to the thermal capacity of the drive (frame dependent) and displays
thermal usage in % of maximum (100% = drive Trip). A test point, “Heatsink
temperature” is available to read temperature directly in degrees C, but cannot be
related to the trip point since “maximums” are only given in %. The IGBT
temperature shown in Figure 20 is used only for internal development and is not
provided to the user.
When the drive is in current limit the output frequency is reduced to try to
reduce the load. This works fine for a variable torque load, but for a constant
torque load reducing the output frequency does not lower the current (load).
Lowering current limit on a CT load will push the drive down to a region where
the thermal issue becomes worse. In this situation the thermal manager will
increase the calculated losses in the power module to track the worst case IGBT.
For example, if the thermal manager normally provides 150% for 3 seconds at
high speeds, it may only provide 150% for one second before generating a fault at
low speeds.
If operating at 60Hz 120%, lowering the current limit may cause a fault sooner
than allowing the drive to continue to operate. In this case the user may want to
disable current limit fold back.
Drive Ratings (kW, Amps, Refer to Fuses and Circuit Breakers on page 106.
Volts)
Droop Vector Droop is used to “shed” load and is usually used when a soft coupling
of two motors is present in an application. The master drive speed regulates and
the follower uses droop so it does not “fight” the master. The input to the droop
block is the commanded motor torque. The output of the droop block reduces
the speed reference. [Droop RPM @ FLA] sets the amount of speed, in RPM,
that the speed reference is reduced when at full load torque. For example, when
[Droop RPM @ FLA] is set to 50 RPM and the drive is running at 100% rated
motor torque, the droop block would subtract 50 RPM from the speed reference.
When steady state speed is achieved, the economizer becomes active and
automatically adjusts the drive output voltage based on applied load. By matching
output voltage to applied load, the motor efficiency is optimized. Reduced load
commands a reduction in motor flux current. The flux current is reduced as long
as the total drive output current does not exceed 75% of motor rated current as
programmed in [Motor NP FLA], parameter 42. The flux current is not allowed
to be less than 50% of the motor flux current as programmed in [Flux Current
Ref ], parameter 63. During acceleration and deceleration, the economizer is
inactive and sensorless vector motor control performs normally.
Maximum Voltage
Motor Nameplate Voltage
Increasing
Rated Flux Current Load
Vtotal
Efficiency The following chart shows typical efficiency for PWM variable frequency drives,
regardless of size. Drives are most efficient at full load and full speed.
100
vs. Speed
95
vs. Load
% Efficiency
90
85
80
75
10 20 30 40 50 60 70 80 90 100
% Speed/% Load
Fan Curve When torque performance (see page 201) is set to Fan/Pump, the relationship
between frequency and voltage is shown in the following figure. The fan/pump
curve generates voltage that is a function of the stator frequency squared up to the
motor nameplate frequency. Above base frequency voltage is a linear function of
frequency. At low speed the fan curve can be offset by the run boost parameter to
provide extra starting torque if needed. No extra parameters are needed for fan/
pump curve.
The pattern matches the speed vs. load characteristics of a centrifugal fan or
pump and optimizes the drive output to those characteristics.
Maximum Voltage
Base Voltage
(Nameplate)
Run Boost
Faults Faults are events or conditions occurring within and/or outside of the drive.
Theses events or conditions are (by default) considered to be of such significant
magnitude that drive operation should or must be discontinued. Faults are
annunciated to the user via the HIM, communications and/or contact outputs.
The condition that caused the fault determines the user response.
Once a fault occurs, the fault condition is latched, requiring the user or
application to perform a fault reset action to clear the latched condition. If the
condition that caused fault still exists when the fault is reset, the drive will fault
again and the fault will be latched again.
2. The fault code is entered into the first buffer of the fault queue (see “Fault
Queue” below for rules).
3. Additional data on the status of the drive at the time that the fault occurred is
recorded. Note that there is only a single copy of this information which is
always related to the most recent fault queue entry [Fault 1 Code], parameter
243. When another fault occurs, this data is overwritten with the new fault
data. The following data/conditions are captured and latched into
non-volatile drive memory:
Fault Queue
Faults are also logged into a fault queue such that a history of the most recent
fault events is retained. Each recorded event includes a fault code (with associated
text) and a fault “time of occurrence.” The PowerFlex 70 drive has a four event
queue and the PowerFlex 700 has an eight event queue.
A fault queue will record the occurrence of each fault event that occurs while no
other fault is latched. Each fault queue entry will include a fault code and a time
stamp value. A new fault event will not be logged to the fault queue if a previous
fault has already occurred, but has not yet been reset. Only faults that actually trip
the drive will be logged. No fault that occurs while the drive is already faulted will
be logged.
The fault queue will be a first-in, first-out (FIFO) queue. Fault queue entry #1
will always be the most-recent entry (newest). Entry 4 (8) will always be the
oldest. As a new fault is logged, each existing entry will be shifted up by one (i.e.
previous entry #1 will move to entry #2, previous entry #2 will move to entry #3,
etc.). If the queue is full when a fault occurs, the oldest entry will be discarded.
The fault queue will be saved in nonvolatile storage at power loss, thus retaining
its contents through a power off - on cycle.
The time stamp value recorded in the fault queue at the time of a fault is the value
of internal drive under power timer. By comparing this value to the [PowerUp
Marker], it is possible to determine when the fault occurred relative to the last
drive power-up.
The time stamp for each fault queue entry can be read via the corresponding
parameter. Time comparisons of one fault to the next and/or with [PowerUp
Marker] are only meaningful if they occur less than or equal to the rollover range.
5. Cycling power to the drive such that the control board goes through a
power-up sequence.
Resetting faults will clear the faulted status indication. If any fault condition still
exists, the fault will relatch and another entry made in the fault queue.
Fault Configuration
The drive can be configured such that some fault conditions do not trip the drive.
Configurable faults include those that are user inputs.
De r Th ss *
cc
rPN os
Au el Inh m *
r L ge
erL
Mo r Pi s
*
Sh t Tr t
s
ea eL
to Lo
tRs ib
we lta
ea ie
er
os
Ph s
tor n
s
Sh Phas
Ov
Mo ase
Po Vo
L o
r
de
ad
c
t
Ou
Un
Lo
In
x x x 0 0 x 0 0 0 1 0 0 1 x 1 0 1 =Enabled
0 =Disabled
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 x =Reserved
Bit # * Vector firmware 3.001 & later
Factory Default Bit Values
Power Up Marker
Copy of factory “drive under power” timer at the last power-up of the drive. Used
to provide relevance of Fault 'n' Time values with respect to the last power-up of
the drive.
This value will rollover to 0 after the drive has been powered on for more than
the hours shown in the Range field (approximately 47.667 years).
Flux Braking Vector You can use flux braking to stop the drive or to shorten the
deceleration time to a lower speed. Other methods of deceleration or stopping
may perform better depending on the motor and the load.
1. [Bus Reg Mode A, B] must be set to “1” Adjust Freq to enable the bus
regulator.
2. [Flux Braking] must be set to 1 “Enabled”.
When enabled, flux braking automatically increases the motor flux resulting in an
increase of motor losses. The flux current is only increased when the bus voltage
regulator is active. When the bus voltage regulator is not active, the flux current is
returned to normal. The maximum flux current is equal to rated motor current
but may be further reduced depending on the load level, IT protection, or current
limits. In general, the flux current is not increased when the motor is at or above
rated speed. At higher speeds, field weakening is active and the motor flux current
cannot be increased. As the speed decreases below base speed, the flux current
increases until there is enough voltage margin to run rated motor current.
Because flux braking increases motor losses, the duty cycle used with this method
must be limited. Check with the motor vendor for flux braking or DC braking
application guidelines. You may also want to consider using external motor
thermal protection.
The first method is a normal start. During a normal start, flux is established as the
output voltage and frequency are applied to the motor. While the flux is being
built, the unpredictable nature of the developed torque may cause the rotor to
oscillate even though acceleration of the load may occur. In the motor, the
acceleration profile may not follow the commanded acceleration profile due to
the lack of developed torque.
Figure 21 Accel Profile during Normal Start - No Flux Up
Frequency
Reference
Frequency
Rated Flux
Stator
Rotor
Oscillation due
to flux being
established
0
Time
The second method is Flux Up Mode. In this mode, DC current is applied to the
motor at a level equal to the lesser of the current limit setting, drive rated current,
and drive DC current rating. The flux up time period is based on the level of flux
up current and the rotor time constant of the motor.
Flux Up Current
Rated Flux Rated Motor Flux
Current
Motor Flux
T1
T2
T3
T4
Flux Up Time
[Flux Up Time]
Once rated flux is reached in the motor, normal operation begins and the desired
acceleration profile is achieved.
Figure 23 Rated Flux Reached
Ir Voltage - SVC
Greater of IR Voltage or
Voltage Boost - V/Hz
Stator Voltage
Flux Up
Rotor Speed
Voltage
Motor Flux Motor Flux
Stator Freq
Flux Up Normal
Operation Time
Flying Start The Flying Start feature is used to start into a rotating motor, as quick as possible,
and resume normal operation with a minimal impact on load or speed.
In Flying Start mode, the drive’s response to a start command will be to identify
the motor’s speed and apply a voltage that is synchronized in frequency,
amplitude and phase to the back emf of the spinning motor. The motor will then
accelerate to the desired frequency. This process will prevent an overcurrent trip
and significantly reduce the time for the motor to reach its desired frequency.
Since the motor is “picked up “smoothly at its rotating speed and ramped to the
proper speed, little or no mechanical stress is present.
Configuration
Flying Start is activated by setting the [Flying Start En] parameter to “Enable”
169 [Flying Start En] Default: 0 “Disabled” 170
Enables/disables the function which Options: 0 “Disabled”
reconnects to a spinning motor at actual 1 “Enabled”
RPM when a start command is issued.
Application Example
In some applications, such as large fans, wind or drafts may rotate the fan in the
reverse direction when the drive is stopped. If the drive were started in the normal
manner, its output would begin at zero Hz, acting as a brake to bring the reverse
rotating fan to a stop and then accelerating it in the correct direction.
This operation can be very hard on the mechanics of the system including fans,
belts and other coupling devices.
Draft/wind blows idle fans in reverse direction. Restart at zero damages fans,
breaks belts. Flying start alleviates the problem
Fuses and Circuit Breakers Refer to the Powerflex 70 Technical Data (publication 20A-TD001) or
PowerFlex 700 Technical Data (publication 20B-TD001) for fuse information.
Grounding, General Refer to “Wiring and Grounding Guidelines for PWM AC Drives,” publication
DRIVES-IN001.
Using Passwords
By default the password is set to 00000 (password protection disabled).
Logging Out
Step Key(s) Example Displays
You are automatically logged out when the User
Display appears. If you want to log out before that,
select “log out” from the Main Menu.
To change a password
Step Key(s) Example Displays
1. Use the Up Arrow or Down Arrow to scroll to Operator
Intrfc. Press Enter. Operator Intrfc:
Change Password
2. Select “Change Password” and press Enter. User Display
Parameters
3. Enter the old password. If a password has not been
set, type “0.” Press Enter.
Password:
4. Enter a new password (1- 65535). Press Enter and Old Code: 0
verify the new password. Press Enter to save the new New Code: 9999
password. Verify: 9999
Filters, EMC
Refer to CE Conformity on page 63.
Input Modes The PowerFlex family of drives does not use a direct choice of 2-wire or 3-wire
input modes, but allows full configuration of the digital I/O. As a means of
defining the modes used, consider the following:
only utilizes one device and 2 wires to closes its contact to Run the drive Run/Stop
control both the Start (normally and opens to Stop the drive.
referred to as “RUN” in 2-wire) and Stop PORT
MOD
NET A
functions in an application.
NET B
MOD
NET A
NET B
Run Reverse
be desirable.
STS
Run
PORT
MOD
NET A
NET B
Forward/Reverse
This input mode utilizes 2 devices button is closed, but unlike 2-wire
STS
Start
requiring 3 wires to control the Start circuits, the drive does not Stop
(proper term for 3-wire) and Stop when the Start button is released.
functions in an application. In this case, Instead, 3-wire control requires a PORT
MOD
NET A
NET B
momentary contact devices, such as Stop input to Stop the drive. Stop
pushbuttons are used.
STS
Stop
Forward
PORT
MOD
NET A
NET B
Reverse
STS
Start
Stop PORT
MOD
NET A
NET B
Forward/Reverse
Input Power Conditioning Refer to Chapter 2 of “Wiring and Grounding Guidelines for PWM AC Drives,”
publication DRIVES-IN001A-EN-P.
For PowerFlex 70 and PowerFlex 700 with Standard Control, the jog reference
will always be a positive number limited between Minimum Speed and
Maximum Speed.
If [Direction Mode] = “Unipolar” the drive will jog using the Jog reference
parameter value and will use the direction currently selected via the DPI
commanded direction. When [Direction Mode] = “Bipolar” and a Jog command
(with no direction) is asserted, the drive will jog using the Jog reference parameter
(which is always positive or forward). To accommodate jogging with direction
while in Bipolar mode (such as from a terminal block), the drive will allow Jog
Fwd and Jog Rev to be configured as terminal block inputs. When these inputs
are asserted, the drive will jog the requested direction. This still implies that a
HIM can only jog in the forward direction when in Bipolar mode since they only
transmit a Jog command with no direction via DPI.
For PowerFlex 700 drives with Vector Control, 2 independent Jog Speeds (1 and
2) are provided. The jog reference is signed and limited between Minimum
Speed or Reverse Speed Limit (whichever is programmed)) and Maximum
Speed. In this control, the jog reference controls both speed and direction of the
jog operation. If the programmed Jog Speed is negative the drive will jog in the
reverse direction: if the Jog Speed value is positive, the drive will jog in the
forward direction.
When a jog command is issued, exclusive control of speed and direction is given
to the Jog function. If the master speed reference is bipolar and commanding
reverse direction but the programmed Jog Speed is a positive value, the drive will
jog in the forward direction, overriding the direction control of a bipolar speed
reference.
Establishing A Link
Step Key(s) Example Displays
1. Select a valid destination parameter (see Table 13) to
be linked. The parameter value screen will appear. FGP: Parameter
Accel Time 1
2. Press Enter to edit the parameter. The cursor will Accel Time 2
move to the value line. Decel Time 1
3. Press ALT and then View (Sel). Next, press the Up or Min: 0.1 Secs
Down Arrow to change “Present Value” to “Define ALT + Sel Max: 3600.0 Secs
Link.” Press Enter. Dflt: 10.0 Secs
or Present Value
4. Enter the Source Parameter Number and press Enter. .
The linked parameter can now be viewed two .
different ways by repeating steps 1-4 and
selecting “Present Value” or “Define Link.” If Define Link
an attempt is made to edit the value of a
linked parameter, “Parameter is Linked!” will
be displayed, indicating that the value is Parameter: #141
coming from a source parameter and can not Accel Time 2
be edited. Link: 017
Analog In1 Value
5. To remove a link, repeat steps 1-5 and change the
source parameter number to zero (0).
Esc
6. Press Esc to return to the group list.
Masks A mask is a parameter that contains one bit for each of the possible Adapters.
Each bit acts like a valve for issued commands. Closing the valve (setting a bit's
value to 0) stops the command from reaching the drive logic. Opening the valve
(setting a bit's value to 1) allows the command to pass through the mask into the
drive logic.
