Chilled Water Pump Head Calcultion: Section Valves & Fitings Pipe Size (Inch) Description of The Pipe Run

This document summarizes the piping layout and pump head calculations for a chilled water system. It includes a table describing the pipe runs between various air handling units (AHUs) and components, including pipe size, valves, fittings. It then shows the flow rate, pipe length, number of valves and fittings to calculate the friction head loss for each run. The total equivalent pipe length is calculated and used to determine the total dynamic head and pump power required. The pump must be rated for a head of 17.8 feet to overcome all friction losses and provide a 15% safety factor.

Uploaded by

ganesh gund
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
453 views3 pages

Chilled Water Pump Head Calcultion: Section Valves & Fitings Pipe Size (Inch) Description of The Pipe Run

This document summarizes the piping layout and pump head calculations for a chilled water system. It includes a table describing the pipe runs between various air handling units (AHUs) and components, including pipe size, valves, fittings. It then shows the flow rate, pipe length, number of valves and fittings to calculate the friction head loss for each run. The total equivalent pipe length is calculated and used to determine the total dynamic head and pump power required. The pump must be rated for a head of 17.8 feet to overcome all friction losses and provide a 15% safety factor.

Uploaded by

ganesh gund
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

CHILLED W

Description of the Pipe


Section Valves & Fitings Pipe Size (Inch)
Run
PIPE 5
GATE VALVE 5
BUTTERFLY VALVE 5
A-I PUMP DISCHAGE TO AHU-1 STRAINER 5
ELBOW 5
NRV 5
DRV 5
I-J HEADER PIPE PIPE 5
PIPE 4
J-k HEADER PIPE REDUCER 4
NO REDUCTION TEE 4
PIPE 3
GATE VALVE 3
K-L AHU-3 LINE
STRAINER 3
REDUCER 3
CHILLED WATER PUMP HEAD CALCULTION
Flow Stright Length No of Valves and
Friction ( ft/100ft)
GPM LPS ft m Fittings
480 30.2784 66 20.1168 3.895 0
480 30.2784 0 0 3.895 1
480 30.2784 0 0 3.895 2
480 30.2784 0 0 3.895 1
480 30.2784 0 0 3.895 5
480 30.2784 0 0 3.895 1
480 30.2784 0 0 3.895 1
360 22.7088 12 3.6576 2.261 0
240 15.1392 14 4.2672 3.255 0
240 15.1392 0 0 3.255 1
240 15.1392 0 0 3.255 1
120 7.5696 16 4.8768 3.433 0
120 7.5696 0 0 3.433 1
120 7.5696 0 0 3.433 1
120 7.5696 0 0 3.433 1

BHP= (GPM* HEAD (FT)* SPECIFIC HEAT OF WATER)/(3960*EFFICENCY OF PUMP)

GPM 480
HEAD 17.76795885
SPECIFIC HEAT OF WATER =1
EFFCIENCY OF PUMP= 85%

BHP 2.53375527272727
HP 2.91381856363636
KW 2.17370864847273
Equivalent Length Total Equivalent Length
(ft) in Stright Pipe (ft) Head Loss
0 66 2.5707
6 6 0.2337
6 12 0.4674
80 80 3.116
8.2 41 1.59695
50 50 1.9475
58 58 2.2591
0 12 0.27132
0 14 0.4557
3.8 3.8 0.12369
6.7 6.7 0.218085
0 16 0.54928
3.2 3.2 0.109856
42 42 1.44186
2.6 2.6 0.089258

PUMP HEAD LOSS (FT) 15.450399


15 SAFETY 2.31755985
TOTAL HEAD LOSS(FT) 17.76795885
TOTAL HEAD LOSS(M) 5.41567385748