EASTRON SMART X96-5 User Manual V1.4

1. The EASTRON SMART X96-5 is an energy analyzer that measures electrical parameters for single and three phase systems, including voltage, current, power, energy, harmonics, and maximum demand. 2. It has an LCD display, communication via RS485 Modbus RTU, and two pulse outputs. Measurement parameters include kWh, kVarh, voltage THD, and individual harmonic distortion up to the 63rd harmonic. 3. The user manual provides instructions on installation, operation, and configuration of the SMART X96-5, which allows measurement of systems from 100V to 500kV with CT and PT scaling from 5A to 9999A.

Uploaded by

mica
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
844 views26 pages

EASTRON SMART X96-5 User Manual V1.4

1. The EASTRON SMART X96-5 is an energy analyzer that measures electrical parameters for single and three phase systems, including voltage, current, power, energy, harmonics, and maximum demand. 2. It has an LCD display, communication via RS485 Modbus RTU, and two pulse outputs. Measurement parameters include kWh, kVarh, voltage THD, and individual harmonic distortion up to the 63rd harmonic. 3. The user manual provides instructions on installation, operation, and configuration of the SMART X96-5, which allows measurement of systems from 100V to 500kV with CT and PT scaling from 5A to 9999A.

Uploaded by

mica
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 26

EASTRON SMART X96-5 User Manual V1.

SMART X96-5
Smart Energy Analyzer for Single and Three Phase Electrical Systems

● Measures kWh, kVarh, kW, kVar, kVA, P,


F, PF, Hz, dmd, V, A, etc.
● Bi-directional Measurement IMP & EXP
● Energy Information of Each Phase
● Two Pulse Outputs
● RS485 Modbus RTU
● Total Harmonic Distortion of Voltage and Current
● 2nd~63rd Individual Harmonic Distortion
● Backlit LCD Display for Full Viewing Angles
● Class 1 , Class 0.5S
● Bar Graph for Power Indication
● Dimension 96x96mm
● 1A/5A CT connection
EASTRON SMART X96-5 User Manual V1.3

Introduction
The multifunction energy analyzer SMART X96 series is a top new-generation intelligent panel meter, used not only in the
electricity transmission and power distribution system, but also in the power consumption measurement and analysis in
high voltage intelligent power grid.
This document provides operating, maintenance and installation instructions for the Eastron SMART X96 series. The unit
measures and displays the characteristics of single phase two wires, three phase three wires and three phase four wires
supplies, including voltage, frequency, current, power and active and reactive energy, imported or exported, Harmonic,
Power factor, Max. Demand etc. Energy is measured in terms of kWh, kVArh. Maximum demand current can be measured
over preset periods of up to 60minutes. In order to measure energy, the unit requires voltage and current inputs in
addition to the supply required to power the product. The requisite current input(s) are obtained via current transformers
The SMART X96 can be configured to work with a wide range of CTs, giving the unit a wide range of operation. Built-in
interfaces provide pulse and RS485 Modbus RTU outputs. Configuration is password protected.

1. Unit Characteristics
1. 1 The Unit can measure and display:
● Line voltage and THD% (total harmonic distortion) of all phases
● 2~63rd voltage IHD% (Individual Harmonic distortion) of all phases
● Line Frequency
● Currents, Current demands and current THD% of all phases
● 2~63rd current IHD% of all phases
● Active power, reactive power, apparent power, maximum power demand and power factor
● Active energy imported and exported
● Reactive energy imported and exported
● Energy of each phase

1.2 The unit has password-protected set-up screens for:


● Communication setting: Modbus address, Baud rate, Parity, Stop bit
● CT setting: CT 1 ( Primary) , CT2 ( Secondary), CT rate
● PT setting: PT1 (Primary), PT2 (Secondary) , PT rate
● Pulse setting: Pulse output 1, Pulse rate, Pulse time
● Demand setting: Demand interval time, demand method
● Time setting: Backlit time, display scroll time
● System configuration: System type, System connect, Change password, Auto display scroll
● Reset

1.3 CT and PT

CT1 (primary current):5~9999A


CT2 (secondary current): 1A or 5A
PT1 (primary voltage): 100V ~ 500,000V
PT2 (secondary voltage): 100 to 480 V AC (L-L)

1.4 RS485 Serial-Modbus RTU

This unit uses a RS485 serial port with Modbus RTU protocol to provide a means of remote monitoring and controlling.
Please check the Part 4.2 for the details of setting.
EASTRON SMART X96-5 User Manual V1.3

1.5 Pulse output

Two pulse outputs indicate real-time energy measurement. Pulse output 1 is configurable, pulse output 2 is fixed to active
energy, 3200imp/kWh.