276 [Logic Mask] 288
Determines which adapters can control the drive. If the bit for an adapter is set to “0,” the thru
adapter will have no control functions except for stop. 297
IP 5
4
IP 3
2
ita 1
l In
DP Port
DP o r t
DP Port
DP o r t
Dig Port
I
I
DP
x x x x x x x x x x 1 1 1 1 1 1 1 =Control Permitted
0 =Control Masked
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 x =Reserved
Bit #
Factory Default Bit Values
277 [Start Mask] See [Logic Mask]. 288
Controls which adapters can issue start commands. thru
297
278 [Jog Mask] See [Logic Mask]. 288
Controls which adapters can issue jog commands. thru
297
279 [Direction Mask] See [Logic Mask]. 288
Controls which adapters can issue forward/reverse thru
297
COMMUNICATION
direction commands.
Masks & Owners
Direction Mask
0 0 0 0 0 1 0 0
Adapter # X 6 5 4 3 2 1 0
This “masks out” the reverse function from all adapters except Adapter 2, making
the local HIM (Adapter 1) REV button inoperable. Also see Owners on
page 125.
MOP The Motor Operated Pot (MOP) function is one of the sources for the frequency
reference. The MOP function uses digital inputs to increment or decrement the
Speed reference at a programmed rate.
The MOP reference rate is defined in [MOP rate]. The MOP function is defined
graphically below
MOP dec
MOP inc
MOP reference
Both the MOP inc and dec will use the same rate (i.e. they can not be separately
configured). The MOP rate is the rate of change of the MOP reference. The
selected active MOP reference still feeds the ramp function to arrive at the
present commanded speed/frequency (eg. is still based on the accel/decel rates).
Asserting both MOP inc and dec inputs simultaneously will result in no change
to the MOP reference.
[Save MOP Ref ] is a packed boolean parameter with two bits used as follows:
Bit 0
0 = Don’t save MOP reference on power-down (default)
1 = Save MOP reference on power-down
If the value is “SAVE MOP Ref ” when the drive power returns, the MOP
reference is reloaded with the value from the non-volatile memory. When the
bit is set to 0, the MOP reference defaults to zero when power is restored. The
MOP save reference parameter and the MOP rate parameter can be changed
while the drive is running.
Bit 1
0 = Reset MOP reference when STOP edge is asserted
1 = Don’t reset MOP reference when STOP is asserted (default)
Important: The MOP reset only occurs on the stop edge and is not continuously
cleared because the stop is asserted (this is always processed when a
stop edge is seen, even if the drive is stopped). The reset only applies
to the stop edge and not when a fault is detected.
Ownership of the MOP function can be obtained even if the MOP reference is
not being used to control the drive. If ownership is granted, the owner has the
right to inc/dec the MOP reference. Whether this reference is the active speed
reference for the drive is separately selected via TB reference select, or Ref A/B
select through DPI.
The MOP Frequency parameter is an output which shows the active value of the
MOP reference in Hz x 10.
If the Direction Mode is configured for “Unipolar,” then the MOP decrement
will clamp at zero not allowing the user to generate a negative MOP reference
that is clamped off by the reference generation. When Direction Mode =
“Bipolar” the MOP reference will permit the decrement function to produce
negative values. If the drive is configured for Direction Mode = “Bipolar” and
then is changed to “Unipolar”, the MOP reference will also be clamped at zero if
it was less than zero.
[Motor NP FLA]
The motor nameplate defines the output amps, when operating at rated voltage,
rated speed, and rated temperature. It is used in the motor thermal overload, and
in the calculation of slip.
[Motor NP Hz]
The motor nameplate base frequency defines the output frequency, when
operating at rated voltage, rated current, rated speed, and rated temperature.
[Motor NP RPM]
The motor nameplate RPM defines the rated speed, when operating at motor
nameplate base frequency, rated current, base voltage, and rated temperature.
This is used to calculate slip.
[Motor NP Power]
The motor nameplate power is used together with the other nameplate values to
calculate default values for motor parameters to and facilitate the commissioning
process. This may be entered in horsepower or in kilowatts as selected in the
previous parameter or kW for certain catalog numbers and HP for others.
Cold
1000
Hot
100
10
100 125 150 175 200 225 250
Full Load Amps (%)
Motor nameplate FLA programming is used to set the overload feature. This
parameter, which is set in the start up procedure, is adjustable from 0 - 200% of
drive rating and should be set for the actual motor FLA rating.
Setting the correct bit in [Fault Config x] to zero disables the motor thermal
overload. Most multimotor applications (using one drive and more than one
motor) will require the MTO to be disabled since the drive would be unable to
distinguish each individual motor’s current and provide protection.
2. [Motor OL Factor] is used to adjust for the service factor of the motor.
Within the drive, motor nameplate FLA is multiplied by motor overload
factor to select the rated current for the motor thermal overload. This can be
used to raise or lower the level of current that will cause the motor thermal
overload to trip without the need to adjust the motor FLA. For example, if
motor nameplate FLA is 10 Amps and motor overload factor is 1.2, then
motor thermal overload will use 12 Amps as 100%.
140
120
Continuous Rating
100
80
OL % = 1.20
60 OL % = 1.00
OL % = 0.80
40
20
0 10 20 30 40 50 60 70 80 90 100
% of Base Speed
100
Continuous Rating
80
OL Hz = 10
60 OL Hz = 25
OL Hz = 50
40
20
0 10 20 30 40 50 60 70 80 90 100
% of Base Speed
When the motor is cold motor thermal overload will allow 3 minutes at 150%.
When the motor is hot motor thermal overload will allow 1 minute at 150%. A
continuous load of 102% will not trip. The duty cycle of the motor thermal
overload is defined as follows. If operating continuous at 100% FLA, and the load
increases to 150% FLA for 59 seconds and then returns to 100%FLA, the load
must remain at 100% FLA for 20 minutes to reach steady state.
1 Minute 1 Minute
150%
100%
20 Minutes
The ratio of 1:20 is the same for all durations of 150%. When operating
continuous at 100%, if the load increases to 150% for 1 second the load must
then return to 100% for 20 seconds before another step to 150%
Cold Trip Hot Trip Cold Trip Hot Trip Cold Trip Hot Trip
FLA% Time Time FLA% Time Time FLA% Time Time
105 6320 5995 155 160 50 205 66 14
110 1794 1500 160 142 42 210 62 12
115 934 667 165 128 36 215 58 11
120 619 375 170 115 31 220 54 10
125 456 240 175 105 27 225 51 10
130 357 167 180 96 23 230 48 9
135 291 122 185 88 21 235 46 8
140 244 94 190 82 19 240 44 8
145 209 74 195 76 17 245 41 7
150 180 60 200 70 15 250 39 7
Motor Overload
Protection PowerFlex 70 PowerFlex 70: Class 10 motor overload protection according to NEC article 430
and motor over-temperature protection according to NEC article
430.126 (A)(2). UL 508C File E59272.
PowerFlex 700 Frames 0…6 Standard Control: PowerFlex 700 drives with standard control, identified by an N,
A, or B in position 15 of the catalog number, only provide Class
10 motor overload protection according to NEC article 430. They
do not provide speed sensitive overload protection, thermal
memory retention and motor over-temperature sensing
according to NEC article 430.126 (A) (2). If such protection is
needed in the end-use product, it must be provided by
additional means.
Frames 0…6 Vector Control: PowerFlex 700 drives with vector control, identified by a C or D in
position 15 of the catalog number, provide class 10 motor
overload protection according to NEC article 430 and motor
over-temperature protection according to NEC article 430.126
(A) (2). UL 508C File E59272.
Frames 7…10 Vector Control: Class 10 motor overload protection according to NEC article 430
and motor over-temperature protection according to NEC article
430.126 (A)(2). UL 508C File E59272.
Bypass Contactors
Notch Filter Vector FV The 700 Vector has a notch filter in the torque reference loop used
to eliminate mechanical resonance created by a gear train. [Notch Filter Freq]
sets the center frequency for the 2 pole notch filter, and [Notch Filter K] sets the
gain.
Figure 24 Notch Filter Frequency
Gain Notch Filter K
0 db
Due to the fact that most mechanical frequencies are described in Hertz, [Notch
Filter Freq] and [Notch Filter K] are in Hertz as well. The following is an
example of a notch filter.
A mechanical gear train consists of two masses (the motor and the load) and
spring (mechanical coupling between the two loads). See Figure 25.
Figure 25 Mechanical Gear Train
Bm BL
Kspring
Jm Jload
( Jm + Jload )
resonance = Kspring ---------------------------------
Jm × Jload
Figure 26 Resonance
Figure 27 shows the same mechanical gear train as Figure 26. [Notch Filter Freq]
is set to 10.
Figure 27 10 Hz Notch
This parameter displays the total output current of the drive. The current value
displayed here is the vector sum of both torque producing and flux producing
current components.
Cable Termination
Voltage doubling at motor terminals, known as reflected wave phenomenon,
standing wave or transmission line effect, can occur when using drives with long
motor cables.
Applications with non-inverter duty motors or any motor with exceptionally long
leads may require an output filter or cable terminator. A filter or terminator will
help limit reflection to the motor, to levels which are less than the motor
insulation rating.
Cable length restrictions for unterminated cables are discussed on page 61.
Remember that the voltage doubling phenomenon occurs at different lengths for
different drive ratings. If your installation requires longer motor cable lengths, a
reactor or cable terminator is recommended.
Bulletin 1321 Reactors can be used for drive input and output. These reactors are
specifically constructed to accommodate IGBT inverter applications with
switching frequencies up to 20 kHz. They have a UL approved dielectric strength
of 4000 volts, opposed to a normal rating of 2500 volts. The first two and last two
turns of each coil are triple insulated to guard against insulation breakdown
resulting from high dv/dt. When using motor line reactors, it is recommended
that the drive PWM frequency be set to its lowest value to minimize losses in the
reactors.
By using an output reactor the effective motor voltage will be lower because of the
voltage drop across the reactor - this may also mean a reduction of motor torque.
This parameter displays the actual output frequency of the drive. The output
frequency is created by a summation of commanded frequency and any active
speed regulator such as slip compensation, PI Loop, bus regulator. The actual
output may be different than the commanded frequency.
Output Power This parameter displays the output kW of the drive. The output power is a
calculated value and tends to be inaccurate at lower speeds. It is not
recommended for use as a process variable to control a process.
Overspeed Limit The Overspeed Limit is a user programmable value that allows operation at
maximum speed but also provides an “overspeed band” that will allow a speed
regulator such as encoder feedback or slip compensation to increase the output
frequency above maximum Speed in order to maintain maximum Motor Speed.
The actual output at maximum speed reference is the sum of the speed reference
plus “speed adder” components from functions such as slip compensation,
encoder feedback or process trim.
The Overspeed Limit is added to Maximum Speed and the sum of the two
(Speed Limit) limits is output. This sum (Speed Limit) is compared to Maximum
Frequency and an alarm is initiated which prevents operation if the Speed Limit
exceeds Maximum Frequency.
Figure 28 Typical V/Hz Curve for Full Custom (with Speed/Frequency Limits
Output Voltage
Control Mode Overspeed
Limit
Break
Voltage
Start
Boost
Run
Boost
0 Minimum Break Motor NP Hz Maximum Output Maximum
Speed Frequency Speed Frequency Frequency
Frequency Limit
Owners An owner is a parameter that contains one bit for each of the possible DPI or
SCANport adapters. The bits are set high (value of 1) when its adapter is
currently issuing that command, and set low when its adapter is not issuing that
command. Ownership falls into two categories;
Exclusive
Only one adapter at a time can issue the command and only one bit in the
parameter will be high.
For example, it is not allowable to have one Adapter command the drive to run in
the forward direction while another Adapter is issuing a command to make the
drive run in reverse. Direction Control, therefore, is exclusive ownership.
Non Exclusive
Multiple adapters can simultaneously issue the same command and multiple bits
may be high.
288 [Stop Owner] Read Only 276
Adapters presently issuing a valid stop command. thru
285
IP 5
4
IP 3
2
ita 1
l In
DP Port
DP o r t
DP Port
DP o r t
Dig Port
I
I
DP
x x x x x x x x x x 0 0 0 0 0 1 1 =Issuing Command
0 =No Command
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 x =Reserved
Bit #
289 [Start Owner] See [Stop Owner] 276
Adapters that are presently issuing a valid start command. thru
285
290 [Jog Owner] See [Stop Owner] 276
Adapters that are presently issuing a valid jog thru
command. 285
291 [Direction Owner] See [Stop Owner] 276
Adapter that currently has exclusive control of direction thru
changes. 285
COMMUNICATIONS
Masks & Owners
Example:
The operator presses the Stop button on the Local HIM to stop the drive. When
the operator attempts to restart the drive by pressing the HIM Start button, the
drive does not restart. The operator needs to determine why the drive will not
restart.
The operator first views the Start owner to be certain that the Start button on the
HIM is issuing a command.
Start Owner
0 0 0 0 0 0 0 0
Adapter # X 6 5 4 3 2 1 0
When the local Start button is pressed, the display indicates that the command is
coming from the HIM.
Start Owner
0 0 0 0 0 0 1 0
Adapter # X 6 5 4 3 2 1 0
The [Start Owner] indicates that there is not any maintained Start commands
causing the drive to run.
Stop Owner
0 0 0 0 0 0 0 1
Adapter # X 6 5 4 3 2 1 0
The operator then checks the Stop Owner. Notice that bit 0 is a value of “1,”
indicating that the Stop device wired to the Digital Input terminal block is open,
issuing a Stop command to the drive.
Until this device is reclosed, a permanent Start Inhibit condition exists and the
drive will not restart.
Parameter Access Level The PowerFlex 70 allows the user to restrict the number of parameters that are
viewable on the LCD or LED HIM. By limiting the parameter view to the most
commonly adjusted set, additional features that may make the drive seem more
complicated are hidden.
If you are trying to gain access to a particular parameter and the HIM skips over
it, you must change the parameter view from “Basic” to “Advanced.” This can be
accomplished in two different ways:
• Press “Alt” and then “View” from the HIM and change the view.
or
Power Loss Some processes or applications cannot tolerate drive output interruptions caused
by momentary power outages. When AC input line power is interrupted to the
drive, user programming can determine the drive’s reaction.
Terms
The following is a definition of terms. Some of these values are drive parameters
and some are not. The description of how these operate is explained below
Term Definition
Vbus The instantaneous DC bus voltage.
Vmem The average DC bus voltage. A measure of the “nominal” bus voltage determined by heavily filtering bus
voltage. Just after the pre-charge relay is closed during the initial power-up bus pre-charge, bus memory
is set equal to bus voltage. Thereafter it is updated by ramping at a very slow rate toward Vbus. The filtered
value ramps at 2.4V DC per minute (for a 480VAC drive). An increase in Vmem is blocked during
deceleration to prevent a false high value due to the bus being pumped up by regeneration. Any change to
Vmem is blocked during inertia ride through.
Vslew The rate of change of Vmem in volts per minute.
Vrecover The threshold for recovery from power loss.
Vtrigger The threshold to detect power loss.
PowerFlex 700
The level is adjustable. The default is the value in the PF700 Bus Level table. If “Pwr Loss Lvl” is selected as
an input function AND energized, Vtrigger is set to Vmem minus [Power Loss Level].
Vopen is normally 60V DC below Vtrigger (in a 480VAC drive). Both Vopen and Vtrigger are limited to a
minimum of Vmin. This is only a factor if [Power Loss Level] is set to a large value.
PowerFlex 70
This is a fixed value.
WARNING:
When using a value of Parameter #186 [Power Loss Level] larger than default, the customer must provide a
minimum line impedance to limit inrush current when the power line recovers. The input impedance
should be equal or greater than the equivalent of a 5% transformer with a VA rating 5 times the drive’s
input VA rating.
Vinertia The software regulation reference for Vbus during inertia ride through.
Vclose The threshold to close the pre-charge contactor.
Vopen The threshold to open the pre-charge contactor.
Vmin The minimum value of Vopen.
Voff The bus voltage below which the switching power supply falls out of regulation.
