0% found this document useful (0 votes)
144 views1 page

Ec Axial Fan - Axiblade: Nominal Data

The document summarizes the specifications of an EC axial fan model W3G800-KS39-03, including its: - Nominal voltage range of 3~380-480V, frequency of 50/60Hz, and speed of 940 RPM - Power of 1950W, current of 3.1A, and mass of 39.85kg - Airflow of 7500 cubic meters/hour at a static pressure of 8.41 Pascals

Uploaded by

Aykut Bacak
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
144 views1 page

Ec Axial Fan - Axiblade: Nominal Data

The document summarizes the specifications of an EC axial fan model W3G800-KS39-03, including its: - Nominal voltage range of 3~380-480V, frequency of 50/60Hz, and speed of 940 RPM - Power of 1950W, current of 3.1A, and mass of 39.85kg - Airflow of 7500 cubic meters/hour at a static pressure of 8.41 Pascals

Uploaded by

Aykut Bacak
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

EC axial fan - AxiBlade

sickled blades (S series)


with guard grille W3G800-KS39-03(mID:185106)

Nominal data
Nominal voltage range V 3~ 380 .. 480 Air performance measured as per ISO 5801 Installation category A.
For detailed information on the measuring setup, please contact ebm-papst.
Frequency Hz 50/60 Suction-side noise levels: LwA measured as per ISO 13347 / LpA with 1 m distance to fan axis.
Fan speed n min-1 940 The values given are valid under the measuring conditions mentioned above and may vary
Input power Ped W 1950 according to the actual installation situation.
With any deviation from the standard setup, the specific values have to be checked and
Current draw I A 3.1 reviewed with the unit installed.
Mass kg 39.85 qv = airflow pfs = static pressure
Min. ambient temp. °C -25 pf = total pressure (static + dynamic) n = fan speed
Max. ambient temp. °C 60 Ped = electrical input power SFP = specific fan power

Max. back pressure Pa 220 ηed = qv x pf / Ped (overall efficiency) ηes = overall static efficiency
I = current draw LWA(A,in) = sound power inlet
Protection class 55
LWA(A,out) = sound power outlet FEIs = Fan energy index static
Approvals CSA C22.2 Nr.77 + CAN/CSA-E60730-1
LWA(A,in+out) = sound power inlet+outlet
UL 1004-7 + 60730-1
ρcalculated to = air density converted to the application
Number of blades 5 ρmeasured at = air density measured environment
Mounting position Shaft horizontal or rotor on bottom Ucontrol = control voltage
rotor on top on request

Data in operating point; (3) no guaranteed accuracy


values areqvwith guard grille out
[cfm]
qv m³/h 7500 5 000 10 000 15 000
280
qv cfm 4414 1.1
260 1.05
pfs Pa 8.41
1
pf Pa 17.7 240 0.95
n min-1 313.2 220 0.9
Ped W 73.91 0.85
200 0.8
SFP kW/(m³/s) 0.0355
0.75
ηed % 49.9 180
0.7
ηes % 23.7 160 0.65

pfs_ [in. wg]


pfs [Pa]

I A 0.119 0.6
140 0.55
LWA(A,in;out;in+out) dB(A) 47.7; 49; 51.4
0.5
Ucontrol V 3.3(³) 120
0.45
FEIs 7.36 100 0.4
Settings 0.35
80
ρcalculated to kg/m³ 1.15 0.3
60 0.25
ρmeasured at kg/m³ 1.16
0.2
40 0.15
0.1
20
0.05
0
7 000 12 000 17 000 22 000 27 000
qv [m³/h]

90 90
80 80
Sound power in dB

Sound power in dB

70 70
57.7
55.5

60 60
47.7

47.2

49
46.5
45.8

44.8
44.3

50 50
41.9

44

40.6
40.3

39.9
33.4

40 40
33

23.3

30 30
21.6

20 20
10 10
63 125 250 500 1000 2000 4000 8000 LwA 63 125 250 500 1000 2000 4000 8000 LwA
Octave band center frequency on the suction side in Hz Octave band center frequency on the pressure side in Hz
ebm-papst FanScout v3.0.3.390 collection: 9047/11.06.2019 printed: 3/16/2020 11:32:18 PM · Page 1 / 1

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com