Smart Energy Analyzer for Single and Three Phase Electrical Systems
Introduction
The multifunction energy analyzer SMART X96 series is a top new-generation intelligent panel meter, used not only in the
electricity transmission and power distribution system, but also in the power consumption measurement and analysis in
high voltage intelligent power grid.
This document provides operating, maintenance and installation instructions for the Eastron SMART X96 series. The unit
measures and displays the characteristics of single phase two wires, three phase three wires and three phase four wires
supplies, including voltage, frequency, current, power and active and reactive energy, imported or exported, Harmonic,
Power factor, Max. Demand etc. Energy is measured in terms of kWh, kVArh. Maximum demand current can be measured
over preset periods of up to 60minutes. In order to measure energy, the unit requires voltage and current inputs in
addition to the supply required to power the product. The requisite current input(s) are obtained via current transformers
The SMART X96 can be configured to work with a wide range of CTs, giving the unit a wide range of operation. Built-in
interfaces provide pulse and RS485 Modbus RTU outputs. Configuration is password protected.
1. Unit Characteristics
1. 1 The Unit can measure and display:
● Line voltage and THD% (total harmonic distortion) of all phases
● 2~63rd voltage IHD% (Individual Harmonic distortion) of all phases
● Line Frequency
● Currents, Current demands and current THD% of all phases
● 2~63rd current IHD% of all phases
● Active power, reactive power, apparent power, maximum power demand and power factor
● Active energy imported and exported
● Reactive energy imported and exported
● Energy of each phase
1.3 CT and PT
This unit uses a RS485 serial port with Modbus RTU protocol to provide a means of remote monitoring and controlling.
Please check the Part 4.2 for the details of setting.
EASTRON SMART X96-5 User Manual V1.3
Two pulse outputs indicate real-time energy measurement. Pulse output 1 is configurable, pulse output 2 is fixed to active
energy, 3200imp/kWh.
2.Start up screens
The first screen lights all LED segments and can be used as a display LED check
The unit performs a self-test and the screen indicates if the test is passed.
2 PF L1 2 PF L1
PF L2 PF L2
PF L3 PF L3
4. Setting-Up
Ma in scre en Pa ssw ord En tr y COMS (C ommun ic ati on) Add r(Ad dre ss) Entry Va lu e betw ee n:
1~ 24 7
PT (System Co nfig ura tio n) PT 2 Entry Sec ond ar y Vol tag e betwe en :
10 0~50 0
PU L S R A tE Se le ct fro m:
0 .0 01
0 .0 1
0 .1
1
10
1 00
1 000 kWh( kVA rh)/i mp
PU L S tIM E Se le ct fro m:
1 00 mS
2 00 mS
6 0 mS
SyS COC t (syste m co nne ct) P h-1 (ph ase 1) Sel ec t from:
F rd /r Ev ( fo rw a rd / re ve r se )
Setting-up mode is password protected, so you must enter the correct password.
By firmly press the button for 2 seconds, the password screen appears. The
default password is 1000. If an incorrect password is entered, the display shows
ERR.
4.2 Communication
The RS485 port can be used for communications using Modbus RTU protocol.
Parameters such as Address, Baud rate, Parity, Stop bit can be selected.
4.2.1 Address
Long press to enter the selection routine, the address setting will flash. Use
and , to set the address with the range 001~247. And press
for confirmation.
From the Set-up menu, Use and to select the Baud rate options.
Long press to enter the selection routine. The Baud Rate setting will flash.
Example shows:
SET Baud rate 19200 (bps)
4.2.3 Parity
From the Set-up menu, Use and to select the Parity options.
Long press to enter the selection routine. The Parity setting will flash. Use
Example shows:
Set Parity: EVEN
And long press for confirmation. Press to return the main set up menu.
Example shows:
Set Parity: Odd
And long press for confirmation. Press to return the main set up menu.
EASTRON SMART X96-5 User Manual V1.3
From the Set-up menu, Use and to select the Stop Bit options.
Long press to enter the Stop Bit routine. The Stop Bit setting will flash. Use
Example shows
Set Stop bit 2
4.3 CT
From the main Set-up menu, Use and to select the CT option.
4.3.1 CT2
Long press to enter the CT2 routine. Press for 2s, the CT2 setting will
Example shows :
Set CT2 1A
4.3.2 CT1
Long press to enter the CT1 routine. Press for 2s, the CT1 setting will
Example shows :
Set CT1 100A
4.4 PT
The PT option sets the secondary voltage of the voltage transformer (PT) that give
into the meter and the PT rate between the primary voltage to the secondary
voltage.
Long press to enter the PT2 routine. Press , the PT2 setting will flash.
