Configuracion de Fase

This document contains information about protection relays for transformers and motors in a power system, including their settings and trip characteristics. It shows the relay models, pickup currents, time dials, and trip times for overcurrent protection relays on the primary and secondary sides of Transformer 4, and for the motor protection relay on Motor 2. Fault current values that would trigger each relay are also listed.

Uploaded by

diego
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
33 views1 page

Configuracion de Fase

This document contains information about protection relays for transformers and motors in a power system, including their settings and trip characteristics. It shows the relay models, pickup currents, time dials, and trip times for overcurrent protection relays on the primary and secondary sides of Transformer 4, and for the motor protection relay on Motor 2. Fault current values that would trigger each relay are also listed.

Uploaded by

diego
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Per Unit

,005 ,01 ,03 ,05 ,1 ,3 ,5 1 3 5 10 30 50 100


1K 1K
Normalized (shifted) TCC
3-Phase (Sym) fault: 8,899kA @ 4,16kV
500 Adj Bus: Barra 8 500
Connector: CT1 - Mtr2
300 SQOP File: Untitled 300

Data Rev: Base


Configuration: Normal
Date: 29-04-2020
100 100
Relay_Motor_2 - P
50
OC1 50
Siemens
30 7SJ61 30
CT Ratio 300:5
IEC - Long Inverse
Pickup = 5,1 (0,5 - 20 Sec - 5A)
10 Time Dial = 0,65 10
Relay_Prim_trafo_4 - P 3x = 39 s, 5x = 19,5 s, 8x = 11,1 s
OC1 Inst = 38 (0,5 - 175 Sec - 5A)
5
Siemens Time Delay = 0,05 s 5

Seconds
Seconds

7SJ61 7,08 kA @ 4,16 kV


3 3
CT Ratio 300:5 t1: 0,05 s
IEC - Long Inverse Relay_Sec_trafo_4 - P
Pickup = 4,35 (0,5 - 10 Sec - 5A)
OC1
Time Dial = 0,21
1 Siemens 1
3x = 12,6 s, 5x = 6,3 s, 8x = 3,6 s
7SJ61
Inst = 15,8 (0,5 - 175 Sec - 5A)
CT Ratio 800:5
,5
Time Delay = 0,25 s ,5
IEC - Long Inverse
2,231 kA @ 13,2 kV
Pickup = 5,2 (0,5 - 10 Sec - 5A)
,3 t1: 0,25 s ,3
Time Dial = 0,19
Relay_Prim_trafo_4
CB3
±
3x = 11,4 s, 5x = 5,7 s, 8x = 3,26 s
I> Inst = 16,6 (0,5 - 175 Sec - 5A)
T4
5 MVA Time Delay = 0,2 s
,1 7,08 kA @ 4,16 kV ,1

t1: 0,2 s
±

I>

CB2 Relay_Sec_trafo_4 Barra 8


,05 ,05

CB1 Relay_Motor_2
,03 ±

I>
,03

Mtr2
1500 kW
,01 ,01
,005 ,01 ,03 ,05 ,1 ,3 ,5 1 3 5 10 30 50 100

Per Unit
ETAP Star 12.6.0H

Star41

Project: Date: 28-04-2020


Location: SN:
Contract: Rev: Base
Engineer: Fault: Phase(Normalized)
Filename: C:\ETAP 1260\TALLERPRACTICO1\TALLERPRACTICO1.OTI