DC Bus Volts
DC Bus Volts
550 550
500 500
450 450
400 400
350 400 450 350 400 450
AC Input Volts AC Input Volts
DC Bus Volts
500 500
450 450
400 400
350 350
300 300
350 400 450 350 400 450
AC Input Volts AC Input Volts
500
450
400
350
300
350 400 450
AC Input Volts
3 wire mode – it is not faulted and if all Enable and Not Stop inputs are
energized.
2 wire mode – it is not faulted and if all Enable, Not Stop, and Run inputs are
energized.
Coast
This is the default mode of operation.
The drive determines a power loss has occurred if the bus voltage drops below
Vtrigger. If the drive is running the inverter output is disabled and the motor
coasts.
The power loss alarm in [Drive Alarm 1] is set and the power loss timer starts.
The Alarm bit in [Drive Status 1] is set if the Power Loss bit in [Alarm Config 1]
is set.
The drive faults with a F003 – Power Loss Fault if the power loss timer exceeds
[Power Loss Time] and the Power Loss bit in [Fault Config 1] is set.
The drive faults with a F004 – UnderVoltage fault if the bus voltage falls below
Vmin and the UnderVoltage bit in [Fault Config 1] is set.
The pre-charge relay opens if the bus voltage drops below Vopen and closes if the
bus voltage rises above Vclose
If the bus voltage rises above Vrecover for 20mS, the drive determines the power
loss is over. The power loss alarm is cleared.
If the drive is in a “run permit” state, the reconnect algorithm is run to match the
speed of the motor. The drive then accelerates at the programmed rate to the set
speed.
680V
Bus Voltage 620V
560V
500V
407V
305V
Motor Speed
Power Loss
Output Enable
Pre-Charge
Drive Fault
Decel
This mode of operation is useful if the mechanical load is high inertia and low
friction. By recapturing the mechanical energy, converting it to electrical energy
and returning it to the drive, the bus voltage is maintained. As long as there is
mechanical energy, the ride through time is extended and the motor remains fully
fluxed up. If AC input power is restored, the drive can ramp the motor to the
correct speed without the need for reconnecting.
The drive determines a power loss has occurred if the bus voltage drops below
Vtrigger.
If the drive is running, the inertia ride through function is activated.
The load is decelerated at just the correct rate so that the energy absorbed from
the mechanical load balances the losses and bus voltage is regulated to the value
Vinertia.
The Power Loss alarm in [Drive Alarm 1] is set and the power loss timer starts.
The Alarm bit in [Drive Status 1] is set if the Power Loss bit in [Alarm Config 1]
is set.
The drive faults with a F003 – Power Loss fault if the power loss timer exceeds
[Power Loss Time] and the Power Loss bit in [Fault Config 1] is set.
The drive faults with a F004 – UnderVoltage fault if the bus voltage falls below
Vmin and the UnderVoltage bit in [E238 Fault Config 1] is set.
The inverter output is disabled and the motor coasts if the output frequency
drops to zero or if the bus voltage drops below Vopen or if any of the “run permit”
inputs are de-energized.
The pre-charge relay opens if the bus voltage drops below Vopen.
The pre-charge relay closes if the bus voltage rises above Vclose
If the bus voltage rises above Vrecover for 20mS, the drive determines the power
loss is over. The power loss alarm is cleared.
If the drive is still in inertia ride through operation, the drive immediately
accelerates at the programmed rate to the set speed. If the drive is coasting and it
is in a “run permit” state, the reconnect algorithm is run to match the speed of the
motor. The drive then accelerates at the programmed rate to the set speed.
680V
Bus Voltage 620V
560V
500V
407V
305V
Motor Speed
Power Loss
Output Enable
Pre-Charge
Drive Fault
480V example shown, see Table 15 for further information.
Half Voltage
This mode provides the maximum power ride through. In a typical application
230VAC motors are used with a 480VAC drive, the input voltage can then drop
to half and the drive is still able to supply full power to the motor.
The drive determines a power loss has occurred if the bus voltage drops below
Vtrigger.
If the drive is running the inverter output is disabled and the motor coasts.
If the bus voltage drops below Vopen/Vmin (In this mode of operation Vopen
and Vmin are the same value) or if the Enable input is de-energized, the inverter
output is disabled and the motor coasts. If the Not Stop or Run inputs are
de-energized, the drive stops in the programmed manner.
The pre-charge relay opens if the bus voltage drops below Vopen/Vmin and closes
if the bus voltage rises above Vclose.
The power loss alarm in [Drive Alarm 1] is set and the power loss timer starts.
The Alarm bit in [Drive Status 1] is set if the Power Loss bit in [Alarm Config 1]
is set.
The drive faults with a F003 – Power Loss fault if the power loss timer exceeds
[Power Loss Time] and the Power Loss bit in [Fault Config 1] is set.
The drive faults with a F004 – UnderVoltage fault if the bus voltage falls below
Vmin and the UnderVoltage bit in [Fault Config 1] is set.
If the bus voltage rises above Vrecover for 20mS, the drive determines the power
loss is over. The power loss alarm is cleared.
If the drive is coasting and if it is in a “run permit” state, the reconnect algorithm
is run to match the speed of the motor. The drive then accelerates at the
programmed rate to the set speed.
680V
Bus Voltage 620V
560V
365V
305V
Motor Speed
Power Loss
Output Enable
Pre-Charge
Drive Fault
The drive determines a power loss has occurred if the “pulse” input is
de-energized OR the bus voltage drops below Vopen. If the drive is running, the
inverter output is disabled.
The Power Loss alarm in [Drive Alarm 1] is set and the power loss timer starts.
The Alarm bit in [Drive Status 1] is set if the Power Loss bit in [Alarm Config 1]
is set.
The drive faults with a F003 – Power Loss fault if the power loss timer exceeds
[Power Loss Time] and the Power Loss bit in [Fault Config 1] is set.
The drive faults with a F004 – UnderVoltage fault if the bus voltage falls below
Vmin and the UnderVoltage bit in [Fault Config 1] is set.
The pre-charge relay opens if the bus voltage drops below Vopen and closes if the
bus voltage rises above Vclose.
If the “pulse” input is re energized and the pre-charge relay is closed, the drive
determines the power loss is over. The power loss alarm is cleared.
If the drive is in a “run permit” state, the reconnect algorithm is run to match the
speed of the motor. The drive then accelerates at the programmed rate to the set
speed.
Preset Frequency There are 7 Preset Frequency parameters that are used to store a discrete
frequency value. This value can be used for a speed reference or PI Reference.
When used as a speed reference, they are accessed via manipulation of the digital
inputs or the DPI reference command. Preset frequencies have a range of plus/
minus [Maximum Speed].
The internal PI function provides closed loop process control with proportional
and integral control action. The function is designed to be used in applications
that require simple control of a process without external control devices. The PI
function allows the microprocessor to follow a single process control loop.
The PI function reads a process variable input to the drive and compares it to a
desired setpoint stored in the drive. The algorithm will then adjust the output of
the PI regulator, changing drive output frequency to try and make the process
variable equal the setpoint.
Proportional control (P) adjusts output based on size of the error (larger error =
proportionally larger correction). If the error is doubled, then the output of the
proportional control is doubled and, conversely, if the error is cut in half then the
output of the proportional output will be cut in half. With proportional control
there is always an error, so the feedback and the reference are never equal.
Integral control (I) adjusts the output based on the duration of the error. (The
longer the error is present, the harder it tries to correct). The integral control by
itself is a ramp output correction. This type of control gives a smoothing effect to
the output and will continue to integrate until zero error is achieved. By itself,
integral control is slower than many applications require and therefore is
combined with proportional control (PI).
Derivative Control (D) adjusts the output based on the rate of change of the error
and, by itself, tends to be unstable. The faster that the error is changing, the larger
change to the output. Derivative control is generally not required and, when it is
used, is almost always combined with proportional and integral control (PID).
There are two ways the PI Controller can be configured to modify the
commanded speed.
• Process Trim - The PI Output can be added to the master speed reference
The selection between these two modes of operation is done in the [PI
Configuration] parameter.
Process Trim
Process Trim takes the output of PI regulator and sums it with a master speed
reference to control the process. In the following example, the master speed
reference sets the wind/unwind speed and the dancer pot signal is used as a PI
Feedback to control the tension in the system. An equilibrium point is
programmed as PI Reference, and as the tension increases or decreases during
winding, the master speed is trimmed to compensate and maintain tension near
the equilibrium point.
0 Volts
10 Volts
When the PI is disabled the commanded speed is the ramped speed reference.
Slip
+ Comp
Slip Adder
+ Open
Linear Ramp Loop
Spd Ref & S-Curve Spd Cmd
Process
+ PI
+
PI Ref
Process PI
Controller
PI Fbk PI Disabled Speed Control
When the PI is enabled, the output of the PI Controller is added to the ramped
speed reference.
Slip
+ Comp
Slip Adder
+ Open
Linear Ramp Loop
Spd Ref & S-Curve Spd Cmd
Process
+ PI
+
PI Ref
Process PI
Controller
PI Fbk PI Enabled Speed Control
Exclusive Control
Process Control takes the output of PI regulator as the speed command. No
master speed reference exists and the PI Output directly controls the drive
output.
Pump Pressure
Transducer
Motor
However, when additional valves in the system are opened and the pressure in the
system drops, the PI error will alter its output frequency to bring the process back
into control.
When the PI is disabled the commanded speed is the ramped speed reference.
Slip
+ Comp
Slip Adder
+ Open
Linear Ramp Loop
Spd Ref & S-Curve Spd Cmd
Process
PI
PI Ref
Process PI
Controller
PI Fbk PI Disabled Speed Control
When the PI is enabled, the speed reference is disconnected and PI Output has
exclusive control of the commanded speed, passing through the linear ramp and
s-curve.
Slip
+ Comp
Slip Adder
+ Open
Linear Ramp Loop
Spd Ref & S-Curve Spd Cmd
Process
PI
PI Ref
Process PI
Controller
PI Fbk PI Enabled Speed Control
Configuration
To operate the drive in PI Regulator Mode for the Standard Control option,
change the mode by selecting “Process PI” through the [Speed Mode] parameter.
Three parameters are used to configure, control, and indicate the status of the
logic associated with the Process PI controller; [PI Configuration], [PI Control],
and [PI Status]. Together these three parameters define the operation of the PI
logic.
1. [PI Configuration] is a set of bits that select various modes of operation. The
value of this parameter can only be changed while the drive is stopped.
• Exclusive Mode - see page 137.
• Invert Error - This feature changes the “sign” of the error, creating a
decrease in output for increasing error and an increase in output for
decreasing error. An example of this might be an HVAC system with
thermostat control. In Summer, a rising thermostat reading commands an
increase in drive output because cold air is being blown. In Winter, a falling
thermostat commands an increase in drive output because warm air is
being blown.
The PI has the option to change the sign of PI Error. This is used when an
increase in feedback should cause an increase in output.
PI_Config
.Invert
+
PI Ref Sel PI Error
PI_Config –
.Sqrt -
PI Fdbk Sel PI Fbk
Spd Cmd
By default, Pre-load Command is off and the PI Load Value is zero, causing
a zero to be loaded into the integrator when the PI is disabled. As below
shown on the left, when the PI is enabled the PI output will start from zero
and regulate to the required level. When PI is enabled with PI Load Value
is set to a non-zero value the output begins with a step as shown below on
the right. This may result in the PI reaching steady state sooner, however if
the step is too large the drive may go into current limit which will extend
the acceleration.
PI Enabled
PI Pre-load Value
PI Output
Spd Cmd
PI Pre-load Value = 0 PI Pre-load Value > 0
Pre-load command may be used when the PI has exclusive control of the
commanded speed. With the integrator preset to the commanded speed
there is no disturbance in commanded speed when PI is enabled. After PI
is enabled the PI output is regulated to the required level.
PI Enabled
Spd Cmd
• Zero Clamp - This feature limits the possible drive action to one direction
only. Output from the drive will be from zero to maximum frequency
forward or zero to maximum frequency reverse. This removes the chance
of doing a “plugging” type operation as an attempt to bring the error to
zero.
The PI has the option to limit operation so that the output frequency will
always have the same sign as the master speed reference. The zero clamp
option is selected in the PI Configuration parameter. Zero clamp is
disabled when PI has exclusive control of speed command.
For example, if master speed reference is +10 Hz and the output of the PI
results in a speed adder of –15 Hz, zero clamp would limit the output
frequency to not become less than zero. Likewise, if master speed reference
is –10 Hz and the output of the PI results in a speed adder of +15 Hz, zero
clamp would limit the output frequency to not become greater than zero.
≥0 +32K
PI_Config 0
.ZeroClamp 0
Linear +
Spd Ref Ramp Spd Ramp Spd Cmd
& S-Curve + -32K
+32K
PI Ref PI Output
Process PI -32K
Controller
PI Fbk
• Feedback Square Root - This feature uses the square root of the feedback
signal as the PI feedback. This is useful in processes that control pressure,
since centrifugal fans and pumps vary pressure with the square of speed.
The PI has the option to take the square root of the selected feedback
signal. This is used to linearize the feedback when the transducer produces
the process variable squared. The result of the square root is normalized
back to full scale to provide a consistent range of operation. The option to
take the square root is selected in the PI Configuration parameter.
100.0
Normalized SQRT(Feedback)
75.0
50.0
25.0
0.0
-25.0
-50.0
-75.0
-100.0
-100.0 -75.0 -50.0 -25.0 0.0 25.0 50.0 75.0 100.0
Normalized Feedback
• Stop Mode (PowerFlex 700 Only). When Stop Mode is set to “1” and a
Stop command is issued to the drive, the PI loop will continue to operate
during the decel ramp until the PI output becomes more than the master
reference. When set to “0,” the drive will disable PI and perform a normal
stop. This bit is active in Trim mode only.
• Vector FV Torque Trim. When Torque Trim is set to “1” the output of
the process PI loop will be added to Torque Reference A and B, instead of
being added to the speed reference.
2. [PI Control] is a set of bits to dynamically enable and disable the operation of
the process PI controller. When this parameter is interactively written to from
a network it must be done through a data link so the values are not written to
EEprom.
The drive must be in run before the PI Enabled status can turn on. The PI
will remain disabled when the drive is jogged. The PI is disabled when the
drive begins a ramp to stop, except in the PowerFlex 700 when it is in Trim
mode and the Stop mode bit in [PI Configuration] is on.
When a digital input is configured as “PI Enable,” the PI Enable bit of [PI
Control] must be turned on for the PI loop to become enabled.
If a digital input is not configured as “PI Enable” and the PI Enable bit in
[PI Control] is turned on, then the PI loop may become enabled. If the PI
Enable bit of [PI Control] is left continuously, then the PI may become
enabled as soon as the drive goes into run. If analog input signal loss is
detected, the PI loop is disabled.
DigInCfg DigIn PI_Control PI_Status
Running Stopping .PI_Enable .PI_Enable .PI_Enable Signal Loss .Enabled
DigInCfg PI_Control
.PI_Enable .PI_Enable
• PI Hold - The Process PI Controller has the option to hold the integrator
at the current value so if some part of the process is in limit the integrator
will maintain the present value to avoid windup in the integrator.
The logic to hold the integrator at the current value is shown in the
following ladder diagram. There are three conditions under which hold
will turn on.
DigInCfg PI_Control
.PI_Hold .PI_Hold
Current Lmt
or Volt Lmt
• PI Reset – This feature holds the output of the integral function at zero.
