Design of Corner Column Footing: 500 X 500 MM 400 Mpa 30 Mpa 200 Kpa 16
Design of Corner Column Footing: 500 X 500 MM 400 Mpa 30 Mpa 200 Kpa 16
q a=200 kPa
kN
γ S =16
m3
kN
γ C =24
m3
ASSUME t=400 mm
P 491+290
A REQUIRED = = =4.739 m 2
qe 164.80
A REQUIRED =L2=4.739 m 2
L=2.177 m
TRY L=2.25 meters
BEARINGCAPCITY ( q C )
q C =302.279 kPa
L a
x= − −d
2 2
2.25 0.500
x= − −0.27645
2 2
x=0.59855 m ≈ 0.60 m
V U =314.773 kN
VU
d=k
ϕ ( 2 b ) √ f 'C
314.773
d=12.043
0.85 ( 2 x 2.25 ) √ 30
d=180.942mm
b O=4 ( a+d )
b O=4 ( 500+276.45 )
b O=3105.80 mm
V U =qU [ L2−( a+ d )2 ]
V U =1039.826 kN
VU
d=k
ϕ ( 4 bO ) √ f 'C
1039.826 x 103
d=12.043
0.85 ( 4 x 3105.80 ) √30
d=216.512mm< 276.45mm ∴ OK
STEEL REINFORCEMENT :
x x2
M U =q U L ( x ) ()2
=qU L
2 ( )
( 0.60 )2
M U =233.165 ( 2.25 ) ( 2 )
M U =94.432 kN −m
MU 94.432 x 10 6
Rn = 2
=
ϕb d 0.90 ( 2250 ) (276.45 )2
Rn =0.610
0.85 f ' C 2 Rn
ρ ACTUAL=
fy [ √
1− 1−
0.85 f ' C ]
ρ ACTUAL=
0.85 ( 30 )
( 400 ) [ √
1− 1−
2 ( 0.610 )
0.85 ( 30 ) ]
ρ ACTUAL=0.00154
1.4 1.4
ρ MIN = = =0.0035
f y 400
A S=15,177.105 mm2
q a=200 kPa
kN
γ S =16
m3
kN
γ C =24
m3
ASSUME t=400 mm
Wt .of soil=16 ( 2.0−t )=16 ( 2.0−0.40 )
P 456+260
A REQUIRED = = =4.345 m2
qe 164.80
A REQUIRED =L2=4.345 m 2
L=2.084 m
TRY L=2.25 meters
BEARINGCAPCITY ( q C )
q C =301.788 kPa
V U =288.104 kN
VU
d=k
ϕ ( 2 b ) √ f 'C
288.104
d=12.043
0.85 ( 2 x 2.25 ) √ 30
d=165.612mm
DEPTH REQUIRED FOR PUNCHING SHEAR :
b O=4 ( a+d )
b O=4 ( 500+276.45 )
b O=3105.80 mm
V U =qU [ L2−( a+ d )2 ]
V U =951.729 kN
VU
d=k
ϕ ( 4 bO ) √ f 'C
951.729 x 103
d=12.043
0.85 ( 4 x 3105.80 ) √30
d=198.169mm< 276.45 mm∴ OK
STEEL REINFORCEMENT :
x x2
M U =q U L ( x ) ()2
=qU L
2 ( )
( 0.60 )2
M U =213.41 ( 2.25 ) ( 2 )
M U =86.431 kN −m
MU 86.431 x 10 6
Rn = 2
=
ϕb d 0.90 ( 2250 ) (276.45 )2
Rn =0.558
0.85 f ' C 2 Rn
ρ ACTUAL=
fy [ √
1− 1−
0.85 f ' C ]
ρ ACTUAL=
( 400 ) [ √
0.85 ( 30 )
1− 1−
2 ( 0.558 )
0.85 ( 30 ) ]
ρ ACTUAL=0.00141
1.4 1.4
