Detection and Control Components

AutoPulse 4XTM Transmitter Module


(542R/542D)

Description Listings and Approvals*


The 4XTM Transmitter Module is an option for the UL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S635
AUTOPULSE® control systems. The module provides a ULC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CS118, CS733
supervised output for local energy municipal box transmitter Factory Mutual (FM) . . . . . . . . . . . . . . . . . . . . . . . . . Approved
(for NFPA 72 Auxiliary Protective Signaling System) and MEA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104-93-E Vol. VI
alarm and trouble reverse polarity circuits (for NFPA 72
CSFM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7165-0028:245
Remote Station Protective Signaling System). Also included
* Listings and Approvals are under NOTIFIER
is a DISABLE switch and disable trouble LED. A jumper
option allows the reverse polarity circuit to open with a Ordering Information
System Trouble condition if no alarm condition exists.
Shipping
Technical Information Weight
Part No. Description lb (kg)
For Local Energy Municipal Box service (NFPA 72 Auxiliary
Protective Signaling System): 417470 4XTM Transmitter Module 1 (0.5)
Supervisory Current. . . . . . . . . . . . . . . . . . . . . . . . . 5.0 mA
Trip Current . . . . . . 0.35 amps (subtracted from indicating
appliance power)
Coil Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.65 VDC
Coil Resistance . . . . . . . . . . . . . . . . . . . . . . . . . 14.6 ohms
Total wire resistance between unit and trip coil . . . 3 ohms
For Remote Station service (NFPA 72 Remote Station
Protective Signaling System):
Maximum Load for each circuit. . . . . . . . . . . . . . . . . 10 mA
Reverse Polarity Output Voltage. . . . . . . . . . . . . . . 24 VDC

4XTM TRANSMITTER MODULE


(POLARITIES SHOWN IN ACTIVATED POSITIONS)

1 +
2 – } REMOTE
ALARM
3
4
+
– } REMOTE
TROUBLE
5
6
+
– } MUNICIPAL
BOX
4 IN.
(102 mm)

TBL
JUMPER
DISCONNECT
LED

2 1/2 IN.
(64 mm)
007342
DISCONNECT SWITCH

AUTOPULSE is a trademark of Tyco International (US), Inc. or its affiliates.


3-57

TYCO SAFETY PRODUCTS, MARINETTE, WI 54143-2542 Form No. T-2007091 Copyright ©2007 Tyco International (US), Inc.