The term “anti windup” is often applied to similar features. It may be used
for integrator preloading during transfer and can be used to hold the
integrator at zero during “manual mode”. Take the example of a process
whose feedback signal is below the reference point, creating error. The
drive will increase its output frequency in an attempt to bring the process
into control. If, however, the increase in drive output does not zero the
error, additional increases in output will be commanded. When the drive
reaches programmed Maximum Frequency, it is possible that a significant
amount of integral value has been “built up” (windup). This may cause
NOTE: In the PowerFlex 70, once the drive has reached the
programmable positive and negative PI limits, the integrator stops
integrating and no further “windup” is possible.
3. [PI Status] parameter is a set of bits that indicate the status of the process PI
controller
• Hold – A signal has been issued and the integrator is being held at its
current value.
• Reset – A signal has been issued and the integrator is being held at zero.
• In Limit – The loop output is being clamped at the value set in [PI Upper/
Lower Limit].
The value used for reference is displayed in PI Reference as a read only parameter.
The value used for feedback is displayed in PI Feedback as a read only parameter.
These displays are active independent of PI Enabled. Full scale is displayed as
±100.00.
The PI feedback can be scaled by using [PI Feedback Hi] and [PI Feedback Lo].
[PI Feedback Hi] determines the high value, in percent, for the PI feedback. [PI
Feedback Lo] determines the low value, in percent, for the PI feedback.
Configuration Example:
The PI reference meter and PI feedback meter should be displayed as positive and
negative values. Feedback from our dancer comes into Analog Input 2 as a 0-10V
DC signal.
PI Feedback Scaling
[Torque Ref A Sel] = “Analog In 1”
[Analog In 2 Hi] [PI Feedback Hi]
10 V 100 %
[Analog In 1 Lo] [PI Feedback Lo]
0V -100 %
PI Setpoint
This parameter can be used as an internal value for the setpoint or reference for
the process. If [PI Reference Sel] points to this Parameter, the value entered here
will become the equilibrium point for the process.
PI Output
The PI Error is then sent to the Proportional and Integral functions, which are
summed together.
PI Gains
The PI Proportional Gain and the PI Integral Gain parameters determine the
response of the PI.
The PI Proportional Gain is unitless and defaults to 1.00 for unit gain. With PI
Proportional Gain set to 1.00 and PI Error at 1.00% the PI output will be 1.00%
of maximum frequency.
The PI Integral Gain is entered in seconds. If the PI Integral Gain is set to 2.0
seconds and PI Error is 100.00% the PI output will integrate from 0 to 100.00%
in 2.0 seconds.
If the application is Process Control, typically these limits would be set to the
maximum allowable frequency setting. This allows the PI regulator to control
over the entire required speed range.
If the application is Process Trim, large trim corrections may not be desirable and
the limits would be programmed for smaller values.
PI PosLmt
PI NegLmt
PI Kp
+
PI Error * PI Output
+
PI_Status
.Hold
+
*
+
In Limit
PI Ki
-1
Z
Output Scaling
The output value produced by the PI is displayed as ±100.00. Internally this is
represented by ±32767 which corresponds to ±maximum frequency.
The output value from the Process PI loop, when in torque trim mode, is
displayed as +/–100% which corresponds to +/–100% of rated motor torque.
PI Neg Limit 0
0
PI Kp
-32K
≥0
PI ExcessErr ≥ PI XS Error
abs Zclamped
Linear + +
*(PI Ref Sel) PI Ref PI Cmd PI Error * PI Output
Ramp
- +
PI_Status +
- *
.Enabled +
In Limit
PI_Config
.RampCmd -1
z
0
PI_Config
.Sqrt
PI_Config
.Invert
PI Ki
PI_Status
.Hold
Preload Value
PI_Config PI_Config
.PreloadCmd .Exclusive
PI_Status Current Limit
.Enabled or Volt Limit
PI Configuration PI Configuration
PI Status 124 0 124 4
134 0 Linear +32K
PI Configuration Ramp & Speed Ramp Speed Cmd
Speed Ref
124 8 S-Curve –32K
+32K
0
Zero
Enable Exclusive Clamp 0
–32K
Torque Ref B Mult ≥0
434
Torque
Ref B Sel 431 Scale
+800
Torque Cmd
–800
Torque Torque 1 +800
Trim Ref A Sel 427 Scale
0
430 Zero
Clamp 0
Torque Ref A Div
–800
≥0
Derivative Term
The Derivative term has been added to the Process PI. This adds to the flexibility
of the Process control.
459 Vector v3 [PI Deriv Time] Default: 0.00 Secs
Refer to formula below: Min/Max: 0.00/100.00 Secs
dPI Error (%) Units: 0.01 Secs
PIOut = KD (Sec) x
dt (Sec)
For example, winders using torque control rely on PD control not PI control.
Also, [PI BW Filter] is useful in filtering out unwanted signal response in the PID
loop. The filter is a Radians/Second low pass filter.
Percent of Reference
124 [PI Configuration] 124
Sets configuration of the PI regulator. thru
138
Ex rt Er de
Ra Cla qrt
Fe Mo Up
Sto -Win *
ti rim
Pre p Re p
cl ror
o
ed de
rqu **
ro S
de
m m
Inv ad M
p d
lo f
An e T
Ze bak
To Ref
Mo
of
e
%
x x x x x x 0 0 0 0 0 0 0 0 0 0 1 =Enabled
0 =Disabled
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 x =Reserved
Bit # * Vector Control Option Only
Factory Default Bit Values ** Vector firmware 3.001 & later
When using Process PID control the output can be selected as percent of the
Speed Reference. This works in Speed trim mode only, not in Torque Trim or
Exclusive Mode.
Example
Trim % of Reference
The Trim function of the drive can be selected as % of Reference or % of
Maximum Frequency.
*
m B
fA
Tri or %
Tri Ref
Re
m
d
Ad
x x x x x x x x x x x x x 0 0 0 1 =Trimmed/%
0 =Not Trimmed/Add
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 x =Reserved
Bit # * Vector firmware 3.001 & later.
Factory Default Bit Values
For example, % selected, Max Frequency = 130, Speed Reference = 22 Hz, Trim
Reference = 20%. 4.4 Hz will be added to the Speed Reference.
% not selected, Max Frequency = 130, Speed Reference = 22 Hz, Trim Reference
= 20%. 26 Hz will be added to the Speed Reference.
The pulses from a Pulse Width Modulation (PWM) inverter using IGBTs are
very short in duration (50 nanoseconds to 1 millisecond). These short pulse
times combined with the fast rise times (50 to 400 nanoseconds) of the IGBT,
will result in excessive over-voltage transients at the motor.
Voltages in excess of twice the DC bus voltage (650V DC nominal at 480V
input) will occur at the motor and can cause motor winding failure.
The patented reflected wave correction software in the PowerFlex 70/700 will
reduce these over-voltage transients from a VFD to the motor. The correction
software modifies the PWM modulator to prevent PWM pulses less than a
minimum time from being applied to the motor. The minimum time between
PWM pulses is 10 microseconds. The modifications to the PWM modulator
limit the over-voltage transient to 2.25 per unit volts line-to-line peak at 600 feet
of cable.
400 V Line = 540V DC bus x 2.25 = 1215V
480 V Line = 650V DC bus x 2.25 = 1463V
600 V Line = 810V DC bus x 2.25 = 1823 V
500 Inverter
V/div
<Tα
0
1670 Vpk
500 Motor
V/div
0 5 10 15 20 25 30 35 40 45 50
Time (µsec)
The above figure shows the inverter line-to-line output voltage (top trace) and
the motor line-to-line voltage (bottom trace) for a 10 HP, 460V AC inverter, and
an unloaded 10 HP AC induction motor at 60 Hz operation. 500 ft. of #12
AWG cable connects the drive to the motor.
The plot below shows the per unit motor overvoltage as a function of cable
length. This is for no correction versus the modulation correction code for varied
lengths of #12 AWG cable to 600 feet for 4 and 8 kHz carrier frequencies. The
output line-to-line voltage was measured at the motor terminals in 100 feet
increments.
No Correction vs Correction Method at 4 kHz and 8 kHz Carrier
Frequencies - Vbus = 650, fe = 60 Hz
2.6
No Correction 4 kHz Carrier
2.5 Corrected 4 kHz Carrier
2.4 No Correction 8 kHz Carrier
Corrected 8 kHz Carrier
per Unit Vout/Vbus
2.3
2.2
2.1
2
1.9
1.8
1.7
1.6
0 100 200 300 400 500 600
Cable Length (Feet)
Without the correction, the overvoltage increases to unsafe levels with increasing
cable length for both carrier frequencies.
The patented modulation correction code reduces the overvoltage for both
carrier frequencies and maintains a relatively flat overvoltage level for increasing
cable lengths beyond 300 feet.
Regen Power Limit Vector FV The [Regen Power Lim] is programmed as a percentage of the
rated power. The mechanical energy that is transformed into electrical power
during a deceleration or overhauling load condition is clamped at this level.
Without the proper limit, a bus overvoltage may occur.
When using the bus regulator [Regen Power Lim] can be left at factory default, –
50%. When using dynamic braking or a regenerative supply, [Regen Power Lim]
can be set to the most negative limit possible (–800%). When the user has
dynamic braking or regenerative supply, but wishes to limit the power to the
dynamic brake or regenerative supply, [Regen Power Lim] can be set to a level
specified by the user.
Reset Meters The Elapsed kW Hour meter and/or Elapsed Time meter parameters are reset
when parameter 200 is set to a value not equal to zero. After the reset has
occurred, this parameter automatically returns to a value of zero.
200 [Reset Meters] Default: 0 “Ready”
Resets selected meters to zero. Options: 0 “Ready”
1 “MWh”
2 “Elapsed Time”
0 = Ready
1 = Reset kW Hour Meter
2 = Reset Elapsed Time Meter
RFI Filter Grounding Refer to “Wiring and Grounding Guidelines for PWM AC Drives,” publication
DRIVES-IN001.
S Curve The S Curve function of the PowerFlex family of drives allows control of the
“jerk” component of acceleration and deceleration through user adjustment of
the S Curve parameter. Jerk is the rate of change of acceleration and controls the
transition from steady state speed to acceleration or deceleration and vice versa.
By adjusting the percentage of S Curve applied to the normal accel/decel ramps,
the ramp takes the shape of an “S”. This allows a smoother transition that
produces less mechanical stress and smoother control for light loads.
80.0
60.0
40.0
20.0
Hz
0.0
-20.0
-40.0
-60.0
-80.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0
Seconds
S-Curve Selection
60.0
50.0
40.0
Hz
30.0
20.0
10.0
0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
Seconds
The acceleration and deceleration times are independent but the same S-curve
percentage is applied to both of them. With S-curve set to 50%, acceleration time
is extended by 0.5 seconds (1.0 * 50%), and deceleration time is extended by 1.0
seconds (2.0 * 50%).
70.0
60.0
50.0
40.0
Hz
30.0
20.0
10.0
0.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0
Seconds
Note that S-curve time is defined for accelerating from 0 to maximum speed.
With maximum speed = 60 Hz, Ta = 2.0 sec, and S-curve = 25%, acceleration
time is extended by 0.5 seconds (2.0 * 25%). When accelerating to only 30 Hz the
acceleration time is still extended by the same amount of time.
70.0
60.0
50.0
40.0
Hz
30.0
20.0
10.0
0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0
Seconds
When the commanded frequency passes through zero the frequency will S-curve
to zero and then S-curve to the commanded frequency.
80.0
60.0
40.0
20.0
0.0
Hz
-20.0
-40.0
-60.0
-80.0
0.0 1.0 2.0 3.0 4.0 5.0
Seconds
The following graph shows an acceleration time of 1.0 second. After 0.75
seconds, the acceleration time is changed to 6.0 seconds. When the acceleration
rate is changed, the commanded rate is reduced to match the requested rate based
on the initial S-curve calculation. After reaching the new acceleration rate, the
S-curve is then changed to be a function of the new acceleration rate.
70.0
60.0
50.0
40.0
Hz
30.0
20.0
10.0
0.0
0.0 1.0 2.0 3.0 4.0 5.0
Seconds
Scale Blocks See also Analog Scaling on page 22 and page 32.
Vector Scale blocks are used to scale a parameter value. [Scalex In Value] is
linked to the parameter that you wish to scale. [Scalex In Hi] determines the high
value for the input to the scale block. [Scalex Out Hi] determines the
corresponding high value for the output of the scale block. [Scalex In Lo]
determines the low value for the input to the scale block. [Scalex Out Lo]
determines the corresponding low value for the output of the scale block. [Scalex
Out Value] is the resulting output of the scale block.
There are (3) ways to use the output of the scale block:
Note that when the Analog Outputs are set to use the scale blocks, the [Scale x
Out Hi] and [Scale x Out Lo] parameters are not active. Instead, [Analog
Outx Hi] and [Analog Outx Lo] determine the scaling for the output of the
scale block. See Example Configuration #2.
3. [PI Reference Sel] and [PI Feedback Sel] can also use the output of the scale
block by setting them to:
– 25, “Scale Block1 Out”
– 26, “Scale Block2 Out”
Note that when [PI Reference Sel] and [PI Feedback Sel] are set to use the
scale blocks, the [Scale x Out Hi] and [Scale x Out Lo] parameters are not
active. Instead, [PI Reference Hi] and [PI Reference Lo], or [PI Feedback Hi]
and [PI Feedback Lo], determine the scaling for the output of the scale block.
See Example Configuration #3.
Example Configuration #1
Use the scale blocks to add a speed trim as a percentage of the speed reference
instead of as a percent of full speed. Analog In 2 will be used to provide a 0-10V
DC trim signal. For example, when the commanded speed is 800 RPM, the
maximum trim with 10V DC at Analog In 2 will be 80 RPM. If the commanded
speed is 1800 RPM the maximum trim will be 180 RPM.
Analog In2 Val (Volts)
10
PM
Scale1 In Value =
M
M
RP
RP
RPM
R
8 00
12 80 0
00
400
= =1
=8
pd pd
pd =
dS dS
pd
6 Cm
dS
Cm
dS
Cm
Cm
4
2
0
0 20 40 60 80 100 120 140 180
Preset Speed 1 (RPM)
Parameter Settings
Parameter Value Description
[Trim In Select] 11, Preset 1 Preset 1 becomes the trim speed
[Scale1 In Hi] 10.0 V Hi value of Analog In 2
[Scale1 In Lo] 0V Lo value of Analog In 2
[Scale1 Out Lo] 0 RPM Lo value of desired Trim
[Scale2 In Hi] 1800 RPM Hi value of Commanded Speed (Max Speed)
[Scale2 In Lo] 0 RPM Lo value of Commanded Speed
[Scale2 Out Hi] 180 RPM 10% of Max Speed
[Scale2 Out Lo] 0 RPM Corresponds to lo value of Commanded Speed
Parameter Links
Destination Parameter Source Parameter Description
[Scale1 In Value] [Analog In2 Value] We are scaling Analog In 2 for our trim
[Scale2 In Value] [Commanded Speed] Use Commanded Speed as Input to Scale Block 2
[Scale1 Out Hi] [Scale2 Out Value] Use the output of Scale Block 2 to set the upper limit of Scale
Block 1 output
[Preset Speed 1] [Scale 1 Out Value] Use the scaled analog input as the trim reference into Preset
Speed 1
Example Configuration #2
Setup a scale block to send parameter 415, [Encoder Speed] to Analog Output 1
as a 0-10V signal.