2.Start up screens
The first screen lights all LED segments and can be used as a display LED check

The second screen indicates the software version of the unit.


(the left picture is just for reference)

The unit performs a self-test and the screen indicates if the test is passed.

After a short delay, the default measurement screen appears.


EASTRON SMART X96-5 User Manual V1.3

3. Buttons and Displays

3.1 Buttons Function

Buttons Click Press 2S

➢ Displays power, voltage, current and ➢ Automatic Scroll display ON / OFF


energy information of each phase
➢ Escape the menu

➢ Display Voltage and current information of ➢ Individual Harmonic Distortion of Voltage up


the selected system type. (3p4w, 3p3w to 63rd
and 1p2w)
➢ Left side move

➢ Display power factor, frequency, Max. ➢ Individual Harmonic Distortion of Current up


Demand. to 63rd
➢ Up page or add value

➢ Display active power, reactive power and


apparent power information of the
selected system type.
➢ Down page or reduce value

➢ Display total / import / export active or ➢ Set-up mode entry


reactive energy information of the ➢ Confirmation
selected system type.
➢ Right side move

3.2 Display Mode Screen Sequence

Click button 3 Phase 4 Wire 3 Phase 3 Wire 1 Phase 2 Wire

Screen Parameters Screen Parameters Screen Parameters

1 Phase 1 – Power 1 Phase 1 – Power 1 Phase 1 – Power


Voltage Voltage Voltage
Current Current Current
kWh kWh kWh

2 Phase 2 – Power 2 Phase 2 – Power


Voltage Voltage
Current Current
kWh kWh

3 Phase 3 – Power 3 Phase 3 – Power


Voltage Voltage
Current Current
kWh kWh
EASTRON SMART X96-5 User Manual V1.3

4 Phase 1 – Power 4 Phase 1 – Power 2 Phase 1 – Power


Voltage Voltage Voltage
Current Current Current
kVarh kVarh kVarh

5 Phase 2 – Power 5 Phase 2 – Power


Voltage Voltage
Current Current
kVarh kVarh

6 Phase 3 – Power 6 Phase 3 – Power


Voltage Voltage
Current Current
kVarh kVarh

1 Voltage L1-N 1 Voltage L1-N


Voltage L2-N
Voltage L3-N

2 Voltage L1-L2 1 Voltage L1-L2


Voltage L2-L3 Voltage L2-L3
Voltage L3-L1 Voltage L3-L1

3 Current L1 2 Current L1 2 Current L1


Current L2 Current L2
Current L3 Current L3
Current Neutral

4 THD% of Voltage L1 3 THD% of Voltage L1-2 3 THD% of Voltage L1


THD% of Voltage L2 THD% of Voltage L2-3
THD% of Voltage L3 THD% of Voltage L3-1

5 THD% of Current L1 4 THD% of Current L1 4 THD% of Current L1


THD% of Current L2 THD% of Current L2
THD% of Current L3 THD% of Current L3

6 Phase Sequence 5 Phase Sequence

1 Total Power Factor 1 Total Power Factor 1 Total Power Factor


Frequency Frequency Frequency

2 PF L1 2 PF L1
PF L2 PF L2
PF L3 PF L3

3 Max. DMD of Current 3 Max. DMD of Current 2 Max. DMD of Current


L1 L1 L1
Max. DMD of Current Max. DMD of Current
L2 L2
Max. DMD of Current Max. DMD of Current
L3 L3

4 Max. DMD of W 4 Max. DMD of W 3 L1 Max. DMD of W


Max. DMD of Var Max. DMD of Var L1 Max. DMD of Var
Max. DMD of VA Max. DMD of VA L1 Max. DMD of VA

1 Active Power L1 1 Active Power L1


Active Power L2 Active Power L2
Active Power L3 Active Power L3
EASTRON SMART X96-5 User Manual V1.3

2 Reactive Power L1 2 Reactive Power L1


Reactive Power L2 Reactive Power L2
Reactive Power L3 Reactive Power L3

3 Apparent Power L1 3 Apparent Power L1


Apparent Power L2 Apparent Power L2
Apparent Power L3 Apparent Power L3

4 Total Active Power 4 Total Active Power 1 L1 Active Power


Total Reactive Power Total Reactive Power L1 Reactive Power
Total Apparent Power Total Apparent Power L1 Apparent Power