4.4.1 PT2
Set secondary voltage input the meter
Range: 100V ~ 480V
Default: 230V
4.4.2 PT1
Set primary voltage input the meter
Range: 174V ~ 500000V
Default: 400V
Then press to enter the PT2 routine. press for 2s, the PT2 setting will
4.5 Pulse
This option allows you to configure the pulse output. The output can be set to provide a pulse for a defined amount of
energy active or reactive.
This option sets the pulse output type, pulse rate, duration time.
From the Set-up menu, Use and to select the Pulse option.
EASTRON SMART X96-5 User Manual V1.3
Example shows:
Pulse Output 1: import kWh
Options: total kWh, total kVarh, imp kWh,exp kWh, imp kVarh, exp kVarh.
press for 2s,the setting will flash. and to choose Options. And long
Pulse rate options: 0.001 , 0.01 , 0.1 , 1, 10, 100, 1000 kWh / kVarh per Pulse
Default : 0.001 kWh / kVarh per pulse
Use and to select Pulse Rate option. Long press , the setting will
Example shows:
Pulse rate: 0.01
EASTRON SMART X96-5 User Manual V1.3
Use and to enter Pulse duration routine. Long press , the setting
will flash. Use and to choose Options. And long press for
Example shows:
Pulse time 200mS
Example shows:
Pulse time 60mS
4.6 Demand
This sets the period in minutes over which the current and power readings are integrated
for maximum demand measurement. The options are: OFF, 5, 8, 10, 15,30, 60 minutes.
From the Set-up menu, Use and to select the Demand option.
EASTRON SMART X96-5 User Manual V1.3
Long press to enter the DIT routine. Press for 2s, the setting will
Long press to enter the routine. The setting will flash. Use and to
choose Options. And long press for confirmation. Press to return the
Demand set up menu.
4.7 Time
This option sets the backlight lasting time and display scroll time.
From the Set-up menu, Use and to select the Time option.
EASTRON SMART X96-5 User Manual V1.3
Long press to enter the Backlit time routine. Press for 2s, the setting
will flash. Use and to choose Options. And long press for
confirmation.
Use and to select Display scroll time option. Press for 2s, the
setting will flash. Use and to choose Options. And Long press for
4.8 System
The Unit has a default setting of 3 phase 4 wire ( 3p4w). Use this section to set the
type of electrical system.
Options: 3P34,3P3W,1P2W
From the Set-up menu, Use and to select the System option
EASTRON SMART X96-5 User Manual V1.3
The screen shows the currently selected power supply is three phase four wire
Long press to enter the System type routine. Press for 2s, the setting will
Example shows:
The screen shows the currently selected power supply is three phase three wire
Example shows:
The screen shows the currently selected power supply is single phase two wire
This unit provides a function with Reverse connected current inputs correction
setting.
Long press to enter the Phase 1 correction. Press for 2s, the setting will
Press enter Phase 2 correction. Press for 2s, the setting will flash. Use
Press enter Phase 3 correction. Press for 2s, the setting will flash. Use
Press for 2s, the setting will flash. Use and , to choose
for 2s, the setting will flash. Use and to choose options “On” or
2 Escape the Setting menu. Long press for 2 secs. For example,
the screen shows the currently selected Automatic Scroll display ON.
Long press for 2 secs, then the screen shows the currently selected Automatic
Scroll display OFF.
4.9 Reset
This unit provides a function with reset for Energy and Demand, and ALL.
Long press to enter the Energy routine. Press for 2s, the setting will
Then press enter Demand Reset routine. Press for 2s, the setting will
Then press enter ALL Reset routine. Press for 2s, the setting will flash,
5. Specification
The unit can monitor and display the following parameters of a single phase, 3-phase 3-wire or 3-phase 4-wire supply.
5.1.1 Voltage and Current
Phase to neutral voltage 100 to 276 V a.c ( not for 3p3w supplies)
Voltage between phases 174 to 480V a.c (3p supplies only)
Installation Category III (600V)
Rated Current: 1A or 5A
Current input range: 5%~120% Ib
Percentage total voltage harmony distortion ( THD%) for each phase to N
Percentage current harmonic distortion for each phase
Current on each phase
Frequency in Hz (45~66Hz)
Instantaneous power: Power 0 to 999MW
Reactive Power 0 to 999MVAr
EASTRON SMART X96-5 User Manual V1.3
5.3 Display
For Modbus RTU, the following RS485 communication parameters can be configured from the Set-up menu:
Baud rate 2400, 4800, 9600, 19200, 38400
Parity none/odd/even
Stop bits 1 or 2
RS485 network address nnn – 3-digit number, 001 to 247
5.4.3 Environment
5.4.4 Mechanics
6. Dimensions
EASTRON SMART X96-5 User Manual V1.3
7. Wiring Diagram
(3 phase 4 wires)
EASTRON SMART X96-5 User Manual V1.3
(3 phase 3 wires)
(1 phase 2 wires)
EASTRON SMART X96-5 User Manual V1.3