1800
Encoder Speed (RPM)
1500
Scale1 In Value =
1200
900
600
300
0
0 1 2 3 4 5 6 7 8 9 10
Analog Out1 Value (Volts)
Parameter Settings
Parameter Value Description
[Analog Out1 Sel] Scale Block1 Out Scale Block1 Output goes to Analog Out1
[Analog Out1 Hi] 10 V Hi value of Analog Output 1 corresponding to Hi value of encoder speed
[Analog Out1 Lo] 0V Lo value of Analog Output 1 corresponding to Lo value of encoder speed
[Scale1 In Hi] 1800 RPM Hi value of the encoder speed
[Scale1 In Lo] 0 RPM Lo value of the encoder speed
Parameter Links
Destination Parameter Source Parameter Description
[Scale1 In Value] [Encoder Speed] We are scaling Encoder Speed
Example Configuration #3
In this configuration Analog In 2 is a –10V to +10V signal which corresponds to
–800% to +800% motor torque from another drive. We want to use the –200%
to +200% range (–2.5V to +2.5V) of that motor torque and correspond it to –
100% to +100% of the PI Reference.
Analog In2 Value (Volts)
2.5
Scale1 In Value =
1.5
0.5
-0.5
-1.5
-2.5
-100 -80 -60 -40 -20 0 20 40 60 80 100
PI Reference
Parameter Settings
Parameter Value Description
[Scale 1 In Hi] 2.5 V 2.5 V = 200% torque from other drive
[Scale 1 In Lo] –2.5V –2.5 V = –200% torque from other drive
[PI Reference Sel] 25, Scale Block1 Out The PI Reference becomes the output of the scale block
[PI Reference Hi] 100 % 100% PI Reference corresponds to 200% torque from other drive
[PI Reference Lo] –100 % –100% PI Reference corresponds to –200% torque from other drive
Parameter Links
Destination Parameter Source Parameter Description
[Scale1 In Value] [Analog In2 Value] We are scaling Analog In 2 value
Shear Pin Fault This feature allows the user to select programming that will fault the drive if the
drive output current exceeds the programmed current limit. As a default,
exceeding the set current limit is not a fault condition. However, if the user wants
to stop the process in the event of excess current, the Shear Pin feature can be
activated. By programming the drive current limit value and enabling the
electronic shear pin, current to the motor is limited, and if excess current is
demanded by the motor, the drive will fault.
Configuration
The Shear Pin Fault is activated by setting Bit 4 of [Fault Config 1] to “1.”
238 [Fault Config 1]
Enables/disables annunciation of the listed faults.
oA s*
*
De r Th ss *
cc
rPN os
Au l Inh *
r L ge
ce erm
erL
Mo r Pi s
Mo ase *
Sh st Tr t
s
ea eL
to Lo
tR ib
we lta
ea ie
os
Ph s
tor n
In Los
Sh Phas
Ov
Po rVo
de
ad
t
Ou
Un
Lo
x x x 0 0 x 0 0 0 1 0 0 1 x 1 0 1 =Enabled
0 =Disabled
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 x =Reserved
Bit # * Vector firmware 3.001 & later
Factory Default Bit Values
The programmable current limit [Current Lmt Sel] should also set to identify
the source of the current limit value. If “Cur Lim Val” is selected, then [Current
Lmt Val] should be set to the required limit value.
DYNAMIC CONTROL
A separate fault (Shear Pin Fault, F63) dedicated to the Shear Pin feature, will be
generated if the function is activated.
Application Example
In some applications, mechanical hardware can be damaged if the motor is
allowed to develop excess torque. If a mechanical jam should occur, shutting
down the system may be the only way to prevent damage. For example, a chain
conveyor may be able to “hook” itself, causing a jam on the conveyor. Excess
torque from the motor could cause chain or other mechanical damage.
By programming the Shear Pin feature, the user can cause the drive to fault,
stopping the excess torque before mechanical damage occurs.
Drive Output
Frequency (A) (A)
Skip + 1/2 Band 35 Hz
Skip Frequency 30 Hz
Skip – 1/2 Band 25 Hz
(B) (B)
Time
Some machinery may have a resonant operating frequency that must be avoided
to minimize the risk of equipment damage. To assure that the motor cannot
continuously operate at one or more of the points, skip frequencies are used.
Parameters 084-086, ([Skip Frequency 1-3]) are available to set the frequencies to
be avoided.
The value programmed into the skip frequency parameters sets the center point
for an entire “skip band” of frequencies. The width of the band (range of
frequency around the center point) is determined by parameter 87, [Skip Freq
Band]. The range is split, half above and half below the skip frequency parameter.
If the commanded frequency of the drive is greater than or equal to the skip
(center) frequency and less than or equal to the high value of the band (skip plus
1/2 band), the drive will set the output frequency to the high value of the band.
See (A) in Figure 31.
If the commanded frequency is less than the skip (center) frequency and greater
than or equal to the low value of the band (skip minus 1/2 band), the drive will
set the output frequency to the low value of the band. See (C) in Figure 31.
0 Hz
Adjusted
Skip Frequency 1 Skip Band
Skip Frequency 2 w/Recalculated
Skip Frequency
0 Hz
0 Hz
Inactive
Skip Frequency 1
Skip Band
60 Hz. Max.
Frequency
0 Hz
Acceleration and deceleration are not affected by the skip frequencies. Normal
accel/decel will proceed through the band once the commanded frequency is
greater than the skip frequency. See (A) & (B) in Figure 31. This function affects
only continuous operation within the band.
Requirements
In addition to enabling the sleep function with [Sleep-Wake Mode], at least one
of the following assignments must be made to a digital input: Enable, Stop-CF,
Run, Run Fwd or Run Rev, and the input must be closed. All normal Start
Permissives must also be satisfied (Not Stop, Enable, Not Fault, Not Alarm, etc.).
Conditions to Start/Restart
ATTENTION: Enabling the Sleep-Wake function can cause
! unexpected machine operation during the Wake mode. Equipment
damage and/or personal injury can result if this parameter is used in an
inappropriate application. Do Not use this function without
considering the table below and applicable local, national &
international codes, standards, regulations or industry guidelines.
(1) When power is cycled, if all conditions are present after power is restored, restart will occur.
(2) If all conditions are present when [Sleep-Wake Mode] is “enabled,” the drive will start.
(3) The active speed reference is determined as explained in the User Manual. The Sleep/Wake function and the
speed reference may be assigned to the same input.
(4) Command must be issued from HIM, TB or network.
(5) Run Command must be cycled.
(6) Signal does not need to be greater than wake level.
Timers
Timers will determine the length of time required for Sleep/Wake levels to
produce true functions. These timers will start counting when the Sleep/Wake
levels are satisfied and will count in the opposite direction whenever the
respective level is dissatisfied. If the timer counts all the way to the user specified
time, it creates an edge to toggle the Sleep/Wake function to the respective
condition (sleep or wake). On power up, timers are initialized to the state that
does not permit a start condition. When the analog signal satisfies the level
requirement, the timers start counting.
Interactive functions
Separate start commands are also honored (including a digital input “start”), but
only when the sleep timer is not satisfied. Once the sleep timer times out, the
sleep function acts as a continuous stop. There are two exceptions to this, which
will ignore the Sleep/Wake function:
1. When a device is commanding “local” control
2. When a jog command is being issued.
When a device is commanding “local” control, the port that is commanding it has
exclusive start control (in addition to ref select), essentially overriding the Sleep/
Wake function, and allowing the drive to run in the presence of a sleep situation.
This holds true even for the case of Port 0, where a digital input start or run will
be able to override a sleep situation.
Sleep/Wake Levels
Normal operation will require that [Wake Level] be set greater than or equal to
[Sleep Level]. However, there are no limits that prevent the parameter settings
from crossing, but the drive will not start until such settings are corrected. These
levels are programmable while the drive is running. If [Sleep Level] is made
greater than [Wake Level] while the drive is running, the drive will continue to
run as long as the analog input remains at a level that doesn’t trigger the sleep
condition. Once the drive goes to sleep in this situation, it will not be allowed to
restart until the level settings are corrected (increase wake, or decrease sleep). If
however, the levels are corrected prior to the drive going to sleep, normal Sleep/
Wake operation will continue.
Sleep/Wake Sources
All defined analog inputs for a product shall be considered as valid Sleep/Wake
sources. The Sleep/Wake function is completely independent of any other
functions that are also using the assigned analog input. Thus, using the same
analog input for both speed reference and wake control is permitted. Also,
[Analog In x Hi] and [Analog In x Lo] parameters have no affect on the function.
However, the factory calibrated result will be used. In addition, the absolute value
of the calibrated result will be used, thus making the function useful for bipolar
direction applications. The analog in loss function is unaffected and therefore
operational with the Sleep/Wake function, but not tied to the sleep or wake
levels.
Drive
Run
Wake Up
Sleep-Wake
Function Go to Sleep
Start
Stop
Sleep Timer
Satisfied
Sleep Level
Satisfied
Wake Timer
Satisfied
Wake Level
Sleep Level
Example Conditions
Wake Time = 3 Seconds
Analog Signal Sleep Time = 3 Seconds
Speed Control, Mode, The purpose of speed regulation is to allow the drive to adjust certain operating
Regulation & Vector conditions, such as output frequency, to compensate for actual motor speed losses
in an attempt to maintain motor shaft speed within the specified regulation
Speed Feedback percentage.
The [Speed Mode] parameter selects the speed regulation method for the drive,
and can be set to one of 3 choices on the PowerFlex 70/700. The PowerFlex 700
Vector option has 5 choices. In addition, [Feedback Select] in the Vector option,
chooses the feedback used for the speed regulator.
Open Loop
As the load on an induction motor increases, the rotor speed or shaft speed of the
motor decreases, creating additional slip (and therefore torque) to drive the larger
load. This decrease in motor speed may have adverse effects on the process. If the
[Speed Mode] parameter is set to “Open Loop,” no speed control will be
exercised. Motor speed will be dependent on load changes and the drive will
make no attempt to correct for increasing or decreasing output frequency due to
load.
Slip Compensation
As the load on an induction motor increases, the rotor speed or shaft speed of the
motor decreases, creating additional slip (and therefore torque) to drive the larger
load. This decrease in motor speed may have adverse effects on the process. If
speed control is required to maintain proper process control, the slip
compensation feature of the PowerFlex drives can be enabled by the user to more
accurately regulate the speed of the motor without additional speed transducers.
When the slip compensation mode is selected, the drive calculates an amount to
increase the output frequency to maintain a consistent motor speed independent
of load. The amount of slip compensation to provide is selected in [Slip RPM @
FLA]. During drive commissioning this parameter is set to the RPM that the
motor will slip when operating with Full Load Amps. The user may adjust this
parameter to provide more or less slip.
Without slip compensation active, as the load increases from no load to 150% of
the motor rating, the rotor speed decreases approximately proportional to the
load.
With slip compensation, the correct amount of slip compensation is added to the
drive output frequency based on motor load. Thus, the rotor speed returns to the
original speed. Conversely, when the load is removed, the rotor speed increases
momentarily until the slip compensation decays to zero.
Motor nameplate data must be entered by the user in order for the drive to
correctly calculate the proper amount of slip compensation. The motor
nameplate reflects slip in the rated speed value at rated load. The user can enter
the Motor Nameplate RPM, Motor Nameplate Frequency, the Motor Nameplate
Current, Motor Nameplate Voltage, and Motor Nameplate HP/kW and during
commissioning the drive calculates the motor rated slip frequency and displays it
in [Slip RPM @ FLA]. The user can adjust the slip compensation for more
accurate speed regulation, by increasing or decreasing [Slip RPM @ FLA] value.
Internally, the drive converts the rated slip in RPM to rated slip in frequency. To
more accurately determine the rated slip frequency in hertz, an estimate of flux
current is necessary. This parameter is either a default value based on motor
nameplate data or the auto tune value. The drive scales the amount of slip
compensation to the motor rated current. The amount of slip frequency added to
the frequency command is then scaled by the sensed torque current (indirect
measurement of the load) and displayed.
Slip compensation also affects the dynamic speed accuracy (ability to maintain
speed during “shock” loading). The effect of slip compensation during transient
operation is illustrated in Figure 34. Initially, the motor is operating at some
speed and no load. At some time later, an impact load is applied to the motor and
the rotor speed decreases as a function of load and inertia. And finally, the impact
load is removed and the rotor speed increases momentarily until the slip
compensation is reduced based on the applied load.
When slip compensation is enabled the dynamic speed accuracy is dependent on
the filtering applied to the torque current. The filtering delays the speed response
of the motor/drive to the impact load and reduces the dynamic speed accuracy.
Reducing the amount of filtering applied to the torque current can increase the
dynamic speed accuracy of the system. However, minimizing the amount of
filtering can result in an unstable motor/drive. The user can adjust the Slip Comp
Gain parameter to decrease or increase the filtering applied to the torque current
and improve the system performance.
Figure 34 Rotor Speed Response Due to Impact Load and Slip Com Gain
Impact Load
Removed
Increasing Slip
Impact Load Comp Gain
Applied
Speed
Rotor Speed
Increasing Slip Reference
Comp Gain
0
0
Time
The diagram below shows a typical application for the Slip Compensation
feature. The PLC controls the frequency reference for all four of the drives. Drive
#1 and Drive #3 control the speed of the belt conveyor. Slip compensation will be
used to maintain the RPM independent of load changes caused by the cutter or
dough feed. By maintaining the required RPM, the baking time remains constant
and therefore the end product is consistent.
With the Slip Compensation feature, the process will only require a new speed
reference when the product is changed. The user will not have to tune the drive
due to a different load characteristic.
Dough Stress
Relief Cookie Line
CUTTERS OVEN
5/40
PowerFlex PowerFlex PowerFlex PowerFlex
Drive Drive Drive Drive
#1 #2 #3 #4
Vector Encoder
There is (1) encoder input on the I/O board of the PowerFlex 700VC. The
encoder input must be line driver type, quadrature (dual channel) or pulse (single
channel). The encoder input accepts 8 or 12V DC encoder signals. There is a
12V DC supply on the drive that can be used to supply power for the encoders.
An encoder offers the best performance for both speed and torque regulation
applications. Encoder feedback is required for applications with high bandwidth
response, tight speed regulation, torque regulation of (+/- 2%) or when the
motor is required to operate at less than 1/120th its’ base speed.
[Enc Position Fdbk] displays the raw encoder count. For single channel encoders,
this count will increase (per rev.) by the amount in [Encoder PPR]. For
quadrature encoders this count will increase by 4 times the amount defined in
[Encoder PPR].
Vector Encoderless/Deadband
Encoderless/Deadband is recommended when more than a 120:1 speed range of
operation is not required and the user will set the speed reference below 0.5Hz/
15 RPM. The deadband will help prevent cogging and unstable motor operation
below a reference of 0.5Hz/15RPM by clamping the speed and torque regulators
to zero.
Vector Simulator
The simulator mode allows the drive to be operated without a motor connected
and is meant for demo purposes only. If a motor is connected with this mode
selected very erratic and unpredictable operation will occur.
Speed Feedback Filter Vector [Fdbk Filter Select] determines the type of filter to use for the speed
feedback. The filter is used to filter out high frequency signals (noise) by
reducing the gain at high frequencies. The selections for the filter are:
Description To select this type of filter . . . Select this value . . .
No filter 0
Gain
0 db
Rad/Sec
A light 35/49 radian Gain 1
feedback filter
0 db
-6 db
35 49 Rad/Sec
A heavy 20/40 radian Gain 2
feedback filter
0 db
-12 db
20 40 Rad/Sec
Selection
Binary Logic
Some references can be selected by binary logic, through digital inputs to the
terminal block or bit manipulation of the Logic Command Word in a
communications adapter. These sources are used when the drive is in “Auto”
mode. The default reference is from the source selected in [Speed Ref A Sel],
parameter 90. This parameter can be set to any one of the 22 choices. If the
binary logic selection is zero, this will be the active speed reference.
Auto/Manual
Many applications require a “manual mode” where adjustments can be made and
setup can be done by taking local control of the drive speed. Typically, these
adjustments would be made via a “local” HIM mounted on the drive. When all
setup is complete, control of the drive frequency command is turned over to
automatic control from a remote source such as a PLC, analog input etc.