1 Total kWh 1 Total kWh 1 Total kWh

2 Total kVarh 2 Total kVarh 2 Total kVarh

3 Import kWh 3 Import kWh 3 Import kWh

4 Export kWh 4 Export kWh 4 Export kWh

5 Import kVarh 5 Import kVarh 5 Import kVarh

6 Export KVarh 6 Export KVarh 6 Export KVarh

3.3 Individual Harmonic Distortion:

Press the button for 2 seconds to check Harmonic distortion of Voltage

2~63rd Harmonic Distortion of Voltage

Press the button for 2 seconds to check Harmonic distortion of Current

2~63rd Harmonic Distortion of Current


EASTRON SMART X96-5 User Manual V1.3

4. Setting-Up
Ma in scre en Pa ssw ord En tr y COMS (C ommun ic ati on) Add r(Ad dre ss) Entry Va lu e betw ee n:
1~ 24 7

b AUd (Ba ud ra te ) Sel ect fr om: (b ps)


240 0
48 00
960 0
19.2 k
38.4 k
PAr I (p a ri ty) Sel ect fr om:
NONE
EVEN
Od d

S tOP ( sto p bi t) Sel ect fr om:


1
2

CT (Syste m Co nfi gur ati on) CT 2 Sel ec t from:


5A
1A
0.1 A
0.33 3V

CT rAtE (W he n CT2=5A/1 A) Entry CT R atio Val ue be twe en :


1~99 99

CT 1 (W h en CT2=0.1 A/0.33 3V) Entry CT 1 Val ue be twee n:


1~99 99

PT (System Co nfig ura tio n) PT 2 Entry Sec ond ar y Vol tag e betwe en :
10 0~50 0

PT rAtE En tr y PT Ra tio Val ue be twe en:


1 ~9 9 9 9

PU LS (Pul se) P U L S OU t 1 Se le ct fro m:


To tal kWh
To tal kVarh
Imp kWh
Exp kWh
Imp kVarh
Exp kVarh

PU L S R A tE Se le ct fro m:
0 .0 01
0 .0 1
0 .1
1
10
1 00
1 000 kWh( kVA rh)/i mp

PU L S tIM E Se le ct fro m:
1 00 mS
2 00 mS
6 0 mS

dMd (De man d) d It (De man d In terv al Ti me) Se le ct fro m:


6 0 mi nu tes
3 0 mi nu tes
1 5 mi nu tes
1 0 mi nu tes
8 mi nute s
5 mi nute s
OFF

d Md MEth (d ema nd meth od ) Se le ct fro m:


sl id in g
fixe d

tIME (Ti me) bAC k LIt (bac klight) S el ect fro m:


1 20 min ute s
6 0 mi nu tes
3 0mi nu tes
1 0 mi nu tes
5 mi nu te s
ON
OFF

d ISP SCr L (d isp la y sc rol l) Se le ct fro m:


1~25 5 s

S yS (Sys te m Confi gu rati on ) Sy S tyPE(sy stem typ e) Se le ct fro m:


3P 4
3 P3
1P 2
1P 3

SyS COC t (syste m co nne ct) P h-1 (ph ase 1) Sel ec t from:
F rd /r Ev ( fo rw a rd / re ve r se )

Ph -2( pha se 2) Se le ct from:


F rd /r Ev ( fo rw a rd /r e ve r se )

P h-3 (ph ase 3) Sel ect fr om:


Fr d /rE v (f o rw a rd /r e ve r se )

PASSWOrd (Ch an ge Pass wor d) En tr y Pa sswo rd Betwe en :


00 00 ~9 99 9

AU tO dISP SCr L Se le ct from:


On
OFF

rSEt (R ese t) Sel ect fro m:


AL L
En Gy
d Md
EASTRON SMART X96-5 User Manual V1.3

4.1 Password Entry

Setting-up mode is password protected, so you must enter the correct password.
By firmly press the button for 2 seconds, the password screen appears. The
default password is 1000. If an incorrect password is entered, the display shows
ERR.

4.2 Communication

The RS485 port can be used for communications using Modbus RTU protocol.
Parameters such as Address, Baud rate, Parity, Stop bit can be selected.

Long press to enter the Address option.