ρ MIN = = =0.0035
f y 400
A S=15,177.105 mm2
F∨SPACINGOF BARS :
π
( 35.7 )2 (2250 )
Ab(b ) 4
S= =
AS 15,177.105
q a=200 kPa
kN
γ S =16
m3
kN
γ C =24
m3
ASSUME t=400 mm
A REQUIRED =L2=2.488 m2
L=1.577 m
TRY L=1.80 meters
BEARINGCAPCITY ( q C )
q C =299.024 kPa
L a
x= − −d
2 2
1.80 0.500
x= − −0.27645
2 2
x=0.37355 m ≈ 0.374 m
V U =127.369 kN
VU
d=k
ϕ ( 2 b ) √ f 'C
127.369
d=12.043
0.85 ( 2 x 1.80 ) √30
d=91.52 mm
b O=4 ( a+d )
b O=4 ( 500+276.45 )
b O=3105.80 mm
V U =qU [ L2−( a+ d )2 ]
V U =498.944 kN
VU
d=k
ϕ ( 4 b O ) √ f 'C
498.944 x 103
d=12.043
0.85 ( 4 x 3105.80 ) √30
d=103.889mm< 276.45 mm∴ OK
STEEL REINFORCEMENT :
x x2
M U =q U L ( x ) ()2
=qU L
2 ( )
( 0.374 )2
M U =189.20 ( 1.80 ) ( 2 )
M U =23.818 kN −m
MU 23.818 x 10 6
Rn = 2
= 2
ϕb d 0.90 ( 1800 )( 276.45 )
Rn =0.192
0.85 f ' C 2 Rn
ρ ACTUAL=
fy [ √
1− 1−
0.85 f ' C ]
ρ ACTUAL=
0.85 ( 30 )
( 400 ) [ √
1− 1−
2 ( 0.192 )
0.85 ( 30 ) ]
ρ ACTUAL=0.000482
1.4 1.4
ρ MIN = = =0.0035
f y 400
A S=12141.684 mm 2
q a=200 kPa
kN
γ S =16
m3
kN
γ C =24
m3
ASSUME t=400 mm
Wt .of soil=16 ( 2.0−t )=16 ( 2.0−0.40 )
P 510+303
A REQUIRED = = =4.933 m 2
qe 164.80
A REQUIRED =L2=4.933 m 2
L=2.221 m
TRY L=2.25 meters
BEARINGCAPCITY ( q C )
q C =302.361 kPa
L a
x= − −d
2 2
2.25 0.500
x= − −0.27645
2 2
x=0.59855 m ≈ 0.60 m
V U =327.760 kN
VU
d=k
ϕ ( 2 b ) √ f 'C
327.760
d=12.043
0.85 ( 2 x 2.25 ) √ 30
d=188.408mm
b O=4 ( a+d )
b O=4 ( 500+276.45 )
b O=3105.80 mm
V U =qU [ L2−( a+ d )2 ]
V U =1082.73 kN
VU
d=k
ϕ ( 4 bO ) √ f 'C
1082.73 x 103
d=12.043
0.85 ( 4 x 3105.80 ) √30
d=225.446 mm<276.45 mm∴ OK
STEEL REINFORCEMENT :
x x2
M U =q U L ( x ) ()
2
=qU L
2 ( )
( 0.60 )2
M U =242.785 ( 2.25 ) ( 2 )
M U =98.328 kN −m
MU 98.328 x 106
Rn = =
ϕb d 2 0.90 ( 2250 ) (276.45 )2
Rn =0.635
0.85 f ' C 2 Rn
ρ ACTUAL=
fy [ √
1− 1−
0.85 f ' C ]
ρ ACTUAL=
( 400 ) [ √
0.85 ( 30 )
1− 1−
2 ( 0.635 )
0.85 ( 30 ) ]
ρ ACTUAL=0.00161
1.4 1.4
ρ MIN = = =0.0035
f y 400
A S=15,177.105 mm2