The source of the speed reference is switched to one of two “manual” sources
when the drive is put into manual mode:
1. Local HIM
If the selection is the HIM, then the digital or analog speed control on the HIM
provides the reference.
If the switch to manual mode was made via a digital input, (parameters 361-366
set to “18, Auto/Manual”) then the source for the reference is defined in [TB
Man Ref Sel], parameter 96. This can be either of the 2 analog inputs or the
digital MOP.
When the drive is returned to automatic mode, the speed reference returns to the
source selected by the binary logic. Also see Auto/Manual on page 36.
DPI
See the DPI on page 92 for a description of DPI. One of the DPI ports can be
selected as the source of the speed reference.
In the PowerFlex 70, 700, and 700VC the speed reference from DPI is scaled so
that [Maximum Freq] = 32767. [Maximum Freq] is the largest output frequency
that the drive will deliver to the motor.
[Overspeed Limit] allows the drive to operate above [Maximum Speed] for
certain functions such as bus regulation, current limit (during regeneration), PI
control, and slip compensation. It is important that [Overspeed Limit] is set to
allow enough headroom for the application. For example, let’s assume we have an
application where [Speed Mode] = “Slip Comp”. Slip compensation adds some
frequency to the commanded speed in order to compensate for slip in a loaded
motor. In this case, [Overspeed Limit] should not be set to 0. Otherwise, if the
drive is running with a commanded frequency of 60 Hz and the motor is loaded
at all, slip compensation will add some frequency and we would get a nuisance
“Overspeed” fault.
• [Maximum Speed] = 60 Hz
• [Overspeed Limit] = 10 Hz
• [Maximum Freq] = 130 Hz (this is default so that users who want to go twice
base speed don't have to change it).
To send out a speed reference to the drive from a controller over RIO, you can
perform the following calculation:
The following example illustrates how a change in P55 [Maximum Freq] in the
PowerFlex 70 or 700 affects the speed reference scaling:
[Overspeed Limit] = 10 Hz (this is factory default)
[Maximum Speed] = 60 Hz (this is factory default).
[Maximum Freq] = [Maximum Speed] + [Overspeed Limit] = 60 Hz + 10 Hz = 70 Hz.
Using the above formula, calculate the Speed Reference sent from a network
using a DPI adapter.
Jog
When the drive is not running, pressing the HIM Jog button or a programmed
Jog digital input will cause the drive to jog at a separately programmed jog
reference. This speed reference value is entered in [ Jog Speed], parameter 100.
Figure 35 Speed Reference Selection
Scaling
Scaling applies only to references from analog inputs and reference sources
selected in [Speed Ref x Sel], parameters 90/93.
• [Analog In x Hi] sets the maximum level on input to be seen (i.e. 10 Volts).
• [Analog In x Lo] sets the minimum level on input to be seen (i.e. 0 Volts).
Each [Speed Ref x Sel] parameter has an additional set of scale parameters:
• [Speed Ref x Hi] selects the reference value for the maximum input specified
in [Analog In x Hi].
• [Speed Ref x Lo] selects the reference value for the minimum input specified
in [Analog In x Lo].
[Analog In x Hi] = 10 V
[Analog In x Lo] = 0 V
[Speed Ref A Hi] = 45 Hz
[Speed Ref x Lo] = 5 Hz
then the speed command for the drive will be linearly scaled between 45 Hz at
maximum analog signal and 5 Hz at minimum analog signal. See additional
examples under Analog Inputs on page 22.
Polarity
The reference can be selected as either unipolar or bipolar. Unipolar is limited to
positive values and supplies only the speed reference. Bipolar supplies both the
speed reference AND the direction command: + signals = forward direction and
– signals = reverse direction.
Trim
If the speed reference is coming from the source specified in [Speed Ref A Sel] or
[Speed Ref B Sel], the a trim signal can be applied to adjust the speed reference by
a programmable amount. The source of the trim signal is made via [Trim In Sel],
parameter 117 and can be any of the sources that are also used as references.
[Trim Out Select], parameter 118 selects which of the references, A/B will be
trimmed.
If the trim source is an analog input, two additional scale parameters are provide
to scale the trim signal.
Figure 36 Trim
Trim Enable Select
Trim B
Both
None
Reference A +
+ Trimmed
Reference A
Reference B +
+ Trimmed
Reference B
Min/Max Speed
[Max Speed]
Maximum and minimum speed limits are applied to the reference. These limits
apply to the positive and negative references. The minimum speed limits will
create a band that the drive will not run continuously within, but will ramp
through. This is due to the positive and negative minimum speeds. If the
reference is positive and less than the positive minimum, it is set to the positive
minimum. If the reference is negative and greater than negative minimum, it is set
to the negative minimum. If the minimum is not 0, hysteresis is applied at 0 to
prevent bouncing between positive and negative minimums. See below.
Min Spd
Min Spd Band
– Min Spd
Maximum frequency
The maximum frequency defines the maximum reference frequency. The actual
output frequency may be greater as a result of slip compensation and other types
of regulation. This parameter also defines scaling for frequency reference. This is
the frequency that corresponds to 32767 counts when the frequency reference is
provided by a network.
Speed Regulator Vector FV The drive takes the speed reference that is specified by the speed
reference control loop and compares it to the speed feedback. The speed
regulator uses proportional and integral gains to adjust the torque reference that
is sent to the motor. This torque reference attempts to operate the motor at the
specified speed. This regulator also produces a high bandwidth response to speed
command and load changes.
[Ki Speed Loop] sets the integral gain of the speed regulator. Its value is
automatically calculated based on the bandwidth setting in [Speed Desired BW].
Integral gain may be manually adjusted by setting [Speed Desired BW] to a value
of zero. Units are (per unit torque/sec) / (per unit speed). For example, when [Ki
Speed Loop] is 50 and the speed error is 1%, the integral output will integrate
from 0 to 50% motor rated torque in 1 second.
value of zero. Units are (per unit torque) / (per unit speed). For example, when
[Kp Speed Loop] is 20, the proportional gain block will output 20% motor rated
torque for every 1% error of motor rated speed.
Speed/Torque Select Vector FV[Speed/Torque Mod] is used to choose the operating mode for the
drive. The drive can be programmed to operate as a velocity regulator, a torque
regulator, or a combination of the two. Refer to Figure 37.
Figure 37
Speed/Torque Mod 88
0
0
1
Spd Reg PI Out
428 Ref A Hi 2
Scale Min
Torque Ref A Sel 427 3
429 Ref A Lo
Max 4
432 Ref B Hi + 6
Scale +
Torque Ref B Sel 431 x
433 Ref B Lo abs
Min
Torq Ref B Mult 434
When set to a “1,” the drive/motor is operated in speed mode. The torque
command changes as needed to maintain the desired speed.
A value of “2” selects torque mode. In torque regulation mode, the drive controls
the desired motor torque. The motor speed will be a result of the torque
command and load present at the motor shaft.
Min and Max mode are selected by values 3 and 4, respectively. These two modes
offer a combination of speed and torque operation. The algebraic minimum or
maximum of speed/torque will be the operating point for the Min and Max
modes. The drive will automatically switch from speed to torque mode (or from
torque to speed) based on the dynamics of the motor/load.
The Min mode is typically used with positive torque and forward speed
operation, the minimum of the two being closest to zero. The Max mode is
opposite, typically used with reverse speed and negative torque, the maximum
being the least negative (closest to zero).
Sum mode is selected when set to “5.” This mode allows an external torque
command to be added to the speed regulator output when desired.
When operating in a torque mode, the motor current will be adjusted to achieve
the desired torque. If the material being wound/unwound breaks, the load will
decrease dramatically and the motor can potentially go into a “runaway”
condition.
Figure 38
Torque Reference:
[Torque Ref A Sel], parameter 427 is scaled by [Torque Ref A Hi] and [Torque
Ref A Lo]. Then divided by [Torq Ref A Div].
[Torque Ref B Sel], parameter 431 is scaled by [Torque Ref B Hi] and [Torque
Ref B Lo]. Then multiplied by [Torq Ref B Mult].
The final torque reference, in the Torque Mode, is the sum of scaled Torque Ref
A and scaled Torque Ref B.
Figure 39 illustrates how min mode operates. The drive starts out operating as a
torque regulator. The torque reference causes the motor to operate at 308rpm.
The speed reference is 468rpm, so the minimum is to operate as a torque
regulator. While operating in torque regulation, the load decreases and the motor
speeds up. Notice the torque command has not changed. When the speed
regulator comes out of saturation, it clamps the speed and now the drive operates
as a speed regulator. The At Speed Relay then closes.
Figure 39
Internal Torque Command
Speed Feedback
308
RPM
Sum Mode
Configuring the drive in this mode allows an external torque input to be summed
with the torque command generated by the speed regulator. The drive requires
both a speed reference and a torque reference to be linked. This mode can be used
for applications that have precise speed changes with critical time constraints. If
the torque requirement and timing is known for a given speed change, then the
external torque input can be used to preload the integrator. The timing of the
speed change and the application of an external torque command change must be
coordinated for this mode to be useful. The sum mode will then work as a feed
forward to the torque regulator.
Important: Zero Torque may excessively heat the motor if operated in this mode
for extended periods of time. No load or flux current is still present
when the drive is operating in zero torque mode. A motor with an
extended speed range or separate cooling methods (blower) may be
required.
Speed Units Vector [Speed Units] selects the units to be used for all speed related
parameters. The options for [Speed Units] are:
Start Inhibits The [Start Inhibits] parameter indicates the inverted state of all start permissive
conditions. If the bit is on (HI or 1), the corresponding permissive requirement
has not been met and the drive is inhibited from starting. It will be updated
continually, not only when a start attempt is made. See also Start Permissives on
page 176.
Start Permissives Start permissives are conditions required to permit the drive to start in any mode
– run, jog, auto-tune, etc. When all permissive conditions are met the drive is
considered ready to start. The ready condition is available as the drive ready
status.
Permissive Conditions
1. No faults can be active.
5. All Stop inputs must be negated (See special Digital Inputs Stops
Configuration issues below).
If all permissive conditions are met, a valid start, run or jog command will start
the drive. The status of all inhibit conditions, except for item 6 above, are
reflected in the output parameter Start Inhibits. The configuration change
condition is a transient (short-term) condition and not directly user controlled. It
is therefore not reflected in the Start Inhibits parameter.
Note that the Start Inhibits conditions do not include any of the functionality
imposed by the DPI logic such as owners, masks, local control, etc.
S.M.A.R.T. Start
During a Start Up, the majority of applications require changes to only a few
parameters. The LCD HIM on a PowerFlex 70 drive offers S.M.A.R.T. start,
which displays the most commonly changed parameters. With these parameters,
you can set the following functions:
Basic Start Up
The Basic Start Up routine leads the user through the necessary information in a
simple question and answer format. The user can make the choice to execute or
skip any section of the routine. Below is a complete flow chart of the routine.
HIM
Main Menu: Basic Start Up (Top Level)
<Diagnostics>
Parameter
Device Select Esc Abort
Memory Storage
StartUp
Preferences
Startup 0-2
PowerFlex 70
StartUp .
The drive must
Drive active? Yes be stopped to
proceed. Press
Esc to cancel. Any state
'Esc' key
No
Stop
0-3
Go to previous
PowerFlex 70 state
StartUp . Resume
Startup Make a selection
previously Yes Abort
7. Done
aborted? <Backup>
/Exit Backup Go to Backup
Resume screen for previous
StartUp Menu state
No
0-0
PowerFlex 70
StartUp .
This routine is
to help setup a
drive for basic Go to 1-0
applications.
Parameter access Backup
through other
menus may be Startup Menu
necessary to
setup advanced Go to 2-0
features.
1. Input
Voltage
Enter
0-1 2. Motor Go to 3-0
PowerFlex 70 Dat/Ramps
StartUp .
Complete these 3. Motor
steps in order: Tests
1. Input Voltage Go to 4-0
2. Motr Dat/Ramp 4. Speed
3. Motor Tests Limits
4. Speed Limits
5. Speed Control
5. Speed
6. Strt,Stop,I/O
Control
7. Done / Exit Go to 5-0
6. Strt,Stop,
I/O
Go to 6-0
Enter
Backup Yes No
1-1 1-2
StartUp StartUp
1. Input Voltage 1. Input Voltage
Enter choice for Enter choice for
Input Supply Input Supply
400V, 50 Hz 208V, 60 Hz
<480V, 60 Hz> <240V, 60 Hz>
Enter Enter
1-3
StartUp
1. Input Voltage
Reset all
parameters to No
their defaults?
<Yes>
No
Yes
1-4
StartUp
1. Input Voltage
Fault Clear Go to 0-1 (2)
Clear fault to
continue.
2-0
Basic Start Up (Motor Data/Ramp)
StartUp
2. Motr Dat/Ramp
Use motor name-
plate data and
required ramp
times for the
following steps.
Enter
2-1
StartUp
2. Motr Dat/Ramp
Enter choice for
Mtr NP Pwr Units
Enter
2-2 2-7
StartUp StartUp
2. Motr Dat/Ramp 2. Motr Dat/Ramp
Enter value for Backup
Enter choice for
Motor NP Power Stop Mode A
123.4 kW
xxx.x <> yyy.y
Enter Enter
2-3
2-10
StartUp
2. Motr Dat/Ramp StartUp
Enter value for Backup 2. Motr Dat/Ramp
Motor NP FLA Stop Mode A Enter choice for
+456.78 Amps = "DC Brake" or No DB Resistor Type
xxx.xx <> yyy.yy "Ramp to None None - Bus Reg Mode A = Adj Freq.
Hold"? Internal Intenal - Bus Reg Mode A = Both, DB 1st.
External External - Bus Reg Mode A = Both, DB 1st.
Enter
2-4 Yes
2-8 Enter
StartUp
2. Motr Dat/Ramp
2-11
StartUp
Enter value for 2. Motr Dat/Ramp StartUp
Motor NP Volts Enter
Enter value for 2. Motr Dat/Ramp
123.4 Volt DC Brake Level No Enter value for
xxx.x <> yyy.y 1.0 Amps Accel Time 1
0.0 < 30.0 Amps 6.0 Secs
0.0 < 60.0 secs
Enter
Enter
2-5
Enter
StartUp Enter 2-12
2. Motr Dat/Ramp
Enter value for Stop Mode A StartUp
Motor NP Hertz Backup = "DC 2. Motr Dat/Ramp
60.0 Hz Brake"? Enter value for
x.x <> y.y Decel Time 1
6.0 Secs
0.0 < 60.0 secs
Enter
Yes
2-6 2-9 Enter
2-13
StartUp StartUp
2. Motr Dat/Ramp 2. Motr Dat/Ramp StartUp
Enter value for Enter value for 2. Motr Dat/Ramp
Motor NP RPM DC BrakeTime Enter value for
+456 RPM 1.0 Secs S Curve % Enter Go to 0-1 (3)
xxx <> yyy 0.0 < 90.0 Secs 0%
0 < 100 %
Auto Tune
3-2
Startup
A. AutoTune
Rotate Tune only Fault Clear
with no load and
low friction.
Static Tune when
load or friction
Direction are present.
Enter/
Test
Backup
Enter
3-3
Startup
A. AutoTune
Make a selectioon
<Rotate Tune>
Static Tune
Rotate/Static
Yes No
Tune complete
(stops drive) (stops drive)
(stops drive)
Enter
4-1 4-2
StartUp StartUp
4. Speed Limits 4. Speed Limits
Disable reverse Enter choice for
operation? No Direction Method
Yes <Fwd/Rev Command>
<No> +/- Speed Ref
Yes Enter
4-3
Backup
StartUp
4. Speed Limits
Enter value for
Maximum Speed Backup
+60.00 Hz
xxx.xx <> yyy.yy
Enter 4-4
StartUp
4. Speed Limits
Enter value for
MaxSpd + OSL No Enter Go to 0-1 (5)
Backup Minimum Speed
> MaxFreq?