4.2.1 Address

An RS485 network can accommodate up to 255 different devices, each identified


by an address.
Modbus address range 001~247
Default 001

Long press to enter the selection routine, the address setting will flash. Use

and , to set the address with the range 001~247. And press

for confirmation.

4.2.2 Baud rate

Baud rate options: 2400 4800 9600 19200 38400 (bps).


Default: 9600bps

From the Set-up menu, Use and to select the Baud rate options.

Long press to enter the selection routine. The Baud Rate setting will flash.

Use and to choose Baud Rate.


EASTRON SMART X96-5 User Manual V1.3

Example shows:
SET Baud rate 19200 (bps)

And long press for confirmation.

4.2.3 Parity

Parity Options: NONE, EVEN, ODD.


Default Parity : NONE
Note that if parity is set to ODD or EVEN, Stop Bits will be set to 1 and cannot be
changed.

From the Set-up menu, Use and to select the Parity options.

Long press to enter the selection routine. The Parity setting will flash. Use

and to choose Parity.

Example shows:
Set Parity: EVEN

And long press for confirmation. Press to return the main set up menu.

Example shows:
Set Parity: Odd

And long press for confirmation. Press to return the main set up menu.
EASTRON SMART X96-5 User Manual V1.3

4.2.4 Stop bit

Stop Bit options: 1 or 2.


Default Stop Bit : 1
Note that if parity is set to ODD or EVEN, Stop Bits will be set to 1 and cannot be
changed.

From the Set-up menu, Use and to select the Stop Bit options.

Long press to enter the Stop Bit routine. The Stop Bit setting will flash. Use

and to choose Stop Bit.

Example shows
Set Stop bit 2

And long press for confirmation. Press to return the Communication


set up menu.

4.3 CT

From the main Set-up menu, Use and to select the CT option.

4.3.1 CT2

Set secondary current input the meter


Options: 5A or 1A
Default CT2: 5A

Long press to enter the CT2 routine. Press for 2s, the CT2 setting will

flash. Use and to choose CT2 with 5A or 1A.


EASTRON SMART X96-5 User Manual V1.3

Example shows :
Set CT2 1A

And long press for confirmation.

4.3.2 CT1

Set primary current input the meter


Options: 1~9999
Default CT1: 5A

Long press to enter the CT1 routine. Press for 2s, the CT1 setting will

flash. Use and to choose CT1 with 1~9999.

And long press for confirmation.

Example shows :
Set CT1 100A

And press for confirmation. Press to return the CT set up menu.

4.4 PT

The PT option sets the secondary voltage of the voltage transformer (PT) that give
into the meter and the PT rate between the primary voltage to the secondary
voltage.

For example: if the PT connect to the meter is 10000/100V (Primary voltage is


10000V, secondary voltage is 100V), then the PT rate is 100.

Long press to enter the PT2 routine. Press , the PT2 setting will flash.

Use and , to choose PT2 with 174~480.


EASTRON SMART X96-5 User Manual V1.3

4.4.1 PT2
Set secondary voltage input the meter
Range: 100V ~ 480V
Default: 230V

And long press for confirmation.

4.4.2 PT1
Set primary voltage input the meter
Range: 174V ~ 500000V
Default: 400V

Then press to enter the PT2 routine. press for 2s, the PT2 setting will

flash. Use and , to select PT2. And long press for

confirmation. Press to return the PT set up menu.

4.5 Pulse

This option allows you to configure the pulse output. The output can be set to provide a pulse for a defined amount of
energy active or reactive.

This option sets the pulse output type, pulse rate, duration time.

From the Set-up menu, Use and to select the Pulse option.
EASTRON SMART X96-5 User Manual V1.3

4.5.1 Pulse output1

Pulse output 1 setting


Output type options: total kwh, import kwh, export kwh, total kVarh, import kVarh,
Export kVarh.
Default: total kWh

Long press to enter the PT Pulse Output 1 routine.

Example shows:
Pulse Output 1: import kWh
Options: total kWh, total kVarh, imp kWh,exp kWh, imp kVarh, exp kVarh.

press for 2s,the setting will flash. and to choose Options. And long

press for confirmation.

4.5.2 Pulse rate

Pulse rate options: 0.001 , 0.01 , 0.1 , 1, 10, 100, 1000 kWh / kVarh per Pulse
Default : 0.001 kWh / kVarh per pulse

Use and to select Pulse Rate option. Long press , the setting will

flash. Use and to choose Options. And long press for


confirmation.