+5.78 Hz
xxx.xx <> yyy.yy
Yes
4-5
StartUp
4. Speed Limits
Maximum Freq and
Overspeed Limit
will be changed
to support your
Maximum Speed.
Enter
4-6 OS Limit =
MaxFreq - MaxSpd
StartUp
4. Speed Limits
Rejecting this
change will
prevent starting Reject
Accept
Reject
MaxFreq = MaxSpd
MaxFreq = 400Hz
+ OS Limit
Accept
MaxSpd + OS
No
Lmt > 400Hz?
Yes
2-wire Enter
2-wire 3-wire 6-12 6-15
6-7 6-9
StartUp StartUp
StartUp StartUp A. Dig Inputs A. Dig Inputs
A. Dig Inputs A. Dig Inputs Digital Input 1 Digital Input 1
Digital Input 1 Digital Input 1 will be set to will be set to
will be set to will be set to Run Forward. Stop.
Not Used. Stop.
Enter Enter
Enter Enter 6-13 6-16
6-8 6-10
StartUp StartUp
StartUp StartUp A. Dig Inputs A. Dig Inputs
A. Dig Inputs A. Dig Inputs Digital Input 2 Digital Input 2
Digital Input 2 Digital Input 2 will be set to will be set to
will be set to will be set to Run Reverse. Start.
Run/Stop. Start.
Enter Enter
Enter
Go to 6-1 (B) Enter
Digital Digital
Out 1 Out 2
Enter
6-25 6-27 6-30
StartUp StartUp StartUp
B. Dig Outputs B. Dig Outputs C. Anlg Outpts
Enter choice for Enter choice for Enter value for
Digital Out 1 Sel Digital Out 2 Sel Analog Out 1 Hi
Enter
Enter Enter 6-31
StartUp
Digital Out 1 Sel Digital Out 2 Sel C. Anlg Outpts
= ENUM choice = ENUM choice Enter value for
No Backup Backup No Analog Out 1 Lo
that uses that uses
"Level"? "Level"?
Drive
active?
STOP
(Stops the Drive) 0-5
No PowerFlex 700
0-4
Start-Up .
PowerFlex 700 SMART startup
programs 11 key Yes
Start-Up . Startup
Make a selection drive parameters
for fast setup . Menu
<1.SMART>
2.Basic Basic startup
Done/Exit programs basic
(allow Start/Jog) 3.Detailed
4.More Info drive functions
and options. .
Detailed startup
programs motor
data, reference;
Backup Basic/ SMART ramps; limits; &
Detailed analog/digital
Go to 8-1 (SMART I/O.
Start)
First time
into Yes
Startup??
Drive
Go to 1-1 (Motor active?
Control)
No
No
Basic Detailed
Go to 1-0
0-1 0-1
PowerFlex 700 PowerFlex 700 Go to 2-0
Start-Up . Start-Up . Motor Control
Complete these Complete these
steps in order: steps in order: Motor Dat/Ramp Go to 3-0
<1.Motor Control> <1.Motor Control>
2.Motr Data/Ramp 2.Motr Data/Ramp Motor Tests
3.Motor Tests 3.Motor Tests Go to 4-0
4.Speed Limits 4.Speed Limits Speed Limits
5.Speed/Trq Cntl 5.Speed/Trq Cntl
6.Start/Stop/I/O 6.Start/Stop/I/O Speed/Torque Control Go to 5-0
7.Done/Exit 7.Appl Features
8.Done/Exit Strt/Stop/ I/O
Appl Features Go to 6-0
Done/Exit Go to 7-0
Go to HIM
Main Menu
1-31 Start-Up
V/Hz
The Fan/Pump
option selects a
1-0 1-1 B B = Basic mode predefined V/Hz
curve.
Start-Up Start-Up The Custom/Std.
1. Motor Control 1. Motor Control option allows
This section Frequency
Make a selection More you to define a
selects the type <1.SVC> 1-18 V/Hz curve or
of Motor Control info
2.V/Hz select a default
the drive will 3.Flux Vector 1-17 Start-Up V/Hz curve.
use. 4.More info Start-Up V/Hz
1.Motor Control Select a V/Hz
More control option: V/Hz
Use SVC Custom/Std.
SVC- Set Flux info for applications <1.V/Hz-Fan/Pump> 1-32 1-23
#53= 0 Vector requiring speed 2.V/Hz-Cust/Std.
1-2 B 1-6 B regulation. 3.More info Start-Up Start-Up
Use V/Hz control V/Hz V/Hz
Start-Up Start-Up for Fan/Pump and Define Custom
SVC Flux Vector Yes Enter choice for
other V/Hz Fan/Pump-Set #53=3 V/Hz curve? Slip Comp
Enter choice of NOTE! An Encoder applications. <Yes>
Speed Units is required for <Enable>
Use Flux Vector 1-19 No Disable
<Hz> the Flux Vector for applications
RPM Control option. requiring Torque Start-Up
control or tight V/Hz Standard- Set #80 to
speed regulation. Enter choice for set params #54 selection made
Slip Comp & 69-72 to
1-7 B <Enable> default values 1-24
1-3 Start-Up Disable B 1-20 Start-Up
SVC Start-Up Start-Up V/Hz
Enter choice for Flux Vector V\Hz Enter value for
Slip Comp Enter value for Control selected Run Boost
<Enable> Encoder PPR is Standard V/Hz 10V
1024 Disable
Disable Set #80=0 xx.x < yy.y
1-8 B 1-25
Enable 1-22
Disable Enable Start-Up Set #80=1 Start-Up
Set #80=0 Set #80=1 Flux Vector Start-Up V/Hz
1-4 1-5 B Enter choice of V/Hz Enter value for
Speed Units Control selected Start Boost
Start-Up Start-Up <Hz> is Fan/Pump 10.0 V
SVC SVC RPM no Slip Comp x.xxxx < y.yyyy
Control selected Control selected 1-21
is SVC with is SVC with 1-9 1-26
no Slip Comp Slip Comp Start-Up Start-Up
Flux Vector V/Hz Start-Up
Enter choice of Control selected V/Hz
Regulation is Fan/Pump Enter value for
<Speed> with Slip Comp Break Voltage
Torque Speed path- 10.0 Hz
Set #88 to 1 x.x < y.y
1-11
Torque path
B
1-27
1-10 Start-Up
Flux V ector Start-Up
Start-Up Control selected V/Hz
Flux Vector is FOC Speed Enter value for
Select Torque Regulate. Break Frequency
Regulate option: 10.0 Hz
<1.Torque Regul.> x.xxxx < y.yyyy
2.Min Torque/Spd 1-16
3.Max Torque/Spd 1-28
4.Sum Torque/Spd Absolute- Start-Up
Min Torque/ 5.Absolute Set #88 Flux Vector Start-Up
Speed - =6 Control selected V/Hz
Set #88 =3 is Torque/FOC Enter value for
Absolute Max Voltage
1-12 Sum Trq/Speed- 10.0 V
Trq Set #88 = 5 x.x < y.y
Max
Start-Up Regulate
Trq/Speed -
Flux Vector Set #88 = 4
Set #88 1-15
Control selected =2 1-30 1-29
is Torque/FOC Start-Up
Min Torque/Speed Flux Vector Start-Up Start-Up
1-13 1-14 Control selected V/Hz V/Hz
is Torque/FOC Control selected Control selected
Start-Up Start-Up Sum Torque/Speed is V/Hz/Custom is V/Hz/Custom
Flux Vector Flux Vector no Slip Comp. with Slip Comp.
Control selected Control selected
is Torque/FOC is Torque/FOC
Max Torque/Speed Torque Regulate
Go to 0-1
2. Motr Dat/Ramp
Note: Enter
- For V/Hz mode, only states 2-0 thru 2-6 & 2-14 are displayed.
- For V/Hz mode, configure Stop Mode A as Coast to Stop.
- Going from state 2-7 to 2-10 directly sets the DC Brake Level/Time Go to 0-1 (3. Motor
parameters to their default value. Tests)
Go to 3-1
4-1
Start-Up B
4. Speed Limits
Enter value for
Maximum Speed
+60.00 Hz
xxx.xx <> yyy.yy
4-2
Start-Up B
4. Speed Limits
Enter value for
Minimum Speed
+5.78 Hz
xxx.xx <> yyy.yy
FOC
Mode? Yes
4-3
No Start-Up B
4. Speed Limits
Go to 0-1 (5. Enter value for
Speed Control) Rev Speed Lim
+5.78 Hz
xxx.xx <> yyy.yy
No
Backup B 6-6 B 6-7
Start-Up Start-Up
A. Dig Inputs A. Dig Inputs
2 wire control 2 wire control
uses a contact Yes uses a contact
that acts as that acts as
both STOP (Open) both STOP (Open)
& Run (Closed). & Run (Closed).
3 wire control 3 wire control
uses 2 contacts; uses 2 contacts;
one for START one for START
& one for STOP. & one for STOP.
6-8 B
6-13 B
Start-Up
A. Dig Inputs Start-Up
Enter choice for A. Dig Inputs More B 6-16
More
Control Method Info.. Enter choice for Info..
<3 wire> Control Method Start-Up
2 wire <3 wire> A. Dig Inputs
More info 2 wire 3-wire Digital Input 3
More info will be set to Fwd/
Reverse.
2-wire 3-wire
6-9 2-wire
B B 6-11 6-14 B
B 6-17
Start-Up Start-Up Start-Up
Start-Up
A. Dig Inputs A. Dig Inputs A. Dig Inputs
A. Dig Inputs
Digital In1 set Digital In1 set Digital In1 set
Digital In1 set
to Not Used. to Stop. to Run Forward.
to Stop.
Digital In2 set Digital In2 set Digital In2 set
Digital In2 set
to Run/Stop. to Start. to Run Reverse.
to Start.
Yes
7-3 7-5
7-2 Start-Up
7.Appl Features Start-Up Start-Up
Enter choice for 7.Appl Features 7.Appl Features
PI Reference Enter value for Enter value for
1 Flying StartGain Auto Rstrt Tries
Analog In 1 4000 0
xxx < yyyy xxx < yyyy
7-3 Start-Up
Go to 7-1 (Auto
7.Appl Features Restart) Auto Restart
Enter choice for tries = 0?
PI Feedback
1 Yes
Analog In 1
Go to 7-1 (Done) No
7-6
Start-Up
7-4 Start-Up 7.Appl Features
7.Appl Features
Enter value for Enter value for
PI Setpoint Auto Rstrt Delay
50.0% 1.0 Secs
xx.x < yy.y xx.x < yy.y
Start-Up
7-5 7.Appl Features
Enter value for
PI Upper Limit
60.0 Hz
xx.x < yy.y
7-6 Start-Up
8.Appl Features
Enter value for
PI Lower Limit
-60.0 Hz
xx.x < yy.y
7-7 Start-Up
8.Appl Features
Enter value for
PI Integral Time
2.0 Secs
x.x < y.y
7-8 Start-Up
8.Appl Features
Select other PI
options in
parameter #124.
8-1
Start-Up
SMART
Enter value for
Digital In 2 Sel
5
Start
8-2
Start-Up
2. Motr Dat/Ramp
Enter choice for
Stop Mode A
Coast
<Ramp>
Ramp to Hold
DC Brake
8-3
Start-Up
SMART
Enter value for
Minimum Speed
0.0 Hz
8-4
Start-Up
SMART
Enter value for
Maximum Speed
60.0 Hz
8-5
Start-Up
SMART
Enter value for
Accel Time 1
10.0 Secs
8-6
Start-Up
SMART
Enter value for
Decel Time 1
10.0 Secs
8-7
Start-Up
SMART
Enter value for
Speed Ref A Sel
Analog In 2
8-8
Start-Up
SMART
Enter value for
Motor NP FLA
0.8 Amps
8-9
Start-Up
SMART
Enter value for
Motor OL Hertz
10.0 Hz
8-10
Start-Up
SMART
Enter value for
Motor OL Factor
1.0
8-11
Start-Up
SMART
SMART Startup
is now complete.
Torque Speed
1-2 1-11
Start-Up Start-Up
Torque Speed
Is an encoder Is an encoder 1-14
present? present?
<Yes> <Yes> Start-Up
No No Frequency-V/Hz
Select Motor V/Hz
Control Mode Custom/Multi
YES-Speed path- Motor - Set
Torque- Set #88 to 1 <V/Hz-Fan/Pump>
Torque- No param #53 to '2'
Yes 1-12 V/Hz-Custom
1-3 V/Hz-Multi Motor & #80 to '0'
1-4 NO 1-15
Start-Up SV-No regulation
Start-Up Start-Up Speed-SVC
Torque-FOC Start-Up
Speed-SVC Control selected Frequency-V/Hz Custom
An Encoder is Enter value for is FOC Speed V/Hz
required for the 1-13 Select V/Hz 1-19
Encoder PPR Regulate. Parameters.
Torque Control 1024
option. Select Start-Up <Standard V/Hz> Start-Up
another Motor Frequency-V/Hz Custom V/Hz Frequency-V/Hz
Torque path Sensorless
Control option 1-5 Select Motor Enter value for
or install an Control Mode Vector - set param #53 Run Boost
encoder. Start-Up <SVC-common> to '0' & #80 to '0' 10V
Torque-FOC V/Hz xx.x < yy.y
Select Torque More info Fan/Pump -
Regulate option: Set param 1-20
<Torque Regulate> #53 to '3' &
Min Torque/Speed #80 to '0' Start-Up
Min Torque/ Max Torque/Speed Frequency-V/Hz
Speed - Sum Torque/Speed 1-16 Enter value for
1-6 Set #88 to 3 Absolute Start Boost
Absolute- 1-10 Start-Up 10.0 V
Set #88 Frequency-V/Hz x.xxxx < y.yyyy
Start-Up
Torque-FOC to 6 Start-Up Control selected
Max is Frequency/SV 1-21
Control selected Sum Trq/Speed- Torque-FOC
is Torque/FOC Trq/Speed - Control selected no Slip Comp Standard Start-Up
Set #88 to 5 Frequency-V/Hz
Min Torque/Speed Set #88 to 4 is Torque/FOC
Trq Absolute Enter value for
1-7 Regulate 1-9 1-17 Break Voltage
Set #88 10.0 Hz
Start-Up to 2 Start-Up 1-25 Start-Up x.x < y.y
Torque-FOC Torque-FOC Frequency-V/Hz
Control selected Control selected Start-Up Control selected 1-22
is Torque/FOC is Torque/FOC Speed-SVC is Freq/Fan/Pump
Max Torque/Speed Sum Torque/Speed Control selected no Slip Comp Start-Up
1-8 is Speed/SVC Frequency-V/Hz
with Slip Comp Enter value for
Start-Up Break Frequency
Torque-FOC 10.0 Hz
Control selected x.xxxx < y.yyyy
is Torque/FOC
Torque Regulate 1-18 1-23
Start-Up Start-Up
Frequency-V/Hz Frequency-V/Hz
Control selected Enter value for
is Freq/V/Hz. Max Voltage
Start-Up 10.0 V
Speed-SVC x.x < y.y
Enter value for
Max Voltage 1-24
10.0 V Go to 1-1 Start-Up
x.x < y.y Frequency-V/Hz
Control selected
Start-Up is Freq/Custom.
Speed-SVC Start-Up
Use Speed-SVC Speed-SVC
for applications Enter choice of
requiring speed Speed Units
regulation. <V/Hz>
RPM
Go to 0-1
2. Motr Dat/Ramp
1. Coast to Stop - When in Coast to Stop, the drive acknowledges the Stop
command by shutting off the output transistors and releasing control of the
motor. The load/motor will coast or free spin until the mechanical energy is
dissipated.