Example shows:
Pulse rate: 0.01
EASTRON SMART X96-5 User Manual V1.3

4.5.3 Pulse Duration

Pulse Duration time option 200, 100, 60mS


Default : 100mS

Use and to enter Pulse duration routine. Long press , the setting

will flash. Use and to choose Options. And long press for

confirmation. Press to return the Pulse Duration set up menu.

Example shows:
Pulse time 200mS

Example shows:
Pulse time 60mS

4.6 Demand

This sets the period in minutes over which the current and power readings are integrated
for maximum demand measurement. The options are: OFF, 5, 8, 10, 15,30, 60 minutes.

From the Set-up menu, Use and to select the Demand option.
EASTRON SMART X96-5 User Manual V1.3

4.6.1 Demand interval time

The screen will show the currently selected integration time.


Default is 60

Long press to enter the DIT routine. Press for 2s, the setting will

flash. Use and to choose Options. And long press for


confirmation.

4.6.2 Demand method

The screen shows the Demand calculation method: Slid


Options: Fix and Slid

Use and to enter Demand calculation method.

Long press to enter the routine. The setting will flash. Use and to

choose Options. And long press for confirmation. Press to return the
Demand set up menu.

4.7 Time

This option sets the backlight lasting time and display scroll time.

From the Set-up menu, Use and to select the Time option.
EASTRON SMART X96-5 User Manual V1.3

4.7.1 Backlight time

The meter provides a function to set the backlit lasting time.


Options: ON/OFF/5/10/30/60/120 minutes.
Default: 60
If it is seated as 5, the backlit will be off in 5 minutes.
Note: if it is set as ON, the backlit will always be on.

Long press to enter the Backlit time routine. Press for 2s, the setting

will flash. Use and to choose Options. And long press for
confirmation.

4.7.2 Display scroll time

The meter provides a function to set the Display scroll time.


Options: 1~255s
Default: 5
If it is seated as 5, the display will scroll every 5s.

Use and to select Display scroll time option. Press for 2s, the

setting will flash. Use and to choose Options. And Long press for

confirmation. Press to return the Time set up menu.

4.8 System

The Unit has a default setting of 3 phase 4 wire ( 3p4w). Use this section to set the
type of electrical system.
Options: 3P34,3P3W,1P2W

From the Set-up menu, Use and to select the System option
EASTRON SMART X96-5 User Manual V1.3

4.8.1 System type

The screen shows the currently selected power supply is three phase four wire

Long press to enter the System type routine. Press for 2s, the setting will

flash. Use and to choose Options. And Long press for


confirmation.

Example shows:
The screen shows the currently selected power supply is three phase three wire

Example shows:
The screen shows the currently selected power supply is single phase two wire

4.8.2 System connect

This unit provides a function with Reverse connected current inputs correction
setting.

Use and to select the correction option.


EASTRON SMART X96-5 User Manual V1.3

Options: Frd ( forward ) and rEv ( reverse)


The default is FRD ( forward )

Long press to enter the Phase 1 correction. Press for 2s, the setting will

flash. Use and to choose Options. And long press for


confirmation.

Press enter Phase 2 correction. Press for 2s, the setting will flash. Use

and to choose Options. And long press for confirmation.

Press enter Phase 3 correction. Press for 2s, the setting will flash. Use

and to choose Options. And long press for confirmation. Press

to return the System set up menu.

4.8.3 Change password

This unit provides a function with password setting.


Default: 1000
Options:0000~99999

Use and to select the change password option.

Press for 2s, the setting will flash. Use and , to choose

Options. And long press for confirmation.


EASTRON SMART X96-5 User Manual V1.3

4.8.4 Automatic display scroll

This unit provides a function with automatic display scroll setting.


Options: on and off
There are two ways:

1 Use and to select the automatic display scroll option. Press

for 2s, the setting will flash. Use and to choose options “On” or

“Off”. And long press for confirmation.

2 Escape the Setting menu. Long press for 2 secs. For example,
the screen shows the currently selected Automatic Scroll display ON.

Long press for 2 secs, then the screen shows the currently selected Automatic
Scroll display OFF.

4.9 Reset

This unit provides a function with reset for Energy and Demand, and ALL.

Use and to select the Reset option.


EASTRON SMART X96-5 User Manual V1.3

Long press to enter the Energy routine. Press for 2s, the setting will

flash, then long press to confirm the reset.