Output Voltage
Output Current
Motor Speed
Time
Coast Time is load dependent
Stop
Command
3. DC Brake is selected by setting [Stop Mode A] to a value of “3.” The user can
also select the amount of time the braking will be applied and the magnitude
of the current used for braking with [DC Brake Time] and [DC Brake Level].
This mode of braking will generate up to 40% of rated motor torque for
braking and is typically used for low inertia loads.
The voltage is applied for the time programmed in [DC Brake Time]. After
this time has expired, all output ceases. If the load is not stopped, it will
continue to coast until all energy is depleted (A on the diagram below). If the
time programmed exceeds the needed time to stop, the drive will continue to
apply the DC hold voltage to the non-rotating motor (B on the diagram
below). Excess motor current could cause motor damage. The user is also
cautioned that motor voltage can exist long after the Stop command is issued.
The right combination of Brake Level and Brake Time must be determined to
provide the safest, most efficient stop (C on the diagram below).
Output Voltage
Output Current
Motor Speed
DC
Hold Level
Time
Stop (B) (C) (A)
Command DC Hold Time
4. Ramp To Stop is selected by setting [Stop Mode x]. The drive will ramp the
frequency to zero based on the deceleration time programmed into [Decel
Time 1/2]. The “normal” mode of machine operation can utilize [Decel Time
1]. If the “Machine Stop” mode requires a faster deceleration than desired for
normal mode, the “Machine Stop” can activate [Decel Time 2] with a faster
rate selected. When in Ramp to Stop, the drive acknowledges the Stop
command by decreasing or “ramping” the output voltage and frequency to
zero in a programmed period (Decel Time), maintaining control of the motor
until the drive output reaches zero. The output transistors are then shut off.
The load/motor should follow the decel ramp. Other factors such as bus
regulation and current limit can alter the decel time and modify the ramp
function.
Ramp mode can also include a “timed” hold brake. Once the drive has reached
zero output hertz on a Ramp-to-Stop and both parameters [DC Hold Time]
and [DC Hold Level] are not zero, the drive applies DC to the motor
producing current at the DC Hold Level for the DC Hold Time.
Output Voltage
Output Current
Motor Speed
Output Current
Output Voltage
DC
Hold
Level
Time
Stop DC Hold Time
Zero
Command Command
Speed
Motor speed during and after the application of DC depends upon the
combination of the these two parameter settings, and the mechanical system.
The drive output voltage will be zero when the hold time is finished.
The level and uniformity of the DC braking offered at zero speed may not be
suitably smooth for many applications. If this is an application requirement, a
vector control drive, motion control drive or mechanical brake should be
used.
The drive output voltage will be zero when the hold time is finished
5. Ramp To Hold is selected by setting [Stop Select x]. The drive will ramp the
frequency to zero based on the deceleration time programmed into [Decel
Time 1/2]. Once the drive reaches zero hertz, a DC Injection holding current
is applied to the motor. The level of current is set in [DC Brake Level].
In this mode, the braking is applied Continuously. [DC Hold Time] has no
effect in this mode. Braking will continue until one of the following events
occur:
Again, caution must be exercised to not overheat the motor by applying excess
voltage and/or for excess time, particularly if the motor is not rotating.
Output Voltage
DC
Hold Level
Time
Stop Zero Re-issuing a
Command Command Start Command
Speed
Test Points
234 [Testpoint 1 Sel] Default: 499
236 [Testpoint 2 Sel] Min/Max: 0/999
Selects the function whose value is displayed value in Display: 1
[Testpoint x Data].
UTILITY (File E)
These are internal values that are not accessible through
Diagnostics
parameters.
See Testpoint Codes and Functions for a listing of
available codes and functions.
235 [Testpoint 1 Data] Default: Read Only
237 [Testpoint 2 Data] Min/Max: 0/65535
32
The present value of the function selected in [Testpoint Display: 1
x Sel].
Torque Limits Vector FV The bus regulator, when enabled, generates a regenerative power
limit to prevent the DC bus voltage from rising. The maximum (value closest to
zero) of the bus regulator regen power limit and [Regen Power Limit] is
converted into a positive and negative torque limit. The positive limit is used
when the motor is regenerating in the reverse direction. The negative limit is used
when the motor is motoring in the reverse direction. Finally, the drive’s torque
reference is limited by the minimum (value closest to zero) of the positive torque
limit from the power limit section and [Pos Torque Limit]. The drive’s torque
reference is also limited by the maximum (value closest to zero) of the negative
torque limit from the power limit section and [Neg Torque Limit].
Motor Torque Ref
from Torque Notch Filter 24
Torque
440 4-7 Limit
Control Status
Torque Pos Limit 435
Speed Feedback 25
Rated Volts 27
DC Bus Memory 13 Bus Min
Bus Reg Mode A 161 Voltage
Regulator Power
Bus Reg Mode B 162
Limit
DC Bus Voltage 12
Regen Power Lim 153 Max
Torque Neg Limit 436
Torque Performance [Torque Perf Mode] or [Motor Cntl Sel] (Vector) selects the output mode of the
Modes drive. The choices are:
• Custom Volts/Hertz
Used in multi-motor or synchronous motor applications.
• Fan/Pump Volts/Hertz
Used for centrifugal fan/pump (variable torque) installations for additional
energy savings.
• Sensorless Vector
Used for most general constant torque applications. Provides excellent
starting, acceleration and running torque.
• Sensorless Vector w/Economizer
Used in constant torque applications that have significant “idle” time (time
spent at greatly reduced load) to offer additional energy conservation.
The following table shows the performance differences between V/Hz and
Sensorless Vector.
Fan/Pump and Flux Vector
Custom V/Hz with SVC with Slip SVC with without Flux Vector with
Torque Mode Slip Comp Comp Feedback Feedback Feedback
Speed Regulation 0.5% 0.5% 0.1% 0.1% 0.001%
(% of base speed)
Operating Speed Range 40:1 80:1 80:1 120:1 1000:1
Speed Bandwidth 10 rad/sec 20 rad/sec 20 rad/sec 50 rad/sec 250 rad/sec
Volts/Hertz
Volts/Hertz operation creates a fixed relationship between output voltage and
output frequency. The relationship can be defined in two ways.
1. Fan/Pump
When this option is chosen, the relationship is 1/X2. Therefore;
for full frequency, full voltage is supplied and for ½1/2 rated frequency,
1/4 voltage is applied, etc. This pattern closely matches the torque
requirement of a variable torque load (centrifugal fan or pump – load
increases as speed increases) and offers the best energy savings for these
applications.
Maximum Voltage
Base Voltage
(Nameplate)
Run Boost
2. Custom
Custom Volts/Hertz allows a wide variety of patterns using linear segments.
The default configuration is a straight line from zero to rated voltage and
frequency. This is the same volts/hertz ratio that the motor would see if it
were started across the line. As seen in the diagram below, the volts/hertz ratio
can be changed to provide increased torque performance when required. The
shaping takes place by programming 5 distinct points on the curve:
– Start Boost - Used to create additional torque for breakaway from zero
speed and acceleration of heavy loads at lower speeds
– Run Boost - Used to create additional running torque at low speeds. The
value is typically less than the required acceleration torque. The drive will
lower the boost voltage to this level when running at low speeds (not
accelerating). This reduces excess motor heating that could be caused if the
higher start / accel boost level were used.
– Break Voltage/Frequency - Used to increase the slope of the lower
portion of the Volts / hertz curve, providing additional torque.
– Motor Nameplate Voltage/Frequency - sets the upper portion of the
curve to match the motor design. Marks the beginning of the constant
horsepower region
– Maximum Voltage/Frequency - Slopes that portion of the curve used
above base speed.
Maximum Voltage
Base Voltage
(Nameplate) Voltage
Break Voltage
Start/Accel Boost
Run Boost
Sensorless Vector
Sensorless Vector technology consists of a basic V/Hz core surrounded by
excellent current resolution (the ability to differentiate flux producing current
from torque producing current), a slip estimator, a high performance current
limiter (or regulator) and the vector algorithms.
V/Hz Control
GATE
SPEED REF. + FREQUENCY REF. Current ELEC. FREQ. V REF. Voltage SIGNALS
V/Hz Inverter Motor
Limit Control
+
TORQUE I EST.
Flux V VECTOR
TORQUE I EST.
Vector
Control
The algorithms operate on the knowledge that motor current is the vector sum of
the torque and flux producing components. Values can be entered to identify the
motor values or an autotune routine can be run to interrogate and identify the
motor values (see Autotune on page 40). Early versions required feedback, but
today, performance is sensorless. It offers high breakaway torque, exceptional
running torque, a wider speed range than V/Hz, higher dynamic response and a
fast accel “feed forward” selectable for low inertia loads (adaptive current limit).
In sensorless vector control, the drive maintains a constant flux current up to base
speed, allowing the balance of the drive available current to develop maximum
motor torque. By manipulating output voltage as a function of load, excellent
motor torque can be generated.
Maximum Voltage
Base Voltage
(Nameplate)
ve
Cur
ll L oad
t e Fu
ima urve
prox dC
App Loa
te No
ima
prox
App
Ir Voltage
In flux vector control, the flux and torque producing currents are independently
controlled. Therefore, we can send a torque reference directly instead of a speed
reference. The independent flux control also allows us to reduce the flux in order
to run above base motor speed.
CURRENT FEEDBACK
Flux V mag
Reg.
SPEED REF. Speed Current Voltage
Reg. Inverter Motor
Reg. Control
TORQUE REF. V ang
Encoder
SLIP
Adaptive
Controller
AUTOTUNE PARAMETERS
SPEED FEEDBACK
Torque Reference Vector FV When the PowerFlex 700 Vector Control drive is operated in
Torque mode, an external signal is used for a Torque reference. Refer to Figure 60.
Figure 60
Torque Ref 1 is then divided by [Torq Ref A Div], parameter 430. This defines
the scaled Torque Ref A.
[Torque Ref B], parameter 431 is used to supply an external reference for how
much torque is desired. The scaling of this parameter is from –800 to +800, via
[Torq Ref B Hi] and [Torq Ref B Lo].
The Torque Ref B is then multiplied by [Torq Ref B Mul], parameter 434. This
defines the scaled Torque Ref B.
Once the scaling is complete on both Torque Ref A and Torque Ref B, the output
is summed to create the external torque reference
Troubleshooting See Faults on page 101 and Advanced Tuning on page 12.
Unbalanced or Refer to “Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)
Ungrounded Distribution AC Drives,” publication DRIVES-IN001 for detailed information on
Unbalanced or Ungrounded Distribution Systems.
Systems
User Sets After a drive has been configured for a given application the user can store a copy
of all of the parameter settings in a specific EEPROM area known as a “User Set.”
Up to 3 User Sets can be stored in the drives memory to be used for backup, batch
“switching” or other needs. All parameter information is stored. The user can
then recall this data to the active drive operating memory as needed. Each User
Set can also be identified with a programmable name, selected by the user for
clarity.
Two operations are available to manage User Sets, “Save To User Set” and
“Restore From User Set.” The user selects 1, 2, or 3 as the area in which to store
data. After data is successfully transferred, “Save User Set” returns to a value of 0.
To copy a given area back into the active EEprom memory, the user selects Set 1,
2, or 3 for “Restore User Set.” After data is successfully transferred, “Restore User
Set” returns to a value of 0. When shipped from the factory all user sets have the
same factory default values. Reset Defaults does not effect the contents of User
Sets.
Important: User Sets can only be transferred via the HIM. No provisions exist
for control via digital I/O or communications module.
Figure 61 User Sets
Reset Defaults
PowerBoard
EEprom
Drive Rating & Motor Non Drive Rating & Motor
Factory Parameters Reset Parameters
Flash Memory
Default Data 1 Active EE
SaveUserSet
400V
2
Default Data 1 User Set 1
Save
User set
480V
3
Default Data Active EE 2 User Set 2
Restore
User set
3 User Set 3
RestoreUserSet
Load
Application Flash Memory
Set
Application Set
Voltage Class PowerFlex drives are sometimes referred to by voltage “class.” This class identifies
the general input voltage to the drive. This general voltage includes a range of
actual voltages. For example, a 400 Volt Class drive will have an input voltage
range of 380-480VAC. While the hardware remains the same for each class,
other variables, such as factory defaults, catalog number and power unit ratings
will change. In most cases, all drives within a voltage class can be reprogrammed
to another drive in the class by resetting the defaults to something other than
“factory” settings. The [Voltage Class] parameter can be used to reset a drive to a
different setup within the voltage class.
As an example, consider a 480 volt drive. This drive comes with factory default
values for 480V, 60 Hz with motor data defaulted for U.S. motors (HP rated,
1750 RPM, etc.) By setting the [Voltage Class] parameter to “low Voltage” (this
represents 400V in this case) the defaults are changed to 400V, 50 Hz settings
with motor data for European motors (kW rated, 1500 RPM, etc.). Refer to
Figure 61.
Notes:
EMC L
Directive 63
Language 111
EMC Instructions 63
Language Parameter 111
Encoder 165
Language Select, HIM 107
ESD, Static Discharge 10
Linking Parameters 111
Exclusive Ownership 125
Local Mask 113
Local Owner 126
F Logic Mask 113
Fan Curve 100 Low Voltage Directive 63
Fault Clr Mask 113
Fault Configuration 103, 157 M
Fault Queue 101
Faults 101 Manual Preload 36
Masks 113
Feedback Select 162
Max Speed 170
Flux Up 104
Maximum frequency 171
Flux Up Mode 104
Min Mode/Max Mode 174
Flying Start En 106
MOP Mask 113
Flying Start Gain 106
MOP Owner 126
Flying StartGain 106
Motor Cable Lengths 61
Fuses 106
Motor Nameplate 116
Motor NP FLA 116
G Motor NP Hz 116
General Precautions 10 Motor NP Power 116
Group Motor NP Pwr Units 116
Digital Inputs 71, 72 Motor NP RPM 116
Digital Outputs 71, 88 Motor NP Volts 116
Power Loss 130 Motor Overload 117
Speed References 16 Motor Overload Protection 119
Motor Start/Stop 120
H
HIM Memory 107 N
HIM Operations 107
Notch Filter 121
Human Interface Module
Language 107
Password 107 O
User Display 108
Output Contactor
Start/Stop 120
I Output Current 123
I/O Wiring Output Devices
Analog 28 Contactors 120, 123
Digital 70 Output Reactor 123
Input Contactor Output Frequency 124
Start/Stop 120 Output Power 124
Input Devices 108 Output Reactor 123
Input Modes 109 Output Voltage 124
Input Power Conditioning 110 Overspeed 124
Owners 125
J
Jog 110 P
Jog Mask 113 Parameter access level 127
Jog Owner 126
T
Terminal Designations 29
Test Points 200
Testpoint 1 Sel 200
Testpoint x Data 200
Thermal Manager Protection 97
Thermal Regulator 200
Torque Performance Modes 201
Torque Ref x Sel 205
Torque Reference 204
Torque Regulation Mode 173
Torque Setpoint2 205
Trim 28
Trim Out Select 149
Troubleshooting 205
U
User Display, HIM 108
User Sets 206
V
Vector Control 203
Vector Feedback 162
Vector Speed Feedback 162
Voltage class 207
Voltage Tolerance 207
Volts/Hertz 201
W
Watts Loss 207
Wiring Examples 29
Z
Zero Torque Mode 175
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer
TechConnectSM support programs. For more information, contact your local distributor or Rockwell Automation
representative, or visit http://www.rockwellautomation.com/support/.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this
manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local
Rockwell Automation representative.
Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400