Then press enter Demand Reset routine. Press for 2s, the setting will

flash, then long press to confirm the reset.

Then press enter ALL Reset routine. Press for 2s, the setting will flash,

then long press to confirm the reset.

Press to return the Reset set up menu.

5. Specification

5.1 Measured Parameters

The unit can monitor and display the following parameters of a single phase, 3-phase 3-wire or 3-phase 4-wire supply.
5.1.1 Voltage and Current

Phase to neutral voltage 100 to 276 V a.c ( not for 3p3w supplies)
Voltage between phases 174 to 480V a.c (3p supplies only)
Installation Category III (600V)
Rated Current: 1A or 5A
Current input range: 5%~120% Ib
Percentage total voltage harmony distortion ( THD%) for each phase to N
Percentage current harmonic distortion for each phase
Current on each phase

5.1.2 Power factor and Frequency and Max. demand

Frequency in Hz (45~66Hz)
Instantaneous power: Power 0 to 999MW
Reactive Power 0 to 999MVAr
EASTRON SMART X96-5 User Manual V1.3

Volt-amps 0 to 999 MVA


Maximum demanded power since last Demand reset Power factor
Maximum demand current, since the last Demand reset (three phase supplies only)

5.1.3 Energy Measurements

Imported active energy 0 to 9999999.9 kWh


Exported active energy 0 to 9999999.9 kWh
Imported reactive energy 0 to 9999999.9 kVArh
Exported reactive energy 0 to 9999999.9 kVArh
Total active energy 0 to 9999999.9 kWh
Total reactive energy 0 to 9999999.9 kVArh
5.2 Accuracy

● Voltage VL-N 0.5%


● Voltage VL-L 0.5%
● Current 0.5%
● Frequency 0.1
● Active power 0.5%
● Apparent power 0.5%
● Reactive power 1%
● Power factor 0.01
● Active energy IEC62053-21 Cl.1 or IEC62053-22 Cl.0.5S
● Reactive energy IEC62053-23 Cl.2
● THD 1%

5.3 Display

Liquid crystal display with backlit (360 full viewing angles)


4 lines, 4 digits per line to show electrical parameters


5th line, 8 digits to show energy
Bar graph for power indication
Display update time: 1 sec. for all parameters
Display scrolling: automatic or manual (Programmable)

5.4.1 Pulse Output

The pulse outputs can be set to generate pulses to represent kWh/kVarh


Pulse constant: 0.001/0.01/0.1/1/10/100/1000 kwh or kVarh per Pulse
Pulse width: 200/100/60 ms.
The pulse output is passive type, complies with IEC62053-31 Class A.

5.4.2 Modbus RTU

Interface standard and protocol: RS485 and MODBUS RTU


Communication address: 1~247
Transmission mode: Half duplex
Data type: Floating point
Transmission distance: 1000m Maximum
Transmission speed: 2400bps~38400bps
Parity: None (default), Odd, Even
Stop bits: 1 or 2
EASTRON SMART X96-5 User Manual V1.3

Response time: <100 mS

For Modbus RTU, the following RS485 communication parameters can be configured from the Set-up menu:
Baud rate 2400, 4800, 9600, 19200, 38400
Parity none/odd/even
Stop bits 1 or 2
RS485 network address nnn – 3-digit number, 001 to 247

5.4.3 Environment

● Operating temperature -25°C to +55°C


● Storage temperature -40°C to +70°C
● Relative humidity 0 to 95%, non-condensing
● Altitude <2000 meters
● Vibration 10Hz to 50Hz, IEC 60068-2-6, 2g
● Pollution degree II

5.4.4 Mechanics

● DIN rail dimensions 96x 96mm (WxH)


● Mounting Panel mounting
● Material Self-extinguishing UL 94 V-0

6. Dimensions
EASTRON SMART X96-5 User Manual V1.3

7. Wiring Diagram

(3 phase 4 wires)
EASTRON SMART X96-5 User Manual V1.3

(3 phase 3 wires)

(1 phase 2 wires)
EASTRON SMART X96-5 User Manual V1.3

Jiaxing Eastron Electronic Instruments Co.,Ltd.


No.1369,Chengnan Rd. Jiaxing, Zhejiang, 314001, China
Tel: +86-573-83698881 83698882
Fax: +86-573-83698883
Email: [email protected]
www.eastron.com.cn
www.eastrongroup.com